- Unavailable keeps an ACTIVE condition active: quality-only BadNoCommunication; on data
return same statement => quality-only Good, Normal => Clear, different => Retrigger.
- A changed alarm reference set (alarm-bearing delta = full rebuild) clears the whole
last-told record so every active condition is re-asserted; the same set keeps it.
- Quality-only events go through the host's AlarmQualityUpdate path, never a projected
snapshot (which could ack a retained unacked condition or rewrite message/severity).
- Deterministic tie-break between equal-level conditions (ordinal nativeCode, then type).
- Dedup key is level+nativeCode+nativeSeverity+qualifier; a text-only change updates nothing.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The parser keeps a condition's text, nativeCode, nativeSeverity, qualifier and type. A new
MTConnectConditionTracker applies MTConnect's multi-condition semantics (per-nativeCode
activation/clearing across /sample deltas, /current baseline reset, Unavailable), and
MTConnectConditionAlarmMapper turns tracker state into Part 9 transitions: Warning=500,
Fault=800, Normal=clear, Unavailable=inactive + BadNoCommunication; escalation or a new
code retriggers. The driver implements IAlarmSource keyed by the alarm tag's RawPath,
diffs against what the server was actually told (only when a handler is attached), so a
reconnect/re-baseline never re-raises an unchanged condition and a missed transition is
delivered on the next subscribe. Ack is a no-op success. Existing CONDITION String tags
are unchanged; a tag becomes an alarm only via the standard TagConfig 'alarm' object.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
New S7DataType members WString/Char/WChar/Dtl/Date/Tod/Time/S5Time mapped onto existing
DriverDataType (String / DateTime / Int32 ms); writes refuse out-of-range with BadOutOfRange.
Optional localTsap/remoteTsap/connectionType through options, factory JSON, probe and AdminUI form.
NegotiatedPduSize snapshotted at connect and exposed via GetDiagnostics (DriverHealth has no bag).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
FOCAS, AbLegacy, AbCip, TwinCAT, S7 and OpcUaClient orphaned the previous
probe/recycle/fixed-tree loops and clients when re-initialised on a live driver.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
MAJOR-1: R4's exact element-type match refused ScadaBridge's CLR-list
writes (its element types are only Boolean/Int32/Float/Double/String/
DateTime) to every Int16/UInt16/Byte/UInt32/Int64/UInt64 array node and a
Double list to a Float array. EvaluateEquipmentWriteStructure now converts
a numeric array of another numeric element type element-wise, CHECKED, into
the node's element type and hands the converted array back through
OnEquipmentTagWrite's ref value, so the node stores and the driver receives
the node's own type. Any out-of-range, fractional-to-integer, NaN/Inf-to-
integer or Float-overflowing element refuses the whole write BadTypeMismatch
(nothing dispatched) - so the UInt32 -> Int32 bit reinterpretation stays
closed. Non-numeric mismatches stay refused. The wrong 'no client relies on
a looser rule' comment is corrected.
MINOR-1: the array-value-to-scalar-node refusal broke writes back to
browse-committed array tags (committed scalar, isArray never set) on
pass-through drivers. It now applies only when the owning driver's scalar
encoder cannot take an array (DriverArrayWriteSupport.
RefusesArrayValueOnScalarTag: Modbus, S7), carried RawTagPlan.
ScalarRefusesArrayValue / UnsReferenceVariable.BackingScalarRefusesArrayValue
-> EnsureVariable(refuseArrayOnScalar) -> a per-node set in the node
manager. OpcUaClient/Galaxy/others keep pre-#610 dispatch. Not on the
classifier whitelist (driver-type edit rebuilds); a mirror whose flag
changes is recreated, not updated in place.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
MAJOR-1: the SDK skips TypeInfo.IsInstanceOfDataType on any node with an
OnWriteValue handler (every writable equipment node), and the node manager's
fail-fast treated numeric<->numeric as compatible, so a UInt32[] to a Galaxy
Int32 array matched MxValueEncoder's int[] arm by CLR covariance and was
written bit-reinterpreted with a Good result. EvaluateEquipmentWriteStructure
now matches an ARRAY write's element type exactly (Byte[]/ByteString the only
equivalence; Variant[]/object[] refused) -> BadTypeMismatch, nothing
dispatched. MxValueEncoder's int[]/long[] arms are exact-type guarded too, and
the Galaxy parity test's false "the SDK refuses" premise is corrected (the
UInt32/UInt64 exclusion is now the encoder's own answer). Scalar writes keep
numeric widening by decision: consumers write CLR-typed values (Double to a
Float node) and every driver's scalar encoder range-checks.
MINOR: Modbus row honours maxRegistersPerWrite (smallest of DriverConfig /
the tag's DeviceConfig, default 123) and FC15's 1968-coil ceiling, and
requires region + numeric address; Modbus/S7/Galaxy require isArray + integer
arrayLength >= 1 (Galaxy: an unbounded node would let a short write resize the
attribute); an array value to a scalar node is refused inline. Docs: Uns.md
array-write rules + upgrade note (ReadWrite array tags become client-writable
on first boot), Modbus.md, Galaxy.md.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- Galaxy: deadline bounds the wait, not the subscribe RPC; BadTimeout for all tags and late handles unsubscribed; doc comment relocated
- S7: probe connect runs on the connect deadline so a timeout opens the backoff window
- S7: a successful write only retires a Faulted the write side owns
- S7: null array elements rejected (BadTypeMismatch); multi-PDU array writes documented non-atomic
- S7 integration: array write test gated on S7_SIM_ALLOW_WRITES=1
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A first-touch native write to a T/C/R status-bit sub-element (T4:0.DN) created
and initialised the tag's runtime before the runtime's write refusal could fire;
the init is one READ, so against a device lacking the file (the ab_server
fixture has no T/C/R) it surfaced as BadCommunicationError + Degraded health
instead of BadNotSupported. The bit-RMW path was not involved: AbLegacyAddress
rejects sub-element + /N, so a status bit's BitIndex is always null.
NativeAbLegacyTagRuntime.WriteRefusal is now the single predicate (status bit
by address whatever the authored type; any PLC-5 write), asked by the driver via
IAbLegacyTagFactory.WriteRefusal (default null, so libplctag is unchanged)
before EnsureTagRuntimeAsync and ahead of the bit-RMW branch.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
STAB-21 ConnectionBackoff in EnsureConnectedAsync; STAB-22 write-pass accumulator with a
write-side Faulted that a clean read does not erase; _health on the Volatile idiom;
S7-016 contiguous array write (Bool arrays stay refused).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe