Re-review of 3de2cc3b/454775c6:
- AlarmTransitions could not reach (inactive, unacked): (active,acked)->(inactive,unacked) emitted Clear
(host stayed acked) and a first-seen cleared-unacked condition emitted nothing. The table is now total;
an exhaustive test replays every (prior, target) pair through the projector's semantics.
- The per-RawPath read-compute-emit was a lock-free TryGetValue/set across SDK publish threads; it now runs
under one lock with the projection and emission.
- Condition BRANCH events (non-null BranchId) were projected (flipping the trunk) and remembered as the ack
target (acking the branch); they are dropped. BranchId is select clause 9.
- EventId is copied, not aliased from the decoded notification.
- An unchanged state re-emitted Unspecified; it now emits nothing unless message/severity changed (an
Unspecified projects from the host projector's default after a redeploy reset it).
- Exact upstream severity rides OpcUaSeverity (#626) instead of being re-bucketed.
- ShutdownAsync no longer forgets the last-told state: a reinit re-subscribes the same set and the refresh
would otherwise re-raise every acked alarm. A CHANGED set (host rebuilt) forgets it.
ConditionRefresh: called after the alarm event item is created, after an in-place reconnect (subscriptions
found on the new session by display name, since a recreate clones them) and on RefreshRequired. Refresh
markers are never projected. BadNotSupported/BadMethodInvalid/... logs once. Wire test: a condition already
active before subscribe is reported Raise; a release+resubscribe refresh re-raises nothing (falsified by
disabling the refresh call).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Found while verifying item 4 of #641. The host routes a native alarm transition
on an exact ConditionId == RawPath match (DriverHostActor.ForwardNativeAlarm),
but AbCipAlarmProjection emitted "{ref}#active" and no Kind, so every ALMD
raise/clear was dropped as "no alarm condition" — and even if routed, an
Unspecified kind projects no state change. It now reports the subscribed
reference (the RawPath) and Raise/Clear. A host test pins that a decorated id
is dropped.
FOCAS has the same id shape plus a device filter keyed by host address (a
RawPath subscription polls nothing); it needs a mapping decision and is
documented in docs/drivers/FOCAS.md rather than patched here.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The driver cleared its whole "last told" record whenever the subscribed alarm
set changed, assuming the rebuild that accompanies an alarm-bearing delta had
reset every condition node. The server now carries each surviving native
condition's state (acknowledgement included) across the rebuild, so re-raising a
survivor would un-acknowledge it. Only entries that left the set are dropped; a
condition that comes back later is told again onto its fresh node.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
NativeAlarmProjector derives Active/Acked ONLY from AlarmEventArgs.Kind, and this driver
never set it - every routed event projected Unspecified, leaving the condition inactive+acked
(only Message/Severity moved). The live-gate expectation 'toggling Active as opc-plc cycles'
could not have passed. Select ActiveState/Id + AckedState/Id (two-element browse paths) and
emit the Kind sequence that moves the projector from the state last told to the host to the
event's (Raise+Acknowledge when a notification carries both).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The alarm index was keyed on ns=N strings resolved once at subscribe time, while an
in-place SDK reconnect transfers the subscription without re-running it - a remote
namespace reorder silently orphaned every alarm tag. Keys are now nsu= on both sides.
Events match the authored nodeId against the event's ConditionId first, then its
SourceNode, so several conditions on one source can be authored 1:1. Acknowledge
passes the EventId of the event that named the remembered condition (paired, so node
and EventId can never come from different conditions) instead of an empty one.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
OtOpcUaNodeManager.MapSeverity re-bucketed every projected severity onto the
SDK's five EventSeverity values (<800 -> 700, else 900), defeating #626's exact
OpcUaSeverity: an MTConnect Fault (800) read and evented as 900; a scripted
alarm graded 1000 published 900 while /alerts said 1000; a native Low (200)
published 300. EventSeverity merely names points on the 1..1000 scale, so the
node now carries the value clamped to 1..1000 (ToPart9Severity), at
materialise, projection and in the delta gate.
MTConnect wire test now asserts Fault ActiveState=true/Severity=800 and the
Normal clear ActiveState=false/Retain=false/Severity=800.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
EventFilter.AddSelectClause(type, "ActiveState/Id") does not split the string;
it selects a single QualifiedName named "ActiveState/Id", which no event carries.
AckedState/Id, ActiveState/Id and EnabledState/Id therefore always arrived null
and Client.CLI 'alarms' (and Client.UI) reported every alarm inactive and
unacknowledged while a direct Read said Active. Pre-existing since a2883b82;
server-side event delivery was correct (proven with two-element select clauses,
incl. after #629). Select them with explicit two-element browse paths.
Over-the-wire test drives OpcUaClientService.SubscribeAlarmsAsync against the
in-process server (native + scripted); ServerEventRig now also selects
ActiveState/Id, Severity and Retain.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
MTConnectConditionAlarmWireTests drives a scripted Agent's Fault/Normal through the real
driver, NativeAlarmProjector and sink to a client event subscription on the raw device
folder. docs/drivers/MTConnect.md replaces 'CONDITION v1: plain String' with the alarm
mapping, opt-in authoring, multi-condition, ack, replay and comms-loss behaviour, and a
live-check recipe; EVENT vocabularies as enumerations marked won't-fix. AlarmTracking.md
lists the MTConnect source and the two new AlarmEventArgs fields.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
New() ran FindNodeInAddressSpace under Lock, taking other node managers' locks (lock-order
risk); the three AlarmConditionType_ShelvingState_* ids are now a static set. Adds wire tests:
TimedShelve/Unshelve by the condition's own instance method ids (object = condition or its
ShelvingState) succeed and report, and a ShelvedStateMachineType_* id call is pinned as
BadMethodInvalid with a positive control.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Create(assignNodeIds: true) asked CustomNodeManager2.New, whose default returns the
node's current id, so every condition child kept the type's ns=0 instance-declaration id
(or an SDK-generated ns=0 number): translate of a child path returned BadNoMatch and a
Read of a browsed child id was BadNodeIdUnknown or served from the TYPE (UnshelveTime 0
on a condition timed-shelved for a minute), bypassing the data-plane ACL.
OtOpcUaNodeManager.New now derives {conditionId}/{browsePath} in the condition's
namespace, so the ACL scope of a child is its condition's scope plus the path. The
ShelvingState methods adopt their original AlarmConditionType_ShelvingState_* id as
MethodDeclarationId so clients calling them by that id still resolve. Condition removal
and rebuild forget the whole PredefinedNodes subtree so a removed condition's children
stop answering.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
New S7DataType members WString/Char/WChar/Dtl/Date/Tod/Time/S5Time mapped onto existing
DriverDataType (String / DateTime / Int32 ms); writes refuse out-of-range with BadOutOfRange.
Optional localTsap/remoteTsap/connectionType through options, factory JSON, probe and AdminUI form.
NegotiatedPduSize snapshotted at connect and exposed via GetDiagnostics (DriverHealth has no bag).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
FOCAS, AbLegacy, AbCip, TwinCAT, S7 and OpcUaClient orphaned the previous
probe/recycle/fixed-tree loops and clients when re-initialised on a live driver.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe