fix(abcip): report ALMD transitions with ConditionId = RawPath and a Kind (#641)
Found while verifying item 4 of #641. The host routes a native alarm transition on an exact ConditionId == RawPath match (DriverHostActor.ForwardNativeAlarm), but AbCipAlarmProjection emitted "{ref}#active" and no Kind, so every ALMD raise/clear was dropped as "no alarm condition" — and even if routed, an Unspecified kind projects no state change. It now reports the subscribed reference (the RawPath) and Raise/Clear. A host test pins that a decorated id is dropped. FOCAS has the same id shape plus a device filter keyed by host address (a RawPath subscription polls nothing); it needs a mapping decision and is documented in docs/drivers/FOCAS.md rather than patched here. Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
This commit is contained in:
@@ -264,6 +264,10 @@ analog alarms are a follow-up) and **disabled by default** — shops running FT
|
||||
Alarm & Events should keep it off and take alarms through the native route, since
|
||||
the projection semantics don't exactly mirror Rockwell FT A&E.
|
||||
|
||||
Each event carries `ConditionId` = the subscribed reference (the alarm tag's RawPath — the key the host
|
||||
routes native transitions on) and `Kind` = `Raise` / `Clear`. Before Gitea #641 the projection sent
|
||||
`"{ref}#active"` with no kind, so the host dropped every ALMD transition as unrouted.
|
||||
|
||||
## Testing
|
||||
|
||||
- **Unit tests** — `tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbCip.Tests/` cover the driver, host-address parser, UDT planner, and alarm projection via fake tag runtimes.
|
||||
|
||||
@@ -294,6 +294,13 @@ Every alarm transition fires `OnAlarmEvent` with:
|
||||
Cleared alarms fire a second event with `" (cleared)"` appended to the message
|
||||
so downstream consumers can ignore the clear if they only care about raises.
|
||||
|
||||
> ⚠️ **Not routable to a v3 raw condition (found under Gitea #641).** The server routes a native transition
|
||||
> only when `ConditionId` equals an alarm-bearing raw tag's RawPath, and the host subscribes those RawPaths —
|
||||
> but this projection filters devices by **host address** (so a RawPath list matches no device and nothing is
|
||||
> polled) and emits `"{host}#{Type}:{AlarmNumber}"` with no `Kind`. FOCAS native alarms therefore reach no
|
||||
> Part 9 condition today. Fixing it needs a mapping decision (the CNC exposes one flat alarm list per device,
|
||||
> not one condition per tag), so it is tracked separately rather than patched.
|
||||
|
||||
## Handle recycling
|
||||
|
||||
FANUC CNCs have a finite FWLIB handle pool (~5–10 concurrent connections) and
|
||||
|
||||