fix(client): alarm filter selected ActiveState/Id as ONE QualifiedName — every event read inactive
EventFilter.AddSelectClause(type, "ActiveState/Id") does not split the string; it selects a single QualifiedName named "ActiveState/Id", which no event carries. AckedState/Id, ActiveState/Id and EnabledState/Id therefore always arrived null and Client.CLI 'alarms' (and Client.UI) reported every alarm inactive and unacknowledged while a direct Read said Active. Pre-existing since a2883b82; server-side event delivery was correct (proven with two-element select clauses, incl. after #629). Select them with explicit two-element browse paths. Over-the-wire test drives OpcUaClientService.SubscribeAlarmsAsync against the in-process server (native + scripted); ServerEventRig now also selects ActiveState/Id, Severity and Retain. Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
This commit is contained in:
@@ -248,6 +248,12 @@ otopcua-cli alarms -u opc.tcp://localhost:4840/OtOpcUa \
|
||||
| `-i` / `--interval` | Publishing interval in milliseconds (default: 1000) |
|
||||
| `--refresh` | Request a `ConditionRefresh` after subscribing to get current retained alarm states |
|
||||
|
||||
The active/acknowledged columns come from the standard `ActiveState/Id`, `AckedState/Id` and
|
||||
`EnabledState/Id` event fields. Before the 2026-10 fix the client's filter selected them with a single
|
||||
QualifiedName named `ActiveState/Id` (a `/`-joined string passed to `EventFilter.AddSelectClause` is **not**
|
||||
split into a browse path), which matched nothing — so every event printed inactive and unacknowledged
|
||||
whatever the condition's real state. A direct Read of the condition was always correct.
|
||||
|
||||
### ack
|
||||
|
||||
Acknowledges an active alarm condition via the OPC UA Part 9 `Acknowledge` method. The server gates this on the **`AlarmAck`** role (fail-closed — a session whose API-key principal holds no `AlarmAck`-conferring `NodeAcl` grant gets `BadUserAccessDenied`; the data plane does not use LDAP; see [ScriptedAlarms.md](ScriptedAlarms.md) §"AlarmAck gate"). The `--event-id` is the hex-encoded `EventId` taken from a prior `alarms` subscription notification for the same condition.
|
||||
|
||||