MAJOR-1: the SDK skips TypeInfo.IsInstanceOfDataType on any node with an
OnWriteValue handler (every writable equipment node), and the node manager's
fail-fast treated numeric<->numeric as compatible, so a UInt32[] to a Galaxy
Int32 array matched MxValueEncoder's int[] arm by CLR covariance and was
written bit-reinterpreted with a Good result. EvaluateEquipmentWriteStructure
now matches an ARRAY write's element type exactly (Byte[]/ByteString the only
equivalence; Variant[]/object[] refused) -> BadTypeMismatch, nothing
dispatched. MxValueEncoder's int[]/long[] arms are exact-type guarded too, and
the Galaxy parity test's false "the SDK refuses" premise is corrected (the
UInt32/UInt64 exclusion is now the encoder's own answer). Scalar writes keep
numeric widening by decision: consumers write CLR-typed values (Double to a
Float node) and every driver's scalar encoder range-checks.
MINOR: Modbus row honours maxRegistersPerWrite (smallest of DriverConfig /
the tag's DeviceConfig, default 123) and FC15's 1968-coil ceiling, and
requires region + numeric address; Modbus/S7/Galaxy require isArray + integer
arrayLength >= 1 (Galaxy: an unbounded node would let a short write resize the
attribute); an array value to a scalar node is refused inline. Docs: Uns.md
array-write rules + upgrade note (ReadWrite array tags become client-writable
on first boot), Modbus.md, Galaxy.md.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Array nodes were forced read-only for every driver. A new single authority,
Core.Abstractions DriverArrayWriteSupport, says which (driver, element type)
pairs encode a whole-array write: Modbus (Coils / numeric HoldingRegisters),
S7 (Byte/Int16/UInt16/Int32/UInt32/Float32), OpcUaClient (pass-through) and
Galaxy (Boolean/Int32/Int64/Float/Double/String/DateTime). Everything else
stays read-only, so the server never advertises a write the driver refuses.
- Composer derives RawTagPlan.ArrayWritable + UnsReferenceVariable
.BackingArrayWritable at compose time (both seams, byte-parity); the
applier's one writability rule is Writable && (!IsArray || ArrayWritable)
for materialise and surgical paths, raw and UNS alike.
- ArrayWritable is on the classifier's surgical raw-tag whitelist and
mirrored on the UNS record (UnsReferenceBackingParityTests updated).
- Node manager refuses a wrong-length / non-array value on an array node
(BadTypeMismatch) and any IndexRange write (BadWriteNotSupported) inline,
before dispatch; WriteOperate/ACL gates and the revert are unchanged.
- Per-driver parity tests pin the table against the real Modbus write path,
S7 EncodeArrayBlock and Galaxy MxValueEncoder (UInt32/UInt64 excluded:
array covariance reinterprets their bits).
- Over-the-wire proof in OpcUaServer.IntegrationTests (ArrayWriteWireTests).
- ValueRank > 1 documented as out of scope by decision (docs/Uns.md).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- Galaxy: deadline bounds the wait, not the subscribe RPC; BadTimeout for all tags and late handles unsubscribed; doc comment relocated
- S7: probe connect runs on the connect deadline so a timeout opens the backoff window
- S7: a successful write only retires a Faulted the write side owns
- S7: null array elements rejected (BadTypeMismatch); multi-PDU array writes documented non-atomic
- S7 integration: array write test gated on S7_SIM_ALLOW_WRITES=1
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
M1: PageErrorBoundary wraps the body of every InteractiveServer page; the inert layout boundary is removed.
m1: DisposeBridge cancels its CTS when the 5 s wait times out.
m2: a CSV import that commits after the modal closed still raises OnSaved.
m3: document SecurityMode=None no-fallback in Client.CLI.md / Client.UI.md.
m4: browsePageDelayMs written only when loaded or changed; negative flagged.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A first-touch native write to a T/C/R status-bit sub-element (T4:0.DN) created
and initialised the tag's runtime before the runtime's write refusal could fire;
the init is one READ, so against a device lacking the file (the ab_server
fixture has no T/C/R) it surfaced as BadCommunicationError + Degraded health
instead of BadNotSupported. The bit-RMW path was not involved: AbLegacyAddress
rejects sub-element + /N, so a status bit's BitIndex is always null.
NativeAbLegacyTagRuntime.WriteRefusal is now the single predicate (status bit
by address whatever the authored type; any PLC-5 write), asked by the driver via
IAbLegacyTagFactory.WriteRefusal (default null, so libplctag is unchanged)
before EnsureTagRuntimeAsync and ahead of the bit-RMW branch.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- Native-condition Acknowledge on a non-Primary node returns BadInvalidState (nothing
routed/applied/reported) via NativeAlarmAckPrimaryGate, fed from
IDriverPrimaryRoleSource by OtOpcUaServerHostedService.
- A re-ack carrying a comment reports one comment event (Acked/Confirmed unchanged).
- TimedShelve applies its requested duration and the scripted projection carries
UnshelveAtUtc, so ShelvingState/UnshelveTime counts down instead of ~24.8 days.
- Native re-ack still routed to the driver (deliberate: documented retry path), pinned.
- AdminUI /alerts client ack/shelve path test; docs/AlarmTracking.md decisions incl.
accepted SDK EventsMonitored residual (item 6).
- Also #599/03/S20: RemoveEquipmentSubtree severs inverse Organizes edges.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- AnnounceAddedNodes raises NodeAdded in the Raw realm for the existing parents of
added raw containers/tags (ComputeRawAddAnnouncements); Uns side unchanged.
- ApplyPureRemove removes UNS reference variables BEFORE the equipment subtree, so a
reference the subtree's id-prefix scope reaches no longer ratchets to a full rebuild
(03/P5). A NotSubsumed filter was not used: in production a reference NodeId is
Area/Line/Equipment/Name, outside the subtree scope, so filtering would leak it.
The matching RemoveEquipmentSubtree severing (03/S20) is in the node-manager commit.
- UnsReferenceBackingParityTests: reflection guard discovering the classifier's surgical
raw-tag whitelist and requiring a same-typed mirror field (03/U11).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
STAB-21 ConnectionBackoff in EnsureConnectedAsync; STAB-22 write-pass accumulator with a
write-side Faulted that a clean read does not erase; _health on the Volatile idiom;
S7-016 contiguous array write (Bool arrays stay refused).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The drain gate counted SyncListenPort; a port with no ApiKey shares nothing (fail-closed
passive endpoint), and an ApiKey-only passive node shares its queue but was never gated.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe