Joseph Doherty bd23f557f3 docs(alarms): native condition state across a rebuild, projector prune, exact ConditionId routing (#641)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 17:09:24 -04:00
Joseph Doherty 64d2514e2a fix(abcip): report ALMD transitions with ConditionId = RawPath and a Kind (#641)
Found while verifying item 4 of #641. The host routes a native alarm transition
on an exact ConditionId == RawPath match (DriverHostActor.ForwardNativeAlarm),
but AbCipAlarmProjection emitted "{ref}#active" and no Kind, so every ALMD
raise/clear was dropped as "no alarm condition" — and even if routed, an
Unspecified kind projects no state change. It now reports the subscribed
reference (the RawPath) and Raise/Clear. A host test pins that a decorated id
is dropped.

FOCAS has the same id shape plus a device filter keyed by host address (a
RawPath subscription polls nothing); it needs a mapping decision and is
documented in docs/drivers/FOCAS.md rather than patched here.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 17:08:47 -04:00
Joseph Doherty 3fe6cbb905 fix(mtconnect): on a changed alarm set forget only the conditions that left (#641)
The driver cleared its whole "last told" record whenever the subscribed alarm
set changed, assuming the rebuild that accompanies an alarm-bearing delta had
reset every condition node. The server now carries each surviving native
condition's state (acknowledgement included) across the rebuild, so re-raising a
survivor would un-acknowledge it. Only entries that left the set are dropped; a
condition that comes back later is told again onto its fresh node.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 17:06:57 -04:00
Joseph Doherty aba3aa7a8d fix(opcua): condition Severity is carried verbatim, not re-bucketed to 5 points
OtOpcUaNodeManager.MapSeverity re-bucketed every projected severity onto the
SDK's five EventSeverity values (<800 -> 700, else 900), defeating #626's exact
OpcUaSeverity: an MTConnect Fault (800) read and evented as 900; a scripted
alarm graded 1000 published 900 while /alerts said 1000; a native Low (200)
published 300. EventSeverity merely names points on the 1..1000 scale, so the
node now carries the value clamped to 1..1000 (ToPart9Severity), at
materialise, projection and in the delta gate.

MTConnect wire test now asserts Fault ActiveState=true/Severity=800 and the
Normal clear ActiveState=false/Retain=false/Severity=800.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 16:19:27 -04:00
Joseph Doherty 49a470a080 fix(client): alarm filter selected ActiveState/Id as ONE QualifiedName — every event read inactive
EventFilter.AddSelectClause(type, "ActiveState/Id") does not split the string;
it selects a single QualifiedName named "ActiveState/Id", which no event carries.
AckedState/Id, ActiveState/Id and EnabledState/Id therefore always arrived null
and Client.CLI 'alarms' (and Client.UI) reported every alarm inactive and
unacknowledged while a direct Read said Active. Pre-existing since a2883b82;
server-side event delivery was correct (proven with two-element select clauses,
incl. after #629). Select them with explicit two-element browse paths.

Over-the-wire test drives OpcUaClientService.SubscribeAlarmsAsync against the
in-process server (native + scripted); ServerEventRig now also selects
ActiveState/Id, Severity and Retain.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 16:19:27 -04:00
Joseph Doherty 95b389497a test+docs(mtconnect): wire test for the Unavailable blip + ack survival; docs for the review rulings (#626)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 15:44:50 -04:00
Joseph Doherty 6a5f5c5a28 Merge branch 'master' into b626-626 2026-10-08 15:32:51 -04:00
Joseph Doherty f4d513e111 test+docs(mtconnect): CONDITION alarm wire test, reinit barrier, docs (#626)
MTConnectConditionAlarmWireTests drives a scripted Agent's Fault/Normal through the real
driver, NativeAlarmProjector and sink to a client event subscription on the raw device
folder. docs/drivers/MTConnect.md replaces 'CONDITION v1: plain String' with the alarm
mapping, opt-in authoring, multi-condition, ack, replay and comms-loss behaviour, and a
live-check recipe; EVENT vocabularies as enumerations marked won't-fix. AlarmTracking.md
lists the MTConnect source and the two new AlarmEventArgs fields.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 15:13:30 -04:00
Joseph Doherty 5051275b78 Merge b626-629 (batch #626+): Part 9 condition children get instance-scoped NodeIds ({ConditionId}/{browse path}); shelve methods keep resolving; subtree forgotten on teardown
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 15:02:07 -04:00
Joseph Doherty 66c47c3ddd fix(opcua): shelve declaration ids from a fixed set, not an address-space lookup; pin instance-id + state-machine-id shelve calls (#629)
New() ran FindNodeInAddressSpace under Lock, taking other node managers' locks (lock-order
risk); the three AlarmConditionType_ShelvingState_* ids are now a static set. Adds wire tests:
TimedShelve/Unshelve by the condition's own instance method ids (object = condition or its
ShelvingState) succeed and report, and a ShelvedStateMachineType_* id call is pinned as
BadMethodInvalid with a positive control.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 15:01:54 -04:00
Joseph Doherty 1219b7b13e fix(opcuaclient): review fixes - drop driver-side OperationLimits chunking (SDK batches), diagnostics as OTel counter, safe discovery selection, options validation at load (#273 #275 #276 #277 #278)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:55:53 -04:00
Joseph Doherty 1de8357d13 Merge commit 'e6028678' into b626-629 2026-10-08 14:55:30 -04:00
Joseph Doherty 935ba8d1d4 Merge branch 'master' into b626-opcuaclient 2026-10-08 14:47:49 -04:00
Joseph Doherty d0052d9fed fix(opcua): Part 9 condition children get instance-scoped NodeIds (#629)
Create(assignNodeIds: true) asked CustomNodeManager2.New, whose default returns the
node's current id, so every condition child kept the type's ns=0 instance-declaration id
(or an SDK-generated ns=0 number): translate of a child path returned BadNoMatch and a
Read of a browsed child id was BadNodeIdUnknown or served from the TYPE (UnshelveTime 0
on a condition timed-shelved for a minute), bypassing the data-plane ACL.

OtOpcUaNodeManager.New now derives {conditionId}/{browsePath} in the condition's
namespace, so the ACL scope of a child is its condition's scope plus the path. The
ShelvingState methods adopt their original AlarmConditionType_ShelvingState_* id as
MethodDeclarationId so clients calling them by that id still resolve. Condition removal
and rebuild forget the whole PredefinedNodes subtree so a removed condition's children
stop answering.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:45:46 -04:00
Joseph Doherty e6028678b3 docs(mtconnect): upgrade note for existing multi-Device MTConnect drivers (#628)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:44:44 -04:00
Joseph Doherty 723392e3da Merge b626-mtconnect (batch #626+)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:43:45 -04:00
Joseph Doherty 7a9b51aeca Merge b626-ablegacy-focas (batch #626+)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:43:44 -04:00
Joseph Doherty 2377da3cb4 Merge b626-630 (batch #626+): release prior device/session state on re-Initialize in six drivers
Conflict in S7Driver.ReleaseConnectionAsync resolved: kept the gated Plc swap from #630 and
carried the negotiated-PDU reset from #632 #294 into it.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:43:44 -04:00
Joseph Doherty 2a41b46b17 Merge b626-s7 (batch #626+)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:43:07 -04:00
Joseph Doherty ba62022e88 feat(opcuaclient): subscription tuning, OperationLimits chunking, diagnostics counters, revocation options, DiscoveryUrl (#273 #275 #276 #277 #278)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:40:20 -04:00
Joseph Doherty 18a20981a5 fix(drivers): #630 review - AbCip disposes alarm projection + clears tag tables, join not abortable by init token; S7 swaps Plc under _gate; doc rationale
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:39:05 -04:00
Joseph Doherty ff055ebd79 fix(s7): numeric TSAP loads in form, shared TSAP conflict error, Test Connect read detects PUT/GET disabled, pin Int32 ms rounding (#632 #638)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:38:49 -04:00
Joseph Doherty d8f3dd7394 fix(ablegacy): review fixes - one family-aware address authority in Contracts, deploy gate + editor check, malformed address -> BadNodeIdUnknown warned once, probe normalised, octal/migration docs (#244 #245 #247)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:38:25 -04:00
Joseph Doherty 34c52defb3 feat(s7): STRING/WSTRING/CHAR/WCHAR and DTL/DATE/TOD/TIME/S5TIME codecs, TSAP/connection-type override, negotiated PDU surfaced (#632 #288 #289 #294 #295)
New S7DataType members WString/Char/WChar/Dtl/Date/Tod/Time/S5Time mapped onto existing
DriverDataType (String / DateTime / Int32 ms); writes refuse out-of-range with BadOutOfRange.
Optional localTsap/remoteTsap/connectionType through options, factory JSON, probe and AdminUI form.
NegotiatedPduSize snapshotted at connect and exposed via GetDiagnostics (DriverHealth has no bag).

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:31:44 -04:00
Joseph Doherty dcc827ca8c feat(mtconnect): one agent client per driver — a second /raw Device is a deploy error (#628)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:29:50 -04:00
Joseph Doherty 461133235a fix(drivers): InitializeAsync releases previous device/session state before overwrite (#630)
FOCAS, AbLegacy, AbCip, TwinCAT, S7 and OpcUaClient orphaned the previous
probe/recycle/fixed-tree loops and clients when re-initialised on a live driver.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:28:55 -04:00
Joseph Doherty 0dc09329b7 feat(ablegacy,focas): PLC-5 octal I/O, MicroLogix function files, indirect-address parse, 16i PMC F/G (#244 #245 #247 #265)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:28:22 -04:00
Joseph Doherty 05ed039c73 fix(twincat): TOD write bound, historian note, driver-level refused-write test (#306)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:26:32 -04:00
Joseph Doherty da33f27544 feat(mtconnect): serve TIME_SERIES observations as variable-length double[] (#627)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:25:45 -04:00
Joseph Doherty 90e3fe1cf7 feat(twincat): TIME/TOD as Double ms, DATE/DT as UTC DateTime with read decode + write encode (#306)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 14:24:12 -04:00
Joseph Doherty 4a10ea1e1c fix(runtime): a removed driver's late writes no longer resurrect its resilience/telemetry state (#609)
DriverHostActor.StopChild released the tracker (Invalidate) and evicted the hub synchronously, but
Context.Stop is asynchronous: the stopping child's in-flight SubscribeBulk completed through its
capability invoker AFTER the release, and its RecordCallStart/RecordSuccess/RecordCallComplete
re-created the tracker entry, which DriverResilienceStatusPublisherService then re-emitted every tick
forever. Confirmed with a temporary stack capture in the tracker (removed): every post-Release write
came from DriverInstanceActor.HandleSubscribeAsync -> CapabilityInvoker.ExecuteAsync; the test failed
whenever it landed before the second publisher tick.

- DriverResilienceStatusTracker.Retire (Release) drops the id's snapshots and ignores every later
  Record* for it; one guarded write path re-checks after the upsert so a write racing Retire cannot
  survive it. Reinstate (called by DriverCapabilityInvokerFactory.Create) lifts it, so the same id
  re-added in a later deployment records again.
- TelemetryLocalHub.Evict now also holds the id (late Health/Resilience dropped, neither cached nor
  fanned out); ITelemetryLocalHub.Readmit (default no-op), called at the top of SpawnChild, lifts it.
- The removal test is now deterministic: an invoker decorator holds the child's subscribe inside the
  real invoker's bracket across the removal and signals when its late writes are done (positive
  control) — red 5/5 without the fix, green 20/20 with it. New unit tests for the tracker guard
  (incl. a Retire race), the factory Release/Create pair, the hub hold/readmit, and a re-add-same-id
  host test.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 09:07:11 -04:00
Joseph Doherty 31346f1ecd Merge review R6 fixes: numeric array writes converted element-wise (checked) to the node's element type, refusing out-of-range/fractional/NaN; array-to-scalar refusal scoped to Modbus/S7; Primary-verdict pre-join window documented + real MemberUp subscription test; passive LocalDb pair half drain-gated on its mesh partner
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 08:43:59 -04:00
Joseph Doherty 3be8a1217e fix(runtime): the passive half of a LocalDb pair stands its alarm drain down for its mesh partner (review R6 MINOR-4)
The drain gate's 'is my queue-sharing peer Primary?' used only the host of
LocalDb:Replication:PeerAddress, which the passive half (ApiKey +
SyncListenPort) does not set - so as Secondary it kept draining beside its
Primary partner and every alarm event reached the historian twice.
DriverHostActor takes a sharesAlarmQueueWithLocal predicate used when no
peer host is known; WithOtOpcUaRuntimeActors builds it
(BuildAlarmQueuePeerPredicate) for a SharesRowsWithPeer node with no
PeerAddress as 'a member of my own cluster-{ClusterId} mesh other than
me'. A node sharing no rows, or with no mesh role, gets none and keeps
draining. AlarmHistorian.md / Redundancy.md / pair-replication runbook
updated.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 08:43:06 -04:00
Joseph Doherty e93d115cbe fix(runtime): pin the Primary-verdict member-event subscription with a test; document the pre-join allow window (review R6 MINOR-2/3)
MINOR-3: new DriverHostActorPrimaryRoleSourceTests case drives the
deny flip with a real ClusterEvent.MemberUp on the EventStream (how the
cluster's domain-event publisher reaches a Cluster.Subscribe subscriber)
instead of a direct RepublishPrimaryVerdict tell; it fails when the
Cluster.Subscribe(IMemberEvent) call is deleted.

MINOR-2: the published verdict MIRRORS the live gate; before this node has
joined its member count is 0 and both allow (seconds; up to the bootstrap
guard's 25 s probe), so the Sparkplug primary-host claim can be held on
both nodes in that window (native ack is unaffected - view and route
agree). Behaviour deliberately unchanged: denying until self is Up would
change the live gate too and delay writes/acks on a single-node cluster's
own join. Comments + AlarmTracking.md / Redundancy.md / Mqtt.md corrected.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 08:33:52 -04:00
Joseph Doherty 52708bff52 fix(address-space): numeric array writes convert (checked) to the node element type; array-to-scalar refusal only for Modbus/S7 (#610 review R6)
MAJOR-1: R4's exact element-type match refused ScadaBridge's CLR-list
writes (its element types are only Boolean/Int32/Float/Double/String/
DateTime) to every Int16/UInt16/Byte/UInt32/Int64/UInt64 array node and a
Double list to a Float array. EvaluateEquipmentWriteStructure now converts
a numeric array of another numeric element type element-wise, CHECKED, into
the node's element type and hands the converted array back through
OnEquipmentTagWrite's ref value, so the node stores and the driver receives
the node's own type. Any out-of-range, fractional-to-integer, NaN/Inf-to-
integer or Float-overflowing element refuses the whole write BadTypeMismatch
(nothing dispatched) - so the UInt32 -> Int32 bit reinterpretation stays
closed. Non-numeric mismatches stay refused. The wrong 'no client relies on
a looser rule' comment is corrected.

MINOR-1: the array-value-to-scalar-node refusal broke writes back to
browse-committed array tags (committed scalar, isArray never set) on
pass-through drivers. It now applies only when the owning driver's scalar
encoder cannot take an array (DriverArrayWriteSupport.
RefusesArrayValueOnScalarTag: Modbus, S7), carried RawTagPlan.
ScalarRefusesArrayValue / UnsReferenceVariable.BackingScalarRefusesArrayValue
-> EnsureVariable(refuseArrayOnScalar) -> a per-node set in the node
manager. OpcUaClient/Galaxy/others keep pre-#610 dispatch. Not on the
classifier whitelist (driver-type edit rebuilds); a mirror whose flag
changes is recreated, not updated in place.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 08:31:46 -04:00
Joseph Doherty 2befe9f9ba docs: correct stale LDAP-role, host-probe, resilience-table, Bad-value claims; fix tasks.json (#624)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 08:16:43 -04:00
Joseph Doherty f383996127 docs: soften shared-volume remark in secrets runbook (#623)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 08:13:18 -04:00
Joseph Doherty 90bfcbe47a docs: rewrite IncrementalSync + AddressSpace for v3, fix driver-specs/driver-stability tier claims, update Secrets runbook for pair replication + KEK rotation (#623)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 08:13:14 -04:00
Joseph Doherty a702875d41 Merge review R4 fixes (#610): array writes require an exact element-type match (BadTypeMismatch, nothing sent); Galaxy encoder refuses uint[]/ulong[]; Modbus array writability bounded by maxRegistersPerWrite/coil cap; arrayLength >= 1 required; Galaxy arrays without a declared length stay read-only; arrays to scalar nodes refused
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 08:08:03 -04:00
Joseph Doherty dabd8eb955 fix(address-space): exact element-type check for array writes + array-capability shape edges (#610 review R4)
MAJOR-1: the SDK skips TypeInfo.IsInstanceOfDataType on any node with an
OnWriteValue handler (every writable equipment node), and the node manager's
fail-fast treated numeric<->numeric as compatible, so a UInt32[] to a Galaxy
Int32 array matched MxValueEncoder's int[] arm by CLR covariance and was
written bit-reinterpreted with a Good result. EvaluateEquipmentWriteStructure
now matches an ARRAY write's element type exactly (Byte[]/ByteString the only
equivalence; Variant[]/object[] refused) -> BadTypeMismatch, nothing
dispatched. MxValueEncoder's int[]/long[] arms are exact-type guarded too, and
the Galaxy parity test's false "the SDK refuses" premise is corrected (the
UInt32/UInt64 exclusion is now the encoder's own answer). Scalar writes keep
numeric widening by decision: consumers write CLR-typed values (Double to a
Float node) and every driver's scalar encoder range-checks.

MINOR: Modbus row honours maxRegistersPerWrite (smallest of DriverConfig /
the tag's DeviceConfig, default 123) and FC15's 1968-coil ceiling, and
requires region + numeric address; Modbus/S7/Galaxy require isArray + integer
arrayLength >= 1 (Galaxy: an unbounded node would let a short write resize the
attribute); an array value to a scalar node is refused inline. Docs: Uns.md
array-write rules + upgrade note (ReadWrite array tags become client-writable
on first boot), Modbus.md, Galaxy.md.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 08:07:36 -04:00
Joseph Doherty 3eefbc7371 Merge review R5 fixes: MTConnect session publish + generation bump atomic, superseded pumps joined on stop; MQTT writes encode the birth's own Sparkplug datatype (unsupported birth types refused BadNotSupported); AbLegacy dead init join removed + Dispose join test; MQTT QoS1 and Postgres key-normalisation documented
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:53:18 -04:00
Joseph Doherty 7628402893 fix(drivers): R5 minors - MTConnect session publish+generation atomic and superseded pump joined; MQTT birth-typed writes use the birth's own datatype; AbLegacy dead init join removed + Dispose join test; docs (#602)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:52:59 -04:00
Joseph Doherty b99aea46b2 Merge review R1 fixes: removed driver's resilience tracker released; SDK timed-unshelve no-op (engine owns expiry); commented re-ack stored as AddComment; native-ack Primary verdict published from start; drain gate SharesRowsWithPeer; malformed cache bytes don't adopt the revision; HostAbortedException passthrough; ClusterRoleInfo seed filtered
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:47:57 -04:00
Joseph Doherty e3dcb180c3 fix(runtime): Primary verdict published from host start, cache boot never adopts malformed bytes, strict drain-gate predicate, HostAbortedException passthrough, seed only Up members
Review R1:
- M1 (#609): DriverHostActor.StopChild releases the instance's resilience state before evicting the hub.
- m2 (#597): DriverHostActor publishes ShouldServiceAsPrimary() to IDriverPrimaryRoleSource at start and on
  cluster membership changes (deduped), so the native-ack gate denies in a pair's boot window.
- m4 (#601): ApplyCachedArtifact returns false on empty/malformed bytes; the cached revision is not adopted,
  Direct mode goes Stale (no RUNNING FROM CACHE), FetchAndCache lands Steady-with-no-revision and a
  re-dispatch of the same revision really applies.
- m3 (#603): LocalDbReplicationPolicy splits into CapturesChanges (PeerAddress||ApiKey, registration) and
  SharesRowsWithPeer (ApiKey && (PeerAddress||SyncListenPort>0), alarm drain gate).
- m5 (#618): Program.cs catch-all filters HostAbortedException (design-time tooling).
- m6 (Cluster-002): ClusterRoleInfo seeds only Up/WeaklyUp members.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:47:34 -04:00
Joseph Doherty 83e9ffd27a fix(alarms): SDK timed-unshelve timer is a no-op; commented re-ack comment is durable (#597)
Review R1 M2: since #597 the SDK timer fires at real expiry, and OnTimedUnshelve routed an operator-style
Unshelve by 'system' from both pair nodes, pre-empting the engine's AutoUnshelve. The engine owns expiry,
so the callback now routes nothing. Integration test: an engine stand-in that acts on a routed Unshelve and
expires late, plus a wrapped OnTimedUnshelve (positive control: the SDK timer fired).
Review R1 m1: Part9StateMachine.ApplyAcknowledge records a commented re-ack as AddComment (persisted and
replicated) instead of a NoOp; an uncommented re-ack is still a no-op.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:47:28 -04:00
Joseph Doherty 8a9bf23048 fix(telemetry): release a removed driver's resilience tracker state so the publisher stops re-emitting it (#609)
Review R1 M1: StopChild evicted the hub cache, but DriverResilienceStatusPublisherService re-emits the
tracker every tick. IDriverCapabilityInvokerFactory.Release (default no-op) now invalidates the pipeline
builder + status tracker; the host calls it before Evict. Test runs a publisher tick after removal, with a
neighbour instance as positive control.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:47:13 -04:00
Joseph Doherty b7a48e2b93 Merge #610: server-side array writes gated per driver capability (DriverArrayWriteSupport); ArrayWritable on the surgical whitelist + UNS Backing; shape/IndexRange refusal; ValueRank>1 out of scope
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe

# Conflicts:
#	docs/drivers/S7.md
2026-10-08 07:39:40 -04:00
Joseph Doherty 18f8eb5d2f feat(address-space): server-side array writes gated per driver capability (#610)
Array nodes were forced read-only for every driver. A new single authority,
Core.Abstractions DriverArrayWriteSupport, says which (driver, element type)
pairs encode a whole-array write: Modbus (Coils / numeric HoldingRegisters),
S7 (Byte/Int16/UInt16/Int32/UInt32/Float32), OpcUaClient (pass-through) and
Galaxy (Boolean/Int32/Int64/Float/Double/String/DateTime). Everything else
stays read-only, so the server never advertises a write the driver refuses.

- Composer derives RawTagPlan.ArrayWritable + UnsReferenceVariable
  .BackingArrayWritable at compose time (both seams, byte-parity); the
  applier's one writability rule is Writable && (!IsArray || ArrayWritable)
  for materialise and surgical paths, raw and UNS alike.
- ArrayWritable is on the classifier's surgical raw-tag whitelist and
  mirrored on the UNS record (UnsReferenceBackingParityTests updated).
- Node manager refuses a wrong-length / non-array value on an array node
  (BadTypeMismatch) and any IndexRange write (BadWriteNotSupported) inline,
  before dispatch; WriteOperate/ACL gates and the revert are unchanged.
- Per-driver parity tests pin the table against the real Modbus write path,
  S7 EncodeArrayBlock and Galaxy MxValueEncoder (UInt32/UInt64 excluded:
  array covariance reinterprets their bits).
- Over-the-wire proof in OpcUaServer.IntegrationTests (ArrayWriteWireTests).
- ValueRank > 1 documented as out of scope by decision (docs/Uns.md).

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:39:05 -04:00
Joseph Doherty b29642c5da Merge #602 stability: FOCAS/AbLegacy loop joins on shutdown, Postgres untyped string binds, MTConnect pump generation, MQTT birth-typed writes + QoS1 plain writes + claim backoff
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:33:03 -04:00
Joseph Doherty babc452740 docs(drivers): MQTT write QoS/claim backoff and Sql Postgres untyped binds (#602)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:32:42 -04:00