OtOpcUaNodeManager.MapSeverity re-bucketed every projected severity onto the
SDK's five EventSeverity values (<800 -> 700, else 900), defeating #626's exact
OpcUaSeverity: an MTConnect Fault (800) read and evented as 900; a scripted
alarm graded 1000 published 900 while /alerts said 1000; a native Low (200)
published 300. EventSeverity merely names points on the 1..1000 scale, so the
node now carries the value clamped to 1..1000 (ToPart9Severity), at
materialise, projection and in the delta gate.
MTConnect wire test now asserts Fault ActiveState=true/Severity=800 and the
Normal clear ActiveState=false/Retain=false/Severity=800.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
EventFilter.AddSelectClause(type, "ActiveState/Id") does not split the string;
it selects a single QualifiedName named "ActiveState/Id", which no event carries.
AckedState/Id, ActiveState/Id and EnabledState/Id therefore always arrived null
and Client.CLI 'alarms' (and Client.UI) reported every alarm inactive and
unacknowledged while a direct Read said Active. Pre-existing since a2883b82;
server-side event delivery was correct (proven with two-element select clauses,
incl. after #629). Select them with explicit two-element browse paths.
Over-the-wire test drives OpcUaClientService.SubscribeAlarmsAsync against the
in-process server (native + scripted); ServerEventRig now also selects
ActiveState/Id, Severity and Retain.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- Unavailable keeps an ACTIVE condition active: quality-only BadNoCommunication; on data
return same statement => quality-only Good, Normal => Clear, different => Retrigger.
- A changed alarm reference set (alarm-bearing delta = full rebuild) clears the whole
last-told record so every active condition is re-asserted; the same set keeps it.
- Quality-only events go through the host's AlarmQualityUpdate path, never a projected
snapshot (which could ack a retained unacked condition or rewrite message/severity).
- Deterministic tie-break between equal-level conditions (ordinal nativeCode, then type).
- Dedup key is level+nativeCode+nativeSeverity+qualifier; a text-only change updates nothing.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
MTConnectConditionAlarmWireTests drives a scripted Agent's Fault/Normal through the real
driver, NativeAlarmProjector and sink to a client event subscription on the raw device
folder. docs/drivers/MTConnect.md replaces 'CONDITION v1: plain String' with the alarm
mapping, opt-in authoring, multi-condition, ack, replay and comms-loss behaviour, and a
live-check recipe; EVENT vocabularies as enumerations marked won't-fix. AlarmTracking.md
lists the MTConnect source and the two new AlarmEventArgs fields.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
New() ran FindNodeInAddressSpace under Lock, taking other node managers' locks (lock-order
risk); the three AlarmConditionType_ShelvingState_* ids are now a static set. Adds wire tests:
TimedShelve/Unshelve by the condition's own instance method ids (object = condition or its
ShelvingState) succeed and report, and a ShelvedStateMachineType_* id call is pinned as
BadMethodInvalid with a positive control.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The parser keeps a condition's text, nativeCode, nativeSeverity, qualifier and type. A new
MTConnectConditionTracker applies MTConnect's multi-condition semantics (per-nativeCode
activation/clearing across /sample deltas, /current baseline reset, Unavailable), and
MTConnectConditionAlarmMapper turns tracker state into Part 9 transitions: Warning=500,
Fault=800, Normal=clear, Unavailable=inactive + BadNoCommunication; escalation or a new
code retriggers. The driver implements IAlarmSource keyed by the alarm tag's RawPath,
diffs against what the server was actually told (only when a handler is attached), so a
reconnect/re-baseline never re-raises an unchanged condition and a missed transition is
delivered on the next subscribe. Ack is a no-op success. Existing CONDITION String tags
are unchanged; a tag becomes an alarm only via the standard TagConfig 'alarm' object.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
AlarmEventArgs gains optional OpcUaSeverity (supersedes the four-bucket mapping, clamped
1..1000) and QualityStatusCode (projected onto the condition's Quality). An Unspecified-kind
event carrying a quality is a quality-only annotation: the host updates the condition but
publishes no alerts row. Both default null, so every existing native source is unchanged.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Create(assignNodeIds: true) asked CustomNodeManager2.New, whose default returns the
node's current id, so every condition child kept the type's ns=0 instance-declaration id
(or an SDK-generated ns=0 number): translate of a child path returned BadNoMatch and a
Read of a browsed child id was BadNodeIdUnknown or served from the TYPE (UnshelveTime 0
on a condition timed-shelved for a minute), bypassing the data-plane ACL.
OtOpcUaNodeManager.New now derives {conditionId}/{browsePath} in the condition's
namespace, so the ACL scope of a child is its condition's scope plus the path. The
ShelvingState methods adopt their original AlarmConditionType_ShelvingState_* id as
MethodDeclarationId so clients calling them by that id still resolve. Condition removal
and rebuild forget the whole PredefinedNodes subtree so a removed condition's children
stop answering.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
New S7DataType members WString/Char/WChar/Dtl/Date/Tod/Time/S5Time mapped onto existing
DriverDataType (String / DateTime / Int32 ms); writes refuse out-of-range with BadOutOfRange.
Optional localTsap/remoteTsap/connectionType through options, factory JSON, probe and AdminUI form.
NegotiatedPduSize snapshotted at connect and exposed via GetDiagnostics (DriverHealth has no bag).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
FOCAS, AbLegacy, AbCip, TwinCAT, S7 and OpcUaClient orphaned the previous
probe/recycle/fixed-tree loops and clients when re-initialised on a live driver.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Live-measured on docker-dev: the backdrop was viewport-wide (1911px) but started at the
panel's left edge (241px) because the theme's .rise animation (fill-mode both) leaves an
identity transform on section.panel, re-basing position:fixed descendants. Override the
fill mode to backwards; drops the speculative backdrop/dialog sizing overrides.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
DriverHostActor.StopChild released the tracker (Invalidate) and evicted the hub synchronously, but
Context.Stop is asynchronous: the stopping child's in-flight SubscribeBulk completed through its
capability invoker AFTER the release, and its RecordCallStart/RecordSuccess/RecordCallComplete
re-created the tracker entry, which DriverResilienceStatusPublisherService then re-emitted every tick
forever. Confirmed with a temporary stack capture in the tracker (removed): every post-Release write
came from DriverInstanceActor.HandleSubscribeAsync -> CapabilityInvoker.ExecuteAsync; the test failed
whenever it landed before the second publisher tick.
- DriverResilienceStatusTracker.Retire (Release) drops the id's snapshots and ignores every later
Record* for it; one guarded write path re-checks after the upsert so a write racing Retire cannot
survive it. Reinstate (called by DriverCapabilityInvokerFactory.Create) lifts it, so the same id
re-added in a later deployment records again.
- TelemetryLocalHub.Evict now also holds the id (late Health/Resilience dropped, neither cached nor
fanned out); ITelemetryLocalHub.Readmit (default no-op), called at the top of SpawnChild, lifts it.
- The removal test is now deterministic: an invoker decorator holds the child's subscribe inside the
real invoker's bracket across the removal and signals when its late writes are done (positive
control) — red 5/5 without the fix, green 20/20 with it. New unit tests for the tracker guard
(incl. a Retire race), the factory Release/Create pair, the hub hold/readmit, and a re-add-same-id
host test.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The drain gate's 'is my queue-sharing peer Primary?' used only the host of
LocalDb:Replication:PeerAddress, which the passive half (ApiKey +
SyncListenPort) does not set - so as Secondary it kept draining beside its
Primary partner and every alarm event reached the historian twice.
DriverHostActor takes a sharesAlarmQueueWithLocal predicate used when no
peer host is known; WithOtOpcUaRuntimeActors builds it
(BuildAlarmQueuePeerPredicate) for a SharesRowsWithPeer node with no
PeerAddress as 'a member of my own cluster-{ClusterId} mesh other than
me'. A node sharing no rows, or with no mesh role, gets none and keeps
draining. AlarmHistorian.md / Redundancy.md / pair-replication runbook
updated.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
MINOR-3: new DriverHostActorPrimaryRoleSourceTests case drives the
deny flip with a real ClusterEvent.MemberUp on the EventStream (how the
cluster's domain-event publisher reaches a Cluster.Subscribe subscriber)
instead of a direct RepublishPrimaryVerdict tell; it fails when the
Cluster.Subscribe(IMemberEvent) call is deleted.
MINOR-2: the published verdict MIRRORS the live gate; before this node has
joined its member count is 0 and both allow (seconds; up to the bootstrap
guard's 25 s probe), so the Sparkplug primary-host claim can be held on
both nodes in that window (native ack is unaffected - view and route
agree). Behaviour deliberately unchanged: denying until self is Up would
change the live gate too and delay writes/acks on a single-node cluster's
own join. Comments + AlarmTracking.md / Redundancy.md / Mqtt.md corrected.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
MAJOR-1: R4's exact element-type match refused ScadaBridge's CLR-list
writes (its element types are only Boolean/Int32/Float/Double/String/
DateTime) to every Int16/UInt16/Byte/UInt32/Int64/UInt64 array node and a
Double list to a Float array. EvaluateEquipmentWriteStructure now converts
a numeric array of another numeric element type element-wise, CHECKED, into
the node's element type and hands the converted array back through
OnEquipmentTagWrite's ref value, so the node stores and the driver receives
the node's own type. Any out-of-range, fractional-to-integer, NaN/Inf-to-
integer or Float-overflowing element refuses the whole write BadTypeMismatch
(nothing dispatched) - so the UInt32 -> Int32 bit reinterpretation stays
closed. Non-numeric mismatches stay refused. The wrong 'no client relies on
a looser rule' comment is corrected.
MINOR-1: the array-value-to-scalar-node refusal broke writes back to
browse-committed array tags (committed scalar, isArray never set) on
pass-through drivers. It now applies only when the owning driver's scalar
encoder cannot take an array (DriverArrayWriteSupport.
RefusesArrayValueOnScalarTag: Modbus, S7), carried RawTagPlan.
ScalarRefusesArrayValue / UnsReferenceVariable.BackingScalarRefusesArrayValue
-> EnsureVariable(refuseArrayOnScalar) -> a per-node set in the node
manager. OpcUaClient/Galaxy/others keep pre-#610 dispatch. Not on the
classifier whitelist (driver-type edit rebuilds); a mirror whose flag
changes is recreated, not updated in place.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe