F1: the driver's outage BadNoCommunication carried the last Good sample's
source timestamp. The recorder historizes SourceTimestampUtc ??
ServerTimestampUtc, so the Bad landed on the Good row's (TagId,
SourceTimeUtc) key and the insert-if-absent historian dropped it - no
outage marker until the host's watchdog marker ~95 s in, none at all for
a short blip. Now stamped with the detection time (source + server), as
the host's comms-loss fan does.
F2: after a same-session recovery the SDK delivered a missed notification
seconds late with an older source time and the node regressed. A
notification older than the newest Good upstream source time for its ref
(notification or recovery read) is dropped and counted
(stale_notification_dropped); equal timestamps pass; the outage Bad never
moves the comparison; a re-initialise resets it.
A bad keep-alive now degrades health (LastSuccessfulRead preserved) and,
once per outage, publishes BadNoCommunication (value retained) for every
subscribed ref plus a quality-only annotation on subscribed alarm
conditions. Good keep-alives and data/event notifications advance
LastSuccessfulRead, so an idle-but-alive subscription never looks dead
to the #527 watchdog. A keep-alive that recovers on the same session
re-reads the Bad refs and republishes them Good; a session that does not
come back is recovered by the watchdog's ShutdownAsync + InitializeAsync
+ re-subscribe.
Deletes the SessionReconnectHandler wiring (it retried forever in SDK
1.5.378, cloned subscriptions the driver never re-tracked and kept health
Healthy), OnReconnectComplete, TryRearmReconnect and the reconnect_*
counters (new keepalive_recovered). Teardown of a lost session skips
wire deletes and bounds CloseSession. SDK warnings reach the driver log.
Wire test reworked: restart => Bad, then watchdog-style reinit => Good.
IHistorianDataSource.TimestampResolutionTicks (default 1; QuestDB 10). A drained tie
cluster now steps off T by the resolution, so a forward one-value-per-page read on a
microsecond backend no longer re-reads the same sample forever (C1). QuestDB AtTime
results carry the client's original request time (M3); regression for the NEXT seek
skipping a tombstone (M1). Conformance backend wires the real writer and updater.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- OtOpcUaNodeManager overrides HistoryUpdateData / HistoryDeleteRawModified / HistoryDeleteAtTime,
block-bridging to the optional IHistorianDataUpdater under the shared HistoryRead batch limiter +
deadline. Insert/Replace/Update map to HistoryUpdateMode; Remove, IsDeleteModified, events and
structure data are BadHistoryOperationUnsupported. Per-item codes stitched back in request order
(MinValue SourceTimestamp => BadInvalidTimestamp, untypeable value => BadTypeMismatch); success
clears the base's pre-seeded Unsupported error.
- HistoryWrite AccessLevel bit OR-ed in for historized nodes when an updater is wired (raw + UNS);
it is dispatch-load-bearing in the SDK base. OtOpcUaSdkServer.SetHistorianDataUpdater; the hosted
service assigns it from an optional HistorianUpdaterHolder before SetSink, clears it on stop.
- AuthorizeHistoryUpdate: ACL on => scoped OpcUaOperation.HistoryUpdate decision (replaces the role
check); ACL off => #563 key re-check + new OpcUaDataPlaneRoles.HistoryUpdate role, conferred by
ApiKeyInterimRoleMapper only from a Cluster-scoped HistoryUpdate grant (WriteOperate does not).
- AdminUI ACL editor offers NodePermissions.HistoryUpdate.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Since #516 a DriverConfig change is stop + respawn, so DriverSpawnPlan.ToApplyDelta
was always empty and the in-place path had no producer. #663 and #664 were both
latent bugs in it. This deletes it:
- host: ApplyChildDelta, _pendingDelta, HandleApplyResult and HandleDeltaApplied
- plan: DriverSpawnPlan.ToApplyDelta
- actor: the ApplyDelta, ApplyResult and DeltaApplied messages, the Connected
reinit handler and the mid-connect AdoptConfigDuringInit
- tests: the actor tests that drove the seam
IDriver.ReinitializeAsync and each driver's implementation and unit tests stay.
Comments and docs that cited AdoptConfigDuringInit as the reason a driver must
release prior state at init now cite the IDriver contract and overlapping
retries, which still apply.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
After an OpcUaClient respawn an upstream inactive+unacked condition went out as
Retrigger+Clear (duplicate Activated+Cleared rows, Active flicker), and a
first-sight inactive+acked one as Unspecified (an Activated row for an inactive
alarm; a retained-Active host condition never cleared).
- New AlarmTransitionKind.InactiveUnacknowledged: one projection, rows only for
what changed (Activated+Cleared from acked, Cleared from active+unacked, none
when already inactive+unacked).
- OpcUaClient uses it for moves into inactive+unacked; first sight of an
inactive condition is InactiveUnacknowledged or Clear+Acknowledge, flagged.
- Projector: a flagged Acknowledge on an already-acked condition writes no row.
- E2E tests through DriverHostActor.ForwardNativeAlarm (red-proven).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- AlarmTransitionKind.ActiveAcknowledged (appended): active AND acked applied as ONE projection.
Galaxy ActiveAcked snapshot entries and OpcUaClient inactive->(active,acked) use it; the
projector writes 'Activated' only if not already active, 'Acknowledged' only if not acked.
- AlarmEventArgs.IsRestatement (optional, default false): set only by Galaxy snapshot entries
and OpcUaClient first sight. A flagged Retrigger on an Active+unacked condition with the same
message and severity, or a flagged Clear on an inactive condition, writes no /alerts row.
- NativeAlarmProjector reports the history rows per transition; ForwardNativeAlarm writes one
row per entry. Unflagged sources (FOCAS/MTConnect/AbCip, live Galaxy) are unchanged.
- Tests: projector rules each with a must-write control; OpcUaClient transition table;
Galaxy feed/driver mapping; Galaxy + OpcUaClient end-to-end through DriverHostActor.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
HistoryRead is served server-side by IHistorianDataSource; nothing ever dispatched
to a driver's IHistoryProvider. Removes IHistoryProvider, the OpcUaClient history
passthrough, DriverCapability.HistoryRead (+ resilience tier rows and AdminUI row),
HistoryReadStatusException and its node-manager catches, and the tests that only
covered them. Shared result types and HistoryAggregateNotSupportedException stay
(moved to Historian/HistoryReadContracts.cs). A stored ResilienceConfig still
carrying a HistoryRead key parses (diagnostic only; new test).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
60 s labelled a slow-but-clean large rebuild degraded. The deadline moves to a
shared Commons DeployTimings constant that ConfigPublishCoordinator reads, and
the node's timeout is deadline - 15 s margin, so the held ack still lands in
time. A timed-out ack's reason now says the outcome was not reported in time,
distinct from a real sink failure.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The apply writes the node's row Applied/null before the address-space outcome
is known; central adds the reason only when it ACCEPTS the ack, so a discarded
(stale/timed-out) ack left a fused node's row reading clean. The prefix moves
to ApplyAck.DegradedReasonPrefix so both writers spell the row identically.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
ApplyAck gains trailing Degraded/DegradedReason (defaulted, so an old node's
DPS JSON or gRPC ack decodes exactly as before). mesh_transport.proto adds
ApplyAckMessage.degraded = 6 / optional degraded_reason = 7. OpcUaPublishActor
replies RebuildCompleted(Degraded, Reason) on every handler path when the
RebuildAddressSpace carries ReportOutcome.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A full RebuildAddressSpace recreated every native Part 9 condition inactive +
acknowledged, and when the alarm-tag set was unchanged (e.g. one
UnsTagReference added to an alarm-bearing raw tag) nothing re-told the new node
its state: the host does not re-subscribe for an unchanged set, and Galaxy /
OpcUaClient have no snapshot to replay anyway. Active alarms read normal until
their next device transition.
OtOpcUaNodeManager now captures each NATIVE condition's live state (from the
node, so a client-applied ack is kept) before the rebuild clears, restores it
when the same id is re-materialised native in the same apply, and reports ONE
condition event per restored off-normal condition at the new
IOpcUaAddressSpaceSink.CompleteAddressSpaceApply (after notifier wiring).
Unclaimed captures are discarded there, so a later re-add is fresh. Quality is
carried silently for normal conditions too (it is only re-annotated on a
connectivity edge). Scripted conditions are untouched (#487 re-asserts them).
OpcUaPublishActor calls CompleteAddressSpaceApply at the end of every apply.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
AlarmEventArgs gains optional OpcUaSeverity (supersedes the four-bucket mapping, clamped
1..1000) and QualityStatusCode (projected onto the condition's Quality). An Unspecified-kind
event carrying a quality is a quality-only annotation: the host updates the condition but
publishes no alerts row. Both default null, so every existing native source is unchanged.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
DriverHostActor.StopChild released the tracker (Invalidate) and evicted the hub synchronously, but
Context.Stop is asynchronous: the stopping child's in-flight SubscribeBulk completed through its
capability invoker AFTER the release, and its RecordCallStart/RecordSuccess/RecordCallComplete
re-created the tracker entry, which DriverResilienceStatusPublisherService then re-emitted every tick
forever. Confirmed with a temporary stack capture in the tracker (removed): every post-Release write
came from DriverInstanceActor.HandleSubscribeAsync -> CapabilityInvoker.ExecuteAsync; the test failed
whenever it landed before the second publisher tick.
- DriverResilienceStatusTracker.Retire (Release) drops the id's snapshots and ignores every later
Record* for it; one guarded write path re-checks after the upsert so a write racing Retire cannot
survive it. Reinstate (called by DriverCapabilityInvokerFactory.Create) lifts it, so the same id
re-added in a later deployment records again.
- TelemetryLocalHub.Evict now also holds the id (late Health/Resilience dropped, neither cached nor
fanned out); ITelemetryLocalHub.Readmit (default no-op), called at the top of SpawnChild, lifts it.
- The removal test is now deterministic: an invoker decorator holds the child's subscribe inside the
real invoker's bracket across the removal and signals when its late writes are done (positive
control) — red 5/5 without the fix, green 20/20 with it. New unit tests for the tracker guard
(incl. a Retire race), the factory Release/Create pair, the hub hold/readmit, and a re-add-same-id
host test.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
MAJOR-1: R4's exact element-type match refused ScadaBridge's CLR-list
writes (its element types are only Boolean/Int32/Float/Double/String/
DateTime) to every Int16/UInt16/Byte/UInt32/Int64/UInt64 array node and a
Double list to a Float array. EvaluateEquipmentWriteStructure now converts
a numeric array of another numeric element type element-wise, CHECKED, into
the node's element type and hands the converted array back through
OnEquipmentTagWrite's ref value, so the node stores and the driver receives
the node's own type. Any out-of-range, fractional-to-integer, NaN/Inf-to-
integer or Float-overflowing element refuses the whole write BadTypeMismatch
(nothing dispatched) - so the UInt32 -> Int32 bit reinterpretation stays
closed. Non-numeric mismatches stay refused. The wrong 'no client relies on
a looser rule' comment is corrected.
MINOR-1: the array-value-to-scalar-node refusal broke writes back to
browse-committed array tags (committed scalar, isArray never set) on
pass-through drivers. It now applies only when the owning driver's scalar
encoder cannot take an array (DriverArrayWriteSupport.
RefusesArrayValueOnScalarTag: Modbus, S7), carried RawTagPlan.
ScalarRefusesArrayValue / UnsReferenceVariable.BackingScalarRefusesArrayValue
-> EnsureVariable(refuseArrayOnScalar) -> a per-node set in the node
manager. OpcUaClient/Galaxy/others keep pre-#610 dispatch. Not on the
classifier whitelist (driver-type edit rebuilds); a mirror whose flag
changes is recreated, not updated in place.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
MAJOR-1: the SDK skips TypeInfo.IsInstanceOfDataType on any node with an
OnWriteValue handler (every writable equipment node), and the node manager's
fail-fast treated numeric<->numeric as compatible, so a UInt32[] to a Galaxy
Int32 array matched MxValueEncoder's int[] arm by CLR covariance and was
written bit-reinterpreted with a Good result. EvaluateEquipmentWriteStructure
now matches an ARRAY write's element type exactly (Byte[]/ByteString the only
equivalence; Variant[]/object[] refused) -> BadTypeMismatch, nothing
dispatched. MxValueEncoder's int[]/long[] arms are exact-type guarded too, and
the Galaxy parity test's false "the SDK refuses" premise is corrected (the
UInt32/UInt64 exclusion is now the encoder's own answer). Scalar writes keep
numeric widening by decision: consumers write CLR-typed values (Double to a
Float node) and every driver's scalar encoder range-checks.
MINOR: Modbus row honours maxRegistersPerWrite (smallest of DriverConfig /
the tag's DeviceConfig, default 123) and FC15's 1968-coil ceiling, and
requires region + numeric address; Modbus/S7/Galaxy require isArray + integer
arrayLength >= 1 (Galaxy: an unbounded node would let a short write resize the
attribute); an array value to a scalar node is refused inline. Docs: Uns.md
array-write rules + upgrade note (ReadWrite array tags become client-writable
on first boot), Modbus.md, Galaxy.md.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Review R1:
- M1 (#609): DriverHostActor.StopChild releases the instance's resilience state before evicting the hub.
- m2 (#597): DriverHostActor publishes ShouldServiceAsPrimary() to IDriverPrimaryRoleSource at start and on
cluster membership changes (deduped), so the native-ack gate denies in a pair's boot window.
- m4 (#601): ApplyCachedArtifact returns false on empty/malformed bytes; the cached revision is not adopted,
Direct mode goes Stale (no RUNNING FROM CACHE), FetchAndCache lands Steady-with-no-revision and a
re-dispatch of the same revision really applies.
- m3 (#603): LocalDbReplicationPolicy splits into CapturesChanges (PeerAddress||ApiKey, registration) and
SharesRowsWithPeer (ApiKey && (PeerAddress||SyncListenPort>0), alarm drain gate).
- m5 (#618): Program.cs catch-all filters HostAbortedException (design-time tooling).
- m6 (Cluster-002): ClusterRoleInfo seeds only Up/WeaklyUp members.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Review R1 M2: since #597 the SDK timer fires at real expiry, and OnTimedUnshelve routed an operator-style
Unshelve by 'system' from both pair nodes, pre-empting the engine's AutoUnshelve. The engine owns expiry,
so the callback now routes nothing. Integration test: an engine stand-in that acts on a routed Unshelve and
expires late, plus a wrapped OnTimedUnshelve (positive control: the SDK timer fired).
Review R1 m1: Part9StateMachine.ApplyAcknowledge records a commented re-ack as AddComment (persisted and
replicated) instead of a NoOp; an uncommented re-ack is still a no-op.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Review R1 M1: StopChild evicted the hub cache, but DriverResilienceStatusPublisherService re-emits the
tracker every tick. IDriverCapabilityInvokerFactory.Release (default no-op) now invalidates the pipeline
builder + status tracker; the host calls it before Evict. Test runs a publisher tick after removal, with a
neighbour instance as positive control.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Array nodes were forced read-only for every driver. A new single authority,
Core.Abstractions DriverArrayWriteSupport, says which (driver, element type)
pairs encode a whole-array write: Modbus (Coils / numeric HoldingRegisters),
S7 (Byte/Int16/UInt16/Int32/UInt32/Float32), OpcUaClient (pass-through) and
Galaxy (Boolean/Int32/Int64/Float/Double/String/DateTime). Everything else
stays read-only, so the server never advertises a write the driver refuses.
- Composer derives RawTagPlan.ArrayWritable + UnsReferenceVariable
.BackingArrayWritable at compose time (both seams, byte-parity); the
applier's one writability rule is Writable && (!IsArray || ArrayWritable)
for materialise and surgical paths, raw and UNS alike.
- ArrayWritable is on the classifier's surgical raw-tag whitelist and
mirrored on the UNS record (UnsReferenceBackingParityTests updated).
- Node manager refuses a wrong-length / non-array value on an array node
(BadTypeMismatch) and any IndexRange write (BadWriteNotSupported) inline,
before dispatch; WriteOperate/ACL gates and the revert are unchanged.
- Per-driver parity tests pin the table against the real Modbus write path,
S7 EncodeArrayBlock and Galaxy MxValueEncoder (UInt32/UInt64 excluded:
array covariance reinterprets their bits).
- Over-the-wire proof in OpcUaServer.IntegrationTests (ArrayWriteWireTests).
- ValueRank > 1 documented as out of scope by decision (docs/Uns.md).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- Native-condition Acknowledge on a non-Primary node returns BadInvalidState (nothing
routed/applied/reported) via NativeAlarmAckPrimaryGate, fed from
IDriverPrimaryRoleSource by OtOpcUaServerHostedService.
- A re-ack carrying a comment reports one comment event (Acked/Confirmed unchanged).
- TimedShelve applies its requested duration and the scripted projection carries
UnshelveAtUtc, so ShelvingState/UnshelveTime counts down instead of ~24.8 days.
- Native re-ack still routed to the driver (deliberate: documented retry path), pinned.
- AdminUI /alerts client ack/shelve path test; docs/AlarmTracking.md decisions incl.
accepted SDK EventsMonitored residual (item 6).
- Also #599/03/S20: RemoveEquipmentSubtree severs inverse Organizes edges.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
ClusterRoleInfo resolved the leader address through Cluster.State.Members, which is
published asynchronously; a miss stored null permanently, so RoleLeader(role) stayed null
(flaky test timed out under load: 6/10 failing with CPU contention, 0/20 after). Only the
address is ever read, so store it directly. Adds a deterministic unit test (fails without
the fix) and InternalsVisibleTo for the Cluster.Tests project.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
options.Roles is unconditionally overwritten by AddOtOpcUaCluster's PostConfigure to equal
EffectiveRoles.Gossiped (T2's own structural-identity fix), so comparing options.Roles against
Gossiped could never observe a divergence — an overlay setting Cluster:Roles was silently
ignored, not fail-start. The validator now injects IConfiguration and re-reads the raw
Cluster:Roles section LIVE (reflecting any overlay applied after EffectiveRoles was first
resolved), normalized through EffectiveRoles.Resolve for reuse of its own validation.
AddOtOpcUaCluster now TryAddSingleton(configuration) so a bare ServiceCollection test harness
(not just WebApplicationBuilder) can supply IConfiguration to the validator.
Both guard tests rewritten to go through the real AddOtOpcUaCluster + PostConfigure pipeline
over a live ConfigurationManager, simulating an overlay as a second provider added AFTER
EffectiveRoles was resolved off the same object — exactly Program.cs's own sequencing. Confirmed
red beforehand: the "changes" test failed to throw against the pre-fix validator.