A Connected ApplyDelta called ReinitializeAsync and kept the actor's data and
native-alarm handles, though every driver's reinit drops the driver-side
subscriptions behind them (#630). The reconcile only re-subscribes a missing
handle, so the driver went silent until a reconnect. Release both at the
driver before the reinit and re-subscribe both in a finally. Unreachable from
deploys since #516; pinned by a two-case test, each case failing against a
different wrong fix.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- Reconcile retries of a failing alarm subscribe back off (skip 2^(n-1)-1
ticks, cap 7 => >= every 4 min at the 30 s tick) so a hanging subscribe
cannot hold the mailbox every tick; the stack is logged once per streak.
- The unreachable handler re-attach logs at Warning (it only fires on a
regression).
- OpcUaClient: a failed SubscribeAlarmsAsync detaches its notification
handler and bounds the session cleanup to 5 s under _gate;
OnEventNotification drops events from subscriptions not registered in
_alarmSubscriptions, so a stray that survives cleanup cannot deliver.
- The retry test also covers 3 failures (crosses the backoff); its tick
positive control documents its dependence on the stub's changing health.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A data re-subscribe (every deploy's bulk SetDesiredSubscriptions push to a
kept driver) dropped the prior data subscription through the full
DetachSubscription, which also unhooked OnAlarmEvent and forgot the alarm
handle. On any deploy that did not respawn the driver, the alarm
subscription kept logging "established" while every event reached nobody
until a reconnect or respawn. The data path now uses DetachDataSubscription;
only a lost connection and PostStop detach both.
The #488 health-poll reconcile only looked at data, so an alarm subscribe
that failed on (re)connect gated the feed for the life of the connection.
ReconcileAlarmSubscription now re-attaches a missing handler and
re-subscribes a stale/missing alarm handle every tick.
OpcUaClient removes a half-built alarm subscription from its session when
SubscribeAlarmsAsync throws, so the new retries cannot accumulate.
Tests: actor-level data-resubscribe + reconcile-retry tests and an
end-to-end NativeAlarmFeedSurvivesDeployTests through DriverHostActor; all
three fail against the unfixed actor.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
After an OpcUaClient respawn an upstream inactive+unacked condition went out as
Retrigger+Clear (duplicate Activated+Cleared rows, Active flicker), and a
first-sight inactive+acked one as Unspecified (an Activated row for an inactive
alarm; a retained-Active host condition never cleared).
- New AlarmTransitionKind.InactiveUnacknowledged: one projection, rows only for
what changed (Activated+Cleared from acked, Cleared from active+unacked, none
when already inactive+unacked).
- OpcUaClient uses it for moves into inactive+unacked; first sight of an
inactive condition is InactiveUnacknowledged or Clear+Acknowledge, flagged.
- Projector: a flagged Acknowledge on an already-acked condition writes no row.
- E2E tests through DriverHostActor.ForwardNativeAlarm (red-proven).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
M1 drop-out is a no-row Unspecified+IsRestatement update (projector case); M2 ack judged over every declared
limit; L1 ActiveAcknowledged for an already-acked new limit; L2 Bad Acked/severity carried/skipped; L3 host
end-to-end test; L4 BOOL member-by-member tests + mixed ALMD/ALMA; L5 detection requires no plain Acked.
ALMD active bit is InAlarm per Rockwell's ALMD reference; InFaulted is input health.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- AlarmTransitionKind.ActiveAcknowledged (appended): active AND acked applied as ONE projection.
Galaxy ActiveAcked snapshot entries and OpcUaClient inactive->(active,acked) use it; the
projector writes 'Activated' only if not already active, 'Acknowledged' only if not acked.
- AlarmEventArgs.IsRestatement (optional, default false): set only by Galaxy snapshot entries
and OpcUaClient first sight. A flagged Retrigger on an Active+unacked condition with the same
message and severity, or a flagged Clear on an inactive condition, writes no /alerts row.
- NativeAlarmProjector reports the history rows per transition; ForwardNativeAlarm writes one
row per entry. Unflagged sources (FOCAS/MTConnect/AbCip, live Galaxy) are unchanged.
- Tests: projector rules each with a must-write control; OpcUaClient transition table;
Galaxy feed/driver mapping; Galaxy + OpcUaClient end-to-end through DriverHostActor.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
HistoryRead is served server-side by IHistorianDataSource; nothing ever dispatched
to a driver's IHistoryProvider. Removes IHistoryProvider, the OpcUaClient history
passthrough, DriverCapability.HistoryRead (+ resilience tier rows and AdminUI row),
HistoryReadStatusException and its node-manager catches, and the tests that only
covered them. Shared result types and HistoryAggregateNotSupportedException stay
(moved to Historian/HistoryReadContracts.cs). A stored ResilienceConfig still
carrying a HistoryRead key parses (diagnostic only; new test).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
CentralCommunicationActor: while the PSK provider is unresolved or the first
ClusterNode load failed, re-arm RefreshContacts every 2 s (max 15) until the
first publish; Information log on first publish; 'NEVER be published' Error
now only after the retry budget is exhausted. Corrected false comments.
Tests: late provider (Grpc+Dps), failed first load, retries stop, bounded budget;
ControlPlaneStarterOrderTests back to the default 60 s refresh.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
R1: NativeAlarmProjector treats Raise-on-Active as a re-statement only when the message matches what
the condition shows; a different alarm appearing during a respawn un-acks and writes its alerts row.
FOCAS condition messages are a deterministic function of the matched set (tested across fresh driver
instances and reordered lists); Runtime E2E now covers both the same alarm and a new one during a
respawn. Residual (source message determinism) documented in AlarmTracking.md.
R2: a non-OK cnc_rdalmmsg2 return is thrown as FocasWireException{Rc} and classified as a CNC
refusal: conditions get a quality-only BadNotSupported once, one Warning, polling continues, and
driver health is untouched (no 90 s watchdog reconnect loop on a production control). Only transport
faults degrade (falsification control in the test).
R3: alarm-path health is tracked apart from the value path and combined in GetHealth: worst state,
later LastSuccessfulRead. A good value read can no longer mask a failing alarm read (no per-poll
/hosts flip) and a good alarm read cannot mask a value Degraded.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
MAJOR-1: a deploy that changes a driver's config respawns it, and the fresh instance's empty told
record re-sent Raise for every still-active alarm, un-acking acknowledged conditions and writing a
duplicate "Activated" alerts row. NativeAlarmProjector now treats Raise on an already-active
condition as a re-statement (keeps Acked; ForwardNativeAlarm skips the alerts row); only Retrigger
(or inactive->active) un-acks. Sources whose upstream ack state is authoritative send Retrigger for
an unacked re-statement: OpcUaClient on first sight (no prior told), Galaxy for an unacked active
snapshot entry. Runtime E2E drives a FRESH FOCAS driver after a redeploy and asserts the ack survives.
MAJOR-2: a failed FOCAS alarm read annotates each subscribed condition BadNoCommunication once per
outage (#626 quality-only path) with one Warning (MINOR-6), lifted to Good on recovery; failed alarm
reads degrade driver health with LastSuccessfulRead frozen (successful ones advance it), so an
alarm-only driver trips the #527 comms-loss watchdog.
MINOR-3 CLAUDE.md #630 bullet; MINOR-4 split line; MINOR-5 a non-empty cnc_rdalmmsg2 payload that
fits neither stride throws; MINOR-7 value-tag + parsed-address tables are built and swapped, never
cleared in place under the retained poll engine. Docs corrected (FOCAS.md, AlarmTracking.md, CLAUDE.md).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
An ALARM: address (*, <Type>, <Type>/<n>, <Type>/<lo>-<hi>, T<code>, OTHER) on a raw tag that
also carries the cross-driver alarm object is ONE condition with ConditionId == RawPath and a
Kind (Raise / Retrigger / Clear), so DriverHostActor.ForwardNativeAlarm routes it and
NativeAlarmProjector activates it. Fixes all seven triage defects:
1. SubscribeAlarmsAsync treated the host's RawPaths as device hosts -> nothing polled.
2. Decorated "{host}#{Type}:{Number}" ConditionId -> every event dropped.
3. No Kind -> projector kept prior state.
4. WireFocasClient.ReadAlarmsAsync answered [] on failure -> mass clear + un-acked re-raise.
It now throws; a failed device read keeps every condition's state.
5. Acks lost on reconnect -> told-record dedup (MTConnect #626 pattern) held for the driver's
lifetime; same-set re-subscribe / re-init re-raise nothing; changed set prunes leavers only.
6. Subscribe threw while AlarmProjection.Enabled=false -> the tag is the opt-in; flag is a no-op.
7. Alarm tags could not be authored -> ALARM: grammar (FocasAlarmSelector, Contracts) backs the
editor, the address picker, the deploy-time inspector and driver init.
Severity: authored alarm.severity -> exact OpcUaSeverity; else the 16i-era type bucket. The type
table stays the only one (moved to Contracts, documented 16i-era; 30i codes not invented; raw
T<code> selector + raw code in every message). Read-only: ack is server-side. Also clears the
value table on a re-initialise (#630 gap that let a removed/moved tag keep reading).
E2E: Runtime.Tests FocasNativeAlarmEndToEndTests drives the real driver through the real
DriverHostActor and asserts the condition goes Active then inactive.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Strict width+kind eligibility for sum-batched scalars (others read singly); latch only on ADS
1793/1794, split 1792/1797/1798 without latching; 32 KiB per-command budget and 500-item ceiling;
short sum response handled per item. Diagnostics: opt-in diagnosticsEnabled (default off), reuse the
probe's ReadState, sample after the host-state transition, JitterMs renamed HeadroomMs, compact
per-device line so many devices fit the 16-entry cap, unavailable-symbol latch cleared on reconnect.
AdminUI: min/max on sum-read max, diagnostics checkbox. Pure planner extracted and unit-tested.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Sum-read (#310): batches a poll's reads per device into sum commands capped at sumReadMaxItems,
per-item ADS errors mapped per tag, falls back to individual reads when the target refuses the
command. Diagnostics (#314): ADS state, app name, online-change count, task cycle/exec/jitter via
IDriverDiagnostics. Re-implemented against the current raw-byte read path (stranded auto/driver-gaps
commits predate it). Sum-write not ported. Unit tests only; live gate pending a route.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Nothing read the mapping table beyond the startup validator; v3 UNS projection is
explicit via UnsTagReference. Legacy keys in stored DriverConfig are ignored (pinned).
Reverts the docker-dev opc-plc seed workaround from fdee129f.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
60 s labelled a slow-but-clean large rebuild degraded. The deadline moves to a
shared Commons DeployTimings constant that ConfigPublishCoordinator reads, and
the node's timeout is deadline - 15 s margin, so the held ack still lands in
time. A timed-out ack's reason now says the outcome was not reported in time,
distinct from a real sink failure.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The apply writes the node's row Applied/null before the address-space outcome
is known; central adds the reason only when it ACCEPTS the ack, so a discarded
(stale/timed-out) ack left a fused node's row reading clean. The prefix moves
to ApplyAck.DegradedReasonPrefix so both writers spell the row identically.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A degraded rebuild advances _lastApplied (deliberately), so re-deploying the
same revision diffed to an empty plan and reported a CLEAN outcome - the
#601 're-deploy re-applies' repair path sealed green over an address space
still known partial. The publish actor now remembers that the last advance
was degraded and, on an empty plan, re-ensures the whole composition
(idempotent, no rebuild), reporting clean only when that pass is clean.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
An Applied+Degraded ack keeps NodeDeploymentState.Status = Applied with
FailureReason 'Applied degraded: <reason>' (no enum/migration change). The
deployment still seals (the revision is running; latest-sealed drives drift)
but Deployment.FailureReason names the degraded nodes and the seal logs at
Warning. Recovered from the DB on singleton failover. Old-node acks (no field,
DPS JSON or gRPC) behave exactly as before.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
DriverHostActor no longer acks Applied the moment the revision advances. It
asks OpcUaPublishActor for the outcome (RebuildAddressSpace.ReportOutcome) and
acks Applied+Degraded(reason) when the apply was degraded; a missing outcome
times out (60 s, inside the coordinator's 2 min deadline) to a degraded ack,
never a clean one. Re-dispatching a revision whose apply was degraded or is
still unconfirmed re-applies instead of taking the clean idempotent
short-circuit - that re-apply is also what repairs the degraded nodes.
Tests with a bare publish probe use a clean-outcome auto-pilot probe.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Native conditions support AddComment / commented Acknowledge, so the comment (and its
ClientUserId) is condition state the rebuild dropped. And the deferred restore report
re-stamped Time with the carried instant even when a client method call had reported a
newer event in the restore->complete window; it now reports at the node's current Time.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
ApplyAck gains trailing Degraded/DegradedReason (defaulted, so an old node's
DPS JSON or gRPC ack decodes exactly as before). mesh_transport.proto adds
ApplyAckMessage.degraded = 6 / optional degraded_reason = 7. OpcUaPublishActor
replies RebuildCompleted(Degraded, Reason) on every handler path when the
RebuildAddressSpace carries ReportOutcome.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
#641 keeps the projector's prior state across a deploy instead of resetting it to the
acked default. The projector never saw a client's ack (the SDK applies it to the node and
the host only routes it), so a Clear after ack+deploy now projected Acked=false and
un-acknowledged the operator's ack - previously masked by the per-deploy reset.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
DriverHostActor cleared NativeAlarmProjector's per-condition prior state on
EVERY apply, so after any deploy a driver Acknowledge of a still-active alarm
projected Active=false (writing it inactive) and a Clear of an unacknowledged
alarm projected Acked=true (silently acknowledging it). The projector is now
pruned to the conditions the new composition still carries (RetainOnly).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A full RebuildAddressSpace recreated every native Part 9 condition inactive +
acknowledged, and when the alarm-tag set was unchanged (e.g. one
UnsTagReference added to an alarm-bearing raw tag) nothing re-told the new node
its state: the host does not re-subscribe for an unchanged set, and Galaxy /
OpcUaClient have no snapshot to replay anyway. Active alarms read normal until
their next device transition.
OtOpcUaNodeManager now captures each NATIVE condition's live state (from the
node, so a client-applied ack is kept) before the rebuild clears, restores it
when the same id is re-materialised native in the same apply, and reports ONE
condition event per restored off-normal condition at the new
IOpcUaAddressSpaceSink.CompleteAddressSpaceApply (after notifier wiring).
Unclaimed captures are discarded there, so a later re-add is fresh. Quality is
carried silently for normal conditions too (it is only re-annotated on a
connectivity edge). Scripted conditions are untouched (#487 re-asserts them).
OpcUaPublishActor calls CompleteAddressSpaceApply at the end of every apply.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
OtOpcUaNodeManager.MapSeverity re-bucketed every projected severity onto the
SDK's five EventSeverity values (<800 -> 700, else 900), defeating #626's exact
OpcUaSeverity: an MTConnect Fault (800) read and evented as 900; a scripted
alarm graded 1000 published 900 while /alerts said 1000; a native Low (200)
published 300. EventSeverity merely names points on the 1..1000 scale, so the
node now carries the value clamped to 1..1000 (ToPart9Severity), at
materialise, projection and in the delta gate.
MTConnect wire test now asserts Fault ActiveState=true/Severity=800 and the
Normal clear ActiveState=false/Retain=false/Severity=800.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- Unavailable keeps an ACTIVE condition active: quality-only BadNoCommunication; on data
return same statement => quality-only Good, Normal => Clear, different => Retrigger.
- A changed alarm reference set (alarm-bearing delta = full rebuild) clears the whole
last-told record so every active condition is re-asserted; the same set keeps it.
- Quality-only events go through the host's AlarmQualityUpdate path, never a projected
snapshot (which could ack a retained unacked condition or rewrite message/severity).
- Deterministic tie-break between equal-level conditions (ordinal nativeCode, then type).
- Dedup key is level+nativeCode+nativeSeverity+qualifier; a text-only change updates nothing.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
New() ran FindNodeInAddressSpace under Lock, taking other node managers' locks (lock-order
risk); the three AlarmConditionType_ShelvingState_* ids are now a static set. Adds wire tests:
TimedShelve/Unshelve by the condition's own instance method ids (object = condition or its
ShelvingState) succeed and report, and a ShelvedStateMachineType_* id call is pinned as
BadMethodInvalid with a positive control.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
AlarmEventArgs gains optional OpcUaSeverity (supersedes the four-bucket mapping, clamped
1..1000) and QualityStatusCode (projected onto the condition's Quality). An Unspecified-kind
event carrying a quality is a quality-only annotation: the host updates the condition but
publishes no alerts row. Both default null, so every existing native source is unchanged.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Create(assignNodeIds: true) asked CustomNodeManager2.New, whose default returns the
node's current id, so every condition child kept the type's ns=0 instance-declaration id
(or an SDK-generated ns=0 number): translate of a child path returned BadNoMatch and a
Read of a browsed child id was BadNodeIdUnknown or served from the TYPE (UnshelveTime 0
on a condition timed-shelved for a minute), bypassing the data-plane ACL.
OtOpcUaNodeManager.New now derives {conditionId}/{browsePath} in the condition's
namespace, so the ACL scope of a child is its condition's scope plus the path. The
ShelvingState methods adopt their original AlarmConditionType_ShelvingState_* id as
MethodDeclarationId so clients calling them by that id still resolve. Condition removal
and rebuild forget the whole PredefinedNodes subtree so a removed condition's children
stop answering.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe