- I1 ScriptRunGuard: a run refused because the previous one is still
executing is a Bad publish plus otopcua.script.run_refused, and no longer
a quarantine strike. Only a timeout (and an allocation breach) counts;
a refusal neither adds to nor resets the timeout streak; a completed run
(value or throw) resets it. On a 1 Hz trigger with a 2 s budget a single
4 s overrun is one timeout plus two refusals and must not quarantine.
Tests updated across the guard, the alarm engine, the Calculation
evaluator and the VT evaluator, plus
Refusals_neither_count_toward_nor_reset_the_timeout_streak.
- I3 ScriptedAlarmEngine: the quality bucket is tracked only after the
predicate completes (or in the inputs-not-ready path), so the tracked
bucket is the last one annotated. A refused or quarantined predicate
used to re-track the input bucket Good before the attempt and then flip
it Bad, emitting QualityChanged on every push. The run-guard tests now
count emissions (exactly 1 across N pushes, refused and quarantined
cases), with a healthy sibling's dispatch count as the positive control
that every push was processed. Both were red before the fix.
Refs #734
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- RunWriteAsync wraps the invoker call in WaitAsync(writeTimeout) (Props,
default 10 s = 2x the 5 s write cap): a token-ignoring hung write now
answers BadTimeout, releases its slot and tag, and its orphan outcome
is observed and discarded - later writes to that tag reach the device.
- WriteCompleted carries the launching incarnation (from the process-wide
generation source); a late completion from a previous incarnation after
a supervision restart is ignored instead of freeing the new
incarnation's slot/tag.
- Test: a hung token-ignoring tag-a write is abandoned and a later tag-a
write reaches the device while the abandoned one is still inside it.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- GatewayHistorianDataSource.ReadRawWindowAsync keeps the cap + 1 probe budget
(budgetCap) separate from the client's cap: a strict-ceiling or crowding
refusal now reports Limit = the server cap that applied and advises setting
NumValuesPerNode at or below it (it said "lower NumValuesPerNode" with
Limit = cap + 1 to a client that sent 0).
- Fuzz: the oracle-source over-cap assertion was vacuous (cap 0 never counts);
it now checks no reverse window reached the forward-only shape. Class docs
name the post-floor cap set (3 ... 1000) and distinguish NumValuesPerNode
1 / 2 from the smallest server cap.
- HistoryPaging.IsFullPage doc says it judges the REQUEST cap (page + ties +
lookahead), which is finite under any limit; AdvertiseMaxReturnDataValues
swallows any exception (returns false for the caller to log), as its doc
promised.
Refs #736
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- Writes: a second write to a tag already inside the driver waits in the
queue behind it (_tagsInFlight) while other tags still run under the
cap of 4; queued writes are stamped and failed BadTimeout at dequeue
once older than the 8 s host Ask budget (Props queuedWriteBudget)
instead of being written late.
- Initialise attempts are bounded pessimistically (initializeTimeout,
default 30 s = 2x Tier C) on top of the invoker's token-only timeout:
an overrun is logged as abandoned, reported InitializeFailed so the
retry loop continues, and its late result is dropped by generation.
Generations come from a process-wide Interlocked counter so a prior
incarnation's late result cannot collide (F6).
- PostStop shares one shutdownTimeout budget across shutdown + dispose.
- TelemetryDialSupervisor cancels the establishment deadline on
StreamStopped; FleetDiagnosticsClient builds the ActorSelection inside
the try (a malformed node degrades to "unavailable"); the diagnostics
page labels the column "Last health publish".
- Tests: same-tag serialisation with a distinct-tag positive control;
stale queued write BadTimeout; token-ignoring hung init -> later
attempt connects; stopwatch assertion demoted to a ceiling.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- R02:H1 ScriptedAlarmHostActor gains a factory Props
(Func<(upstream, engine)>) so every incarnation builds and owns its own
engine; a supervision restart no longer re-creates the actor around a
disposed engine. The legacy instance-taking Props stays source-compatible
and is now restart-safe in the weaker sense (PreRestart marks the stop as
a restart, PostStop then detaches instead of disposing). DriverHostActor
still spawns through the legacy overload (not owned by this lane — F3).
- R02:H3 OnAlarmCommand runs every engine op under a 10 s token linked to
the actor's lifetime (DefaultCommandTimeout / Props commandTimeout) and
logs a Warning on timeout instead of suspending the mailbox on a stalled
store.
- R02:L3 DependencyMuxTagUpstreamSource.RetainOnly(loaded dep-ref union),
called after every successful load.
- R02:P6 VirtualTagActor's per-failure ScriptLogEntry is rate-limited per
tag (ScriptLogRateLimiter, 20/min + one summary); the Bad publish and the
metric are untouched.
- R07:H6 DependencyMuxActor retains the last (value, status, ts) per
ever-registered ref (through unregisters) and replays them in one batch to
a RegisterInterest(ReplayRetained: true) — VirtualTagActor, the Calculation
mux adapter and the alarm host opt in; the historization recorder does not
(a replay there would record a stale sample per deploy). CalculationDriver
records inputs regardless of _running so a replay landing before
InitializeAsync still satisfies the change-gate.
- R07:P4 CalculationEvaluator negative-caches compile failures by source
hash (one Roslyn attempt + one Warning per source until redeploy); the
driver's script-log entry fires on the Good→Bad transition or a change of
reason, matching the once-per-transition Bad publish.
- R07:H8 array results dedup structurally.
- R07:L2 ShutdownAsync drops the compiled scripts (collectible ALCs).
- R07:U5 DraftValidator rule CalculationNoEffectiveTrigger: a tag with no
timer whose change trigger is off or whose script has no literal
ctx.GetTag read can never evaluate.
Refs #734
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- R05:1/12 ScriptedAlarmEngine: _valueCache is cleared in LoadAsync (it is
re-seeded for the referenced paths) so retired tags no longer accrete across
deploys; OnUpstreamChange no longer writes the cache after Dispose.
- R05:3 ScriptedAlarmEngine.Dispose drains in-flight work for at most 5 s
(DisposeDrainTimeout), then cancels it through a shutdown token every
DrainDirtyAsync/ShelvingCheckAsync now runs on, logs a Warning and gives
one second of grace — a stalled IAlarmStateStore.SaveAsync can no longer
hang host shutdown. A save that completes inside the bound is still drained
(positive control test).
- R05:6 ScriptedAlarmSource logs a throwing OnAlarmEvent subscriber at
Warning (naming the alarm) instead of swallowing it.
- R05:7 LocalDbStoreAndForwardSink keeps a cached dead-letter counter in step
with every dead-letter/revive/purge path and resyncs it with the queued
counter on the same cadence; GetStatus no longer runs a COUNT(*) scan.
- R05:9 ScriptLogRateLimiter (20 per source per minute, fixed window, one
summary entry naming the dropped count when the window rolls) behind
ScriptLogTopicSink (key = script|vtag|alarm) and ScriptLogCompanionSink
(key = script name).
Refs #734
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- NodeManagerHistoryReadRawCapFuzzTests: 10k seeds (env OTOPCUA_PAGING_FUZZ_ITERATIONS)
through a real SDK node manager against wire-faithful fakes of SqlServer / QuestDB /
Gateway that enforce the backend half of the cap; random series with ties, random
windows (empty, on/past a tie, between samples, forward/reverse/end-only, bounds),
N in {0,1,2,small,huge}, cap in {off,3..1000}, tie budget {3,8,65536}. Pages must
concatenate to the cap-off one-shot answer (checked against the series), terminate
within values + 2 (+ one empty step per oversized boundary cluster), never exceed
the cap, never ask the backend for 0 / over-cap; refusals only past the budget.
- HistoryPaging.AdvertiseMaxReturnDataValues writes HistoryServerCapabilities/
MaxReturnDataValues (i=11273), read back through the SDK master node manager.
- MinMaxRawValuesPerRead raised to 3: at 2 a resumed page has no room (value + its
boundary tie + lookahead) and every value cost an empty page + CP (seed 15).
- RawPageLimit rows pin the default-cap arithmetic (9 999 first page, 9 998 resumed).
Fuzz findings recorded as follow-ups: a bounded read whose data fits one page
returns cap + 1 (end bound fitted against N, not the cap; node manager, F2);
the Gateway walk-back's cost on a sparse series under a tiny tie budget is
pre-existing (seed 320: 82 reads uncapped, 93 capped).
Refs #736
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
DriverInstanceDiagnostics.Name carries the string driver-instance id
(what /hosts, telemetry and the artifact key on) and DriverInstanceId
the DB row Guid; the wire record has no slot for the authored display
name. The write-cap test asserts entry order per slot pair instead of
completion order of two concurrent writes.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
R05:10 — the namespace deny-list covered System.Threading.Tasks but not
System.Threading, so SemaphoreSlim / Monitor / SpinWait / Mutex /
EventWaitHandle could park a script's pool thread past its budget (or touch a
system-global kernel object); System.Type.GetType(string) / GetMethod* /
InvokeMember and System.Runtime.CompilerServices.RuntimeHelpers resolved and
reach a forbidden type without naming it syntactically.
ForbiddenTypeAnalyzer now denies the whole System.Threading namespace with a
type-granular allow-list (CancellationToken, Interlocked, Volatile — the
sync-free primitives), adds a member deny-list for System.Type's reflection
entry points (GetType/GetMethod(s)/InvokeMember/GetProperty(ies)/GetField(s)/
GetMember(s)/GetConstructor(s)/GetEvent(s)/GetDefaultMembers; instance
object.GetType() stays allowed) and puts RuntimeHelpers on the type deny-list.
Thread/ThreadPool/Timer leave the type list — the prefix rule reaches them.
R05:11 — the allocation budget landed with E1's ScriptRunGuard
(Scripting:MaxAllocBytesPerRun, default 64 MB): sampled around each run,
breach quarantines. It is observation after the fact; a pre-emptive OOM guard
still needs an out-of-process runner (follow-up issue in the lane report).
The Monaco editor shares the analyzer, so DiagnoseTests pins every new form
as an OTSCRIPT_FORBIDDEN marker and every allow-listed form as clean.
Refs #734
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
DriverHostActor wraps the health publisher it hands its children in a
ChildHealthLedger (last snapshot per driver id, forwarded to the real
publisher), so GetDiagnostics now answers with each child's row id,
authored name, last-published state, device counts (host statuses when
the driver probes hosts, else one device) and last-change time — instead
of Guid.Empty / "Spawned" / 0 / now. Entries are forgotten on StopChild
and operator Restart.
IFleetDiagnosticsClient gains its first consumer: the new
/fleet/diagnostics page (node selector + ?node= query, revision,
running-from-cache notice, per-driver table). FleetDiagnosticsClient
logs the degrade-to-empty path at Warning.
Review ref: 02/U1.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
A timed-out script is abandoned, not stopped, and every seam re-ran it on the
next trigger, leaking one pool thread per trigger (R03:1.1, R05:2, R07:L1).
A shared ScriptRunGuard, keyed per script instance, now:
- refuses a run while that script's previous orphan is still executing
(Bad "previous evaluation still running" + otopcua.script.run_refused);
- quarantines after 3 consecutive non-completions or an allocation-budget
breach (sampled with GC.GetAllocatedBytesForCurrentThread; default 64 MB):
no further dispatch, Bad quality, one Error, otopcua.script.quarantined,
cleared on source change / redeploy / reset;
- starts the budget clock when the pool picks the run up, so starvation is
no longer charged to the script (R07:P5), and cancels the evaluator token
on timeout.
Wired into RoslynVirtualTagEvaluator, CalculationEvaluator (new async
EvaluateAsync; the driver's pump and timer ticks now await the run behind a
SemaphoreSlim gate) and ScriptedAlarmEngine (a non-completing predicate
holds state and annotates the condition BadInternalError). ScriptingOptions
(Scripting:MaxAllocBytesPerRun, Scripting:QuarantineAfterConsecutiveTimeouts)
carries the knobs; the Calculation driver config accepts the same two keys.
Tests: guard unit suite (incl. the 30-trigger runaway leaving one orphan with
a healthy sibling as positive control), per-seam refusal/quarantine/reset
tests. The S12 race test now uses one vtag id per loop: twelve concurrent
evaluations of ONE id is a shape production never produces and the guard
refuses by design.
Refs #734
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
CallTimeoutSeconds was bound, defaulted and documented but consumed
nowhere. TelemetryDialSupervisor now arms a per-generation deadline on
every dial: a dial that has delivered no event by the deadline is
cancelled and treated as a transport failure (reconnect with a failure
streak). A live node replays its snapshots on subscribe, so this bites
only a dial that never connects (a black-holed host, where the socket
connect has no timeout). An established stream is deliberately not
bounded — the wire has no heartbeat, keepalive pings own its liveness.
Review ref: 02/U2.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- DriverHostActor.StopChild removes the driver's _lastReprovisionUtc stamp
(and its deferred-reprovision timer): the map grew per removed id and a
re-added driver inherited a backoff it never earned (02/L2).
- Stale now registers explicit drops for AttributeValueBatchPublished,
AttributeAlarmPublished, ArtifactForApply and ApplyWedged instead of
letting them hit Unhandled (02/H5).
- DbHealthProbeActor runs its SELECT on the thread pool and pipes the
outcome back (single-flight), with a 2 s command timeout on relational
providers, so a hung SQL Server no longer pins the actor thread and the
cached GetStatus answer stays reachable (02/P7).
- TelemetryLocalHub eviction tombstones are timestamped and swept past a
10 min TTL on the next Evict; a TimeProvider ctor is the test seam (02/L4).
- Tests: ValuePublishes.Single helper replaces the per-value
AttributeValuePublished in CalculationDependencyFlowTests (02/U4, test
half; the production receive is owned by Lane E).
- R05/8 audit: PollGroupEngine.Unsubscribe has no production caller; every
driver already uses UnsubscribeAsync (no change).
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
WriteAttribute was a ReceiveAsync, suspending the child's mailbox for the
whole device round-trip (up to 5 s): writes serialised, the second of two
operator writes to a slow device missed the host's 8 s Ask and was
reverted although the device took it, and every data change queued behind
the write. Writes are now a synchronous Receive that launches the device
call on the thread pool (sender captured, reply from the task, slot freed
by a self-sent WriteCompleted) under a per-driver cap (default 4; excess
writes queue in order). Queued writes fail fast on every exit from
Connected. Subscribe/unsubscribe stay ReceiveAsync.
Review ref: 02/P2.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review R08:1.1: an uncapped HistoryRead-Raw (NumValuesPerNode = 0) read a
tag's whole window into memory on every backend (SQL TOP(int.MaxValue),
QuestDB LIMIT, Gateway max_values = int.MaxValue + a second snapshot copy).
New ServerHistorian:MaxRawValuesPerRead (default 10 000; <= 0 unbounded with
a Validate() warning; 1 raised to 2). Each backend data source takes it,
reports it as IHistorianDataSource.MaxRawValuesPerRead (the Gateway: min
with a strict gateway's learned ceiling), so the node manager's existing
RawPageLimit paging serves N = 0 and N > cap as pages of at most the cap
with a continuation point. Independently, a backend raw read asking for 0
or more than the cap reads cap + 1 rows and is REFUSED
(HistoryReadLimitExceededException => BadTooManyOperations) when the window
holds more - never answered truncated, since the server's paging reads a
short answer as the last page. Bound through the Host registry, the
SqlServer/QuestDb providers and GatewayHistorian.CreateDataSource.
Tests: options (default/binding/warnings), provider binding, Gateway unit +
through a real SDK node manager (uncapped -> 999/998/998/605 + CPs), and a
conformance case for the SQL backends.
Refs #736
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The Reconnecting retry timer started a new ShutdownAsync + InitializeAsync
pair on every tick whether or not the previous attempt had finished; the
generation token only discarded the older RESULT, so with an Initialize
bound longer than the cadence the teardown ran underneath an attempt still
inside the driver (the dispose-before-overwrite race). An _initInFlight
gate, cleared by the piped InitializeSucceeded/Failed, skips a tick while
an attempt is running; the pre-reconnect teardown is bounded by the
shutdown timeout; PostStop cancels an in-flight attempt before shutting
the driver down.
Review ref: 02/H2.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
DriverInstanceActor.PostStop now bounds IDriver.ShutdownAsync by a
shutdownTimeout (default 5 s, logged on overrun) and then disposes the
driver (IAsyncDisposable preferred, else IDisposable) — but only on a
real stop. PreRestart flags the restart so the PostStop it triggers
skips the dispose, because a supervision restart re-uses the same
driver object (Props closure) and the host re-initialises it.
DiscoveryDriverBrowser disposes its throwaway capture/probe driver
after the bounded shutdown, including after a failed or timed-out one.
Review refs: 02/L1, 02/P4, 06/G-1 (host context), 07/L2.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Keeps the root CLAUDE.md lean by lazy-loading per-area detail (drivers, topology,
data-plane auth, alarms, historian) only when matching files are touched.
Clears CommentChecker findings in src/ (3,280 -> 209, the remainder being false
positives like PLC-5/IEEE-754/M0.0) by adding missing summaries/params/returns,
normalising inheritdoc usage, and removing Gitea/review tracking IDs while keeping
the rationale they annotated. Comment-only: comment-stripped sources are identical
to the parent commit.