AbLegacyDriver stamped LastSuccessfulRead (init, read, write), the read's sample
timestamps and host-state change times from raw DateTime.UtcNow; only the backoff
path read the injectable Clock. All of them now read Clock(), so
NativePcccBridgeStatusHealthTests drives a manual clock (init at T0, read at T1)
and asserts LastSuccessfulRead == T1 exactly instead of spin-waiting for the wall
clock to pass the init stamp (#767). Without the driver change the 6 tests fail
(init stamp is wall-clock, not T0).
Directory.Build.props sets TreatWarningsAsErrors for every project since #766, so
the 75 per-csproj copies (64 src + 11 tests) are removed and the props comment
says it is now the only place. tools/mem-probe keeps its explicit opt-out.
Release build: 0 warnings, 0 errors; a planted CS0168 still fails the build in a
src project and in a test project that used to carry its own copy.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
P8: on the native transport the bounded-parallel read window is also the cap
on services per Multiple Service Packet (the device's shared scheduler packs
whatever is queued, within the connection's request/reply byte budget), so the
default 8 cost a 1000-tag controller ~125 round trips per poll instead of ~10.
The effective window (AbCipDriver.ReadWindow) is now max(64, option) when the
native tag factory serves reads; libplctag and injected factories keep the
option exactly. Option doc + AdminUI help text updated (Razor: Wave 4 live
check).
P7 addendum: a work item now takes its window slot only after its runtime
exists. A cold create queues on its device's single-flight connect gate, and
holding a slot there let one dead device's backoff-expiry attempt occupy the
whole window for a full Timeout, stalling every other device's reads.
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Clears CommentChecker findings in src/ (3,280 -> 209, the remainder being false
positives like PLC-5/IEEE-754/M0.0) by adding missing summaries/params/returns,
normalising inheritdoc usage, and removing Gitea/review tracking IDs while keeping
the rationale they annotated. Comment-only: comment-stripped sources are identical
to the parent commit.
M1 drop-out is a no-row Unspecified+IsRestatement update (projector case); M2 ack judged over every declared
limit; L1 ActiveAcknowledged for an already-acked new limit; L2 Bad Acked/severity carried/skipped; L3 host
end-to-end test; L4 BOOL member-by-member tests + mixed ALMD/ALMA; L5 detection requires no plain Acked.
ALMD active bit is InAlarm per Rockwell's ALMD reference; InFaulted is input health.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
#572: listing continues at max(instance in page)+1 (no ascending-order assumption, no-progress guard kept);
browsePageDelayMs (default 5 ms) paces pages; DiscoverAsync reads templates through one batch reader
(IAbCipTemplateReaderFactory.CreateBatch) holding one lease.
#575: differential harness reports a same-status template refusal as an equal refusal; offline test pins the
open-attempt budget without relying on the abort ending the phase.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The old AdminUI cannot author the per-driver transport key (#576), so the
'pin before upgrading' recipe had no working path. A node-level appsetting
(env Drivers__AbCip__DefaultTransport) now supplies the default for AbCip
drivers with no key: explicit key > node default > compiled Native. Bound
and validated unconditionally (bad value fails host start); the driver
factory and the Test Connect probe both read it so they agree. AbCip.md
upgrade recipe rewritten around the key; Configuration.md documents it.
Also documents first-wins for AllowPacking/probe and host-alias throttles
(final review M6) and moves the status-bit note out of AbCip.md (M5).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Task 22 (spec section 8 P5), with the controller rulings that exclude PLC-5 and LogixPccc.
- Transport is nullable on both option records; null (key absent) means "use the default" and is
never serialized. Factory DTO parse: absent -> null; a bad value still fails via ParseEnum.
- One resolver per driver (AbCipTransportResolver / AbLegacyTransportResolver), used by the driver
constructor, the Test Connect probe and (through the driver) the CLI.
AbCip: null -> Native. AbLegacy: null -> Native unless any device is Plc5 or LogixPccc, then the
whole driver resolves to Libplctag. Explicit values always win; explicit Native with a
Plc5/LogixPccc device logs one Warning at init.
- Init log shows configured vs effective, e.g. transport=Native (default).
- AdminUI forms: "Default (...)" / "Native (managed)" / "libplctag (fallback)". Default omits the
key on save (reverses Task 19's explicit re-emit, which would have pinned every edited driver).
- CLIs: --transport default|native|libplctag, default "default" via the resolver, so
--plc-type Plc5 with no --transport runs libplctag.
- Tests pinned to Libplctag where a default-path runtime was created: found by instrumenting the
native factories with the current xUnit test name (one unit test, AbLegacyReinitConfigAdoption;
plus the two fixture-gated AbCip probe E2E tests whose exact messages were proven on libplctag).
TransportMatrix and the differential harness already pass explicit transports.
- Switch/resolver/CLI/form tests are falsified by mutating the resolver (default -> Libplctag,
exclusion removed, AbLegacy default -> Libplctag): each mutation turns them red.
- Replaces the inline role-name literal in AbCipDriverFactoryExtensions' ParseEnum call with a named
constant; RoleAuthorityGuardTests was already red on the base commit for that line.
- Docs: AbCip.md / AbLegacy.md default + release note; CLAUDE.md AB section.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The 5069-L3x supports the Large open, as the press proved. The narrow/refusing case is a pre-v20 1769-L3x or a bridge. AbCipDeviceOptions.ConnectionSize: the native transport honours it on the wire; libplctag ignores it.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
#556 item 1 — leading whitespace defeated every Inspect's pre-filter. Seven
factories (Modbus/S7/AbCip/AbLegacy/TwinCAT/FOCAS/Mqtt) tested
`reference[0] != '{'`, so a padded blob returned EMPTY and a tag the driver
refuses deployed clean. The check now trims first, matching the idiom
Sql/Calculation/MTConnect/OpcUaClient already used. The raw reference is still
what is handed to the mapper — the driver reads the stored blob, not a trimmed
copy — so the gate keeps mirroring the runtime rather than becoming lenient.
Both directions are pinned: a padded blob the mapper accepts still draws
nothing, and one that is not object-framed AFTER trimming still draws nothing
(it is not an equipment-tag TagConfig at all).
Six of the seven mappers hand the blob to a whitespace-tolerant
JsonDocument.Parse, so their verdict is unchanged by padding. MQTT is the
exception: both its readers carry the same framing gate, so a padded blob is
genuinely refused — which is why the untrimmed pre-filter was a real defect
there and not a cosmetic mismatch.
#556 item 2 — FOCAS and MQTT appended advisories unconditionally and then gated
the catch-all rejection message on `warnings.Count == 0`, so an advisory (which
fires on ACCEPTED blobs too, and says nothing about a refusal) silently
swallowed the only message naming a refusal nothing else can. The two classes
now accumulate in SEPARATE lists and the backstop gates on the rejection count
alone — structural, not string matching. MQTT's swallow was reachable in
production (a padded blob its readers refuse while every describe branch finds
the parsed document well-formed); FOCAS's backstop is currently unreachable by
audit, so its guard is protective.
#557 item 2 — decided and pinned: KEEP the union verdict. Evidence:
FromSparkplugTagConfig hard-codes PayloadFormat=Json and never consults the key;
only MqttSubscriptionManager (the Plain ingest path) decodes by it; and
MqttTagConfigModel.ToJson deliberately omits the key entirely in Sparkplug mode
(#513). So a Sparkplug driver genuinely serves the tag and rejecting it would be
stricter than the runtime. The cost — served behaviour depends on the driver's
MqttMode, which no tag row records — is paid by an ADVISORY naming the key and
the mode dependency, not by changing the verdict, so both gates keep agreeing.
The same invalid value on a blob the union REFUSES stays a rejection; the class
is decided by the accept gate, never by the key.
Falsified: reverting Modbus's trim reddens the padded-rejection theory;
neutering MQTT's backstop guard to the pre-#556 shape reddens the
advisory-plus-unnameable-rejection test; disabling the #557 advisory reddens the
contract pin; and for FOCAS, removing a describe branch alone stays green (the
backstop covers it) while additionally neutering the guard goes red.
Gitea #551.
1. CSV import ran no driver-typed config gate. Its typed columns were always
strictly parsed, but the free-form TagConfigJson column reached the database
unread, so a CSV could author a tag the driver rejects — one that deploys
green and reads BadNodeIdUnknown forever. RawTagCsvMapper.Parse now names the
offending row in the staged review grid, and RawTreeService enforces the same
gate on CreateTag/UpdateTag/ImportTags: a form cannot be the guarantee (the
API and any future caller reach none of them, and this repo has no bUnit).
A rejected import row is an ERROR — the batch inserts nothing and the row is
named — never a skip.
Note the brief's premise that manual entry rides ImportTagsAsync is wrong:
RawManualTagEntryModal commits row-by-row via CreateTagAsync, which is why
the gate had to land on all three write paths.
2/3. The seven pre-#549 Inspect methods ran a hand-list of DescribeInvalidEnum
checks, so every rejection cause not on the list was invisible. They are now
ACCEPT-GATE-FIRST (the MTConnect/Sql/OpcUaClient/Calculation shape): ask the
driver's own reader for the verdict, then explain the refusal, with a
catch-all so "the parse rejects but Inspect said nothing" is unreachable.
That closes S7's absent dataType, AbCip members[], Modbus stringByteOrder and
the type-dependent guards, plus causes the issue did not name (absent
region/address/tagPath/symbolPath/topic, TwinCAT Structure, MQTT's Sparkplug
tuple). FOCAS and MQTT keep advisories about ACCEPTED blobs, so they
diagnose rather than return empty.
Authoring half: ModbusTagConfigModel gains stringByteOrder;
AbCipTagConfigModel asks the new AbCipTagDefinitionFactory.DescribeInvalidMember;
S7TagConfigModel captures whether the SOURCE blob declared dataType and asks
S7TagDefinitionFactory.DataTypeKey/DeclaresDataType. One authority per rule.
4. Doc sweep: the six factory Inspect summaries, EquipmentTagConfigInspector's
class remarks and AdminOperationsActor's comment all claimed invalid enums are
"silently defaulted by the lenient runtime" — false since R2-11 Phase C made
the runtime reads strict. They describe rejections now.
A browse-committed AB CIP / TwinCAT / FOCAS tag bound with its model's DEFAULT
data type, not the one the device reported. A browsed REAL committed as
`{"tagPath":"Pump_1_Speed","dataType":"DInt"}` — and those three drivers decode
the wire bytes by that field, not by the raw row's OPC UA DataType — so the tag
read four bytes of a float through an integer decoder and published a plausible
wrong number with no error raised anywhere. FOCAS was missed when #536 was filed.
The type is CARRIED, not derived. Reverse-mapping the leaf's driver-agnostic
DriverDataType looks like the smaller fix and is wrong: SInt/Int/DInt/USInt/UInt
all collapse into Int32 on the way out of the driver, so that version would bind
a 16-bit INT as a 32-bit DINT while appearing to fix the REAL. Drivers now state
their own type name on DriverAttributeInfo.NativeDataType, which reaches the
picker as AttributeInfo.AddressFields["dataType"] and the commit mapper from
there. A leaf that states nothing keeps the model default — the pre-#536
behaviour, kept deliberately as the fallback rather than a guess.
Numeric strings are refused before parsing: Enum.TryParse accepts "9" for any
enum and Enum.IsDefined then confirms it, so an unguarded parse would bind a tag
to a type nobody named. A test caught this in the first version of the guard.
--- and the other half, which the fixture was hiding ---
Test Connect on a device with NO authored tags — every AB CIP device at the
moment an operator first presses the button — reported "CIP handshake failed"
against a healthy controller. That was written down as a fixture limitation
("ab_server doesn't implement @raw_cpu_type"). Both halves of that were wrong:
* @raw_cpu_type is not a libplctag special tag at all (only @raw, @tags and
@udt/ are), so it goes out as an ordinary symbolic name that no controller
defines, and the controller's "tag does not exist" IS the successful answer.
* ab_server answered an unresolvable tag path with CIP 0x03 where a Logix
controller answers 0x04 — ErrorBadParam vs ErrorNotFound, which the probe
classifies oppositely. Fixed in vendored patch 0002.
* With the fixture then telling the truth, the real defect surfaced:
AbCipDriverProbe.IsReachableException matched the native C status spellings
("STATUS_NOT_FOUND"), but libplctag.NET throws with the MANAGED enum name
("ErrorNotFound"). Those substrings can never match, so the reachable
classification could not fire on the exception path — which is the path every
no-authored-tags probe takes. This was failing on real hardware too, not just
against the sim. It now recovers the Status and defers to IsReachableStatus,
so there is one classification rather than two that can drift.
Rejected: switching the fallback to @tags. libplctag builds a tag-listing tag
with NO network I/O, so it reports OK against any TCP listener — measured green
against a Mosquitto broker.
Verification: full solution suite green. Falsification runs confirm exactly the
intended tests go red — 9 for the type carry, 3 (the reachable statuses only) for
the probe classification. Live on docker-dev: browse-committed TestString/
Motor_Run/TestSINT now store String/Bool/SInt, alongside last session's
Pump_1_Speed still holding the wrong DInt. TestSINT is the falsifier — its row
DataType is Int32, identical to TestDINT's, so no reverse map could have produced
"SInt".
Known consequence: pre-existing browse-committed tags keep their wrong dataType;
the fix applies to new commits only.
Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
Apply the reviewed Modbus exemplar to the AbCip multi-device driver:
- Mapper AbCipEquipmentTagParser -> AbCipTagDefinitionFactory; TryParse -> FromTagConfig(tagConfig, rawPath, out def); drop leading-{ heuristic + the deviceHostAddress key; add inverse ToTagConfig; round-trip arrays/members/safety for coverage.
- Options: Tags (typed) -> RawTags (RawTagEntry list); Devices list kept.
- Driver: byName-only resolver over _tagsByRawPath (Ordinal); table built from RawTags via FromTagConfig, threading entry.DeviceName (device routing key) + entry.WriteIdempotent onto the def. Multi-device routing keys on DeviceName-or-host via a _devicesByRoutingKey index; discovery groups _declaredTags by RoutesToDevice.
- Factory: retire the pre-declared Tags DTO/BuildTag; bind List<RawTagEntry> RawTags.
- Probe: derive probe tag path from RawTags via the mapper.
- Cli BuildOptions projects typed tags -> RawTagEntry (ToTagConfig).
- Tests: AbCipRawTags helper (typed def -> RawTagEntry); parser tests -> FromTagConfig; blob-fallback driver tests rewritten to author via RawTags + read by RawPath. Driver.AbCip.Tests 342/342, Cli.Tests 42/42.
TODO(v3 WaveC): DeviceName becomes a pure logical name once the device connection host moves to the Device row's DeviceConfig.
R2-11 Phase C. All six equipment-tag parsers (Modbus/S7/AbCip/AbLegacy/
TwinCAT/Focas) now read enum fields via the new TagConfigJson.TryReadEnumStrict:
absent -> fallback, valid -> parsed, present-but-invalid (typo) -> TryParse
returns false -> EquipmentTagRefResolver.TryResolve false -> driver surfaces
BadNodeIdUnknown, instead of the old lenient path that silently defaulted a
typo to a wrong-width Good.
Modbus flips all three enum fields (region/dataType/byteOrder); the other five
flip dataType. The deploy-time Deployment:TagConfigValidationMode=Error gate is
unchanged and remains the operator pre-flight.
Coverage:
- Six *EquipmentTagParserStrictnessTests inverted from Freeze_typo_* (lenient)
to Typo_*_rejects_the_tag + Valid_*_still_parses.
- TagConfigJsonTests.TryReadEnumStrict_rejects_only_invalid matrix.
- Driver-level end-to-end proof:
AbCipEquipmentTagTests.Driver_read_of_a_typod_dataType_ref_surfaces_BadNodeIdUnknown
drives the real AbCipDriver.ReadAsync through resolve->status.
Golden parity corpus has no typo'd enums, so the flip is a no-op there.
Full solution builds clean; all six driver suites + core + parity + gate green.
Adds <summary>/<param>/<returns>/<inheritdoc> where missing and removes
project bookkeeping IDs (task/tracking refs) from shipped code comments,
so the docs read cleanly and CommentChecker is quiet except for known
false positives (PLC/protocol terms, event/IEqualityComparer inheritdoc).
Doc/comment-only; no logic changed; solution builds clean.
First review at 7286d320. 6 findings (doc fixes -005/-006 resolved; -001 writable-hardcode,
-002 Dt-units doc, -003 dead [Display] attrs, -004 parser test gap left Open). Surfaced
cross-module: AbCipTagDto/AbCipMemberDto in the factory drop ElementCount/IsArray.
Move AbCipDriverOptions (and AbCipDataType enum) to a new
Driver.AbCip.Contracts sibling project. AbCipDataTypeExtensions
(which uses DriverDataType from Core.Abstractions) stays in the
runtime driver as AbCipDataTypeExtensions.cs.
Replace two doc-comment <see cref="Core.Abstractions.IAlarmSource"/>
and <see cref="Core.Abstractions.IHostConnectivityProbe"/> with <c>X</c>
per the approved decision — no compilable using was present.
The runtime Driver.AbCip project gains a ProjectReference to .Contracts;
the .slnx is updated accordingly.