fix(browse): commit the browsed data type, and fix the probe classification the fixture was hiding (#536)
v2-ci / build (push) Successful in 4m17s
v2-ci / unit-tests (push) Failing after 16m47s

A browse-committed AB CIP / TwinCAT / FOCAS tag bound with its model's DEFAULT
data type, not the one the device reported. A browsed REAL committed as
`{"tagPath":"Pump_1_Speed","dataType":"DInt"}` — and those three drivers decode
the wire bytes by that field, not by the raw row's OPC UA DataType — so the tag
read four bytes of a float through an integer decoder and published a plausible
wrong number with no error raised anywhere. FOCAS was missed when #536 was filed.

The type is CARRIED, not derived. Reverse-mapping the leaf's driver-agnostic
DriverDataType looks like the smaller fix and is wrong: SInt/Int/DInt/USInt/UInt
all collapse into Int32 on the way out of the driver, so that version would bind
a 16-bit INT as a 32-bit DINT while appearing to fix the REAL. Drivers now state
their own type name on DriverAttributeInfo.NativeDataType, which reaches the
picker as AttributeInfo.AddressFields["dataType"] and the commit mapper from
there. A leaf that states nothing keeps the model default — the pre-#536
behaviour, kept deliberately as the fallback rather than a guess.

Numeric strings are refused before parsing: Enum.TryParse accepts "9" for any
enum and Enum.IsDefined then confirms it, so an unguarded parse would bind a tag
to a type nobody named. A test caught this in the first version of the guard.

--- and the other half, which the fixture was hiding ---

Test Connect on a device with NO authored tags — every AB CIP device at the
moment an operator first presses the button — reported "CIP handshake failed"
against a healthy controller. That was written down as a fixture limitation
("ab_server doesn't implement @raw_cpu_type"). Both halves of that were wrong:

  * @raw_cpu_type is not a libplctag special tag at all (only @raw, @tags and
    @udt/ are), so it goes out as an ordinary symbolic name that no controller
    defines, and the controller's "tag does not exist" IS the successful answer.
  * ab_server answered an unresolvable tag path with CIP 0x03 where a Logix
    controller answers 0x04 — ErrorBadParam vs ErrorNotFound, which the probe
    classifies oppositely. Fixed in vendored patch 0002.
  * With the fixture then telling the truth, the real defect surfaced:
    AbCipDriverProbe.IsReachableException matched the native C status spellings
    ("STATUS_NOT_FOUND"), but libplctag.NET throws with the MANAGED enum name
    ("ErrorNotFound"). Those substrings can never match, so the reachable
    classification could not fire on the exception path — which is the path every
    no-authored-tags probe takes. This was failing on real hardware too, not just
    against the sim. It now recovers the Status and defers to IsReachableStatus,
    so there is one classification rather than two that can drift.

Rejected: switching the fallback to @tags. libplctag builds a tag-listing tag
with NO network I/O, so it reports OK against any TCP listener — measured green
against a Mosquitto broker.

Verification: full solution suite green. Falsification runs confirm exactly the
intended tests go red — 9 for the type carry, 3 (the reachable statuses only) for
the probe classification. Live on docker-dev: browse-committed TestString/
Motor_Run/TestSINT now store String/Bool/SInt, alongside last session's
Pump_1_Speed still holding the wrong DInt. TestSINT is the falsifier — its row
DataType is Int32, identical to TestDINT's, so no reverse map could have produced
"SInt".

Known consequence: pre-existing browse-committed tags keep their wrong dataType;
the fix applies to new commits only.

Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
This commit is contained in:
Joseph Doherty
2026-08-01 15:20:07 -04:00
parent c2c3c52274
commit 6b3da93151
21 changed files with 585 additions and 51 deletions
+6 -1
View File
@@ -33,7 +33,12 @@ Family ↔ CIP-path cheat sheet:
### `probe` — is the PLC up?
```powershell
# ControlLogix — read the canonical libplctag system tag
# ControlLogix — read a real tag
otopcua-abcip-cli probe -g ab://10.0.0.5/1,0 -t TestDINT --type DInt
# …or any name at all: `@raw_cpu_type` is NOT a libplctag special tag (only `@raw`, `@tags`
# and `@udt/` are), so it goes out as an ordinary symbolic name that no controller defines.
# The "tag does not exist" answer is itself proof the CIP session came up.
otopcua-abcip-cli probe -g ab://10.0.0.5/1,0 -t @raw_cpu_type --type DInt
# Micro800 — point at a user-supplied global
@@ -1132,12 +1132,24 @@ neither agreed with a controller. Fixed, with the layout now pinned by a capture
### Follow-ups discovered during the second gate
1. **Browse-commit discards the discovered data type** — a browsed REAL commits with
`"dataType":"DInt"` in its `TagConfig`, and the driver decodes off that field rather than the
row's `DataType`. Filed as **Gitea #536**; affects AbCip and (by inspection) TwinCAT.
2. **Test Connect fails against this fixture regardless of the device** — the probe falls back to
`@raw_cpu_type` when no tags are authored, which `ab_server` does not implement. Fixture
limitation, documented in the fixture README; browse is unaffected.
1. ~~**Browse-commit discards the discovered data type**~~ — **CLOSED 2026-08-01 (Gitea #536).** A
browsed REAL committed with `"dataType":"DInt"`, and AbCip/TwinCAT/**FOCAS** decode off that field
rather than the raw row's `DataType`, so the tag published a plausible wrong number with no error
raised. FOCAS was missed when the issue was filed. Fixed by carrying the driver's own type name on
`DriverAttributeInfo.NativeDataType` → `AttributeInfo.AddressFields["dataType"]` →
`RawBrowseCommitMapper`. **It could not be fixed by reverse-mapping the leaf's driver-agnostic
`DriverDataType`**: `SInt`/`Int`/`DInt`/`USInt`/`UInt` all collapse into `Int32`, so that "fix"
would still bind a 16-bit INT as a 32-bit DINT while looking correct on a REAL.
2. ~~**Test Connect fails against this fixture regardless of the device**~~ — **CLOSED 2026-08-01, and
the stated cause was wrong.** `@raw_cpu_type` is not a libplctag special tag at all (only `@raw`,
`@tags`, `@udt/` are), so it is sent as an ordinary symbolic name and the controller's "tag does not
exist" IS the successful answer. Two real defects hid behind the "fixture limitation" label: the sim
answered CIP **0x03** where a controller answers **0x04** (fixed in vendored patch 0002), and
`AbCipDriverProbe.IsReachableException` matched the native C status spellings (`STATUS_NOT_FOUND`)
that libplctag.NET never emits — it throws with the managed enum name — so the reachable
classification could not fire on the exception path, which is the path every no-authored-tags probe
takes. **Test Connect was therefore failing on real hardware too, not just against the sim.**
Pinned by `AbCip_WithNoAuthoredTags_ReportsTheControllerReachable` plus offline classification tests.
### Follow-ups discovered during the first gate
@@ -50,7 +50,7 @@ public sealed class CapturedTreeBrowseSession(CapturedTree tree) : IBrowseSessio
var attrs = new List<AttributeInfo>();
if (n.Attribute is { } a)
attrs.Add(new AttributeInfo(n.Name, a.DriverDataType.ToString(), a.IsArray,
a.SecurityClass.ToString(), a.IsAlarm || n.IsAlarmMarked));
a.SecurityClass.ToString(), a.IsAlarm || n.IsAlarmMarked, NativeTypeFields(a)));
attrs.AddRange(n.Properties.Select(p =>
new AttributeInfo(p.Name, p.Type.ToString(), false, "", false)));
return Task.FromResult<IReadOnlyList<AttributeInfo>>(attrs);
@@ -65,6 +65,29 @@ public sealed class CapturedTreeBrowseSession(CapturedTree tree) : IBrowseSessio
private CapturedTree Tree() => _tree ?? throw new ObjectDisposedException(nameof(CapturedTreeBrowseSession));
/// <summary>
/// Surfaces a leaf's driver-native type name as the <c>dataType</c> address field, so a
/// browse-commit can stamp the driver-typed <c>TagConfig</c> with the type the controller
/// actually reported (Gitea #536).
/// </summary>
/// <param name="a">The captured attribute.</param>
/// <returns>The address fields, or null when the driver reported no native type.</returns>
/// <remarks>
/// It rides <see cref="AttributeInfo.AddressFields"/> rather than
/// <see cref="AttributeInfo.DriverDataType"/> because that field is the driver-AGNOSTIC
/// type and several consumers already read it as such. The commit mapper cannot recover the
/// native type from it: <c>SInt</c>/<c>Int</c>/<c>DInt</c> all arrive as <c>Int32</c>, so a
/// reverse map would bind a 16-bit INT as a 32-bit DINT and read four bytes for two.
/// <para>
/// Null when the driver stamped nothing — the mapper then leaves the model's own default in
/// place, which is exactly the pre-#536 behaviour rather than a guess.
/// </para>
/// </remarks>
private static IReadOnlyDictionary<string, string>? NativeTypeFields(DriverAttributeInfo a)
=> string.IsNullOrWhiteSpace(a.NativeDataType)
? null
: new Dictionary<string, string>(StringComparer.Ordinal) { ["dataType"] = a.NativeDataType };
private static BrowseNode Map(CapturedNode n) => n.IsLeaf
? new BrowseNode(n.Id, n.DisplayName, BrowseNodeKind.Leaf, false)
: new BrowseNode(n.Id, n.DisplayName, BrowseNodeKind.Folder, n.Children.Count > 0);
@@ -45,6 +45,21 @@ namespace ZB.MOM.WW.OtOpcUa.Core.Abstractions;
/// Set when <paramref name="Source"/> is <see cref="NodeSourceKind.ScriptedAlarm"/> —
/// stable logical id the ScriptedAlarmEngine addresses by. Null otherwise.
/// </param>
/// <param name="NativeDataType">
/// The driver's OWN type name for this attribute (e.g. <c>"Real"</c> for an
/// <c>AbCipDataType</c>, <c>"Int16"</c> for a <c>TwinCATDataType</c>) when the driver binds
/// by a driver-specific type enum in its <c>TagConfig</c>; null for a driver whose tag config
/// carries no type (OPC UA Client, Galaxy) or which takes the type from the wire (MQTT
/// Sparkplug births, MTConnect probe inference).
/// <para>
/// <b>It exists because <paramref name="DriverDataType"/> is lossy in exactly the direction a
/// browse-commit needs</b> (Gitea #536): <c>AbCipDataType.SInt</c>, <c>.Int</c> and <c>.DInt</c>
/// all map to <see cref="DriverDataType.Int32"/>, so a commit that reverse-mapped the
/// driver-agnostic type would bind a 16-bit INT as a 32-bit DINT. Nothing downstream of the
/// address-space build reads this — it is authoring metadata carried alongside the type the
/// node manager actually uses.
/// </para>
/// </param>
public sealed record DriverAttributeInfo(
string FullName,
DriverDataType DriverDataType,
@@ -56,7 +71,8 @@ public sealed record DriverAttributeInfo(
bool WriteIdempotent = false,
NodeSourceKind Source = NodeSourceKind.Driver,
string? VirtualTagId = null,
string? ScriptedAlarmId = null);
string? ScriptedAlarmId = null,
string? NativeDataType = null);
/// <summary>
/// Discriminates which runtime subsystem owns this node's Read/Write/
@@ -14,8 +14,10 @@ public sealed class ProbeCommand : AbCipCommandBase
{
/// <summary>Gets the tag path to probe.</summary>
[CommandOption("tag", 't', Description =
"Tag path to probe. ControlLogix default is '@raw_cpu_type' (the canonical libplctag " +
"system tag); Micro800 takes a user-supplied global (e.g. '_SYSVA_CLOCK_HOUR').",
"Tag path to probe — a real tag on the controller. Any name works to prove reachability: " +
"libplctag knows only @raw, @tags and @udt/ as special names, so anything else (including " +
"'@raw_cpu_type', which no controller defines) is sent as an ordinary symbolic name and the " +
"controller's 'tag does not exist' answer already proves the CIP session is live.",
IsRequired = true)]
public string TagPath { get; init; } = default!;
@@ -213,8 +213,11 @@ public sealed class AbCipProbeOptions
/// Tag path used for the probe. When <see cref="Enabled"/> is <c>true</c> but this is
/// <c>null</c>/blank, the driver logs a warning and runs no probe loops;
/// <c>GetHostStatuses()</c> will then report every device as <c>Unknown</c>. A family-default
/// system-tag fallback (e.g. <c>@raw_cpu_type</c> on ControlLogix) is a deferred follow-up;
/// today an operator opting into the probe must supply a tag path explicitly.
/// fallback is a deferred follow-up; today an operator opting into the probe must supply a tag
/// path explicitly. (This used to name <c>@raw_cpu_type</c> as the ControlLogix system tag such
/// a default would read. It is not one — libplctag's CIP special-tag dispatch knows only
/// <c>@raw</c>, <c>@tags</c> and <c>@udt/</c> — so any default here would be a name the
/// controller rejects, which proves reachability but never returns a value.)
/// </summary>
public string? ProbeTagPath { get; init; }
}
@@ -1068,7 +1068,8 @@ public sealed class AbCipDriver : IDriver, IReadable, IWritable, ITagDiscovery,
: SecurityClassification.ViewOnly,
IsHistorized: false,
IsAlarm: false,
WriteIdempotent: member.WriteIdempotent));
WriteIdempotent: member.WriteIdempotent,
NativeDataType: member.DataType.ToString()));
}
continue;
}
@@ -1145,7 +1146,8 @@ public sealed class AbCipDriver : IDriver, IReadable, IWritable, ITagDiscovery,
: SecurityClassification.Operate,
IsHistorized: false,
IsAlarm: false,
WriteIdempotent: false));
WriteIdempotent: false,
NativeDataType: discovered.DataType.ToString()));
}
}
}
@@ -1248,7 +1250,8 @@ public sealed class AbCipDriver : IDriver, IReadable, IWritable, ITagDiscovery,
: SecurityClassification.Operate,
IsHistorized: false,
IsAlarm: false,
WriteIdempotent: false));
WriteIdempotent: false,
NativeDataType: member.DataType.ToString()));
anyEmitted = true;
}
@@ -1277,7 +1280,8 @@ public sealed class AbCipDriver : IDriver, IReadable, IWritable, ITagDiscovery,
: SecurityClassification.ViewOnly,
IsHistorized: false,
IsAlarm: false,
WriteIdempotent: tag.WriteIdempotent);
WriteIdempotent: tag.WriteIdempotent,
NativeDataType: tag.DataType.ToString());
/// <summary>Count of registered devices — exposed for diagnostics + tests.</summary>
internal int DeviceCount => _devices.Count;
@@ -91,9 +91,16 @@ public sealed class AbCipDriverProbe : IDriverProbe
// Prefer the first authored tag path as the probe tag name (it must exist on the PLC). v3: the
// tags arrive as RawTagEntry blobs — map each through the pure factory to recover its TagPath +
// device routing key. Fall back to a benign system attribute present on all ControlLogix /
// CompactLogix controllers (@raw_cpu_type); still returns ErrorNotFound on Micro800 / MicroLogix,
// which is sufficient to confirm CIP reachability.
// device routing key.
//
// The fallback is NOT a system attribute the controller can read, despite its name and despite
// what this comment used to claim: libplctag's CIP special-tag dispatch knows only @raw, @tags
// and @udt/, so "@raw_cpu_type" is encoded and sent as an ORDINARY symbolic name. That is what
// makes it a usable probe — no controller defines it, so the controller answers CIP 0x04 ("tag
// does not exist") and the answer itself proves the session is live. IsReachableStatus is what
// turns that into a green tick, so a device with no authored tags reports reachable, not failed.
// Do not "fix" this to @tags: libplctag builds a tag-listing tag WITHOUT any network I/O, so it
// reports OK against any TCP listener — measured green against a Mosquitto broker.
var mappedTags = opts.RawTags
.Select(e => AbCipTagDefinitionFactory.FromTagConfig(e.TagConfig, e.RawPath, out var d)
? (Ok: true, Device: e.DeviceName, d.TagPath)
@@ -167,22 +174,35 @@ public sealed class AbCipDriverProbe : IDriverProbe
/// but the probe tag name was not found or did not match — sufficient to confirm CIP
/// reachability. Returns <c>true</c> for <see cref="Status.Ok"/> (tag was found).
/// </summary>
private static bool IsReachableStatus(Status s) => s is
internal static bool IsReachableStatus(Status s) => s is
Status.Ok or
Status.ErrorNotFound or
Status.ErrorNoMatch or
Status.ErrorBadDevice;
/// <summary>
/// Inspects a <see cref="LibPlcTagException"/> message to decide whether the error is a
/// "controller answered CIP but tag not found" condition (reachable) versus a session /
/// transport failure (unreachable). Falls back to checking the exception message for
/// known tag-not-found phrases used by the libplctag native library.
/// Decides whether a <see cref="LibPlcTagException"/> is a "controller answered CIP but the
/// probe tag did not resolve" condition (reachable) or a session / transport failure
/// (unreachable), by recovering the <see cref="Status"/> the wrapper threw on and deferring
/// to <see cref="IsReachableStatus"/> — one classification, not two that can drift.
/// </summary>
private static bool IsReachableException(LibPlcTagException ex)
/// <param name="ex">The exception libplctag threw out of <c>InitializeAsync</c>.</param>
/// <returns><c>true</c> when the controller answered; <c>false</c> for a transport/session failure.</returns>
/// <remarks>
/// <b>The status arrives as the managed enum NAME.</b> <c>NativeTagWrapper.ThrowIfStatusNotOk</c>
/// constructs the exception with <c>Status.ToString()</c>, so the message is exactly
/// <c>"ErrorNotFound"</c> — never the native C spelling <c>"STATUS_NOT_FOUND"</c> this method
/// used to look for. Those substrings could not match, so the reachable classification was
/// unreachable on this path — and this IS the path a probe takes whenever its tag does not
/// resolve, which is every Test Connect against a device with no authored tags. The native
/// spellings are kept as a secondary match in case a future wrapper reports them.
/// </remarks>
internal static bool IsReachableException(LibPlcTagException ex)
{
// libplctag wraps the Status in the message as "STATUS_NOT_FOUND", "STATUS_NO_MATCH", etc.
var msg = ex.Message ?? string.Empty;
if (Enum.TryParse<Status>(msg.Trim(), ignoreCase: true, out var status) && Enum.IsDefined(status))
return IsReachableStatus(status);
return msg.Contains("NOT_FOUND", StringComparison.OrdinalIgnoreCase)
|| msg.Contains("NO_MATCH", StringComparison.OrdinalIgnoreCase)
|| msg.Contains("BAD_DEVICE", StringComparison.OrdinalIgnoreCase);
@@ -613,7 +613,8 @@ public sealed class FocasDriver : IDriver, IReadable, IWritable, ITagDiscovery,
SecurityClass: SecurityClassification.ViewOnly,
IsHistorized: false,
IsAlarm: false,
WriteIdempotent: tag.WriteIdempotent));
WriteIdempotent: tag.WriteIdempotent,
NativeDataType: tag.DataType.ToString()));
}
}
return Task.CompletedTask;
@@ -638,7 +639,8 @@ public sealed class FocasDriver : IDriver, IReadable, IWritable, ITagDiscovery,
SecurityClass: SecurityClassification.ViewOnly,
IsHistorized: false,
IsAlarm: false,
WriteIdempotent: false));
WriteIdempotent: false,
NativeDataType: NativeName(type)));
}
private static void EmitAxisVariable(
@@ -653,9 +655,24 @@ public sealed class FocasDriver : IDriver, IReadable, IWritable, ITagDiscovery,
SecurityClass: SecurityClassification.ViewOnly,
IsHistorized: false,
IsAlarm: false,
WriteIdempotent: false));
WriteIdempotent: false,
NativeDataType: nameof(FocasDataType.Float64)));
}
/// <summary>
/// The <see cref="FocasDataType"/> name a fixed-tree node binds by, for the browse-commit
/// path (Gitea #536). The fixed tree only ever emits these three, and each has an
/// identically-named <see cref="FocasDataType"/> member — the driver-agnostic
/// <see cref="DriverDataType"/> cannot be reversed (Byte/Int16/Int32 all collapse to
/// <see cref="DriverDataType.Int32"/>), so the native name is carried rather than derived.
/// </summary>
private static string NativeName(FocasDriverDataType type) => type switch
{
FocasDriverDataType.Int32 => nameof(FocasDataType.Int32),
FocasDriverDataType.Float64 => nameof(FocasDataType.Float64),
_ => nameof(FocasDataType.String),
};
/// <summary>
/// Emit a variable under a named fixed-tree folder (Program, OperationMode,
/// …). Full-reference shape is <c>{deviceHost}/{folderPath}/{field}</c>.
@@ -673,7 +690,13 @@ public sealed class FocasDriver : IDriver, IReadable, IWritable, ITagDiscovery,
SecurityClass: SecurityClassification.ViewOnly,
IsHistorized: false,
IsAlarm: false,
WriteIdempotent: false));
WriteIdempotent: false,
NativeDataType: NativeName(type switch
{
DriverDataType.Int32 => FocasDriverDataType.Int32,
DriverDataType.Float64 => FocasDriverDataType.Float64,
_ => FocasDriverDataType.String,
})));
}
/// <summary>
@@ -421,7 +421,8 @@ public sealed class TwinCATDriver : IDriver, IReadable, IWritable, ITagDiscovery
: SecurityClassification.ViewOnly,
IsHistorized: false,
IsAlarm: false,
WriteIdempotent: tag.WriteIdempotent));
WriteIdempotent: tag.WriteIdempotent,
NativeDataType: tag.DataType.ToString()));
}
// Controller-side symbol browse — opt-in. Falls back to pre-declared-only on any
@@ -452,7 +453,8 @@ public sealed class TwinCATDriver : IDriver, IReadable, IWritable, ITagDiscovery
: SecurityClassification.Operate,
IsHistorized: false,
IsAlarm: false,
WriteIdempotent: false));
WriteIdempotent: false,
NativeDataType: dt.ToString()));
}
}
catch (OperationCanceledException) { throw; }
@@ -3,7 +3,10 @@ using ZB.MOM.WW.OtOpcUa.AdminUI.Uns.TagEditors;
using ZB.MOM.WW.OtOpcUa.Commons.Types;
using ZB.MOM.WW.OtOpcUa.Configuration.Enums;
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
using ZB.MOM.WW.OtOpcUa.Driver.AbCip;
using ZB.MOM.WW.OtOpcUa.Driver.FOCAS;
using ZB.MOM.WW.OtOpcUa.Driver.Sql.Contracts;
using ZB.MOM.WW.OtOpcUa.Driver.TwinCAT;
using ZB.MOM.WW.OtOpcUa.Driver.Mqtt;
namespace ZB.MOM.WW.OtOpcUa.AdminUI.Uns;
@@ -192,11 +195,19 @@ public static class RawBrowseCommitMapper
}
/// <summary>
/// Builds the driver-typed <c>TagConfig</c> JSON for a browse-committed tag, setting ONLY the driver's
/// address field to <paramref name="fullName"/> and leaving every other field at its model default. Reuses
/// the <c>&lt;Driver&gt;TagConfigModel</c> for driver types that have a typed editor; the model-less Galaxy
/// Builds the driver-typed <c>TagConfig</c> JSON for a browse-committed tag: the driver's address field
/// from <paramref name="fullName"/>, plus — for a driver that binds by its OWN data-type enum — the
/// native type the browse leaf stated (see <see cref="NativeType{TEnum}"/>). Every other field stays at
/// its model default, for the operator to author afterwards. Reuses the
/// <c>&lt;Driver&gt;TagConfigModel</c> for driver types that have a typed editor; the model-less Galaxy
/// driver gets the canonical camelCase <c>attributeRef</c> key directly.
/// <para>
/// <b>The data type is not optional decoration for AB CIP / TwinCAT / FOCAS</b> — their tag-definition
/// factories decode the wire bytes by this field, not by the raw tag row's OPC UA <c>DataType</c>. A
/// committed leaf left at the model default therefore reads real data through the wrong decoder and
/// publishes a plausible wrong number rather than an error (Gitea #536).
/// </para>
/// <para>
/// <b>MQTT is the one driver whose address is not a single string</b> — a Sparkplug tag binds by a
/// <c>(group, edgeNode, device?, metric)</c> tuple — so it is built from the browse session's stated
/// <paramref name="addressFields"/> instead. See <see cref="BuildMqttTagConfig"/>.
@@ -218,13 +229,25 @@ public static class RawBrowseCommitMapper
if (Is(driverType, DriverTypeNames.OpcUaClient))
return new OpcUaClientTagConfigModel { NodeId = address }.ToJson();
if (Is(driverType, DriverTypeNames.AbCip))
return new AbCipTagConfigModel { TagPath = address }.ToJson();
return new AbCipTagConfigModel
{
TagPath = address,
DataType = NativeType(addressFields, AbCipDataType.DInt),
}.ToJson();
if (Is(driverType, DriverTypeNames.AbLegacy))
return new AbLegacyTagConfigModel { Address = address }.ToJson();
if (Is(driverType, DriverTypeNames.TwinCAT))
return new TwinCATTagConfigModel { SymbolPath = address }.ToJson();
return new TwinCATTagConfigModel
{
SymbolPath = address,
DataType = NativeType(addressFields, TwinCATDataType.DInt),
}.ToJson();
if (Is(driverType, DriverTypeNames.FOCAS))
return new FocasTagConfigModel { Address = address }.ToJson();
return new FocasTagConfigModel
{
Address = address,
DataType = NativeType(addressFields, FocasDataType.Int32),
}.ToJson();
if (Is(driverType, DriverTypeNames.S7))
return new S7TagConfigModel { Address = address }.ToJson();
// MTConnect: the DataItem id. The driver also accepts "address"/"dataItemId", but the typed
@@ -338,6 +361,46 @@ public static class RawBrowseCommitMapper
+ "the tag manually.";
}
/// <summary>
/// Reads the browse leaf's driver-native data type out of the stated address fields, falling
/// back to <paramref name="fallback"/> — the driver model's own default — when the browser
/// stated none or stated one this driver's enum does not name.
/// </summary>
/// <typeparam name="TEnum">The driver's own data-type enum.</typeparam>
/// <param name="addressFields">The leaf's stated address fields.</param>
/// <param name="fallback">The model default to keep when no usable native type was stated.</param>
/// <returns>The parsed native type, or <paramref name="fallback"/>.</returns>
/// <remarks>
/// <b>The type is READ, never derived (Gitea #536).</b> A commit used to leave this at the
/// model default, so every browsed AB CIP leaf — a REAL, a BOOL, a STRING — was written as
/// <c>DInt</c> and the driver decoded four bytes of a float as an integer: a plausible
/// number, no error, wrong value. Deriving it from the leaf's driver-AGNOSTIC
/// <c>DriverDataType</c> instead would fix the REAL and still get the integers wrong —
/// <c>SInt</c>, <c>Int</c> and <c>DInt</c> all collapse into <c>Int32</c> on the way out, so
/// a 16-bit INT would come back as a 32-bit DINT. The producing driver knows its own type
/// and states it; see <c>CapturedTreeBrowseSession.NativeTypeFields</c>.
/// <para>
/// Case-insensitive because the key travels as an enum NAME, and a driver is free to spell
/// it however its own enum does. An unparseable value keeps the default rather than failing
/// the commit: the address — the part that cannot be re-derived later — is still correct,
/// and the operator can fix the type in the typed editor.
/// </para>
/// <para>
/// <b>A numeric string is refused before parsing.</b> <c>Enum.TryParse</c> accepts <c>"9"</c>
/// for any enum and hands back whatever member sits at ordinal 9 — which <c>Enum.IsDefined</c>
/// then happily confirms — so a driver that stamped a number would bind a tag to a type nobody
/// named. Same trap <c>MTConnectTagConfigModel</c> documents for its own <c>dataType</c>.
/// </para>
/// </remarks>
private static TEnum NativeType<TEnum>(IReadOnlyDictionary<string, string>? addressFields, TEnum fallback)
where TEnum : struct, Enum
=> TryGetField(addressFields, "dataType") is { Length: > 0 } raw
&& !char.IsAsciiDigit(raw[0]) && raw[0] is not ('-' or '+')
&& Enum.TryParse<TEnum>(raw, ignoreCase: true, out var parsed)
&& Enum.IsDefined(parsed)
? parsed
: fallback;
/// <summary>Reads one non-blank address field, or <c>null</c> when it is absent or blank.</summary>
/// <param name="fields">The stated address fields, or null.</param>
/// <param name="key">The field to read.</param>
@@ -70,6 +70,43 @@ public class CapturedTreeBrowseSessionTests
alarmAttrs.Single().IsAlarm.ShouldBeTrue();
}
/// <summary>
/// A driver's OWN type name reaches the picker as the <c>dataType</c> address field, so the
/// browse-commit can stamp the driver-typed TagConfig with the type the device reported rather
/// than the tag model's default (Gitea #536). It cannot ride
/// <see cref="AttributeInfo.DriverDataType"/>: that is the driver-agnostic type, and several
/// native types share one agnostic value.
/// </summary>
[Fact]
public async Task AttributesCarryTheDriverNativeTypeForTheCommitPath()
{
var b = new CapturingAddressSpaceBuilder();
b.Variable("Speed", "Speed", new DriverAttributeInfo(
"Pump_1_Speed", DriverDataType.Float32, false, null,
SecurityClassification.Operate, false, NativeDataType: "Real"));
await using var s = new CapturedTreeBrowseSession(b.Build());
var a = (await s.AttributesAsync("Pump_1_Speed", CancellationToken.None)).Single();
a.AddressFields.ShouldNotBeNull()["dataType"].ShouldBe("Real");
a.DriverDataType.ShouldBe(DriverDataType.Float32.ToString()); // the agnostic type is unchanged
}
/// <summary>
/// A driver that states no native type states NOTHING — the commit then keeps its model default
/// instead of a guess. An empty-but-present dictionary would be indistinguishable from "the
/// driver stamped a blank type", so the absence has to be represented as absence.
/// </summary>
[Fact]
public async Task AttributesCarryNoAddressFieldsWhenTheDriverStatedNoNativeType()
{
await using var s = new CapturedTreeBrowseSession(SampleTree());
var a = (await s.AttributesAsync("Plc1.Speed", CancellationToken.None)).Single();
a.AddressFields.ShouldBeNull();
}
[Fact]
public async Task TruncatedTreeAppendsMarkerFolderAtRoot()
{
@@ -12,10 +12,12 @@ clone needs Docker Desktop and nothing else.
|---|---|
| [`Dockerfile`](Dockerfile) | Multi-stage: build from libplctag at pinned tag → copy binary into `debian:bookworm-slim` runtime image |
| [`docker-compose.yml`](docker-compose.yml) | One service per family (`controllogix` / `compactlogix` / `micro800` / `guardlogix`); all bind `:44818` |
| [`patches/`](patches/) | Applied to the libplctag checkout before the build — see [Local patches](#local-patches) |
| [`patches/`](patches/) | Applied to the libplctag checkout before the build, in filename order — see [Local patches](#local-patches) |
## Local patches
### 0001 — serve the Symbol Object listing
`patches/0001-ab_server-serve-cip-symbol-object-listing.patch` teaches `ab_server`
to answer **CIP service 0x55 (Get Instance Attribute List) on class 0x6B**, the
Symbol Object listing a client reads through the `@tags` pseudo-tag to enumerate
@@ -49,7 +51,28 @@ Partial-transfer paging is exercised the same way by starting `ab_server` with a
few hundred tags: all of them should come back, with no duplicates and no gaps
at the page boundaries.
**Bumping `LIBPLCTAG_TAG` means re-checking the patch against the new tag.** It
### 0002 — answer "tag does not exist" the way a controller does
`patches/0002-ab_server-answer-tag-not-found-with-cip-0x04.patch` changes the reply
to an unresolvable tag path from CIP **0x03** (invalid parameter) to CIP **0x04**
(*IOI could not be deciphered or tag does not exist*), which is what a Logix
controller returns. libplctag translates the two very differently — `ErrorBadParam`
versus `ErrorNotFound` — and every client that classifies by status code reads the
first as "your request was malformed" and the second as "the controller answered,
that tag isn't there."
The distinction is load-bearing here: the driver's Test Connect probe falls back to a
name no controller defines, so **"tag not found" is the successful answer** when a
device has no authored tags yet. Before this patch the fixture reported a perfectly
healthy sim as a failed handshake, and — worse — the discrepancy was written down as
a fixture limitation, which hid a real driver defect behind it for as long as it
stood (`AbCipDriverProbe.IsReachableException` matched the native C spellings, which
the .NET wrapper never produces, so the reachable classification could not fire at
all). `AbCip_WithNoAuthoredTags_ReportsTheControllerReachable` in
`Host.IntegrationTests` is the pin, and it needs the fixture **rebuilt** from this
patch, not merely running.
**Bumping `LIBPLCTAG_TAG` means re-checking both patches against the new tag.** It
is a concrete tag rather than the `release` branch precisely so that this stays
a deliberate act — the branch moves, and the Dockerfile previously called it
"pinned" while tracking it.
@@ -117,11 +140,6 @@ place means updating both.
unit tests with golden byte buffers. The Symbol Object patch above lists
symbols, including their types; it does not add Template Object support, so a
browsed UDT still cannot be expanded into members here.
- **No `@raw_cpu_type`** — the driver's Test Connect probe falls back to that
pseudo-tag when a device has no authored tags, and `ab_server` answers
`ErrorBadParam`. So **Test Connect reports failure against this fixture even
when the device is fine**, and browse works regardless. Author one tag and the
probe uses it instead.
- **Controller-scope listing only** — a program-scope listing arrives with a
leading symbolic segment naming the program, and `ab_server` has no notion of
programs. `Program:`-scoped tags cannot be browsed here.
@@ -0,0 +1,30 @@
diff --git a/src/tools/ab_server/cip.c b/src/tools/ab_server/cip.c
index 68a5794..f286504 100644
--- a/src/tools/ab_server/cip.c
+++ b/src/tools/ab_server/cip.c
@@ -746,7 +746,11 @@ slice_s handle_read_request(uint8_t cip_service, slice_s cip_service_path, slice
if(!parse_tag_path(cip_service_path, plc, &tag, &num_indexes, &(indexes[0]))) {
log_info("Unable to parse tag path:");
log_info_slice(cip_service_path);
- return make_cip_log_error(output, cip_service, CIP_ERR_INVALID_PARAM, false, 0);
+ /* A Logix controller answers an unresolvable tag path with 0x04 ("IOI could not be
+ * deciphered or tag does not exist"), which clients read as "tag not found" and
+ * distinguish from a malformed request. Answering 0x03 instead reported a live
+ * controller as a failed handshake to any client that classifies by status code. */
+ return make_cip_log_error(output, cip_service, CIP_ERR_PATH_SEGMENT, false, 0);
}
/* Record request arrival time for latency tracking */
@@ -916,7 +920,11 @@ slice_s handle_write_request(uint8_t cip_service, slice_s cip_service_path, slic
if(!parse_tag_path(cip_service_path, plc, &tag, &num_indexes, &(indexes[0]))) {
log_info("Unable to parse tag path:");
log_info_slice(cip_service_path);
- return make_cip_log_error(output, cip_service, CIP_ERR_INVALID_PARAM, false, 0);
+ /* A Logix controller answers an unresolvable tag path with 0x04 ("IOI could not be
+ * deciphered or tag does not exist"), which clients read as "tag not found" and
+ * distinguish from a malformed request. Answering 0x03 instead reported a live
+ * controller as a failed handshake to any client that classifies by status code. */
+ return make_cip_log_error(output, cip_service, CIP_ERR_PATH_SEGMENT, false, 0);
}
/* Record request arrival time for latency tracking */
@@ -0,0 +1,44 @@
using Shouldly;
using Xunit;
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
namespace ZB.MOM.WW.OtOpcUa.Driver.AbCip.Tests;
/// <summary>
/// Pins the one property of <see cref="AbCipDataTypeExtensions.ToDriverDataType"/> that another
/// subsystem depends on: it is LOSSY, so it cannot be run backwards.
/// </summary>
[Trait("Category", "Unit")]
public sealed class AbCipDataTypeExtensionsTests
{
/// <summary>
/// Four distinct Logix integer widths leave the driver as one driver-agnostic type. This is why a
/// browse-commit carries the native type instead of deriving it from the leaf's
/// <see cref="DriverDataType"/> (Gitea #536) — a reverse map would have to pick one width for all
/// four, and picking wrong reads the wrong number of bytes with no error raised anywhere.
/// </summary>
[Fact]
public void The_integer_widths_collapse_which_is_why_the_native_type_is_carried()
{
var widths = new[]
{
AbCipDataType.SInt, AbCipDataType.Int, AbCipDataType.DInt,
AbCipDataType.USInt, AbCipDataType.UInt,
};
widths.Select(t => t.ToDriverDataType()).Distinct().ShouldHaveSingleItem()
.ShouldBe(DriverDataType.Int32);
}
/// <summary>
/// The falsifying half: an unsigned 32-bit tag does NOT collapse with the rest, so a test that only
/// showed "several types share an output" would pass against a map that collapsed everything.
/// </summary>
[Fact]
public void The_wider_unsigned_types_stay_distinct()
{
AbCipDataType.UDInt.ToDriverDataType().ShouldBe(DriverDataType.UInt32);
AbCipDataType.ULInt.ToDriverDataType().ShouldBe(DriverDataType.UInt64);
AbCipDataType.Real.ToDriverDataType().ShouldBe(DriverDataType.Float32);
}
}
@@ -34,6 +34,36 @@ public sealed class AbCipDriverDiscoveryTests
builder.Variables.Single(v => v.BrowseName == "Temperature").Info.SecurityClass.ShouldBe(SecurityClassification.ViewOnly);
}
/// <summary>
/// Every emitted variable states its Logix type, so a browse-commit binds the tag with the type
/// the controller has rather than the tag model's <c>DInt</c> default (Gitea #536). The
/// driver-agnostic <see cref="DriverAttributeInfo.DriverDataType"/> cannot serve — <c>SInt</c>,
/// <c>Int</c> and <c>DInt</c> all arrive there as <see cref="DriverDataType.Int32"/>.
/// </summary>
[Fact]
public async Task Emitted_variables_state_their_Logix_type_for_the_commit_path()
{
var builder = new RecordingBuilder();
var drv = new AbCipDriver(new AbCipDriverOptions
{
Devices = [new AbCipDeviceOptions("ab://10.0.0.5/1,0")],
RawTags = AbCipRawTags.From(
new AbCipTagDefinition("Speed", "ab://10.0.0.5/1,0", "Motor1.Speed", AbCipDataType.Real),
new AbCipTagDefinition("Count", "ab://10.0.0.5/1,0", "C", AbCipDataType.Int)),
}, "drv-1");
await drv.InitializeAsync("{}", CancellationToken.None);
await drv.DiscoverAsync(builder, CancellationToken.None);
builder.Variables.Single(v => v.BrowseName == "Speed").Info.NativeDataType.ShouldBe("Real");
// Int and DInt are indistinguishable downstream — this pair is the whole reason the native
// name is carried, so assert both halves rather than only the one that differs by kind.
var count = builder.Variables.Single(v => v.BrowseName == "Count").Info;
count.NativeDataType.ShouldBe("Int");
count.DriverDataType.ShouldBe(DriverDataType.Int32);
}
/// <summary>Verifies that device folder display name falls back to host address when not provided.</summary>
[Fact]
public async Task Device_folder_displayname_falls_back_to_host_address()
@@ -1,5 +1,6 @@
using System.Net;
using System.Net.Sockets;
using libplctag;
using Shouldly;
using Xunit;
@@ -144,4 +145,45 @@ public sealed class AbCipDriverProbeTests
$"Expected 'timed out' or 'Connect failed' but got: {result.Message}");
result.Latency.ShouldBeNull();
}
// -------------------------------------------------------------------------
// 5. Reachable-vs-failed classification (offline — no controller needed)
// -------------------------------------------------------------------------
/// <summary>
/// The exception path classifies by the SAME rule as the status path. libplctag.NET builds
/// <see cref="LibPlcTagException"/> with <c>Status.ToString()</c>, so its message is
/// "ErrorNotFound" — this method used to look for the native C spelling "STATUS_NOT_FOUND",
/// which that message can never contain, so a controller that answered "tag does not exist"
/// was reported as a failed handshake. That is the answer every Test Connect gets on a device
/// with no authored tags, i.e. every device at the moment an operator first presses the button.
/// </summary>
/// <param name="status">The status libplctag threw on.</param>
/// <param name="expectedReachable">Whether the controller should be reported reachable.</param>
[Theory]
[InlineData(Status.ErrorNotFound, true)]
[InlineData(Status.ErrorNoMatch, true)]
[InlineData(Status.ErrorBadDevice, true)]
[InlineData(Status.ErrorTimeout, false)]
[InlineData(Status.ErrorBadConnection, false)]
[InlineData(Status.ErrorBadGateway, false)]
[InlineData(Status.ErrorBadParam, false)]
public void ThrownStatus_IsClassifiedTheSameWayAsAReturnedStatus(Status status, bool expectedReachable)
{
// Exactly how NativeTagWrapper.ThrowIfStatusNotOk constructs it.
var ex = new LibPlcTagException(status.ToString());
AbCipDriverProbe.IsReachableException(ex).ShouldBe(expectedReachable);
AbCipDriverProbe.IsReachableStatus(status).ShouldBe(expectedReachable);
}
/// <summary>
/// A message that names no status at all stays UNreachable rather than defaulting green — the
/// conservative half, and the one an over-eager "treat anything we cannot parse as reachable"
/// fix would break.
/// </summary>
[Fact]
public void AnUnrecognisedExceptionMessageIsNotTreatedAsReachable()
=> AbCipDriverProbe.IsReachableException(
new LibPlcTagException("something the wrapper has never said")).ShouldBeFalse();
}
@@ -36,6 +36,13 @@ public sealed class FocasCapabilityTests
// Writable field, because WireFocasClient.WriteAsync always returns BadNotWritable.
builder.Variables.Single(v => v.BrowseName == "Run").Info.SecurityClass.ShouldBe(SecurityClassification.ViewOnly);
builder.Variables.Single(v => v.BrowseName == "Alarm").Info.SecurityClass.ShouldBe(SecurityClassification.ViewOnly);
// Each variable states its FOCAS type for the browse-commit path (Gitea #536). Byte is the
// case that matters: it reaches Info.DriverDataType as Int32, exactly like Int16 and Int32,
// so a commit deriving the type from there would read four PMC bytes for a one-byte tag.
var run = builder.Variables.Single(v => v.BrowseName == "Run").Info;
run.NativeDataType.ShouldBe("Byte");
run.DriverDataType.ShouldBe(DriverDataType.Int32);
}
// ---- ISubscribable ----
@@ -34,6 +34,12 @@ public sealed class TwinCATCapabilityTests
builder.Folders.ShouldContain(f => f.BrowseName == "ads://5.23.91.23.1.1:851" && f.DisplayName == "Mach1");
builder.Variables.Single(v => v.BrowseName == "Speed").Info.SecurityClass.ShouldBe(SecurityClassification.Operate);
builder.Variables.Single(v => v.BrowseName == "Status").Info.SecurityClass.ShouldBe(SecurityClassification.ViewOnly);
// Each variable states its IEC type, so a browse-commit binds the tag with the type the PLC
// declares rather than TwinCATTagConfigModel's DInt default (Gitea #536). It cannot be
// recovered from Info.DriverDataType — Byte/Int16/Int32 all land there as Int32.
builder.Variables.Single(v => v.BrowseName == "Status").Info.NativeDataType.ShouldBe("Bool");
builder.Variables.Single(v => v.BrowseName == "Speed").Info.NativeDataType.ShouldBe("DInt");
}
// ---- ISubscribable ----
@@ -6,6 +6,7 @@ using ZB.MOM.WW.OtOpcUa.AdminUI.Uns;
using ZB.MOM.WW.OtOpcUa.Commons.Types;
using ZB.MOM.WW.OtOpcUa.Configuration.Enums;
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
using ZB.MOM.WW.OtOpcUa.Driver.AbCip;
using ZB.MOM.WW.OtOpcUa.Driver.Mqtt;
namespace ZB.MOM.WW.OtOpcUa.AdminUI.Tests.Uns;
@@ -98,6 +99,126 @@ public sealed class RawBrowseCommitMapperTests
JsonNode.Parse(json)!.AsObject()["address"]!.GetValue<string>().ShouldBe("40001");
}
// ---- BuildTagConfig: the browsed data type (Gitea #536) --------------------------------------
/// <summary>The address fields a captured browse leaf states for its driver-native type.</summary>
/// <param name="nativeType">The driver's own data-type enum name, as the driver stamped it.</param>
/// <returns>The stated address fields.</returns>
private static Dictionary<string, string> NativeTypeFields(string nativeType) =>
new() { ["dataType"] = nativeType };
/// <summary>
/// The committed <c>dataType</c> is the type the CONTROLLER reported, not the model default.
/// AB CIP / TwinCAT / FOCAS decode the wire bytes by this field, so a browsed REAL left at the
/// <c>DInt</c> default reads four bytes of a float as an integer and publishes a plausible
/// wrong number with no error anywhere.
/// </summary>
/// <param name="driverType">The owning device's driver type.</param>
/// <param name="nativeType">The native type the browse leaf stated.</param>
/// <param name="reference">The leaf's driver-side reference.</param>
[Theory]
[InlineData("AbCip", "Real", "Pump_1_Speed")]
[InlineData("AbCip", "Bool", "Motor_Run")]
[InlineData("AbCip", "String", "Recipe_Name")]
[InlineData("TwinCAT", "Bool", "MAIN.bStart")]
[InlineData("FOCAS", "Float64", "MACRO100")]
public void BuildTagConfig_stamps_the_browsed_data_type(
string driverType, string nativeType, string reference)
{
var json = RawBrowseCommitMapper.BuildTagConfig(driverType, reference, NativeTypeFields(nativeType));
JsonNode.Parse(json)!.AsObject()["dataType"]!.GetValue<string>().ShouldBe(nativeType);
}
/// <summary>
/// The narrow integer widths are the reason the native type is CARRIED rather than derived from
/// the leaf's driver-agnostic <c>DriverDataType</c>: <c>SInt</c>, <c>Int</c> and <c>DInt</c> all
/// leave the driver as <c>Int32</c>, so a reverse map would read a 16-bit INT through a 32-bit
/// decoder — two bytes of the next tag's memory included — and still look like a fix.
/// </summary>
/// <param name="nativeType">The Logix integer width the controller reported.</param>
[Theory]
[InlineData("SInt")]
[InlineData("Int")]
[InlineData("DInt")]
[InlineData("UDInt")]
public void BuildTagConfig_keeps_integer_widths_that_the_agnostic_type_collapses(string nativeType)
{
// That these widths really do collapse on the way out of the driver is pinned next to the map
// itself — AbCipDataTypeExtensionsTests.The_integer_widths_collapse_which_is_why_the_native_type_is_carried.
var json = RawBrowseCommitMapper.BuildTagConfig("AbCip", "Line1_Count", NativeTypeFields(nativeType));
JsonNode.Parse(json)!.AsObject()["dataType"]!.GetValue<string>().ShouldBe(nativeType);
}
/// <summary>
/// A leaf that states no type — a browser that reports none, or a session captured before the
/// driver stamped it — keeps the model default rather than guessing. That is the pre-#536
/// behaviour, deliberately retained as the fallback.
/// </summary>
/// <param name="driverType">The owning device's driver type.</param>
/// <param name="expectedDefault">The model default the commit must fall back to.</param>
[Theory]
[InlineData("AbCip", "DInt")]
[InlineData("TwinCAT", "DInt")]
[InlineData("FOCAS", "Int32")]
public void BuildTagConfig_falls_back_to_the_model_default_when_no_type_is_stated(
string driverType, string expectedDefault)
{
var noFields = RawBrowseCommitMapper.BuildTagConfig(driverType, "X");
var unparseable = RawBrowseCommitMapper.BuildTagConfig(
driverType, "X", NativeTypeFields("NotATypeThisDriverKnows"));
JsonNode.Parse(noFields)!.AsObject()["dataType"]!.GetValue<string>().ShouldBe(expectedDefault);
JsonNode.Parse(unparseable)!.AsObject()["dataType"]!.GetValue<string>().ShouldBe(expectedDefault);
}
/// <summary>
/// A numeric string is NOT a type name. <c>Enum.TryParse</c> accepts "3" for any enum and yields
/// whatever member happens to sit at 3, so an unguarded parse would silently bind a tag to a type
/// nobody named — the same trap <c>MTConnectTagConfigModel</c> documents for its own dataType.
/// </summary>
[Fact]
public void BuildTagConfig_rejects_a_numeric_type_rather_than_indexing_the_enum()
{
// AbCipDataType member 9 is Real; a numeric parse would hand back exactly that.
((AbCipDataType)9).ShouldBe(AbCipDataType.Real);
var json = RawBrowseCommitMapper.BuildTagConfig("AbCip", "X", NativeTypeFields("9"));
JsonNode.Parse(json)!.AsObject()["dataType"]!.GetValue<string>().ShouldBe("DInt");
}
/// <summary>
/// The stated type never displaces the address — the two travel in different fields and a commit
/// that got the type right by losing the binding would be no better than the defect.
/// </summary>
[Fact]
public void BuildTagConfig_stamps_the_type_without_disturbing_the_address()
{
var json = RawBrowseCommitMapper.BuildTagConfig(
"AbCip", "Program:Main.Motor.Speed", NativeTypeFields("Real"));
var o = JsonNode.Parse(json)!.AsObject();
o["tagPath"]!.GetValue<string>().ShouldBe("Program:Main.Motor.Speed");
o["dataType"]!.GetValue<string>().ShouldBe("Real");
}
/// <summary>
/// A driver whose tag config carries no data type is unaffected — the key must not appear, or a
/// typed editor would round-trip a field its model does not own.
/// </summary>
/// <param name="driverType">The owning device's driver type.</param>
[Theory]
[InlineData("OpcUaClient")]
[InlineData("GalaxyMxGateway")]
public void BuildTagConfig_does_not_invent_a_data_type_for_a_driver_that_has_none(string driverType)
{
var json = RawBrowseCommitMapper.BuildTagConfig(driverType, "X", NativeTypeFields("Real"));
JsonNode.Parse(json)!.AsObject().ContainsKey("dataType").ShouldBeFalse();
}
// ---- BuildTagConfig: MQTT (the address is a DESCRIPTOR, not a single reference string) --------
/// <summary>The Sparkplug address a browse session states for a metric under a device.</summary>
@@ -173,11 +173,7 @@ public sealed class DriverProbeHandshakeE2eTests
{
SkipUnless(DockerHost, AbCipPort);
// Probe an explicit tag that the ab_server ControlLogix sim actually defines
// (`TestDINT:DINT[1]`). The no-tags fallback (`@raw_cpu_type`) is NOT exercised here:
// ab_server answers an unknown/unsupported tag with libplctag ErrorBadParam (a REAL
// ControlLogix instead returns ErrorNotFound, which the probe classifies as
// reachable). Whether the `@raw_cpu_type` system-tag fallback is valid on a real
// ControlLogix is a hardware-gated follow-up (AbCipDriverOptions.cs flags it deferred).
// (`TestDINT:DINT[1]`). The no-tags fallback is exercised separately, below.
// ⚠️ The config must use the v3 `RawTags` shape — `[{RawPath, TagConfig, WriteIdempotent,
// DeviceName}]`, where the Logix tag path lives inside the TagConfig blob as `tagPath`. This
// test passed the retired v2 `Tags: [{DeviceHostAddress, TagPath}]` shape until 2026-08-01, so
@@ -200,4 +196,34 @@ public sealed class DriverProbeHandshakeE2eTests
// ever resolved. Reading the authored tag is the entire point of this test.
result.Message.ShouldBe("CIP session OK");
}
/// <summary>
/// Test Connect on a device with NO authored tags — which is every AB CIP device at the moment
/// an operator first presses the button — must report the controller as reachable.
/// </summary>
/// <remarks>
/// The probe falls back to a name no controller defines, so the green answer arrives as a CIP
/// "tag does not exist" (0x04 → libplctag <c>ErrorNotFound</c>), which
/// <c>AbCipDriverProbe.IsReachableStatus</c> classifies as reachable. Until 2026-08-01 that
/// classification had never been exercised against any backend: <c>ab_server</c> answered an
/// unresolvable tag path with 0x03 (<c>ErrorBadParam</c>) where a Logix controller answers 0x04,
/// so the fixture reported a healthy sim as a failed handshake and the discrepancy was written
/// down as a fixture limitation rather than fixed. It is now fixed in the vendored patch —
/// <c>Docker/patches/0002-ab_server-answer-tag-not-found-with-cip-0x04.patch</c> — so this test
/// needs the fixture rebuilt from that patch, not merely running.
/// </remarks>
[Fact]
public async Task AbCip_WithNoAuthoredTags_ReportsTheControllerReachable()
{
SkipUnless(DockerHost, AbCipPort);
var result = await new AbCipDriverProbe().ProbeAsync(
$"{{\"Devices\":[{{\"HostAddress\":\"ab://{DockerHost}:{AbCipPort}/1,0\"}}],\"RawTags\":[]}}",
Timeout, Ct);
result.Ok.ShouldBeTrue($"Probe message: {result.Message}");
// EXACT for the same reason as the test above, and here it carries the extra weight of proving
// WHICH green this is: the fallback's "probe tag not found", not a tag that was actually read.