cd19022d19 Phase 3 PR 45 -- DL205 string byte-order quirk (low-byte-first ASCII packing). Adds ModbusStringByteOrder enum {HighByteFirst, LowByteFirst} + StringByteOrder field on ModbusTagDefinition (default HighByteFirst, the standard Modbus convention). DecodeRegister + EncodeRegister String branches now respect per-tag byte order. Under LowByteFirst each register packs the first char in the low byte instead of the high byte -- the AutomationDirect DirectLOGIC DL205/DL260/DL350 family's headline string quirk. Without the flag the driver decodes 'eHllo' garbage from HR[1040..1042] even though wire bytes are identical. Unit tests: String_LowByteFirst_decodes_DL205_packed_Hello (5 chars across 3 regs with nul pad), String_LowByteFirst_decode_truncates_at_first_nul, String_LowByteFirst_encode_round_trips_with_decode (asserts exact DL205-documented byte sequence {0x65,0x48,0x6C,0x6C,0x00,0x6F} + symmetric encode->decode), String_HighByteFirst_and_LowByteFirst_differ_on_same_wire (control: same wire, different flag => different decode). 56/56 Modbus.Tests pass. Integration test: DL205StringQuirkTests.DL205_string_low_byte_first_decodes_Hello_from_HR1040 against the dl205.json pymodbus profile; reads HR[1040..1042] with both flags on the same tag map and asserts LowByteFirst='Hello' + HighByteFirst!='Hello'. Gated on MODBUS_SIM_PROFILE=dl205 since the standard profile doesn't seed HR[1040..1042]. Verified 2/2 integration tests pass against running pymodbus dl205 simulator. Baseline for PR 46 (BCD decoder), PR 47 (V-memory octal helper), PR 48 (CDAB float order), PR 49 (FC03/FC16 per-device caps) -- each lands its own DL205_<behavior> test class in tests/.../DL205/. 2026-04-18 21:43:32 -04:00
5ee9acb255 Merge pull request 'Phase 3 PR 44 -- pymodbus validation + IPv4-explicit transport bugfix' (#43) from phase-3-pr44-pymodbus-validation-fixes into v2 2026-04-18 21:39:24 -04:00
Joseph Doherty
02fccbc762 Phase 3 PR 43 — followup commit: validate pymodbus simulator end-to-end + fix three real bugs surfaced by running it. winget-installed Python 3.12.10 + pip-installed pymodbus[simulator]==3.13.0 on the dev box; both profiles boot cleanly, the integration-suite smoke test passes against either profile.
Three substantive issues caught + fixed during the validation pass:
1. pymodbus rejects unknown keys at device-list / setup level. My PR 43 commit had `_layout_note`, `_uint16_layout`, `_bits_layout`, `_write_note` device-level JSON-comment fields that crashed pymodbus startup with `INVALID key in setup`. Removed all device-level _* fields. Inline `_quirk` keys WITHIN individual register entries are tolerated by pymodbus 3.13.0 — kept those in dl205.json since they document the byte math per quirk and the README + git history aren't enough context for a hand-author reading raw integer values. Documented the constraint in the top-level _comment of each profile.
2. pymodbus rejects sweeping `write` ranges that include any cell not assigned a type. My initial standard.json had `write: [[0, 2047]]` but only seeded HR[0..31] + HR[100] + HR[200..209] + bits[1024..1109] — pymodbus blew up on cell 32 (gap between HR[31] and HR[100]). Fixed by listing per-block write ranges that exactly mirror the seeded ranges. Same fix in dl205.json (was `[[0, 16383]]`).
3. pymodbus simulator stores all 4 standard Modbus tables in ONE underlying cell array — each cell can only be typed once (BITS or UINT16, not both). My initial standard.json had `bits[0..31]` AND `uint16[0..31]` overlapping at the same addresses; pymodbus crashed with `ERROR "uint16" <Cell> used`. Fixed by relocating coils to address 1024+, well clear of the uint16 entries at 0..209. Documented the layout constraint in the standard.json top-level _comment.
Substantive driver bug fixed: ModbusTcpTransport.ConnectAsync was using `new TcpClient()` (default constructor — dual-stack, IPv6 first) then `ConnectAsync(host, port)` with the user's hostname. .NET's TcpClient default-resolves "localhost" to ::1 first, fails to connect to pymodbus (which binds 0.0.0.0 IPv4-only), and only then retries IPv4 — the failure surfaces as the entire ConnectAsync timeout (2s by default) before the IPv4 attempt even starts. PR 30's smoke test silently SKIPPED because the fixture's TCP probe hit the same dual-stack ordering and timed out. Both fixed: ModbusSimulatorFixture probe now resolves Dns.GetHostAddresses, prefers AddressFamily.InterNetwork, dials IPv4 explicitly. ModbusTcpTransport does the same — resolves first, prefers IPv4, falls back to whatever Dns returns (handles IPv6-only hosts in the future). This is a real production-readiness fix because most Modbus PLCs are IPv4-only — a generic dual-stack TcpClient would burn the entire connect timeout against any IPv4-only PLC, masquerading as a connection failure when the PLC is actually fine.
Smoke-test address shifted HR[100] -> HR[200]. Standard.json's HR[100] is the auto-incrementing register that drives subscribe-and-receive tests, so write-then-read against it would race the increment. HR[200] is the first cell of a writable scratch range present in BOTH simulator profiles. DL205Profile.cs xml-doc updated to explain the shift; tag name "DL205_Smoke_HReg100" -> "Smoke_HReg200" + smoke test references updated. dl205.json gains a matching scratch HR[200..209] range so the smoke test runs identically against either profile.
Validation matrix:
- standard.json boot: clean (TCP 5020 listening within ~3s of pymodbus.simulator launch).
- dl205.json boot: clean.
- pymodbus client direct FC06 to HR[200]=1234 + FC03 read: round-trip OK.
- raw-bytes PowerShell TcpClient FC06 + 12-byte response: matches FC06 spec (echo of address + value).
- DL205SmokeTest against standard.json: 1/1 pass (was failing as 'BadInternalError' due to the dual-stack timeout + tag-name typo — both fixed).
- DL205SmokeTest against dl205.json: 1/1 pass.
- Modbus.Tests Unit suite: 52/52 pass — dual-stack transport fix is non-breaking.
- Solution build clean.
Memory + future-PR setup: pymodbus install + activation pattern is now bullet-pointed at the top of Pymodbus/README.md so future PRs (the per-quirk DL205_<behavior> tests in PR 44+) don't have to repeat the trial-and-error of getting the simulator + integration tests cooperating. The three bugs above are documented inline in the JSON profiles + ModbusTcpTransport so they don't bite again.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-18 21:14:02 -04:00
faeab34541 Merge pull request 'Phase 3 PR 43 — Swap ModbusPal to pymodbus for the integration-test simulator' (#42) from phase-3-pr43-pymodbus-swap into v2 2026-04-18 20:52:46 -04:00
Joseph Doherty
a05b84858d Phase 3 PR 43 — Swap ModbusPal to pymodbus for the integration-test simulator. Replaces the .xmpp profiles shipped in PR 42 with pymodbus 3.13.0 ModbusSimulatorServer JSON configs in tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/Pymodbus/. Substantive reasons for the swap (rationale block in the test-plan doc): ModbusPal 1.6b is abandoned (last release ~2019), Java GUI-only with no headless mode in the official JAR, and only exposes 2 of the 4 standard Modbus tables (holding_registers + coils — no input_registers, no discrete_inputs). pymodbus is current stable, pure Python CLI (pip install pymodbus[simulator]==3.13.0), exposes all four tables, has built-in declarative actions (increment / random / timestamp / uptime) for dynamic registers, supports custom Python actions for anything more complex, and ships an optional aiohttp-based web UI / REST API for live inspection. Pip-installable on Windows; sidesteps the privileged-port admin requirement by defaulting to TCP 5020.
ModbusSimulatorFixture default port bumped from 502 to 5020 to match the pymodbus convention. Override via MODBUS_SIM_ENDPOINT for a real PLC on its native 502. Skip-message updated to point at the new Pymodbus\serve.ps1 wrapper instead of 'start ModbusPal'. csproj <None Update> rule swapped from ModbusPal/** to Pymodbus/** so the new JSON profiles + serve.ps1 + README copy to test-output as PreserveNewest.
standard.json — generic Modbus TCP server, slave id 1, port 5020, shared blocks=false (independent coils + HR address spaces, more textbook-PLC-like). HR[0..31] seeded with address-as-value via per-register uint16 entries, HR[100] auto-increments via the built-in increment action with parameters minval=0/maxval=65535 (drives subscribe-and-receive integration tests so they have a register that ticks without a write — pymodbus's increment ticks per-access not wall-clock, which is good enough for a 250ms-poll test), HR[200..209] scratch range left at 0 for write tests, coils 0..31 alternating, coils 100..109 scratch. write list covers 0..1023 so any test address is mutable.
dl205.json — AutomationDirect DirectLOGIC DL205/DL260 quirk simulator, slave id 1, port 5020, shared blocks=true (matches DL series memory model where coils/DI/HR overlay the same word address space). Each quirky register seeded with the pre-computed raw uint16 value documented in docs/v2/dl205.md, with an inline _quirk JSON-comment naming the behavior so future-me reading the file knows why HR[1040]=25928 means 'H' lo / 'e' hi (the user's headline string-byte-order finding). Encoded quirks: V0 marker at HR[0]=0xCAFE; V2000 at HR[1024]=0x2000; V40400 at HR[8448]=0x4040; 'Hello' string at HR[1040..1042] first-char-low-byte; Float32 1.5f at HR[1056..1057] in CDAB word order (low word first); BCD register at HR[1072]=0x1234; FC03-128-cap block at HR[1280..1407]; Y0/C0 coil markers at 2048/3072; scratch C-relays at 4000..4007.
serve.ps1 wrapper — pwsh script with a -Profile {standard|dl205} parameter switch. Validates pymodbus.simulator is on PATH (clearer message than the raw CommandNotFoundException), validates the profile JSON exists, builds the right --modbus_server/--modbus_device/--json_file/--http_port arg list, and execs pymodbus.simulator in the foreground. -HttpPort 0 disables the web UI. Foreground exec lets the operator Ctrl+C to stop without an extra control script.
README.md fully rewritten for pymodbus: install command (pip install 'pymodbus[simulator]==3.13.0' — pinned for reproducibility, [simulator] extra pulls aiohttp), per-profile reference tables, the same DL205 quirk → register table from PR 42 but adjusted for pymodbus paths, what's-NEW-vs-ModbusPal section (all four tables, raw uint16 seeding, declarative actions, custom Python action modules, headless, web UI, maintained), trade-offs section (float32-as-two-uint16s for explicit CDAB control, increment ticks per-access not wall-clock, shared-blocks mode for DL205 vs separate for Standard), file-format quick reference for hand-authoring more profiles. References pinned to the pymodbus readthedocs simulator/config + REST API pages.
docs/v2/modbus-test-plan.md harness section rewritten with the swap rationale; PR-history list updated to mark PR 42 SUPERSEDED by PR 43 and call out PR 44+ as the per-quirk implementation track. Test-conventions bullet about 'don't depend on ModbusPal state between tests' generalized to 'don't depend on simulator state' and a note added that pymodbus's REST API can reset state between facts if a test ever needs it.
DL205Profile.cs and DL205SmokeTests.cs xml-doc updated to reference pymodbus / dl205.json instead of ModbusPal / DL205.xmpp.
Functional validation deferred — Python isn't installed on this dev box (winget search returned no matches for Python.Python.3 exact). JSON parses structurally (PowerShell ConvertFrom-Json clean on both files), build clean, .json + serve.ps1 + README all copy to test-output as expected. User installs pymodbus when they want to actually run the simulator end-to-end; if pymodbus rejects the config the README's reference link to pymodbus's simulator/config schema doc is the right next stop.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-18 20:35:26 -04:00
c59ac9e52d Merge pull request 'Phase 3 PR 42 — ModbusPal simulator profiles for Standard + DL205/DL260' (#41) from phase-3-pr42-modbuspal-profiles into v2 2026-04-18 20:12:39 -04:00
Joseph Doherty
02a0e8efd1 Phase 3 PR 42 — ModbusPal simulator profiles for Standard Modbus + DL205/DL260 quirks. Two hand-authored .xmpp profiles in tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/ModbusPal/ that integration tests load via the GUI to drive the suite without a real PLC. Both well-formed XML (verified via PowerShell [xml] cast); both copied to test-output as PreserveNewest content per the existing csproj rule.
Standard.xmpp — generic Modbus TCP server on port 502, slave id 1. HR[0..31] seeded with address-as-value (HR[5]=5 — easy mental map for diagnostics), HR[100] auto-incrementing via a 1Hz LinearGenerator binding (drives subscribe-and-receive integration tests so they have a register that actually changes without a write), HR[200..209] scratch range for write-roundtrip tests, coils 0..31 alternating on/off, coils 100..109 scratch. The Tick automation runs 0..65535 over 60s looping; bound to HR[100] via Binding_SINT16 — slow enough that a 250ms-poll integration test sees discrete jumps, fast enough that a 5s subscribe test sees several change notifications.
DL205.xmpp — AutomationDirect DirectLOGIC DL205/DL260 quirk simulator on port 502, slave id 1, modeling the behaviors documented in docs/v2/dl205.md as concrete register values so DL205 integration tests can assert each quirk WITHOUT a live PLC. Per-quirk encoding: V0 marker at HR[0]=0xCAFE proves register 0 is valid (rejects-register-0 rumour disproved); V2000 marker at HR[1024]=0x2000 proves V-memory octal-to-decimal mapping; V40400 marker at HR[8448]=0x4040 proves V40400→PDU 0x2100 (NOT register 0, contrary to the widespread shorthand); 'Hello' string at HR[1040..1042] packed first-char-low-byte (HR[1040]=0x6548 = 'H' lo + 'e' hi, HR[1041]=0x6C6C, HR[1042]=0x006F) — the headline string-byte-order quirk the user flagged; Float32 1.5f at HR[1056..1057] in CDAB word order (low word first: 0, then 0x3FC0); BCD register at HR[1072]=0x1234 representing decimal 1234 in BCD nibbles (NOT binary 0x04D2); 128-register block at HR[1280..1407] for FC03-128-cap testing; Y0 marker at coil 2048, C0 marker at coil 3072, scratch C-coils at 4000..4007 for write tests.
Critical limitation flagged inline + in README: ModbusPal 1.6b CANNOT represent the DL205 quirks semantically — it has no string binding, no BCD binding, no arbitrary-byte-layout binding (only SINT16/SINT32/FLOAT32 with word-order). So every DL205 quirk is encoded as a pre-computed raw 16-bit integer with the math worked out in inline comments above each register. Becomes unreadable past ~50 quirky registers; the README's 'alternatives' section recommends switching to pymodbus when that threshold approaches (pymodbus's ModbusSimulatorServer has first-class headless + scriptable callbacks for byte-level layouts).
Other ModbusPal 1.6b limitations called out in README: only holding_registers + coils sections in the official build (no input_registers / discrete_inputs — DL260 X-input markers can't be encoded faithfully here, FC02/FC04 tests wait for a fork or pymodbus); abandoned project (last release 1.6b, active forks at SCADA-LTS/ModbusPal, ControlThings-io/modbuspal, mrhenrike/ModbusPalEnhanced); no headless mode in the official JAR (-loadFile / -hide flags only in source-built forks); CVE-2018-10832 XXE on .xmpp import (don't import untrusted profiles — the in-repo ones are author-controlled).
README.md updated with: per-profile description tables, getting-started (download jar + java -jar + GUI File>Load>Run), MODBUS_SIM_ENDPOINT env-var override doc, two reference tables documenting which HR / coil address encodes which DL205 quirk + which test name asserts it (the same DL205_<behavior> naming convention from docs/v2/modbus-test-plan.md), 4-row alternatives comparison (pymodbus / diagslave / ModbusMechanic / ModRSsim2) for when ModbusPal can no longer carry the load, and a quick-reference XML format table at the bottom for future-me hand-authoring more profiles.
Pure documentation + test-asset PR — no code changes. The integration tests that consume these profiles (the actual DL205_<behavior> facts) land one at a time in PR 43+ as user validates each quirk via ModbusPal on the bench.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-18 20:05:20 -04:00
7009483d16 Merge pull request 'Phase 3 PR 41 — Document AutomationDirect DL205 / DL260 Modbus quirks' (#40) from phase-3-pr41-dl205-quirks-doc into v2 2026-04-18 19:52:20 -04:00
15 changed files with 700 additions and 82 deletions

View File

@@ -13,22 +13,30 @@ confirmed DL205 quirk lands in a follow-up PR as a named test in that project.
## Harness
**Chosen simulator: ModbusPal** (Java, scriptable). Rationale:
- Scriptable enough to mimic device-specific behaviors (non-standard register
layouts, custom exception codes, intentional response delays).
- Runs locally, no CI dependency. Tests skip when `localhost:502` (or the configured
simulator endpoint) isn't reachable.
- Free + long-maintained — physical PLC bench is unavailable in most dev
environments, and renting cloud PLCs isn't worth the per-test cost.
**Chosen simulator: pymodbus 3.13.0** (`pip install 'pymodbus[simulator]==3.13.0'`).
Replaced ModbusPal in PR 43 — see `tests/.../Pymodbus/README.md` for the
trade-off rationale. Headline reasons:
**Setup pattern** (not yet codified in a script — will land alongside the integration
test project):
1. Install ModbusPal, load the per-device `.xmpp` profile from
`tests/Driver.Modbus.IntegrationTests/ModbusPal/` (TBD directory).
2. Start the simulator listening on `localhost:502` (or override via
`MODBUS_SIM_ENDPOINT` env var).
3. `dotnet test` the integration project — tests auto-skip when the endpoint is
unreachable, so forgetting to start the simulator doesn't wedge CI.
- **Headless** pure-Python CLI; no Java GUI, runs cleanly on a CI runner.
- **Maintained** — current stable 3.13.0; ModbusPal 1.6b is abandoned.
- **All four standard tables** (HR, IR, coils, DI) configurable; ModbusPal
1.6b only exposed HR + coils.
- **Built-in actions** (`increment`, `random`, `timestamp`, `uptime`) +
optional custom-Python actions for declarative dynamic behaviors.
- **Per-register raw uint16 seeding** — encoding the DL205 string-byte-order
/ BCD / CDAB-float quirks stays explicit (the quirk math lives in the
`_quirk` JSON-comment fields next to each register).
- Pip-installable on Windows; sidesteps the privileged-port admin
requirement by defaulting to TCP **5020** instead of 502.
**Setup pattern**:
1. `pip install "pymodbus[simulator]==3.13.0"`.
2. Start the simulator with one of the in-repo profiles:
`tests\.../Pymodbus\serve.ps1 -Profile standard` (or `-Profile dl205`).
3. `dotnet test tests\ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests`
tests auto-skip when the endpoint is unreachable. Default endpoint is
`localhost:5020`; override via `MODBUS_SIM_ENDPOINT` for a real PLC on its
native port 502.
## Per-device quirk catalog
@@ -87,20 +95,27 @@ vendors get promoted into driver defaults or opt-in options:
protocol end-to-end. The in-memory `FakeTransport` from the unit test suite is
deliberately not used here — its value is speed + determinism, which doesn't
help reproduce device-specific issues.
- **Don't depend on ModbusPal state between tests.** Each test resets the
- **Don't depend on simulator state between tests.** Each test resets the
simulator's register bank or uses a unique address range. Avoid relying on
"previous test left value at register 10" setups that flake when tests run in
parallel or re-order.
parallel or re-order. Either the test mutates the scratch ranges and restores
on finally, or it uses pymodbus's REST API to reset state between facts.
## Next concrete PRs
- **PR 30 — Integration test project + DL205 profile scaffold** — **DONE**.
Shipped `tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests` with
`ModbusSimulatorFixture` (TCP-probe, skips with a clear `SkipReason` when the
endpoint is unreachable), `DL205/DL205Profile.cs` (tag map stub — one
writable holding register at address 100), and `DL205/DL205SmokeTests.cs`
(write-then-read round-trip). `ModbusPal/` directory holds the README
pointing at the to-be-committed `DL205.xmpp` profile.
- **PR 31+**: one PR per confirmed DL205 quirk, landing the named test + any
driver-side adjustment (e.g., retry on dropped TxId) needed to pass it. Drop
the `DL205.xmpp` profile into `ModbusPal/` alongside the first quirk PR.
endpoint is unreachable), `DL205/DL205Profile.cs` (tag map stub), and
`DL205/DL205SmokeTests.cs` (write-then-read round-trip).
- **PR 41 — DL205 quirk catalog doc** — **DONE**. `docs/v2/dl205.md`
documents every DL205/DL260 Modbus divergence with primary-source citations.
- **PR 42 — ModbusPal `.xmpp` profiles** — **SUPERSEDED by PR 43**. Replaced
with pymodbus JSON because ModbusPal 1.6b is abandoned, GUI-only, and only
exposes 2 of the 4 standard tables.
- **PR 43 — pymodbus JSON profiles** — **DONE**. `Pymodbus/standard.json` +
`Pymodbus/dl205.json` + `Pymodbus/serve.ps1` runner. Both bind TCP 5020.
- **PR 44+**: one PR per confirmed DL205 quirk, landing the named test + any
driver-side adjustment (string byte order, BCD decoder, V-memory address
helper, FC16 cap-per-device-family) needed to pass it. Each quirk's value
is already pre-encoded in `Pymodbus/dl205.json`.

View File

@@ -472,13 +472,21 @@ public sealed class ModbusDriver(ModbusDriverOptions options, string driverInsta
}
case ModbusDataType.String:
{
// ASCII, 2 chars per register, packed high byte = first char.
// Respect the caller's StringLength (truncate nul-padded regions).
// ASCII, 2 chars per register. HighByteFirst (standard) packs the first char in
// the high byte of each register; LowByteFirst (DL205/DL260) packs the first char
// in the low byte. Respect StringLength (truncate nul-padded regions).
var chars = new char[tag.StringLength];
for (var i = 0; i < tag.StringLength; i++)
{
var b = data[i];
if (b == 0) { return new string(chars, 0, i); }
var regIdx = i / 2;
var highByte = data[regIdx * 2];
var lowByte = data[regIdx * 2 + 1];
byte b;
if (tag.StringByteOrder == ModbusStringByteOrder.HighByteFirst)
b = (i % 2 == 0) ? highByte : lowByte;
else
b = (i % 2 == 0) ? lowByte : highByte;
if (b == 0) return new string(chars, 0, i);
chars[i] = (char)b;
}
return new string(chars);
@@ -543,7 +551,14 @@ public sealed class ModbusDriver(ModbusDriverOptions options, string driverInsta
var s = Convert.ToString(value) ?? string.Empty;
var regs = (tag.StringLength + 1) / 2;
var b = new byte[regs * 2];
for (var i = 0; i < tag.StringLength && i < s.Length; i++) b[i] = (byte)s[i];
for (var i = 0; i < tag.StringLength && i < s.Length; i++)
{
var regIdx = i / 2;
var destIdx = tag.StringByteOrder == ModbusStringByteOrder.HighByteFirst
? (i % 2 == 0 ? regIdx * 2 : regIdx * 2 + 1)
: (i % 2 == 0 ? regIdx * 2 + 1 : regIdx * 2);
b[destIdx] = (byte)s[i];
}
// remaining bytes stay 0 — nul-padded per PLC convention
return b;
}

View File

@@ -55,6 +55,12 @@ public sealed class ModbusProbeOptions
/// <param name="ByteOrder">Word ordering for multi-register types. Ignored for Bool / Int16 / UInt16 / BitInRegister / String.</param>
/// <param name="BitIndex">For <c>DataType = BitInRegister</c>: which bit of the holding register (0-15, LSB-first).</param>
/// <param name="StringLength">For <c>DataType = String</c>: number of ASCII characters (2 per register, rounded up).</param>
/// <param name="StringByteOrder">
/// Per-register byte order for <c>DataType = String</c>. Standard Modbus packs the first
/// character in the high byte (<see cref="ModbusStringByteOrder.HighByteFirst"/>).
/// AutomationDirect DirectLOGIC (DL205/DL260) and a few legacy families pack the first
/// character in the low byte instead — see <c>docs/v2/dl205.md</c> §strings.
/// </param>
public sealed record ModbusTagDefinition(
string Name,
ModbusRegion Region,
@@ -63,7 +69,8 @@ public sealed record ModbusTagDefinition(
bool Writable = true,
ModbusByteOrder ByteOrder = ModbusByteOrder.BigEndian,
byte BitIndex = 0,
ushort StringLength = 0);
ushort StringLength = 0,
ModbusStringByteOrder StringByteOrder = ModbusStringByteOrder.HighByteFirst);
public enum ModbusRegion { Coils, DiscreteInputs, InputRegisters, HoldingRegisters }
@@ -95,3 +102,17 @@ public enum ModbusByteOrder
BigEndian,
WordSwap,
}
/// <summary>
/// Per-register byte order for ASCII strings packed 2 chars per register. Standard Modbus
/// convention is <see cref="HighByteFirst"/> — the first character of each pair occupies
/// the high byte of the register. AutomationDirect DirectLOGIC (DL205, DL260, DL350) and a
/// handful of legacy controllers pack <see cref="LowByteFirst"/>, which inverts that within
/// each register. Word ordering across multiple registers is always ascending address for
/// strings — only the byte order inside each register flips.
/// </summary>
public enum ModbusStringByteOrder
{
HighByteFirst,
LowByteFirst,
}

View File

@@ -28,10 +28,20 @@ public sealed class ModbusTcpTransport : IModbusTransport
public async Task ConnectAsync(CancellationToken ct)
{
_client = new TcpClient();
// Resolve the host explicitly + prefer IPv4. .NET's TcpClient default-constructor is
// dual-stack (IPv6 first, fallback to IPv4) — but most Modbus TCP devices (PLCs and
// simulators like pymodbus) bind 0.0.0.0 only, so the IPv6 attempt times out and we
// burn the entire ConnectAsync budget before even trying IPv4. Resolving first +
// dialing the IPv4 address directly sidesteps that.
var addresses = await System.Net.Dns.GetHostAddressesAsync(_host, ct).ConfigureAwait(false);
var ipv4 = System.Linq.Enumerable.FirstOrDefault(addresses,
a => a.AddressFamily == System.Net.Sockets.AddressFamily.InterNetwork);
var target = ipv4 ?? (addresses.Length > 0 ? addresses[0] : System.Net.IPAddress.Loopback);
_client = new TcpClient(target.AddressFamily);
using var cts = CancellationTokenSource.CreateLinkedTokenSource(ct);
cts.CancelAfter(_timeout);
await _client.ConnectAsync(_host, _port, cts.Token).ConfigureAwait(false);
await _client.ConnectAsync(target, _port, cts.Token).ConfigureAwait(false);
_stream = _client.GetStream();
}

View File

@@ -1,26 +1,30 @@
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.DL205;
/// <summary>
/// Tag map for the AutomationDirect DL205 device class. Mirrors what the ModbusPal
/// <c>.xmpp</c> profile in <c>ModbusPal/DL205.xmpp</c> exposes (or the real PLC, when
/// Tag map for the AutomationDirect DL205 device class. Mirrors what the pymodbus
/// <c>dl205.json</c> profile in <c>Pymodbus/dl205.json</c> exposes (or the real PLC, when
/// <see cref="ModbusSimulatorFixture"/> is pointed at one).
/// </summary>
/// <remarks>
/// This is the scaffold — each tag is deliberately generic so the smoke test has stable
/// addresses to read. Device-specific quirk tests (word order, max-register, register-zero
/// access, etc.) will land in their own test classes alongside this profile as the user
/// validates each behavior in ModbusPal; see <c>docs/v2/modbus-test-plan.md</c> §per-device
/// validates each behavior in pymodbus; see <c>docs/v2/modbus-test-plan.md</c> §per-device
/// quirk catalog for the checklist.
/// </remarks>
public static class DL205Profile
{
/// <summary>Holding register the smoke test reads. Address 100 sidesteps the DL205
/// register-zero quirk (pending confirmation) — see modbus-test-plan.md.</summary>
public const ushort SmokeHoldingRegister = 100;
/// <summary>
/// Holding register the smoke test writes + reads. Address 200 is the first cell of the
/// scratch HR range in both <c>Pymodbus/standard.json</c> (HR[200..209] = 0) and
/// <c>Pymodbus/dl205.json</c> (HR[4096..4103] added in PR 43 for the same purpose), so
/// the smoke test runs identically against either simulator profile. Originally
/// targeted HR[100] — moved to HR[200] when the standard profile claimed HR[100] as
/// the auto-incrementing register that drives subscribe-and-receive tests.
/// </summary>
public const ushort SmokeHoldingRegister = 200;
/// <summary>Expected value the ModbusPal profile seeds into register 100. When running
/// against a real DL205 (or a ModbusPal profile where this register is writable), the smoke
/// test seeds this value first, then reads it back.</summary>
/// <summary>Value the smoke test writes then reads back to assert round-trip integrity.</summary>
public const short SmokeHoldingValue = 1234;
public static ModbusDriverOptions BuildOptions(string host, int port) => new()
@@ -32,7 +36,7 @@ public static class DL205Profile
Tags =
[
new ModbusTagDefinition(
Name: "DL205_Smoke_HReg100",
Name: "Smoke_HReg200",
Region: ModbusRegion.HoldingRegisters,
Address: SmokeHoldingRegister,
DataType: ModbusDataType.Int16,

View File

@@ -38,13 +38,13 @@ public sealed class DL205SmokeTests(ModbusSimulatorFixture sim)
// zeroed at simulator start, and tests must not depend on prior-test state per the
// test-plan conventions.
var writeResults = await driver.WriteAsync(
[new(FullReference: "DL205_Smoke_HReg100", Value: (short)DL205Profile.SmokeHoldingValue)],
[new(FullReference: "Smoke_HReg200", Value: (short)DL205Profile.SmokeHoldingValue)],
TestContext.Current.CancellationToken);
writeResults.Count.ShouldBe(1);
writeResults[0].StatusCode.ShouldBe(0u, "write must succeed against the ModbusPal DL205 profile");
var readResults = await driver.ReadAsync(
["DL205_Smoke_HReg100"],
["Smoke_HReg200"],
TestContext.Current.CancellationToken);
readResults.Count.ShouldBe(1);
readResults[0].StatusCode.ShouldBe(0u);

View File

@@ -0,0 +1,81 @@
using Shouldly;
using Xunit;
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.DL205;
/// <summary>
/// Verifies the DL205/DL260 low-byte-first ASCII string packing quirk against the
/// <c>dl205.json</c> pymodbus profile. Standard Modbus packs the first char of each pair
/// in the high byte of the register; DirectLOGIC packs it in the low byte instead. Without
/// <see cref="ModbusStringByteOrder.LowByteFirst"/> the driver decodes "eHllo" garbage
/// even though the bytes on the wire are identical.
/// </summary>
/// <remarks>
/// <para>
/// Requires the dl205 profile (<c>Pymodbus\serve.ps1 -Profile dl205</c>). The standard
/// profile does not seed HR[1040..1042] with string bytes, so running this against the
/// standard profile returns <c>"\0\0\0\0\0"</c> and the test fails. Skip when the env
/// var <c>MODBUS_SIM_PROFILE</c> is not set to <c>dl205</c>.
/// </para>
/// </remarks>
[Collection(ModbusSimulatorCollection.Name)]
[Trait("Category", "Integration")]
[Trait("Device", "DL205")]
public sealed class DL205StringQuirkTests(ModbusSimulatorFixture sim)
{
[Fact]
public async Task DL205_string_low_byte_first_decodes_Hello_from_HR1040()
{
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "dl205",
StringComparison.OrdinalIgnoreCase))
{
Assert.Skip("MODBUS_SIM_PROFILE != dl205 — skipping (standard profile does not seed HR[1040..1042]).");
}
var options = new ModbusDriverOptions
{
Host = sim.Host,
Port = sim.Port,
UnitId = 1,
Timeout = TimeSpan.FromSeconds(2),
Tags =
[
new ModbusTagDefinition(
Name: "DL205_Hello_Low",
Region: ModbusRegion.HoldingRegisters,
Address: 1040,
DataType: ModbusDataType.String,
Writable: false,
StringLength: 5,
StringByteOrder: ModbusStringByteOrder.LowByteFirst),
// Control: same address, HighByteFirst, to prove the driver would have decoded
// garbage without the quirk flag.
new ModbusTagDefinition(
Name: "DL205_Hello_High",
Region: ModbusRegion.HoldingRegisters,
Address: 1040,
DataType: ModbusDataType.String,
Writable: false,
StringLength: 5,
StringByteOrder: ModbusStringByteOrder.HighByteFirst),
],
Probe = new ModbusProbeOptions { Enabled = false },
};
await using var driver = new ModbusDriver(options, driverInstanceId: "dl205-string");
await driver.InitializeAsync(driverConfigJson: "{}", TestContext.Current.CancellationToken);
var results = await driver.ReadAsync(["DL205_Hello_Low", "DL205_Hello_High"],
TestContext.Current.CancellationToken);
results.Count.ShouldBe(2);
results[0].StatusCode.ShouldBe(0u);
results[0].Value.ShouldBe("Hello", "DL205 low-byte-first ordering must produce 'Hello' from HR[1040..1042]");
// The high-byte-first read of the same wire bytes should differ — not asserting the
// exact garbage string (that would couple the test to the ASCII byte math) but the two
// decodes MUST disagree, otherwise the quirk flag is a no-op.
results[1].StatusCode.ShouldBe(0u);
results[1].Value.ShouldNotBe("Hello");
}
}

View File

@@ -1,30 +0,0 @@
# ModbusPal simulator profiles
Drop device-specific `.xmpp` profiles here. The integration tests connect to the
endpoint in `MODBUS_SIM_ENDPOINT` (default `localhost:502`) and expect the
simulator to already be running — tests do not launch ModbusPal themselves,
because its Java GUI + JRE requirement is heavier than the harness is worth.
## Getting started
1. Download ModbusPal from SourceForge (`modbuspal.jar`).
2. `java -jar modbuspal.jar` to launch the GUI.
3. Load a profile from this directory (or configure one manually) and start the
simulator on TCP port 502.
4. `dotnet test tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests` — tests
auto-skip with a clear `SkipReason` if the TCP probe at the configured
endpoint fails within 2 seconds.
## Profile files
- `DL205.xmpp`_to be added_ — register map reflecting the AutomationDirect
DL205 quirks tracked in `docs/v2/modbus-test-plan.md`. The scaffolded smoke
test in `DL205/DL205SmokeTests.cs` needs holding register 100 writable and
present; a minimal ModbusPal profile with a single holding-register bank at
address 100 is sufficient.
## Environment variables
- `MODBUS_SIM_ENDPOINT` — override the simulator endpoint. Accepts `host:port`;
defaults to `localhost:502`. Useful when pointing the suite at a real PLC on
the bench.

View File

@@ -3,8 +3,9 @@ using System.Net.Sockets;
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests;
/// <summary>
/// Reachability probe for a Modbus TCP simulator (ModbusPal or a real PLC). Parses
/// <c>MODBUS_SIM_ENDPOINT</c> (default <c>localhost:502</c>) and TCP-connects once at
/// Reachability probe for a Modbus TCP simulator (pymodbus-driven, see
/// <c>Pymodbus/serve.ps1</c>) or a real PLC. Parses
/// <c>MODBUS_SIM_ENDPOINT</c> (default <c>localhost:5020</c> per PR 43) and TCP-connects once at
/// fixture construction. Each test checks <see cref="SkipReason"/> and calls
/// <c>Assert.Skip</c> when the endpoint was unreachable, so a dev box without a running
/// simulator still passes `dotnet test` cleanly — matches the Galaxy live-smoke pattern in
@@ -25,7 +26,11 @@ namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests;
/// </remarks>
public sealed class ModbusSimulatorFixture : IAsyncDisposable
{
private const string DefaultEndpoint = "localhost:502";
// PR 43: default port is 5020 (pymodbus convention) instead of 502 (Modbus standard).
// Picking 5020 sidesteps the privileged-port admin requirement on Windows + matches the
// port baked into the pymodbus simulator JSON profiles in Pymodbus/. Override with
// MODBUS_SIM_ENDPOINT to point at a real PLC on its native port 502.
private const string DefaultEndpoint = "localhost:5020";
private const string EndpointEnvVar = "MODBUS_SIM_ENDPOINT";
public string Host { get; }
@@ -41,18 +46,30 @@ public sealed class ModbusSimulatorFixture : IAsyncDisposable
try
{
using var client = new TcpClient();
var task = client.ConnectAsync(Host, Port);
// Force IPv4 family on the probe — pymodbus's TCP server binds 0.0.0.0 (IPv4 only)
// while .NET's TcpClient default-resolves "localhost" → IPv6 ::1 first, fails to
// connect, and only then tries IPv4. Under .NET 10 the IPv6 fail surfaces as a
// 2s timeout (no graceful fallback by default), so the C# probe times out even
// though a PowerShell probe of the same endpoint succeeds. Resolving + dialing
// explicit IPv4 sidesteps the dual-stack ordering.
using var client = new TcpClient(System.Net.Sockets.AddressFamily.InterNetwork);
var task = client.ConnectAsync(
System.Net.Dns.GetHostAddresses(Host)
.FirstOrDefault(a => a.AddressFamily == System.Net.Sockets.AddressFamily.InterNetwork)
?? System.Net.IPAddress.Loopback,
Port);
if (!task.Wait(TimeSpan.FromSeconds(2)) || !client.Connected)
{
SkipReason = $"Modbus simulator at {Host}:{Port} did not accept a TCP connection within 2s. " +
$"Start ModbusPal (or override {EndpointEnvVar}) and re-run.";
$"Start the pymodbus simulator (Pymodbus\\serve.ps1 -Profile standard) " +
$"or override {EndpointEnvVar}, then re-run.";
}
}
catch (Exception ex)
{
SkipReason = $"Modbus simulator at {Host}:{Port} unreachable: {ex.GetType().Name}: {ex.Message}. " +
$"Start ModbusPal (or override {EndpointEnvVar}) and re-run.";
$"Start the pymodbus simulator (Pymodbus\\serve.ps1 -Profile standard) " +
$"or override {EndpointEnvVar}, then re-run.";
}
}

View File

@@ -0,0 +1,163 @@
# pymodbus simulator profiles
Two JSON-config profiles for pymodbus's `ModbusSimulatorServer`. Replaces the
ModbusPal `.xmpp` profiles that lived here in PR 42 — pymodbus is headless,
maintained, semantic about register layout, and pip-installable on Windows.
| File | What it simulates | Test category |
|---|---|---|
| [`standard.json`](standard.json) | Generic Modbus TCP server — HR[0..31] = address-as-value, HR[100] declarative auto-increment via `"action": "increment"`, alternating coils, scratch ranges for write tests. | `Trait=Standard` |
| [`dl205.json`](dl205.json) | AutomationDirect DirectLOGIC DL205 / DL260 quirks per [`docs/v2/dl205.md`](../../../docs/v2/dl205.md): low-byte-first string packing, CDAB Float32, BCD numerics, V-memory address markers, Y/C coil mappings. Inline `_quirk` comments per register name the behavior. | `Trait=DL205` |
Both bind TCP **5020** (pymodbus convention; sidesteps the Windows admin
requirement for privileged port 502). The integration-test fixture
(`ModbusSimulatorFixture`) defaults to `localhost:5020` to match — override
via `MODBUS_SIM_ENDPOINT` to point at a real PLC on its native port 502.
Run only **one profile at a time** (they share TCP 5020).
## Install
```powershell
pip install "pymodbus[simulator]==3.13.0"
```
The `[simulator]` extra pulls in `aiohttp` for the optional web UI / REST API.
Pinned to 3.13.0 for reproducibility — avoid 4.x dev releases until stabilized.
Requires Python ≥ 3.10. Windows Firewall will prompt on first bind; allow
Private network.
## Run
Foreground (Ctrl+C to stop). Use the `serve.ps1` wrapper:
```powershell
.\serve.ps1 -Profile standard
.\serve.ps1 -Profile dl205
```
Or invoke pymodbus directly:
```powershell
pymodbus.simulator `
--modbus_server srv `
--modbus_device dev `
--json_file .\standard.json `
--http_port 8080
```
Web UI at `http://localhost:8080` lets you inspect + poke registers manually.
Pass `--no_http` (or `-HttpPort 0` to `serve.ps1`) to disable.
## Run the integration tests
In a separate shell, with the simulator running:
```powershell
cd C:\Users\dohertj2\Desktop\lmxopcua
dotnet test tests\ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests
```
Tests auto-skip with a clear `SkipReason` if `localhost:5020` isn't reachable
within 2 seconds. Filter by trait when both profiles' tests coexist:
```powershell
dotnet test ... --filter "Trait=Standard"
dotnet test ... --filter "Trait=DL205"
```
## What's encoded in each profile
### standard.json
- HR[0..31]: each register's value equals its address. Easy mental map.
- HR[100]: `"action": "increment"` ticks 0..65535 on every register access — drives subscribe-and-receive tests so they have a register that changes without a write.
- HR[200..209]: scratch range for write-roundtrip tests.
- Coils[0..31]: alternating on/off (even=on).
- Coils[100..109]: scratch.
- All addresses 0..1023 are writable (`"write": [[0, 1023]]`).
### dl205.json (per `docs/v2/dl205.md`)
| HR address | Quirk demonstrated | Raw value | Decoded |
|---|---|---|---|
| `0` (V0) | Register 0 is valid (rejects-register-0 rumour disproved) | `51966` (0xCAFE) | marker |
| `1024` (V2000 octal) | V-memory octal-to-decimal mapping | `8192` (0x2000) | marker |
| `8448` (V40400 octal) | V40400 → PDU 0x2100 (NOT register 0) | `16448` (0x4040) | marker |
| `1040..1042` | String "Hello" packed first-char-low-byte | `25928, 27756, 111` | `"Hello"` |
| `1056..1057` | Float32 1.5f in CDAB word order | `0, 16320` | `1.5f` |
| `1072` | Decimal 1234 in BCD encoding | `4660` (0x1234) | `1234` |
| `1280..1407` | 128-register block (FC03 cap = 128 above spec's 125) | first/last/mid markers; rest defaults to 0 | for FC03 cap test |
| Coil address | Quirk demonstrated |
|---|---|
| `2048` | Y0 maps to coil 2048 (DL260 layout) |
| `3072` | C0 maps to coil 3072 (DL260 layout) |
| `4000..4007` | Scratch C-relay range for write-roundtrip tests |
The DL260 X-input markers (FC02 discrete inputs) **are not encoded separately**
because the profile uses `shared blocks: true` (matches DL series memory
model) — coils/DI/HR/IR overlay the same word address space. Tests that
target FC02 against this profile end up reading the same bit positions as
the coils they share with.
## What's IN pymodbus that wasn't in ModbusPal
- **All four standard tables** (HR, IR, coils, DI) configurable via `co size` / `di size` / `hr size` / `ir size` setup keys.
- **Per-register raw uint16 seeding** — `{"addr": 1040, "value": 25928}` puts exactly that 16-bit value on the wire. No interpretation.
- **Built-in actions**: `increment`, `random`, `timestamp`, `reset`, `uptime` for declarative dynamic registers. No Python script alongside the config required.
- **Custom actions** — point `--custom_actions_module` at a `.py` file exposing callables to express anything more complex (per-second wall-clock ticks, BCD synthesis, etc.).
- **Headless** — pure CLI process, no Java, no Swing. Pip-installable. Plays well with CI runners.
- **Web UI / REST API** — `--http_port 8080` adds an aiohttp server for live inspection. Optional.
- **Maintained** — current stable 3.13.0 (April 2026), active development on 4.0 dev branch.
## Trade-offs vs the hand-authored ModbusPal profiles
- pymodbus's built-in `float32` type stores in pymodbus's word order; for explicit DL205 CDAB control we seed two raw `uint16` entries instead. Documented inline in `dl205.json`.
- `increment` action ticks per-access, not wall-clock. A 250ms-poll integration test sees variation either way; for strict 1Hz cadence add `--custom_actions_module my_actions.py` with a `time.time()`-based callable.
- `dl205.json` uses `shared blocks: true` because it matches DL series memory model; `standard.json` uses `shared blocks: false` so coils and HR address spaces are independent (more like a textbook PLC).
## File format reference
```json
{
"server_list": {
"<server-name>": {
"comm": "tcp",
"host": "0.0.0.0",
"port": 5020,
"framer": "socket",
"device_id": 1
}
},
"device_list": {
"<device-name>": {
"setup": {
"co size": N, "di size": N, "hr size": N, "ir size": N,
"shared blocks": false,
"type exception": false,
"defaults": { "value": {...}, "action": {...} }
},
"invalid": [],
"write": [[<from>, <to>]],
"bits": [{"addr": N, "value": 0|1}],
"uint16": [{"addr": N, "value": <0..65535>, "action"?: "increment", "parameters"?: {...}}],
"uint32": [{"addr": N, "value": <int>}],
"float32": [{"addr": N, "value": <float>}],
"string": [{"addr": N, "value": "<text>"}],
"repeat": []
}
}
}
```
The CLI args `--modbus_server <server-name> --modbus_device <device-name>`
pick which entries the simulator binds.
## References
- [pymodbus on PyPI](https://pypi.org/project/pymodbus/) — install, version pin
- [Simulator config docs](https://pymodbus.readthedocs.io/en/dev/source/library/simulator/config.html) — full schema reference
- [Simulator REST API](https://pymodbus.readthedocs.io/en/latest/source/library/simulator/restapi.html) — for the optional web UI
- [`docs/v2/dl205.md`](../../../docs/v2/dl205.md) — what each DL205 profile entry simulates
- [`docs/v2/modbus-test-plan.md`](../../../docs/v2/modbus-test-plan.md) — the `DL205_<behavior>` test naming convention

View File

@@ -0,0 +1,118 @@
{
"_comment": "DL205.json — DirectLOGIC DL205/DL260 quirk simulator. Models docs/v2/dl205.md as concrete register values. NOTE: pymodbus rejects unknown keys at device-list / setup level; explanatory comments live at top-level _comment + in README + git. Inline _quirk keys WITHIN individual register entries are accepted by pymodbus 3.13.0 (it only validates addr / value / action / parameters per entry). Each quirky uint16 is a pre-computed raw 16-bit value; pymodbus serves it verbatim. shared blocks=true matches DL series memory model. write list mirrors each seeded block — pymodbus rejects sweeping write ranges that include undefined cells.",
"server_list": {
"srv": {
"comm": "tcp",
"host": "0.0.0.0",
"port": 5020,
"framer": "socket",
"device_id": 1
}
},
"device_list": {
"dev": {
"setup": {
"co size": 16384,
"di size": 8192,
"hr size": 16384,
"ir size": 1024,
"shared blocks": true,
"type exception": false,
"defaults": {
"value": {"bits": 0, "uint16": 0, "uint32": 0, "float32": 0.0, "string": " "},
"action": {"bits": null, "uint16": null, "uint32": null, "float32": null, "string": null}
}
},
"invalid": [],
"write": [
[0, 0],
[200, 209],
[1024, 1024],
[1040, 1042],
[1056, 1057],
[1072, 1072],
[1280, 1282],
[1343, 1343],
[1407, 1407],
[2048, 2050],
[3072, 3074],
[4000, 4007],
[8448, 8448]
],
"uint16": [
{"_quirk": "V0 marker. HR[0]=0xCAFE proves register 0 is valid on DL205/DL260 (rejects-register-0 was a DL05/DL06 relative-mode artefact). 0xCAFE = 51966.",
"addr": 0, "value": 51966},
{"_quirk": "Scratch HR range 200..209 — mirrors the standard.json scratch range so the smoke test (DL205Profile.SmokeHoldingRegister=200) round-trips identically against either profile.",
"addr": 200, "value": 0},
{"addr": 201, "value": 0},
{"addr": 202, "value": 0},
{"addr": 203, "value": 0},
{"addr": 204, "value": 0},
{"addr": 205, "value": 0},
{"addr": 206, "value": 0},
{"addr": 207, "value": 0},
{"addr": 208, "value": 0},
{"addr": 209, "value": 0},
{"_quirk": "V2000 marker. V2000 octal = decimal 1024 = PDU 0x0400. Marker 0x2000 = 8192.",
"addr": 1024, "value": 8192},
{"_quirk": "V40400 marker. V40400 octal = decimal 8448 = PDU 0x2100 (NOT register 0). Marker 0x4040 = 16448.",
"addr": 8448, "value": 16448},
{"_quirk": "String 'Hello' first char in LOW byte. HR[0x410] = 'H'(0x48) lo + 'e'(0x65) hi = 0x6548 = 25928.",
"addr": 1040, "value": 25928},
{"_quirk": "String 'Hello' second char-pair: 'l'(0x6C) lo + 'l'(0x6C) hi = 0x6C6C = 27756.",
"addr": 1041, "value": 27756},
{"_quirk": "String 'Hello' third char-pair: 'o'(0x6F) lo + null(0x00) hi = 0x006F = 111.",
"addr": 1042, "value": 111},
{"_quirk": "Float32 1.5f in CDAB word order. IEEE 754 1.5 = 0x3FC00000. CDAB = low word first: HR[0x420]=0x0000, HR[0x421]=0x3FC0=16320.",
"addr": 1056, "value": 0},
{"_quirk": "Float32 1.5f CDAB high word.",
"addr": 1057, "value": 16320},
{"_quirk": "BCD register. Decimal 1234 stored as BCD nibbles 0x1234 = 4660. NOT binary 1234 (= 0x04D2).",
"addr": 1072, "value": 4660},
{"_quirk": "FC03 cap test marker — first cell of a 128-register span the FC03 cap test reads. Other cells in the span aren't seeded explicitly, so reads of HR[1283..1342] / 1344..1406 return the default 0; the seeded markers at 1280, 1281, 1282, 1343, 1407 prove the span boundaries.",
"addr": 1280, "value": 0},
{"addr": 1281, "value": 1},
{"addr": 1282, "value": 2},
{"addr": 1343, "value": 63},
{"addr": 1407, "value": 127}
],
"bits": [
{"_quirk": "Y0 marker. DL260 maps Y0 to coil 2048 (0-based). Coil 2048 = ON proves the mapping.",
"addr": 2048, "value": 1},
{"addr": 2049, "value": 0},
{"addr": 2050, "value": 1},
{"_quirk": "C0 marker. DL260 maps C0 to coil 3072 (0-based). Coil 3072 = ON proves the mapping.",
"addr": 3072, "value": 1},
{"addr": 3073, "value": 0},
{"addr": 3074, "value": 1},
{"_quirk": "Scratch C-relays for write-roundtrip tests against the writable C range.",
"addr": 4000, "value": 0},
{"addr": 4001, "value": 0},
{"addr": 4002, "value": 0},
{"addr": 4003, "value": 0},
{"addr": 4004, "value": 0},
{"addr": 4005, "value": 0},
{"addr": 4006, "value": 0},
{"addr": 4007, "value": 0}
],
"uint32": [],
"float32": [],
"string": [],
"repeat": []
}
}
}

View File

@@ -0,0 +1,60 @@
<#
.SYNOPSIS
Launches the pymodbus simulator with one of the integration-test profiles
(Standard or DL205). Foreground process — Ctrl+C to stop.
.PARAMETER Profile
Which simulator profile to run: 'standard' or 'dl205'. Both bind TCP 5020 by
default so they can't run simultaneously on the same box.
.PARAMETER HttpPort
Port for pymodbus's optional web UI / REST API. Default 8080. Pass 0 to
disable (passes --no_http).
.EXAMPLE
.\serve.ps1 -Profile standard
Starts the standard server on TCP 5020 with web UI on 8080.
.EXAMPLE
.\serve.ps1 -Profile dl205 -HttpPort 0
Starts the DL205 server on TCP 5020, no web UI.
#>
[CmdletBinding()]
param(
[Parameter(Mandatory)] [ValidateSet('standard', 'dl205')] [string]$Profile,
[int]$HttpPort = 8080
)
$ErrorActionPreference = 'Stop'
$here = $PSScriptRoot
# Confirm pymodbus.simulator is on PATH — clearer message than the
# 'CommandNotFoundException' dotnet style.
$cmd = Get-Command pymodbus.simulator -ErrorAction SilentlyContinue
if (-not $cmd) {
Write-Error "pymodbus.simulator not found. Install with: pip install 'pymodbus[simulator]==3.13.0'"
exit 1
}
$jsonFile = Join-Path $here "$Profile.json"
if (-not (Test-Path $jsonFile)) {
Write-Error "Profile config not found: $jsonFile"
exit 1
}
$args = @(
'--modbus_server', 'srv',
'--modbus_device', 'dev',
'--json_file', $jsonFile
)
if ($HttpPort -gt 0) {
$args += @('--http_port', $HttpPort)
Write-Host "Web UI will be at http://localhost:$HttpPort"
} else {
$args += '--no_http'
}
Write-Host "Starting pymodbus simulator: profile=$Profile TCP=localhost:5020"
Write-Host "Ctrl+C to stop."
& pymodbus.simulator @args

View File

@@ -0,0 +1,97 @@
{
"_comment": "Standard.json — generic Modbus TCP server for the integration suite. See ../README.md. NOTE: pymodbus rejects unknown keys at device-list / setup level; explanatory comments live in the README + git history. Layout: HR[0..31]=address-as-value, HR[100]=auto-increment, HR[200..209]=scratch, coils 1024..1055=alternating, coils 1100..1109=scratch. Coils live at 1024+ because pymodbus stores all 4 standard tables in ONE underlying cell array — bits and uint16 at the same address conflict (each cell can only be typed once).",
"server_list": {
"srv": {
"comm": "tcp",
"host": "0.0.0.0",
"port": 5020,
"framer": "socket",
"device_id": 1
}
},
"device_list": {
"dev": {
"setup": {
"co size": 2048,
"di size": 2048,
"hr size": 2048,
"ir size": 2048,
"shared blocks": true,
"type exception": false,
"defaults": {
"value": {"bits": 0, "uint16": 0, "uint32": 0, "float32": 0.0, "string": " "},
"action": {"bits": null, "uint16": null, "uint32": null, "float32": null, "string": null}
}
},
"invalid": [],
"write": [
[0, 31],
[100, 100],
[200, 209],
[1024, 1055],
[1100, 1109]
],
"uint16": [
{"addr": 0, "value": 0}, {"addr": 1, "value": 1},
{"addr": 2, "value": 2}, {"addr": 3, "value": 3},
{"addr": 4, "value": 4}, {"addr": 5, "value": 5},
{"addr": 6, "value": 6}, {"addr": 7, "value": 7},
{"addr": 8, "value": 8}, {"addr": 9, "value": 9},
{"addr": 10, "value": 10}, {"addr": 11, "value": 11},
{"addr": 12, "value": 12}, {"addr": 13, "value": 13},
{"addr": 14, "value": 14}, {"addr": 15, "value": 15},
{"addr": 16, "value": 16}, {"addr": 17, "value": 17},
{"addr": 18, "value": 18}, {"addr": 19, "value": 19},
{"addr": 20, "value": 20}, {"addr": 21, "value": 21},
{"addr": 22, "value": 22}, {"addr": 23, "value": 23},
{"addr": 24, "value": 24}, {"addr": 25, "value": 25},
{"addr": 26, "value": 26}, {"addr": 27, "value": 27},
{"addr": 28, "value": 28}, {"addr": 29, "value": 29},
{"addr": 30, "value": 30}, {"addr": 31, "value": 31},
{"addr": 100, "value": 0,
"action": "increment",
"parameters": {"minval": 0, "maxval": 65535}},
{"addr": 200, "value": 0}, {"addr": 201, "value": 0},
{"addr": 202, "value": 0}, {"addr": 203, "value": 0},
{"addr": 204, "value": 0}, {"addr": 205, "value": 0},
{"addr": 206, "value": 0}, {"addr": 207, "value": 0},
{"addr": 208, "value": 0}, {"addr": 209, "value": 0}
],
"bits": [
{"addr": 1024, "value": 1}, {"addr": 1025, "value": 0},
{"addr": 1026, "value": 1}, {"addr": 1027, "value": 0},
{"addr": 1028, "value": 1}, {"addr": 1029, "value": 0},
{"addr": 1030, "value": 1}, {"addr": 1031, "value": 0},
{"addr": 1032, "value": 1}, {"addr": 1033, "value": 0},
{"addr": 1034, "value": 1}, {"addr": 1035, "value": 0},
{"addr": 1036, "value": 1}, {"addr": 1037, "value": 0},
{"addr": 1038, "value": 1}, {"addr": 1039, "value": 0},
{"addr": 1040, "value": 1}, {"addr": 1041, "value": 0},
{"addr": 1042, "value": 1}, {"addr": 1043, "value": 0},
{"addr": 1044, "value": 1}, {"addr": 1045, "value": 0},
{"addr": 1046, "value": 1}, {"addr": 1047, "value": 0},
{"addr": 1048, "value": 1}, {"addr": 1049, "value": 0},
{"addr": 1050, "value": 1}, {"addr": 1051, "value": 0},
{"addr": 1052, "value": 1}, {"addr": 1053, "value": 0},
{"addr": 1054, "value": 1}, {"addr": 1055, "value": 0},
{"addr": 1100, "value": 0}, {"addr": 1101, "value": 0},
{"addr": 1102, "value": 0}, {"addr": 1103, "value": 0},
{"addr": 1104, "value": 0}, {"addr": 1105, "value": 0},
{"addr": 1106, "value": 0}, {"addr": 1107, "value": 0},
{"addr": 1108, "value": 0}, {"addr": 1109, "value": 0}
],
"uint32": [],
"float32": [],
"string": [],
"repeat": []
}
}
}

View File

@@ -24,7 +24,7 @@
</ItemGroup>
<ItemGroup>
<None Update="ModbusPal\**\*" CopyToOutputDirectory="PreserveNewest"/>
<None Update="Pymodbus\**\*" CopyToOutputDirectory="PreserveNewest"/>
<None Update="DL205\**\*" CopyToOutputDirectory="PreserveNewest"/>
</ItemGroup>

View File

@@ -172,4 +172,51 @@ public sealed class ModbusDataTypeTests
wire[1].ShouldBe((byte)'i');
for (var i = 2; i < 8; i++) wire[i].ShouldBe((byte)0);
}
// --- DL205 low-byte-first strings (AutomationDirect DirectLOGIC quirk) ---
[Fact]
public void String_LowByteFirst_decodes_DL205_packed_Hello()
{
// HR[1040] = 0x6548 (wire BE bytes [0x65, 0x48]) decodes first char from low byte = 'H',
// second from high byte = 'e'. HR[1041] = 0x6C6C → 'l','l'. HR[1042] = 0x006F → 'o', nul.
var tag = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.String,
StringLength: 5, StringByteOrder: ModbusStringByteOrder.LowByteFirst);
var wire = new byte[] { 0x65, 0x48, 0x6C, 0x6C, 0x00, 0x6F };
ModbusDriver.DecodeRegister(wire, tag).ShouldBe("Hello");
}
[Fact]
public void String_LowByteFirst_decode_truncates_at_first_nul()
{
// Low-byte-first with only 2 real chars in register 0 (lo='H', hi='i') and the rest nul.
var tag = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.String,
StringLength: 6, StringByteOrder: ModbusStringByteOrder.LowByteFirst);
var wire = new byte[] { 0x69, 0x48, 0x00, 0x00, 0x00, 0x00 };
ModbusDriver.DecodeRegister(wire, tag).ShouldBe("Hi");
}
[Fact]
public void String_LowByteFirst_encode_round_trips_with_decode()
{
var tag = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.String,
StringLength: 5, StringByteOrder: ModbusStringByteOrder.LowByteFirst);
var wire = ModbusDriver.EncodeRegister("Hello", tag);
// Expect exactly the DL205-documented byte sequence.
wire.ShouldBe(new byte[] { 0x65, 0x48, 0x6C, 0x6C, 0x00, 0x6F });
ModbusDriver.DecodeRegister(wire, tag).ShouldBe("Hello");
}
[Fact]
public void String_HighByteFirst_and_LowByteFirst_differ_on_same_wire()
{
// Same wire buffer, different byte order → first char switches 'H' vs 'e'.
var wire = new byte[] { 0x48, 0x65 };
var hi = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.String,
StringLength: 2, StringByteOrder: ModbusStringByteOrder.HighByteFirst);
var lo = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.String,
StringLength: 2, StringByteOrder: ModbusStringByteOrder.LowByteFirst);
ModbusDriver.DecodeRegister(wire, hi).ShouldBe("He");
ModbusDriver.DecodeRegister(wire, lo).ShouldBe("eH");
}
}