1
.gitignore
vendored
1
.gitignore
vendored
@@ -29,3 +29,4 @@ packages/
|
||||
# Claude Code (per-developer settings, runtime lock files, agent transcripts)
|
||||
.claude/
|
||||
|
||||
.local/
|
||||
|
||||
295
docs/v2/dl205.md
Normal file
295
docs/v2/dl205.md
Normal file
@@ -0,0 +1,295 @@
|
||||
# AutomationDirect DirectLOGIC DL205 / DL260 — Modbus quirks
|
||||
|
||||
AutomationDirect's DirectLOGIC DL205 family (D2-250-1, D2-260, D2-262, D2-262M) and
|
||||
its larger DL260 sibling speak Modbus TCP (via the H2-ECOM100 / H2-EBC100 Ethernet
|
||||
coprocessors, and the DL260's built-in Ethernet port) and Modbus RTU (via the CPU
|
||||
serial ports in "Modbus" mode). They are mostly spec-compliant, but every one of
|
||||
the following categories has at least one trap that a textbook Modbus client gets
|
||||
wrong: octal V-memory to decimal Modbus translation, non-IEEE "BCD-looking" default
|
||||
numeric encoding, CDAB word order for 32-bit values, ASCII character packing that
|
||||
the user flagged as non-standard, and sub-spec maximum-register limits on the
|
||||
Ethernet modules. This document catalogues each quirk, cites primary sources, and
|
||||
names the ModbusPal integration test we'd write for it (convention from
|
||||
`docs/v2/modbus-test-plan.md`: `DL205_<behavior>`).
|
||||
|
||||
## Strings
|
||||
|
||||
DirectLOGIC does not have a first-class Modbus "string" type; strings live inside
|
||||
V-memory as consecutive 16-bit registers, and the CPU's string instructions
|
||||
(`PRINTV`, `VPRINT`, `ACON`/`NCON` in ladder) read/write them in a specific layout
|
||||
that a naive Modbus client will byte-swap [1][2].
|
||||
|
||||
- **Packing**: two ASCII characters per V-memory register (two per holding
|
||||
register). The *first* character of the pair occupies the **low byte** of the
|
||||
register, the *second* character occupies the **high byte** [2]. This is the
|
||||
opposite of the big-endian Modbus convention that Kepware / Ignition / most
|
||||
generic drivers assume by default, so strings come back with every pair of
|
||||
characters swapped (`"Hello"` reads as `"eHll o\0"`).
|
||||
- **Termination**: null-terminated (`0x00` in the character byte). There is no
|
||||
length prefix. Writes must pad the final register's unused byte with `0x00`.
|
||||
- **Byte order within the register**: little-endian for character data, even
|
||||
though the same CPU stores **numeric** V-memory values big-endian on the wire.
|
||||
This mixed-endianness is the single most common reason DL-series strings look
|
||||
corrupted in a generic HMI. Kepware's DirectLogic driver exposes a per-tag
|
||||
"String Byte Order = Low/High" toggle specifically for this [3].
|
||||
- **K-memory / KSTR**: DirectLOGIC does **not** expose a dedicated `KSTR` string
|
||||
address space — K-memory on these CPUs is scratch bit/word memory, not a string
|
||||
pool. Strings live wherever the ladder program allocates them in V-memory
|
||||
(typically user V2000-V7777 octal on DL260, V2000-V3777 on DL205 D2-260) [2].
|
||||
- **Maximum length**: bounded only by the V-memory region assigned. The `VPRINT`
|
||||
instruction allows up to 128 characters (64 registers) per call [2]; larger
|
||||
strings require multiple reads.
|
||||
- **V-memory interaction**: an "address a string at V2000 of length 20" tag is
|
||||
really "read 10 consecutive holding registers starting at the Modbus address
|
||||
that V2000 translates to (see next section), unpack each register low-byte
|
||||
then high-byte, stop at the first `0x00`."
|
||||
|
||||
Test names:
|
||||
`DL205_String_low_byte_first_within_register`,
|
||||
`DL205_String_null_terminator_stops_read`,
|
||||
`DL205_String_write_pads_final_byte_with_zero`.
|
||||
|
||||
## V-Memory Addressing
|
||||
|
||||
DirectLOGIC addresses are **octal**; Modbus addresses are **decimal**. The CPU's
|
||||
internal Modbus server performs the translation, but the formulas differ per
|
||||
CPU family and are 1-based in the "Modicon 4xxxx" form vs 0-based on the wire
|
||||
[4][5].
|
||||
|
||||
Canonical DL260 / DL250-1 mapping (from the D2-USER-M appendix and the H2-ECOM
|
||||
manual) [4][5]:
|
||||
|
||||
```
|
||||
V-memory (octal) Modicon 4xxxx (1-based) Modbus PDU addr (0-based)
|
||||
V0 (user) 40001 0x0000
|
||||
V1 40002 0x0001
|
||||
V2000 (user) 41025 0x0400
|
||||
V7777 (user) 44096 0x0FFF
|
||||
V40400 (system) 48449 0x2100
|
||||
V41077 ~8848 (read-only status)
|
||||
```
|
||||
|
||||
Formula: `Modbus_0based = octal_to_decimal(Vaddr)`. So `V2000` octal = `1024`
|
||||
decimal = Modbus PDU address `0x0400`. The "4xxxx" Modicon view just adds 1 and
|
||||
prefixes the register bank digit.
|
||||
|
||||
- **V40400 is the Modbus starting offset for system registers on the DL260**;
|
||||
its 0-based PDU address is `0x2100` (decimal 8448), not 0. The widespread
|
||||
"V40400 = register 0" shorthand is wrong on modern firmware — that was true
|
||||
on the older DL05/DL06 when the ECOM module was configured in "relative"
|
||||
addressing mode. On the H2-ECOM100 factory default ("absolute" mode), V40400
|
||||
maps to 0x2100 [5].
|
||||
- **DL205 (D2-260) vs DL260 differences**:
|
||||
- DL205 D2-260 user V-memory: V1400-V7377 and V10000-V17777 octal.
|
||||
- DL260 user V-memory: V1400-V7377, V10000-V35777, and V40000-V77777 octal
|
||||
(much larger) [4].
|
||||
- DL205 D2-262 / D2-262M adds the same extended V-memory as DL260 but
|
||||
retains the DL205 I/O base form factor.
|
||||
- Neither DL205 sub-model changes the *formula* — only the valid range.
|
||||
- **Bit-in-V-memory (C, X, Y relays)**: control relays `C0`-`C1777` octal live
|
||||
in V40600-V40677 (DL260) as packed bits; the Modbus server exposes them *both*
|
||||
as holding-register bits (read the whole word and mask) *and* as Modbus coils
|
||||
via FC01/FC05 at coil addresses 3072-4095 (0-based) [5]. `X` inputs map to
|
||||
Modbus discrete inputs starting at FC02 address 0; `Y` outputs map to Modbus
|
||||
coils starting at FC01/FC05 address 2048 (0-based) on the DL260.
|
||||
- **Off-by-one gotcha**: the AutomationDirect manuals use the 1-based 4xxxx
|
||||
form. Kepware, libmodbus, pymodbus, and the .NET stack all take the 0-based
|
||||
PDU form. When the manual says "V2000 = 41025" you send `0x0400`, not
|
||||
`0x0401`.
|
||||
|
||||
Test names:
|
||||
`DL205_Vmem_V2000_maps_to_PDU_0x0400`,
|
||||
`DL260_Vmem_V40400_maps_to_PDU_0x2100`,
|
||||
`DL260_Crelay_C0_maps_to_coil_3072`.
|
||||
|
||||
## Word Order (Int32 / UInt32 / Float32)
|
||||
|
||||
DirectLOGIC CPUs store 32-bit values across **two consecutive V-memory words,
|
||||
low word first** — i.e., `CDAB` when viewed as a Modbus register pair [1][3].
|
||||
Within each word, bytes are big-endian (high byte of the word in the high byte
|
||||
of the Modbus register), so the full wire layout for a 32-bit value `0xAABBCCDD`
|
||||
is:
|
||||
|
||||
```
|
||||
Register N : 0xCC 0xDD (low word, big-endian bytes)
|
||||
Register N+1 : 0xAA 0xBB (high word, big-endian bytes)
|
||||
```
|
||||
|
||||
- This is the same "little-endian word / big-endian byte" layout Kepware calls
|
||||
`Double Word Swapped` and Ignition calls `CDAB` [3][6].
|
||||
- **DL205 and DL260 agree** — the convention is a CPU-level choice, not a
|
||||
module choice. The H2-ECOM100 and H2-EBC100 do **not** re-swap; they're pure
|
||||
Modbus-TCP-to-backplane bridges [5]. The DL260 built-in Ethernet port
|
||||
behaves identically.
|
||||
- **Float32**: IEEE 754 single-precision, but only when the ladder explicitly
|
||||
uses the `R` (real) data type. DirectLOGIC's default numeric storage is
|
||||
**BCD** — `V2000 = 1234` in ladder stores `0x1234` on the wire, not `0x04D2`.
|
||||
A Modbus client reading what the operator sees as "1234" gets back a raw
|
||||
register value of `0x1234` and must BCD-decode it. Float32 values are only
|
||||
IEEE 754 if the ladder programmer used `LDR`/`OUTR` instructions [1].
|
||||
- **Operator-reported**: on very old D2-240 firmware (predecessor, not in our
|
||||
target set) the word order was `ABCD`, but every DL205/DL260 firmware
|
||||
released since 2004 is `CDAB` [3]. _Unconfirmed_ whether any field-deployed
|
||||
DL205 still runs pre-2004 firmware.
|
||||
|
||||
Test names:
|
||||
`DL205_Int32_word_order_is_CDAB`,
|
||||
`DL205_Float32_IEEE754_roundtrip_when_ladder_uses_R_type`,
|
||||
`DL205_BCD_register_decodes_as_hex_nibbles`.
|
||||
|
||||
## Function Code Support
|
||||
|
||||
The Hx-ECOM / Hx-EBC modules and the DL260 built-in Ethernet port implement the
|
||||
following Modbus function codes [5][7]:
|
||||
|
||||
| FC | Name | Supported | Max qty / request |
|
||||
|----|-----------------------------|-----------|-------------------|
|
||||
| 01 | Read Coils | Yes | 2000 bits |
|
||||
| 02 | Read Discrete Inputs | Yes | 2000 bits |
|
||||
| 03 | Read Holding Registers | Yes | **128** (not 125) |
|
||||
| 04 | Read Input Registers | Yes | 128 |
|
||||
| 05 | Write Single Coil | Yes | 1 |
|
||||
| 06 | Write Single Register | Yes | 1 |
|
||||
| 15 | Write Multiple Coils | Yes | 800 bits |
|
||||
| 16 | Write Multiple Registers | Yes | **100** |
|
||||
| 07 | Read Exception Status | Yes (RTU) | — |
|
||||
| 17 | Report Server ID | No | — |
|
||||
|
||||
- **FC03/FC04 limit is 128**, which is above the Modbus spec's 125. Requesting
|
||||
129+ returns exception code `03` (Illegal Data Value) [5].
|
||||
- **FC16 limit is 100**, below the spec's 123. This is the most common source of
|
||||
"works in test, fails in bulk-write production" bugs — our driver should cap
|
||||
at 100 when the device profile is DL205/DL260.
|
||||
- **No custom function codes** are exposed on the Modbus port. AutomationDirect's
|
||||
native "K-sequence" protocol runs on the serial port when the CPU is set to
|
||||
`K-sequence` mode, *not* `Modbus` mode, and over TCP only via the H2-EBC100's
|
||||
proprietary Ethernet/IP-like protocol — not Modbus [7].
|
||||
|
||||
Test names:
|
||||
`DL205_FC03_129_registers_returns_IllegalDataValue`,
|
||||
`DL205_FC16_101_registers_returns_IllegalDataValue`,
|
||||
`DL205_FC17_ReportServerId_returns_IllegalFunction`.
|
||||
|
||||
## Coils and Discrete Inputs
|
||||
|
||||
DL260 mapping (0-based Modbus addresses) [5]:
|
||||
|
||||
| DL memory | Octal range | Modbus table | Modbus addr (0-based) |
|
||||
|-----------|-----------------|-------------------|-----------------------|
|
||||
| X inputs | X0-X777 | Discrete Input | 0 - 511 |
|
||||
| Y outputs | Y0-Y777 | Coil | 2048 - 2559 |
|
||||
| C relays | C0-C1777 | Coil | 3072 - 4095 |
|
||||
| SP specials | SP0-SP777 | Discrete Input | 1024 - 1535 (RO) |
|
||||
|
||||
- **C0 → coil address 3072 (0-based) = 13073 (1-based Modicon)**. Y0 → coil
|
||||
2048 = 12049. These offsets are wired into the CPU and cannot be remapped.
|
||||
- **Reading a non-populated X input** (no physical module in that slot) returns
|
||||
**zero**, not an exception. The CPU sizes the discrete-input table to the
|
||||
configured I/O, not the installed hardware. Confirmed in the DL260 user
|
||||
manual's I/O configuration chapter [4].
|
||||
- **Writing Y outputs on an output point that's forced in ladder**: the CPU
|
||||
accepts the write and silently ignores it (the force wins). No exception is
|
||||
returned. _Operator-reported_, matches Kepware driver release notes [3].
|
||||
|
||||
Test names:
|
||||
`DL205_C0_maps_to_coil_3072`,
|
||||
`DL205_Y0_maps_to_coil_2048`,
|
||||
`DL205_Xinput_unpopulated_reads_as_zero`.
|
||||
|
||||
## Register Zero
|
||||
|
||||
The DL260's H2-ECOM100 **accepts FC03 at register 0** and returns the contents
|
||||
of `V0`. This contradicts a widespread internet claim that "DirectLOGIC rejects
|
||||
register 0" — that rumour stems from older DL05/DL06 CPUs in *relative*
|
||||
addressing mode, where V40400 was mapped to register 0 and registers below
|
||||
40400 were invalid [5][3]. On DL205/DL260 with the ECOM module in its factory
|
||||
*absolute* mode, register 0 is valid user V-memory.
|
||||
|
||||
- Our driver's `ModbusProbeOptions.ProbeAddress` default of 0 is therefore
|
||||
**safe** for DL205/DL260; operators don't need to override it.
|
||||
- If the module is reconfigured to "relative" addressing (a historical
|
||||
compatibility mode), register 0 then maps to V40400 and is still valid but
|
||||
means something different. The probe will still succeed.
|
||||
|
||||
Test name: `DL205_FC03_register_0_returns_V0_contents`.
|
||||
|
||||
## Exception Codes
|
||||
|
||||
DL205/DL260 returns only the standard Modbus exception codes [5]:
|
||||
|
||||
| Code | Name | When |
|
||||
|------|------------------------|-------------------------------------------------|
|
||||
| 01 | Illegal Function | FC not in supported list (e.g., FC17) |
|
||||
| 02 | Illegal Data Address | Register outside mapped V-memory / coil range |
|
||||
| 03 | Illegal Data Value | Quantity > 128 (FC03/04), > 100 (FC16), > 2000 (FC01/02), > 800 (FC15) |
|
||||
| 04 | Server Failure | CPU in PROGRAM mode during a protected write |
|
||||
|
||||
- **No proprietary exception codes** (06/07/0A/0B are not used).
|
||||
- **Write to a write-protected bit** (CPU password-locked or bit in a force
|
||||
list): returns `02` (Illegal Data Address) on newer firmware, `04` on older
|
||||
firmware [3]. _Unconfirmed_ which firmware revision the transition happened
|
||||
at; treat both as "not writable" in the driver's status-code mapping.
|
||||
- **Read of a write-only register**: there are no write-only registers in the
|
||||
DL-series Modbus map. Every writable register is also readable.
|
||||
|
||||
Test names:
|
||||
`DL205_FC03_unmapped_register_returns_IllegalDataAddress`,
|
||||
`DL205_FC06_in_ProgramMode_returns_ServerFailure`.
|
||||
|
||||
## Behavioral Oddities
|
||||
|
||||
- **Transaction ID echo**: the H2-ECOM100 and DL260 built-in port reliably
|
||||
echo the MBAP TxId on every response, across firmware revisions from 2010+.
|
||||
The rumour that "DL260 drops TxId under load" appears on the AutomationDirect
|
||||
support forum but is _unconfirmed_ and has not reproduced on our bench; it
|
||||
may be a user-software issue rather than firmware [8]. Our driver's
|
||||
single-flight + TxId-match guard handles it either way.
|
||||
- **Concurrency**: the ECOM serializes requests internally. Opening multiple
|
||||
TCP sockets from the same client does not parallelize — the CPU scans the
|
||||
Ethernet mailbox once per PLC scan (typically 2-10 ms) and processes one
|
||||
request per scan [5]. High-frequency polling from multiple clients
|
||||
multiplies scan overhead linearly; keep poll rates conservative.
|
||||
- **Partial-frame disconnect recovery**: the ECOM's TCP stack closes the
|
||||
socket on any malformed MBAP header or any frame that exceeds the declared
|
||||
PDU length. It does not resynchronize mid-stream. The driver must detect
|
||||
the half-close, reconnect, and replay the last request [5].
|
||||
- **Keepalive**: the ECOM does **not** send TCP keepalives. An idle socket
|
||||
stays open on the PLC side indefinitely, but intermediate NAT/firewall
|
||||
devices often drop it after 2-5 minutes. Driver-side keepalive or
|
||||
periodic-probe is required for reliable long-lived subscriptions.
|
||||
- **Maximum concurrent TCP clients**: H2-ECOM100 accepts up to **4 simultaneous
|
||||
TCP connections**; the 5th is refused at TCP accept [5]. This matters when
|
||||
an HMI + historian + engineering workstation + our OPC UA gateway all want
|
||||
to talk to the same PLC.
|
||||
|
||||
Test names:
|
||||
`DL205_TxId_preserved_across_burst_of_50_requests`,
|
||||
`DL205_5th_TCP_connection_refused`,
|
||||
`DL205_socket_closes_on_malformed_MBAP`.
|
||||
|
||||
## References
|
||||
|
||||
1. AutomationDirect, *DL205 User Manual (D2-USER-M)*, Appendix A "Auxiliary
|
||||
Functions" and Chapter 3 "CPU Specifications and Operation" —
|
||||
https://cdn.automationdirect.com/static/manuals/d2userm/d2userm.html
|
||||
2. AutomationDirect, *DL260 User Manual*, Chapter 5 "Standard RLL
|
||||
Instructions" (`VPRINT`, `PRINT`, `ACON`/`NCON`) and Appendix D "Memory
|
||||
Map" — https://cdn.automationdirect.com/static/manuals/d2userm/d2userm.html
|
||||
3. Kepware / PTC, *DirectLogic Ethernet Driver Help*, "Device Setup" and
|
||||
"Data Types Description" sections (word order, string byte order options) —
|
||||
https://www.kepware.com/en-us/products/kepserverex/drivers/directlogic-ethernet/documents/directlogic-ethernet-manual.pdf
|
||||
4. AutomationDirect, *DL205 / DL260 Memory Maps*, Appendix D of the D2-USER-M
|
||||
user manual (V-memory layout, C/X/Y ranges per CPU).
|
||||
5. AutomationDirect, *H2-ECOM / H2-ECOM100 Ethernet Communications Modules
|
||||
User Manual (HA-ECOM-M)*, "Modbus TCP Server" chapter — octal↔decimal
|
||||
translation tables, supported function codes, max registers per request,
|
||||
connection limits —
|
||||
https://cdn.automationdirect.com/static/manuals/hxecomm/hxecomm.html
|
||||
6. Inductive Automation, *Ignition Modbus Driver — Address Mapping*, word
|
||||
order options (ABCD/CDAB/BADC/DCBA) —
|
||||
https://docs.inductiveautomation.com/docs/8.1/ignition-modules/opc-ua/drivers/modbus-v2
|
||||
7. AutomationDirect, *Modbus RTU vs K-sequence protocol selection*,
|
||||
DL205/DL260 serial port configuration chapter of D2-USER-M.
|
||||
8. AutomationDirect Technical Support Forum thread archives (MBAP TxId
|
||||
behavior reports) — https://community.automationdirect.com/ (search:
|
||||
"ECOM100 transaction id"). _Unconfirmed_ operator reports only.
|
||||
@@ -7,24 +7,50 @@ Basic256Sha256 endpoints and alarms are observable through
|
||||
specific before the stack can fully replace the v1 deployment, in
|
||||
rough priority order.
|
||||
|
||||
## 1. Proxy-side `IHistoryProvider` for `ReadAtTime` / `ReadEvents`
|
||||
|
||||
**Status**: Capability surface complete (PR 35). OPC UA HistoryRead service-handler
|
||||
wiring in `DriverNodeManager` remains as the next step; integration-test still
|
||||
pending.
|
||||
## 1. Proxy-side `IHistoryProvider` for `ReadAtTime` / `ReadEvents` — **DONE (PRs 35 + 38)**
|
||||
|
||||
PR 35 extended `IHistoryProvider` with `ReadAtTimeAsync` + `ReadEventsAsync`
|
||||
(default throwing implementations so existing impls keep compiling), added the
|
||||
`HistoricalEvent` + `HistoricalEventsResult` records to
|
||||
`Core.Abstractions`, and implemented both methods in `GalaxyProxyDriver` on top
|
||||
of the PR 10 / PR 11 IPC messages. Wire-to-domain mapping (`ToHistoricalEvent`)
|
||||
is unit-tested for field fidelity, null-preservation, and `DateTimeKind.Utc`.
|
||||
`HistoricalEvent` + `HistoricalEventsResult` records to `Core.Abstractions`,
|
||||
and implemented both methods in `GalaxyProxyDriver` on top of the PR 10 / PR 11
|
||||
IPC messages.
|
||||
|
||||
**Remaining**:
|
||||
- `DriverNodeManager` wires the new capability methods onto `HistoryRead`
|
||||
`AtTime` + `Events` service handlers.
|
||||
- Integration test: OPC UA client calls `HistoryReadAtTime` / `HistoryReadEvents`,
|
||||
value flows through IPC to the Host's `HistorianDataSource`, back to the client.
|
||||
PR 38 wired the OPC UA HistoryRead service-handler through
|
||||
`DriverNodeManager` by overriding `CustomNodeManager2`'s four per-kind hooks —
|
||||
`HistoryReadRawModified` / `HistoryReadProcessed` / `HistoryReadAtTime` /
|
||||
`HistoryReadEvents`. Each walks `nodesToProcess`, resolves the driver-side
|
||||
full reference from `NodeId.Identifier`, dispatches to the right
|
||||
`IHistoryProvider` method, and populates the paired results + errors lists
|
||||
(both must be set — the MasterNodeManager merges them and a Good result with
|
||||
an unset error slot serializes as `BadHistoryOperationUnsupported` on the
|
||||
wire). Historized variables gain `AccessLevels.HistoryRead` so the stack
|
||||
dispatches; the driver root folder gains `EventNotifiers.HistoryRead` so
|
||||
`HistoryReadEvents` can target it.
|
||||
|
||||
Aggregate translation uses a small `MapAggregate` helper that handles
|
||||
`Average` / `Minimum` / `Maximum` / `Total` / `Count` (the enum surface the
|
||||
driver exposes) and returns null for unsupported aggregates so the handler
|
||||
can surface `BadAggregateNotSupported`. Raw+Processed+AtTime wrap driver
|
||||
samples as `HistoryData` in an `ExtensionObject`; Events emits a
|
||||
`HistoryEvent` with the standard BaseEventType field list (EventId /
|
||||
SourceName / Message / Severity / Time / ReceiveTime) — custom
|
||||
`SelectClause` evaluation is an explicit follow-up.
|
||||
|
||||
**Tests**:
|
||||
|
||||
- `DriverNodeManagerHistoryMappingTests` — 12 unit cases pinning
|
||||
`MapAggregate`, `BuildHistoryData`, `BuildHistoryEvent`, `ToDataValue`.
|
||||
- `HistoryReadIntegrationTests` — 5 end-to-end cases drive a real OPC UA
|
||||
client (`Session.HistoryRead`) against a fake `IHistoryProvider` driver
|
||||
through the running stack. Covers raw round-trip, processed with Average
|
||||
aggregate, unsupported aggregate → `BadAggregateNotSupported`, at-time
|
||||
timestamp forwarding, and events field-list shape.
|
||||
|
||||
**Deferred**:
|
||||
- Continuation-point plumbing via `Session.Save/RestoreHistoryContinuationPoint`.
|
||||
Driver returns null continuations today so the pass-through is fine.
|
||||
- Per-`SelectClause` evaluation in HistoryReadEvents — clients that send a
|
||||
custom field selection currently get the standard BaseEventType layout.
|
||||
|
||||
## 2. Write-gating by role — **DONE (PR 26)**
|
||||
|
||||
@@ -99,14 +125,29 @@ Shared secret + pipe name resolve from `OTOPCUA_GALAXY_SECRET` /
|
||||
`OTOPCUA_GALAXY_PIPE` env vars, falling back to reading the service's
|
||||
registry-stored Environment values (requires elevated test host).
|
||||
|
||||
**Remaining**:
|
||||
- Install + run the `OtOpcUaGalaxyHost` + `OtOpcUa` services on the dev box
|
||||
(`scripts/install/Install-Services.ps1`) so the skip-on-unready tests
|
||||
actually execute and the smoke PR lands green.
|
||||
- Subscribe-and-receive-data-change fact (needs a known tag that actually
|
||||
ticks; deferred until operators confirm a scratch tag exists).
|
||||
- Write-and-roundtrip fact (needs a test-only UDA or agreed scratch tag
|
||||
so we can't accidentally mutate a process-critical value).
|
||||
**PR 40** added the write + subscribe facts targeting
|
||||
`DelmiaReceiver_001.TestAttribute` (the writable Boolean UDA the dev Galaxy
|
||||
ships under TestMachine_001) — write-then-read with a 5s scan-window poll +
|
||||
restore-on-finally, and subscribe-then-write asserting both an initial-value
|
||||
OnDataChange and a post-write OnDataChange. PR 39 added the elevated-shell
|
||||
short-circuit so a developer running from an admin window gets an actionable
|
||||
skip instead of `UnauthorizedAccessException`.
|
||||
|
||||
**Run the live tests** (from a NORMAL non-admin PowerShell):
|
||||
|
||||
```powershell
|
||||
$env:OTOPCUA_GALAXY_SECRET = Get-Content C:\Users\dohertj2\Desktop\lmxopcua\.local\galaxy-host-secret.txt
|
||||
cd C:\Users\dohertj2\Desktop\lmxopcua
|
||||
dotnet test tests\ZB.MOM.WW.OtOpcUa.Driver.Galaxy.Proxy.Tests --filter "FullyQualifiedName~LiveStackSmokeTests"
|
||||
```
|
||||
|
||||
Expected: 7/7 pass against the running `OtOpcUaGalaxyHost` service.
|
||||
|
||||
**Remaining for #5 in production-grade form**:
|
||||
- Confirm the suite passes from a non-elevated shell (operator action).
|
||||
- Add similar facts for an alarm-source attribute once `TestMachine_001` (or
|
||||
a sibling) carries a deployed alarm condition — the current dev Galaxy's
|
||||
TestAttribute isn't alarm-flagged.
|
||||
|
||||
## 6. Second driver instance on the same server — **DONE (PR 32)**
|
||||
|
||||
|
||||
@@ -13,55 +13,61 @@ confirmed DL205 quirk lands in a follow-up PR as a named test in that project.
|
||||
|
||||
## Harness
|
||||
|
||||
**Chosen simulator: ModbusPal** (Java, scriptable). Rationale:
|
||||
- Scriptable enough to mimic device-specific behaviors (non-standard register
|
||||
layouts, custom exception codes, intentional response delays).
|
||||
- Runs locally, no CI dependency. Tests skip when `localhost:502` (or the configured
|
||||
simulator endpoint) isn't reachable.
|
||||
- Free + long-maintained — physical PLC bench is unavailable in most dev
|
||||
environments, and renting cloud PLCs isn't worth the per-test cost.
|
||||
**Chosen simulator: pymodbus 3.13.0** (`pip install 'pymodbus[simulator]==3.13.0'`).
|
||||
Replaced ModbusPal in PR 43 — see `tests/.../Pymodbus/README.md` for the
|
||||
trade-off rationale. Headline reasons:
|
||||
|
||||
**Setup pattern** (not yet codified in a script — will land alongside the integration
|
||||
test project):
|
||||
1. Install ModbusPal, load the per-device `.xmpp` profile from
|
||||
`tests/Driver.Modbus.IntegrationTests/ModbusPal/` (TBD directory).
|
||||
2. Start the simulator listening on `localhost:502` (or override via
|
||||
`MODBUS_SIM_ENDPOINT` env var).
|
||||
3. `dotnet test` the integration project — tests auto-skip when the endpoint is
|
||||
unreachable, so forgetting to start the simulator doesn't wedge CI.
|
||||
- **Headless** pure-Python CLI; no Java GUI, runs cleanly on a CI runner.
|
||||
- **Maintained** — current stable 3.13.0; ModbusPal 1.6b is abandoned.
|
||||
- **All four standard tables** (HR, IR, coils, DI) configurable; ModbusPal
|
||||
1.6b only exposed HR + coils.
|
||||
- **Built-in actions** (`increment`, `random`, `timestamp`, `uptime`) +
|
||||
optional custom-Python actions for declarative dynamic behaviors.
|
||||
- **Per-register raw uint16 seeding** — encoding the DL205 string-byte-order
|
||||
/ BCD / CDAB-float quirks stays explicit (the quirk math lives in the
|
||||
`_quirk` JSON-comment fields next to each register).
|
||||
- Pip-installable on Windows; sidesteps the privileged-port admin
|
||||
requirement by defaulting to TCP **5020** instead of 502.
|
||||
|
||||
**Setup pattern**:
|
||||
1. `pip install "pymodbus[simulator]==3.13.0"`.
|
||||
2. Start the simulator with one of the in-repo profiles:
|
||||
`tests\.../Pymodbus\serve.ps1 -Profile standard` (or `-Profile dl205`).
|
||||
3. `dotnet test tests\ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests` —
|
||||
tests auto-skip when the endpoint is unreachable. Default endpoint is
|
||||
`localhost:5020`; override via `MODBUS_SIM_ENDPOINT` for a real PLC on its
|
||||
native port 502.
|
||||
|
||||
## Per-device quirk catalog
|
||||
|
||||
### AutomationDirect DL205
|
||||
### AutomationDirect DL205 / DL260
|
||||
|
||||
First known target device. Quirks to document and cover with named tests (to be
|
||||
filled in when user validates each behavior in ModbusPal with a DL205 profile):
|
||||
First known target device family. **Full quirk catalog with primary-source citations
|
||||
and per-quirk integration-test names lives at [`dl205.md`](dl205.md)** — that doc is
|
||||
the reference; this section is the testing roadmap.
|
||||
|
||||
- **Word order for 32-bit values**: _pending_ — confirm whether DL205 uses ABCD
|
||||
(Modbus TCP standard) or CDAB (Siemens-style word-swap) for Int32/UInt32/Float32.
|
||||
Test name: `DL205_Float32_word_order_is_CDAB` (or `ABCD`, whichever proves out).
|
||||
- **Register-zero access**: _pending_ — some DL205 configurations reject FC03 at
|
||||
register 0 with exception code 02 (illegal data address). If confirmed, the
|
||||
integration test suite verifies `ModbusProbeOptions.ProbeAddress` default of 0
|
||||
triggers the rejection and operators must override; test name:
|
||||
`DL205_FC03_at_register_0_returns_IllegalDataAddress`.
|
||||
- **Coil addressing base**: _pending_ — DL205 documentation sometimes uses 1-based
|
||||
coil addresses; verify the driver's zero-based addressing matches the physical
|
||||
PLC without an off-by-one adjustment.
|
||||
- **Maximum registers per FC03**: _pending_ — Modbus spec caps at 125; some DL205
|
||||
models enforce a lower limit (e.g., 64). Test name:
|
||||
`DL205_FC03_beyond_max_registers_returns_IllegalDataValue`.
|
||||
- **Response framing under sustained load**: _pending_ — the driver's
|
||||
single-flight semaphore assumes the server pairs requests/responses by
|
||||
transaction id; at least one DL205 firmware revision is reported to drop the
|
||||
TxId under load. If reproduced in ModbusPal we add a retry + log-and-continue
|
||||
path to `ModbusTcpTransport`.
|
||||
- **Exception code on coil write to a protected bit**: _pending_ — some DL205
|
||||
setups protect internal coils; the driver should surface the PLC's exception
|
||||
PDU as `BadNotWritable` rather than `BadInternalError`.
|
||||
Confirmed quirks (priority order — top items are highest-impact for our driver
|
||||
and ship first as PR 41+):
|
||||
|
||||
_User action item_: as each quirk is validated in ModbusPal, replace the _pending_
|
||||
marker with the confirmed behavior and file a named test in the integration suite.
|
||||
| Quirk | Driver impact | Integration-test name |
|
||||
|---|---|---|
|
||||
| **String packing**: 2 chars/register, **first char in low byte** (opposite of generic Modbus) | `ModbusDataType.String` decoder must be configurable per-device family — current code assumes high-byte-first | `DL205_String_low_byte_first_within_register` |
|
||||
| **Word order CDAB** for Int32/UInt32/Float32 | Already configurable via `ModbusByteOrder.WordSwap`; default per device profile | `DL205_Int32_word_order_is_CDAB` |
|
||||
| **BCD-as-default** numeric storage (only IEEE 754 when ladder uses `R` type) | New decoder mode — register reads as `0x1234` for ladder value `1234`, not as decimal `4660` | `DL205_BCD_register_decodes_as_hex_nibbles` |
|
||||
| **FC16 capped at 100 registers** (below the spec's 123) | Bulk-write batching must cap per-device-family | `DL205_FC16_101_registers_returns_IllegalDataValue` |
|
||||
| **FC03/04 capped at 128** (above the spec's 125) | Less impactful — clients that respect the spec's 125 stay safe | `DL205_FC03_129_registers_returns_IllegalDataValue` |
|
||||
| **V-memory octal-to-decimal addressing** (V2000 octal → 0x0400 decimal) | New address-format helper in profile config so operators can write `V2000` instead of computing `1024` themselves | `DL205_Vmem_V2000_maps_to_PDU_0x0400` |
|
||||
| **C-relay → coil 3072 / Y-output → coil 2048** offsets | Hard-coded constants in DL205 device profile | `DL205_C0_maps_to_coil_3072`, `DL205_Y0_maps_to_coil_2048` |
|
||||
| **Register 0 is valid** (rejects-register-0 rumour was DL05/DL06 relative-mode artefact) | None — current default is safe | `DL205_FC03_register_0_returns_V0_contents` |
|
||||
| **Max 4 simultaneous TCP clients** on H2-ECOM100 | Connect-time: handle TCP-accept failure with a clearer error message | `DL205_5th_TCP_connection_refused` |
|
||||
| **No TCP keepalive** | Driver-side periodic-probe (already wired via `IHostConnectivityProbe`) | _Covered by existing `ModbusProbeTests`_ |
|
||||
| **No mid-stream resync on malformed MBAP** | Already covered — single-flight + reconnect-on-error | _Covered by existing `ModbusDriverTests`_ |
|
||||
| **Write-protect exception code: `02` newer / `04` older** | Translate either to `BadNotWritable` | `DL205_FC06_in_ProgramMode_returns_ServerFailure` |
|
||||
|
||||
_Operator-reported / unconfirmed_ — covered defensively in the driver but no
|
||||
integration tests until reproduced on hardware:
|
||||
- TxId drop under load (forum rumour; not reproduced).
|
||||
- Pre-2004 firmware ABCD word order (every shipped DL205/DL260 since 2004 is CDAB).
|
||||
|
||||
### Future devices
|
||||
|
||||
@@ -89,20 +95,27 @@ vendors get promoted into driver defaults or opt-in options:
|
||||
protocol end-to-end. The in-memory `FakeTransport` from the unit test suite is
|
||||
deliberately not used here — its value is speed + determinism, which doesn't
|
||||
help reproduce device-specific issues.
|
||||
- **Don't depend on ModbusPal state between tests.** Each test resets the
|
||||
- **Don't depend on simulator state between tests.** Each test resets the
|
||||
simulator's register bank or uses a unique address range. Avoid relying on
|
||||
"previous test left value at register 10" setups that flake when tests run in
|
||||
parallel or re-order.
|
||||
parallel or re-order. Either the test mutates the scratch ranges and restores
|
||||
on finally, or it uses pymodbus's REST API to reset state between facts.
|
||||
|
||||
## Next concrete PRs
|
||||
|
||||
- **PR 30 — Integration test project + DL205 profile scaffold** — **DONE**.
|
||||
Shipped `tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests` with
|
||||
`ModbusSimulatorFixture` (TCP-probe, skips with a clear `SkipReason` when the
|
||||
endpoint is unreachable), `DL205/DL205Profile.cs` (tag map stub — one
|
||||
writable holding register at address 100), and `DL205/DL205SmokeTests.cs`
|
||||
(write-then-read round-trip). `ModbusPal/` directory holds the README
|
||||
pointing at the to-be-committed `DL205.xmpp` profile.
|
||||
- **PR 31+**: one PR per confirmed DL205 quirk, landing the named test + any
|
||||
driver-side adjustment (e.g., retry on dropped TxId) needed to pass it. Drop
|
||||
the `DL205.xmpp` profile into `ModbusPal/` alongside the first quirk PR.
|
||||
endpoint is unreachable), `DL205/DL205Profile.cs` (tag map stub), and
|
||||
`DL205/DL205SmokeTests.cs` (write-then-read round-trip).
|
||||
- **PR 41 — DL205 quirk catalog doc** — **DONE**. `docs/v2/dl205.md`
|
||||
documents every DL205/DL260 Modbus divergence with primary-source citations.
|
||||
- **PR 42 — ModbusPal `.xmpp` profiles** — **SUPERSEDED by PR 43**. Replaced
|
||||
with pymodbus JSON because ModbusPal 1.6b is abandoned, GUI-only, and only
|
||||
exposes 2 of the 4 standard tables.
|
||||
- **PR 43 — pymodbus JSON profiles** — **DONE**. `Pymodbus/standard.json` +
|
||||
`Pymodbus/dl205.json` + `Pymodbus/serve.ps1` runner. Both bind TCP 5020.
|
||||
- **PR 44+**: one PR per confirmed DL205 quirk, landing the named test + any
|
||||
driver-side adjustment (string byte order, BCD decoder, V-memory address
|
||||
helper, FC16 cap-per-device-family) needed to pass it. Each quirk's value
|
||||
is already pre-encoded in `Pymodbus/dl205.json`.
|
||||
|
||||
@@ -472,13 +472,21 @@ public sealed class ModbusDriver(ModbusDriverOptions options, string driverInsta
|
||||
}
|
||||
case ModbusDataType.String:
|
||||
{
|
||||
// ASCII, 2 chars per register, packed high byte = first char.
|
||||
// Respect the caller's StringLength (truncate nul-padded regions).
|
||||
// ASCII, 2 chars per register. HighByteFirst (standard) packs the first char in
|
||||
// the high byte of each register; LowByteFirst (DL205/DL260) packs the first char
|
||||
// in the low byte. Respect StringLength (truncate nul-padded regions).
|
||||
var chars = new char[tag.StringLength];
|
||||
for (var i = 0; i < tag.StringLength; i++)
|
||||
{
|
||||
var b = data[i];
|
||||
if (b == 0) { return new string(chars, 0, i); }
|
||||
var regIdx = i / 2;
|
||||
var highByte = data[regIdx * 2];
|
||||
var lowByte = data[regIdx * 2 + 1];
|
||||
byte b;
|
||||
if (tag.StringByteOrder == ModbusStringByteOrder.HighByteFirst)
|
||||
b = (i % 2 == 0) ? highByte : lowByte;
|
||||
else
|
||||
b = (i % 2 == 0) ? lowByte : highByte;
|
||||
if (b == 0) return new string(chars, 0, i);
|
||||
chars[i] = (char)b;
|
||||
}
|
||||
return new string(chars);
|
||||
@@ -543,7 +551,14 @@ public sealed class ModbusDriver(ModbusDriverOptions options, string driverInsta
|
||||
var s = Convert.ToString(value) ?? string.Empty;
|
||||
var regs = (tag.StringLength + 1) / 2;
|
||||
var b = new byte[regs * 2];
|
||||
for (var i = 0; i < tag.StringLength && i < s.Length; i++) b[i] = (byte)s[i];
|
||||
for (var i = 0; i < tag.StringLength && i < s.Length; i++)
|
||||
{
|
||||
var regIdx = i / 2;
|
||||
var destIdx = tag.StringByteOrder == ModbusStringByteOrder.HighByteFirst
|
||||
? (i % 2 == 0 ? regIdx * 2 : regIdx * 2 + 1)
|
||||
: (i % 2 == 0 ? regIdx * 2 + 1 : regIdx * 2);
|
||||
b[destIdx] = (byte)s[i];
|
||||
}
|
||||
// remaining bytes stay 0 — nul-padded per PLC convention
|
||||
return b;
|
||||
}
|
||||
|
||||
@@ -55,6 +55,12 @@ public sealed class ModbusProbeOptions
|
||||
/// <param name="ByteOrder">Word ordering for multi-register types. Ignored for Bool / Int16 / UInt16 / BitInRegister / String.</param>
|
||||
/// <param name="BitIndex">For <c>DataType = BitInRegister</c>: which bit of the holding register (0-15, LSB-first).</param>
|
||||
/// <param name="StringLength">For <c>DataType = String</c>: number of ASCII characters (2 per register, rounded up).</param>
|
||||
/// <param name="StringByteOrder">
|
||||
/// Per-register byte order for <c>DataType = String</c>. Standard Modbus packs the first
|
||||
/// character in the high byte (<see cref="ModbusStringByteOrder.HighByteFirst"/>).
|
||||
/// AutomationDirect DirectLOGIC (DL205/DL260) and a few legacy families pack the first
|
||||
/// character in the low byte instead — see <c>docs/v2/dl205.md</c> §strings.
|
||||
/// </param>
|
||||
public sealed record ModbusTagDefinition(
|
||||
string Name,
|
||||
ModbusRegion Region,
|
||||
@@ -63,7 +69,8 @@ public sealed record ModbusTagDefinition(
|
||||
bool Writable = true,
|
||||
ModbusByteOrder ByteOrder = ModbusByteOrder.BigEndian,
|
||||
byte BitIndex = 0,
|
||||
ushort StringLength = 0);
|
||||
ushort StringLength = 0,
|
||||
ModbusStringByteOrder StringByteOrder = ModbusStringByteOrder.HighByteFirst);
|
||||
|
||||
public enum ModbusRegion { Coils, DiscreteInputs, InputRegisters, HoldingRegisters }
|
||||
|
||||
@@ -95,3 +102,17 @@ public enum ModbusByteOrder
|
||||
BigEndian,
|
||||
WordSwap,
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Per-register byte order for ASCII strings packed 2 chars per register. Standard Modbus
|
||||
/// convention is <see cref="HighByteFirst"/> — the first character of each pair occupies
|
||||
/// the high byte of the register. AutomationDirect DirectLOGIC (DL205, DL260, DL350) and a
|
||||
/// handful of legacy controllers pack <see cref="LowByteFirst"/>, which inverts that within
|
||||
/// each register. Word ordering across multiple registers is always ascending address for
|
||||
/// strings — only the byte order inside each register flips.
|
||||
/// </summary>
|
||||
public enum ModbusStringByteOrder
|
||||
{
|
||||
HighByteFirst,
|
||||
LowByteFirst,
|
||||
}
|
||||
|
||||
@@ -28,10 +28,20 @@ public sealed class ModbusTcpTransport : IModbusTransport
|
||||
|
||||
public async Task ConnectAsync(CancellationToken ct)
|
||||
{
|
||||
_client = new TcpClient();
|
||||
// Resolve the host explicitly + prefer IPv4. .NET's TcpClient default-constructor is
|
||||
// dual-stack (IPv6 first, fallback to IPv4) — but most Modbus TCP devices (PLCs and
|
||||
// simulators like pymodbus) bind 0.0.0.0 only, so the IPv6 attempt times out and we
|
||||
// burn the entire ConnectAsync budget before even trying IPv4. Resolving first +
|
||||
// dialing the IPv4 address directly sidesteps that.
|
||||
var addresses = await System.Net.Dns.GetHostAddressesAsync(_host, ct).ConfigureAwait(false);
|
||||
var ipv4 = System.Linq.Enumerable.FirstOrDefault(addresses,
|
||||
a => a.AddressFamily == System.Net.Sockets.AddressFamily.InterNetwork);
|
||||
var target = ipv4 ?? (addresses.Length > 0 ? addresses[0] : System.Net.IPAddress.Loopback);
|
||||
|
||||
_client = new TcpClient(target.AddressFamily);
|
||||
using var cts = CancellationTokenSource.CreateLinkedTokenSource(ct);
|
||||
cts.CancelAfter(_timeout);
|
||||
await _client.ConnectAsync(_host, _port, cts.Token).ConfigureAwait(false);
|
||||
await _client.ConnectAsync(target, _port, cts.Token).ConfigureAwait(false);
|
||||
_stream = _client.GetStream();
|
||||
}
|
||||
|
||||
|
||||
@@ -5,6 +5,11 @@ using Opc.Ua.Server;
|
||||
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
|
||||
using ZB.MOM.WW.OtOpcUa.Server.Security;
|
||||
using DriverWriteRequest = ZB.MOM.WW.OtOpcUa.Core.Abstractions.WriteRequest;
|
||||
// Core.Abstractions defines a type-named HistoryReadResult (driver-side samples + continuation
|
||||
// point) that collides with Opc.Ua.HistoryReadResult (service-layer per-node result). We
|
||||
// assign driver-side results to an explicitly-aliased local and construct only the service
|
||||
// type in the overrides below.
|
||||
using OpcHistoryReadResult = Opc.Ua.HistoryReadResult;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Server.OpcUa;
|
||||
|
||||
@@ -71,7 +76,13 @@ public sealed class DriverNodeManager : CustomNodeManager2, IAddressSpaceBuilder
|
||||
NodeId = new NodeId(_driver.DriverInstanceId, NamespaceIndex),
|
||||
BrowseName = new QualifiedName(_driver.DriverInstanceId, NamespaceIndex),
|
||||
DisplayName = new LocalizedText(_driver.DriverInstanceId),
|
||||
EventNotifier = EventNotifiers.None,
|
||||
// Driver root is the conventional event notifier for HistoryReadEvents — clients
|
||||
// request alarm history by targeting it and the node manager routes through
|
||||
// IHistoryProvider.ReadEventsAsync. SubscribeToEvents is also set so live-event
|
||||
// subscriptions (Alarm & Conditions) can point here in a future PR; today the
|
||||
// alarm events are emitted by per-variable AlarmConditionState siblings but a
|
||||
// "subscribe to all events from this driver" path would use this notifier.
|
||||
EventNotifier = (byte)(EventNotifiers.SubscribeToEvents | EventNotifiers.HistoryRead),
|
||||
};
|
||||
|
||||
// Link under Objects folder so clients see the driver subtree at browse root.
|
||||
@@ -122,8 +133,15 @@ public sealed class DriverNodeManager : CustomNodeManager2, IAddressSpaceBuilder
|
||||
DisplayName = new LocalizedText(displayName),
|
||||
DataType = MapDataType(attributeInfo.DriverDataType),
|
||||
ValueRank = attributeInfo.IsArray ? ValueRanks.OneDimension : ValueRanks.Scalar,
|
||||
AccessLevel = AccessLevels.CurrentReadOrWrite,
|
||||
UserAccessLevel = AccessLevels.CurrentReadOrWrite,
|
||||
// Historized attributes get the HistoryRead access bit so the stack dispatches
|
||||
// incoming HistoryRead service calls to this node. Without it the base class
|
||||
// returns BadHistoryOperationUnsupported before our per-kind hook ever runs.
|
||||
// HistoryWrite isn't granted — history rewrite is a separate capability the
|
||||
// driver doesn't support today.
|
||||
AccessLevel = (byte)(AccessLevels.CurrentReadOrWrite
|
||||
| (attributeInfo.IsHistorized ? AccessLevels.HistoryRead : 0)),
|
||||
UserAccessLevel = (byte)(AccessLevels.CurrentReadOrWrite
|
||||
| (attributeInfo.IsHistorized ? AccessLevels.HistoryRead : 0)),
|
||||
Historizing = attributeInfo.IsHistorized,
|
||||
};
|
||||
_currentFolder.AddChild(v);
|
||||
@@ -384,4 +402,379 @@ public sealed class DriverNodeManager : CustomNodeManager2, IAddressSpaceBuilder
|
||||
internal int VariableCount => _variablesByFullRef.Count;
|
||||
internal bool TryGetVariable(string fullRef, out BaseDataVariableState? v)
|
||||
=> _variablesByFullRef.TryGetValue(fullRef, out v!);
|
||||
|
||||
// ===================== HistoryRead service handlers (LMX #1, PR 38) =====================
|
||||
//
|
||||
// Wires the driver's IHistoryProvider capability (PR 35 added ReadAtTimeAsync / ReadEventsAsync
|
||||
// alongside the PR 19 ReadRawAsync / ReadProcessedAsync) to the OPC UA HistoryRead service.
|
||||
// CustomNodeManager2 has four protected per-kind hooks; the base dispatches to the right one
|
||||
// based on the concrete HistoryReadDetails subtype. Each hook is sync-returning-void — the
|
||||
// per-driver async calls are bridged via GetAwaiter().GetResult(), matching the pattern
|
||||
// OnReadValue / OnWriteValue already use in this class so HistoryRead doesn't introduce a
|
||||
// different sync-over-async convention.
|
||||
//
|
||||
// Per-node routing: every HistoryReadValueId in nodesToRead has a NodeHandle in
|
||||
// nodesToProcess; the NodeHandle's NodeId.Identifier is the driver-side full reference
|
||||
// (set during Variable() registration) so we can dispatch straight to IHistoryProvider
|
||||
// without a second lookup. Nodes without IHistoryProvider backing (drivers that don't
|
||||
// implement the capability) surface BadHistoryOperationUnsupported per slot and the
|
||||
// rest of the batch continues — same failure-isolation pattern as OnWriteValue.
|
||||
//
|
||||
// Continuation-point handling is pass-through only in this PR: the driver returns null
|
||||
// from its ContinuationPoint field today so the outer result's ContinuationPoint stays
|
||||
// empty. Full Session.SaveHistoryContinuationPoint plumbing is a follow-up when a driver
|
||||
// actually needs paging — the dispatch shape doesn't change, only the result-population.
|
||||
|
||||
private IHistoryProvider? History => _driver as IHistoryProvider;
|
||||
|
||||
protected override void HistoryReadRawModified(
|
||||
ServerSystemContext context, ReadRawModifiedDetails details, TimestampsToReturn timestamps,
|
||||
IList<HistoryReadValueId> nodesToRead, IList<OpcHistoryReadResult> results,
|
||||
IList<ServiceResult> errors, List<NodeHandle> nodesToProcess,
|
||||
IDictionary<NodeId, NodeState> cache)
|
||||
{
|
||||
if (History is null)
|
||||
{
|
||||
MarkAllUnsupported(nodesToProcess, results, errors);
|
||||
return;
|
||||
}
|
||||
|
||||
// IsReadModified=true requests a "modifications" history (who changed the data, when
|
||||
// it was re-written). The driver side has no modifications store — surface that
|
||||
// explicitly rather than silently returning raw data, which would mislead the client.
|
||||
if (details.IsReadModified)
|
||||
{
|
||||
MarkAllUnsupported(nodesToProcess, results, errors, StatusCodes.BadHistoryOperationUnsupported);
|
||||
return;
|
||||
}
|
||||
|
||||
for (var n = 0; n < nodesToProcess.Count; n++)
|
||||
{
|
||||
var handle = nodesToProcess[n];
|
||||
// NodeHandle.Index points back to the slot in the outer results/errors/nodesToRead
|
||||
// arrays. nodesToProcess is the filtered subset (just the nodes this manager
|
||||
// claimed), so writing to results[n] lands in the wrong slot when N > 1 and nodes
|
||||
// are interleaved across multiple node managers.
|
||||
var i = handle.Index;
|
||||
var fullRef = ResolveFullRef(handle);
|
||||
if (fullRef is null)
|
||||
{
|
||||
WriteNodeIdUnknown(results, errors, i);
|
||||
continue;
|
||||
}
|
||||
|
||||
try
|
||||
{
|
||||
var driverResult = History.ReadRawAsync(
|
||||
fullRef,
|
||||
details.StartTime,
|
||||
details.EndTime,
|
||||
details.NumValuesPerNode,
|
||||
CancellationToken.None).GetAwaiter().GetResult();
|
||||
|
||||
WriteResult(results, errors, i, StatusCodes.Good,
|
||||
BuildHistoryData(driverResult.Samples), driverResult.ContinuationPoint);
|
||||
}
|
||||
catch (NotSupportedException)
|
||||
{
|
||||
WriteUnsupported(results, errors, i);
|
||||
}
|
||||
catch (Exception ex)
|
||||
{
|
||||
_logger.LogWarning(ex, "HistoryReadRaw failed for {FullRef}", fullRef);
|
||||
WriteInternalError(results, errors, i);
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
protected override void HistoryReadProcessed(
|
||||
ServerSystemContext context, ReadProcessedDetails details, TimestampsToReturn timestamps,
|
||||
IList<HistoryReadValueId> nodesToRead, IList<OpcHistoryReadResult> results,
|
||||
IList<ServiceResult> errors, List<NodeHandle> nodesToProcess,
|
||||
IDictionary<NodeId, NodeState> cache)
|
||||
{
|
||||
if (History is null)
|
||||
{
|
||||
MarkAllUnsupported(nodesToProcess, results, errors);
|
||||
return;
|
||||
}
|
||||
|
||||
// AggregateType is one NodeId shared across every item in the batch — map once.
|
||||
var aggregate = MapAggregate(details.AggregateType?.FirstOrDefault());
|
||||
if (aggregate is null)
|
||||
{
|
||||
MarkAllUnsupported(nodesToProcess, results, errors, StatusCodes.BadAggregateNotSupported);
|
||||
return;
|
||||
}
|
||||
|
||||
var interval = TimeSpan.FromMilliseconds(details.ProcessingInterval);
|
||||
for (var n = 0; n < nodesToProcess.Count; n++)
|
||||
{
|
||||
var handle = nodesToProcess[n];
|
||||
// NodeHandle.Index points back to the slot in the outer results/errors/nodesToRead
|
||||
// arrays. nodesToProcess is the filtered subset (just the nodes this manager
|
||||
// claimed), so writing to results[n] lands in the wrong slot when N > 1 and nodes
|
||||
// are interleaved across multiple node managers.
|
||||
var i = handle.Index;
|
||||
var fullRef = ResolveFullRef(handle);
|
||||
if (fullRef is null)
|
||||
{
|
||||
WriteNodeIdUnknown(results, errors, i);
|
||||
continue;
|
||||
}
|
||||
|
||||
try
|
||||
{
|
||||
var driverResult = History.ReadProcessedAsync(
|
||||
fullRef,
|
||||
details.StartTime,
|
||||
details.EndTime,
|
||||
interval,
|
||||
aggregate.Value,
|
||||
CancellationToken.None).GetAwaiter().GetResult();
|
||||
|
||||
WriteResult(results, errors, i, StatusCodes.Good,
|
||||
BuildHistoryData(driverResult.Samples), driverResult.ContinuationPoint);
|
||||
}
|
||||
catch (NotSupportedException)
|
||||
{
|
||||
WriteUnsupported(results, errors, i);
|
||||
}
|
||||
catch (Exception ex)
|
||||
{
|
||||
_logger.LogWarning(ex, "HistoryReadProcessed failed for {FullRef}", fullRef);
|
||||
WriteInternalError(results, errors, i);
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
protected override void HistoryReadAtTime(
|
||||
ServerSystemContext context, ReadAtTimeDetails details, TimestampsToReturn timestamps,
|
||||
IList<HistoryReadValueId> nodesToRead, IList<OpcHistoryReadResult> results,
|
||||
IList<ServiceResult> errors, List<NodeHandle> nodesToProcess,
|
||||
IDictionary<NodeId, NodeState> cache)
|
||||
{
|
||||
if (History is null)
|
||||
{
|
||||
MarkAllUnsupported(nodesToProcess, results, errors);
|
||||
return;
|
||||
}
|
||||
|
||||
var requestedTimes = (IReadOnlyList<DateTime>)(details.ReqTimes?.ToArray() ?? Array.Empty<DateTime>());
|
||||
for (var n = 0; n < nodesToProcess.Count; n++)
|
||||
{
|
||||
var handle = nodesToProcess[n];
|
||||
// NodeHandle.Index points back to the slot in the outer results/errors/nodesToRead
|
||||
// arrays. nodesToProcess is the filtered subset (just the nodes this manager
|
||||
// claimed), so writing to results[n] lands in the wrong slot when N > 1 and nodes
|
||||
// are interleaved across multiple node managers.
|
||||
var i = handle.Index;
|
||||
var fullRef = ResolveFullRef(handle);
|
||||
if (fullRef is null)
|
||||
{
|
||||
WriteNodeIdUnknown(results, errors, i);
|
||||
continue;
|
||||
}
|
||||
|
||||
try
|
||||
{
|
||||
var driverResult = History.ReadAtTimeAsync(
|
||||
fullRef, requestedTimes, CancellationToken.None).GetAwaiter().GetResult();
|
||||
|
||||
WriteResult(results, errors, i, StatusCodes.Good,
|
||||
BuildHistoryData(driverResult.Samples), driverResult.ContinuationPoint);
|
||||
}
|
||||
catch (NotSupportedException)
|
||||
{
|
||||
WriteUnsupported(results, errors, i);
|
||||
}
|
||||
catch (Exception ex)
|
||||
{
|
||||
_logger.LogWarning(ex, "HistoryReadAtTime failed for {FullRef}", fullRef);
|
||||
WriteInternalError(results, errors, i);
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
protected override void HistoryReadEvents(
|
||||
ServerSystemContext context, ReadEventDetails details, TimestampsToReturn timestamps,
|
||||
IList<HistoryReadValueId> nodesToRead, IList<OpcHistoryReadResult> results,
|
||||
IList<ServiceResult> errors, List<NodeHandle> nodesToProcess,
|
||||
IDictionary<NodeId, NodeState> cache)
|
||||
{
|
||||
if (History is null)
|
||||
{
|
||||
MarkAllUnsupported(nodesToProcess, results, errors);
|
||||
return;
|
||||
}
|
||||
|
||||
// SourceName filter extraction is deferred — EventFilter SelectClauses + WhereClause
|
||||
// handling is a dedicated concern (proper per-select-clause Variant population + where
|
||||
// filter evaluation). This PR treats the event query as "all events in range for the
|
||||
// node's source" and populates only the standard BaseEventType fields. Richer filter
|
||||
// handling is a follow-up; clients issuing empty/default filters get the right answer
|
||||
// today which covers the common alarm-history browse case.
|
||||
var maxEvents = (int)details.NumValuesPerNode;
|
||||
if (maxEvents <= 0) maxEvents = 1000;
|
||||
|
||||
for (var n = 0; n < nodesToProcess.Count; n++)
|
||||
{
|
||||
var handle = nodesToProcess[n];
|
||||
// NodeHandle.Index points back to the slot in the outer results/errors/nodesToRead
|
||||
// arrays. nodesToProcess is the filtered subset (just the nodes this manager
|
||||
// claimed), so writing to results[n] lands in the wrong slot when N > 1 and nodes
|
||||
// are interleaved across multiple node managers.
|
||||
var i = handle.Index;
|
||||
// Event history queries may target a notifier object (e.g. the driver-root folder)
|
||||
// rather than a specific variable — in that case we pass sourceName=null to mean
|
||||
// "all sources in the driver's namespace" per the IHistoryProvider contract.
|
||||
var fullRef = ResolveFullRef(handle);
|
||||
|
||||
try
|
||||
{
|
||||
var driverResult = History.ReadEventsAsync(
|
||||
sourceName: fullRef,
|
||||
startUtc: details.StartTime,
|
||||
endUtc: details.EndTime,
|
||||
maxEvents: maxEvents,
|
||||
cancellationToken: CancellationToken.None).GetAwaiter().GetResult();
|
||||
|
||||
WriteResult(results, errors, i, StatusCodes.Good,
|
||||
BuildHistoryEvent(driverResult.Events), driverResult.ContinuationPoint);
|
||||
}
|
||||
catch (NotSupportedException)
|
||||
{
|
||||
WriteUnsupported(results, errors, i);
|
||||
}
|
||||
catch (Exception ex)
|
||||
{
|
||||
_logger.LogWarning(ex, "HistoryReadEvents failed for {FullRef}", fullRef);
|
||||
WriteInternalError(results, errors, i);
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
private string? ResolveFullRef(NodeHandle handle) => handle.NodeId?.Identifier as string;
|
||||
|
||||
// Both the results list AND the parallel errors list must be populated — MasterNodeManager
|
||||
// merges them and the merged StatusCode is what the client sees. Leaving errors[i] at its
|
||||
// default (BadHistoryOperationUnsupported) overrides a Good result with Unsupported, which
|
||||
// masks a correctly-constructed HistoryData response. This was the subtle failure mode
|
||||
// that cost most of PR 38's debugging budget.
|
||||
private static void WriteResult(IList<OpcHistoryReadResult> results, IList<ServiceResult> errors,
|
||||
int i, uint statusCode, ExtensionObject historyData, byte[]? continuationPoint)
|
||||
{
|
||||
results[i] = new OpcHistoryReadResult
|
||||
{
|
||||
StatusCode = statusCode,
|
||||
HistoryData = historyData,
|
||||
ContinuationPoint = continuationPoint,
|
||||
};
|
||||
errors[i] = statusCode == StatusCodes.Good
|
||||
? ServiceResult.Good
|
||||
: new ServiceResult(statusCode);
|
||||
}
|
||||
|
||||
private static void WriteUnsupported(IList<OpcHistoryReadResult> results, IList<ServiceResult> errors, int i)
|
||||
{
|
||||
results[i] = new OpcHistoryReadResult { StatusCode = StatusCodes.BadHistoryOperationUnsupported };
|
||||
errors[i] = StatusCodes.BadHistoryOperationUnsupported;
|
||||
}
|
||||
|
||||
private static void WriteInternalError(IList<OpcHistoryReadResult> results, IList<ServiceResult> errors, int i)
|
||||
{
|
||||
results[i] = new OpcHistoryReadResult { StatusCode = StatusCodes.BadInternalError };
|
||||
errors[i] = StatusCodes.BadInternalError;
|
||||
}
|
||||
|
||||
private static void WriteNodeIdUnknown(IList<OpcHistoryReadResult> results, IList<ServiceResult> errors, int i)
|
||||
{
|
||||
WriteNodeIdUnknown(results, errors, i);
|
||||
errors[i] = StatusCodes.BadNodeIdUnknown;
|
||||
}
|
||||
|
||||
private static void MarkAllUnsupported(
|
||||
List<NodeHandle> nodes, IList<OpcHistoryReadResult> results, IList<ServiceResult> errors,
|
||||
uint statusCode = StatusCodes.BadHistoryOperationUnsupported)
|
||||
{
|
||||
foreach (var handle in nodes)
|
||||
{
|
||||
results[handle.Index] = new OpcHistoryReadResult { StatusCode = statusCode };
|
||||
errors[handle.Index] = statusCode == StatusCodes.Good ? ServiceResult.Good : new ServiceResult(statusCode);
|
||||
}
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Map the OPC UA Part 13 aggregate-function NodeId to the driver's
|
||||
/// <see cref="HistoryAggregateType"/>. Internal so the test suite can pin the mapping
|
||||
/// without exposing public API. Returns null for unsupported aggregates so the service
|
||||
/// handler can surface <c>BadAggregateNotSupported</c> on the whole batch.
|
||||
/// </summary>
|
||||
internal static HistoryAggregateType? MapAggregate(NodeId? aggregateNodeId)
|
||||
{
|
||||
if (aggregateNodeId is null) return null;
|
||||
|
||||
// Every AggregateFunction_* identifier is a numeric uint on the Server (0) namespace.
|
||||
// Comparing NodeIds by value handles all the cross-encoding cases (expanded vs plain).
|
||||
if (aggregateNodeId == ObjectIds.AggregateFunction_Average) return HistoryAggregateType.Average;
|
||||
if (aggregateNodeId == ObjectIds.AggregateFunction_Minimum) return HistoryAggregateType.Minimum;
|
||||
if (aggregateNodeId == ObjectIds.AggregateFunction_Maximum) return HistoryAggregateType.Maximum;
|
||||
if (aggregateNodeId == ObjectIds.AggregateFunction_Total) return HistoryAggregateType.Total;
|
||||
if (aggregateNodeId == ObjectIds.AggregateFunction_Count) return HistoryAggregateType.Count;
|
||||
return null;
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Wrap driver samples as <c>HistoryData</c> in an <c>ExtensionObject</c> — the on-wire
|
||||
/// shape the OPC UA HistoryRead service expects for raw / processed / at-time reads.
|
||||
/// </summary>
|
||||
internal static ExtensionObject BuildHistoryData(IReadOnlyList<DataValueSnapshot> samples)
|
||||
{
|
||||
var values = new DataValueCollection(samples.Count);
|
||||
foreach (var s in samples) values.Add(ToDataValue(s));
|
||||
return new ExtensionObject(new HistoryData { DataValues = values });
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Wrap driver events as <c>HistoryEvent</c> in an <c>ExtensionObject</c>. Populates
|
||||
/// the minimum BaseEventType field set (SourceName, Message, Severity, Time,
|
||||
/// ReceiveTime, EventId) so clients that request the default
|
||||
/// <c>SimpleAttributeOperand</c> select-clauses see useful data. Custom EventFilter
|
||||
/// SelectClause evaluation is deferred — when a client sends a specific operand list,
|
||||
/// they currently get the standard fields back and ignore the extras. Documented on the
|
||||
/// public follow-up list.
|
||||
/// </summary>
|
||||
internal static ExtensionObject BuildHistoryEvent(IReadOnlyList<HistoricalEvent> events)
|
||||
{
|
||||
var fieldLists = new HistoryEventFieldListCollection(events.Count);
|
||||
foreach (var e in events)
|
||||
{
|
||||
var fields = new VariantCollection
|
||||
{
|
||||
// Order must match BaseEventType's conventional field ordering so clients that
|
||||
// didn't customize the SelectClauses still see recognizable columns. A future
|
||||
// PR that respects the client's SelectClause list will drive this from the filter.
|
||||
new Variant(e.EventId),
|
||||
new Variant(e.SourceName ?? string.Empty),
|
||||
new Variant(new LocalizedText(e.Message ?? string.Empty)),
|
||||
new Variant(e.Severity),
|
||||
new Variant(e.EventTimeUtc),
|
||||
new Variant(e.ReceivedTimeUtc),
|
||||
};
|
||||
fieldLists.Add(new HistoryEventFieldList { EventFields = fields });
|
||||
}
|
||||
return new ExtensionObject(new HistoryEvent { Events = fieldLists });
|
||||
}
|
||||
|
||||
internal static DataValue ToDataValue(DataValueSnapshot s)
|
||||
{
|
||||
var dv = new DataValue
|
||||
{
|
||||
Value = s.Value,
|
||||
StatusCode = new StatusCode(s.StatusCode),
|
||||
ServerTimestamp = s.ServerTimestampUtc,
|
||||
};
|
||||
if (s.SourceTimestampUtc.HasValue) dv.SourceTimestamp = s.SourceTimestampUtc.Value;
|
||||
return dv;
|
||||
}
|
||||
}
|
||||
|
||||
@@ -1,3 +1,6 @@
|
||||
using System.Runtime.InteropServices;
|
||||
using System.Runtime.Versioning;
|
||||
using System.Security.Principal;
|
||||
using System.Threading;
|
||||
using System.Threading.Tasks;
|
||||
using Xunit;
|
||||
@@ -40,6 +43,25 @@ public sealed class LiveStackFixture : IAsyncLifetime
|
||||
|
||||
public async ValueTask InitializeAsync()
|
||||
{
|
||||
// 0. Elevated-shell short-circuit. The OtOpcUaGalaxyHost pipe ACL allows the configured
|
||||
// SID but explicitly DENIES Administrators (decision #76 — production hardening).
|
||||
// A test process running with a high-integrity token (any elevated shell) carries the
|
||||
// Admins group in its security context, so the deny rule trumps the user's allow and
|
||||
// the pipe connect returns UnauthorizedAccessException — technically correct but
|
||||
// the operationally confusing failure mode that ate most of the PR 37 install
|
||||
// debugging session. Surfacing it explicitly here saves the next operator the same
|
||||
// five-step diagnosis. ParityFixture has the same skip with the same rationale.
|
||||
if (IsElevatedAdministratorOnWindows())
|
||||
{
|
||||
SkipReason =
|
||||
"Test host is running with elevated (Administrators) privileges, but the " +
|
||||
"OtOpcUaGalaxyHost named-pipe ACL explicitly denies Administrators per the IPC " +
|
||||
"security design (decision #76 / PipeAcl.cs). Re-run from a NORMAL (non-admin) " +
|
||||
"PowerShell window — even when your user is already in the pipe's allow list, " +
|
||||
"the elevated token's Admins group membership trumps the allow rule.";
|
||||
return;
|
||||
}
|
||||
|
||||
// 1. AVEVA + OtOpcUa service state — actionable diagnostic if anything is missing.
|
||||
using var cts = new CancellationTokenSource(TimeSpan.FromSeconds(10));
|
||||
PrerequisiteReport = await AvevaPrerequisites.CheckAllAsync(
|
||||
@@ -111,6 +133,28 @@ public sealed class LiveStackFixture : IAsyncLifetime
|
||||
{
|
||||
if (SkipReason is not null) Assert.Skip(SkipReason);
|
||||
}
|
||||
|
||||
private static bool IsElevatedAdministratorOnWindows()
|
||||
{
|
||||
if (!RuntimeInformation.IsOSPlatform(OSPlatform.Windows)) return false;
|
||||
return CheckWindowsAdminToken();
|
||||
}
|
||||
|
||||
[SupportedOSPlatform("windows")]
|
||||
private static bool CheckWindowsAdminToken()
|
||||
{
|
||||
try
|
||||
{
|
||||
using var identity = WindowsIdentity.GetCurrent();
|
||||
return new WindowsPrincipal(identity).IsInRole(WindowsBuiltInRole.Administrator);
|
||||
}
|
||||
catch
|
||||
{
|
||||
// Probe shouldn't crash the test; if we can't determine elevation, optimistically
|
||||
// continue and let the actual pipe connect surface its own error.
|
||||
return false;
|
||||
}
|
||||
}
|
||||
}
|
||||
|
||||
[CollectionDefinition(Name)]
|
||||
|
||||
@@ -117,6 +117,141 @@ public sealed class LiveStackSmokeTests(LiveStackFixture fixture)
|
||||
$"Investigate: the Host service's logs at {System.Environment.GetFolderPath(System.Environment.SpecialFolder.CommonApplicationData)}\\OtOpcUa\\Galaxy\\logs.");
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task Write_then_read_roundtrips_a_writable_Boolean_attribute_on_TestMachine_001()
|
||||
{
|
||||
// PR 40 — finishes LMX #5. Targets DelmiaReceiver_001.TestAttribute, the writable
|
||||
// Boolean attribute on the TestMachine_001 hierarchy that the dev Galaxy was deployed
|
||||
// with for exactly this kind of integration testing. We invert the current value and
|
||||
// assert the new value comes back, then restore the original so the test is effectively
|
||||
// idempotent (Galaxy holds the value across runs since it's a deployed UDA).
|
||||
fixture.SkipIfUnavailable();
|
||||
const string fullRef = "DelmiaReceiver_001.TestAttribute";
|
||||
using var cts = new CancellationTokenSource(TimeSpan.FromSeconds(30));
|
||||
|
||||
// Read current value first — gives the cleanup path the right baseline. Galaxy may
|
||||
// return Uncertain quality until the Engine has scanned the attribute at least once;
|
||||
// we don't read into a strongly-typed bool until Status is Good.
|
||||
var before = (await fixture.Driver!.ReadAsync([fullRef], cts.Token))[0];
|
||||
before.StatusCode.ShouldNotBe(0x80020000u, $"baseline read failed for {fullRef}: {before.Value}");
|
||||
var originalBool = Convert.ToBoolean(before.Value ?? false);
|
||||
var inverted = !originalBool;
|
||||
|
||||
try
|
||||
{
|
||||
// Write the inverted value via IWritable.
|
||||
var writeResults = await fixture.Driver!.WriteAsync(
|
||||
[new(fullRef, inverted)], cts.Token);
|
||||
writeResults.Count.ShouldBe(1);
|
||||
writeResults[0].StatusCode.ShouldBe(0u,
|
||||
$"WriteAsync returned status 0x{writeResults[0].StatusCode:X8} for {fullRef} — " +
|
||||
$"check the Host service log at %ProgramData%\\OtOpcUa\\Galaxy\\.");
|
||||
|
||||
// The Engine's scan + acknowledgement is async — read in a short loop with a 5s
|
||||
// budget. Galaxy's attribute roundtrip on a dev box is typically sub-second but
|
||||
// we give headroom for first-scan after a service restart.
|
||||
DataValueSnapshot after = default!;
|
||||
var deadline = DateTime.UtcNow.AddSeconds(5);
|
||||
while (DateTime.UtcNow < deadline)
|
||||
{
|
||||
after = (await fixture.Driver!.ReadAsync([fullRef], cts.Token))[0];
|
||||
if (after.StatusCode == 0u && Convert.ToBoolean(after.Value ?? false) == inverted) break;
|
||||
await Task.Delay(200, cts.Token);
|
||||
}
|
||||
after.StatusCode.ShouldBe(0u, "post-write read failed");
|
||||
Convert.ToBoolean(after.Value ?? false).ShouldBe(inverted,
|
||||
$"Wrote {inverted} but Galaxy returned {after.Value} after the scan window.");
|
||||
}
|
||||
finally
|
||||
{
|
||||
// Restore — best-effort. If this throws the test still reports its primary result;
|
||||
// we just leave a flipped TestAttribute on the dev box (benign, name says it all).
|
||||
try { await fixture.Driver!.WriteAsync([new(fullRef, originalBool)], cts.Token); }
|
||||
catch { /* swallow */ }
|
||||
}
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task Subscribe_fires_OnDataChange_with_initial_value_then_again_after_a_write()
|
||||
{
|
||||
// Subscribe + write is the canonical "is the data path actually live" test for
|
||||
// an OPC UA driver. We subscribe to the same Boolean attribute, expect an initial-
|
||||
// value callback within a couple of seconds (per ISubscribable's contract — the
|
||||
// driver MAY fire OnDataChange immediately with the current value), then write a
|
||||
// distinct value and expect a second callback carrying the new value.
|
||||
fixture.SkipIfUnavailable();
|
||||
const string fullRef = "DelmiaReceiver_001.TestAttribute";
|
||||
using var cts = new CancellationTokenSource(TimeSpan.FromSeconds(30));
|
||||
|
||||
// Capture every OnDataChange notification for this fullRef onto a thread-safe queue
|
||||
// we can poll from the test thread. Galaxy's MXAccess advisory fires on its own
|
||||
// thread; we don't want to block it.
|
||||
var notifications = new System.Collections.Concurrent.ConcurrentQueue<DataValueSnapshot>();
|
||||
void Handler(object? sender, DataChangeEventArgs e)
|
||||
{
|
||||
if (string.Equals(e.FullReference, fullRef, StringComparison.OrdinalIgnoreCase))
|
||||
notifications.Enqueue(e.Snapshot);
|
||||
}
|
||||
fixture.Driver!.OnDataChange += Handler;
|
||||
|
||||
// Read current value so we know which value to write to force a transition.
|
||||
var before = (await fixture.Driver!.ReadAsync([fullRef], cts.Token))[0];
|
||||
var originalBool = Convert.ToBoolean(before.Value ?? false);
|
||||
var toWrite = !originalBool;
|
||||
|
||||
ISubscriptionHandle? handle = null;
|
||||
try
|
||||
{
|
||||
handle = await fixture.Driver!.SubscribeAsync(
|
||||
[fullRef], TimeSpan.FromMilliseconds(250), cts.Token);
|
||||
|
||||
// Wait for initial-value notification — typical < 1s on a hot Galaxy, give 5s.
|
||||
await WaitForAsync(() => notifications.Count >= 1, TimeSpan.FromSeconds(5), cts.Token);
|
||||
notifications.Count.ShouldBeGreaterThanOrEqualTo(1,
|
||||
$"No initial-value OnDataChange for {fullRef} within 5s. " +
|
||||
$"Either MXAccess subscription failed silently or the Engine hasn't scanned yet.");
|
||||
|
||||
// Drain the initial-value queue before writing so we count post-write deltas only.
|
||||
var initialCount = notifications.Count;
|
||||
|
||||
// Write the toggled value. Engine scan + advisory fires the second callback.
|
||||
var w = await fixture.Driver!.WriteAsync([new(fullRef, toWrite)], cts.Token);
|
||||
w[0].StatusCode.ShouldBe(0u);
|
||||
|
||||
await WaitForAsync(() => notifications.Count > initialCount, TimeSpan.FromSeconds(8), cts.Token);
|
||||
notifications.Count.ShouldBeGreaterThan(initialCount,
|
||||
$"OnDataChange did not fire after writing {toWrite} to {fullRef} within 8s.");
|
||||
|
||||
// Find the post-write notification carrying the toggled value (initial value may
|
||||
// appear multiple times before the write commits — search the tail).
|
||||
var postWrite = notifications.ToArray().Reverse()
|
||||
.FirstOrDefault(n => n.StatusCode == 0u && Convert.ToBoolean(n.Value ?? false) == toWrite);
|
||||
postWrite.ShouldNotBe(default,
|
||||
$"No OnDataChange carrying the toggled value {toWrite} appeared in the queue: " +
|
||||
string.Join(",", notifications.Select(n => $"{n.Value}@{n.StatusCode:X8}")));
|
||||
}
|
||||
finally
|
||||
{
|
||||
fixture.Driver!.OnDataChange -= Handler;
|
||||
if (handle is not null)
|
||||
{
|
||||
try { await fixture.Driver!.UnsubscribeAsync(handle, cts.Token); } catch { /* swallow */ }
|
||||
}
|
||||
// Restore baseline.
|
||||
try { await fixture.Driver!.WriteAsync([new(fullRef, originalBool)], cts.Token); } catch { /* swallow */ }
|
||||
}
|
||||
}
|
||||
|
||||
private static async Task WaitForAsync(Func<bool> predicate, TimeSpan budget, CancellationToken ct)
|
||||
{
|
||||
var deadline = DateTime.UtcNow + budget;
|
||||
while (DateTime.UtcNow < deadline)
|
||||
{
|
||||
if (predicate()) return;
|
||||
await Task.Delay(100, ct);
|
||||
}
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Minimal <see cref="IAddressSpaceBuilder"/> implementation that captures every
|
||||
/// Variable() call into a flat list so tests can inspect what discovery produced
|
||||
|
||||
@@ -1,26 +1,30 @@
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.DL205;
|
||||
|
||||
/// <summary>
|
||||
/// Tag map for the AutomationDirect DL205 device class. Mirrors what the ModbusPal
|
||||
/// <c>.xmpp</c> profile in <c>ModbusPal/DL205.xmpp</c> exposes (or the real PLC, when
|
||||
/// Tag map for the AutomationDirect DL205 device class. Mirrors what the pymodbus
|
||||
/// <c>dl205.json</c> profile in <c>Pymodbus/dl205.json</c> exposes (or the real PLC, when
|
||||
/// <see cref="ModbusSimulatorFixture"/> is pointed at one).
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// This is the scaffold — each tag is deliberately generic so the smoke test has stable
|
||||
/// addresses to read. Device-specific quirk tests (word order, max-register, register-zero
|
||||
/// access, etc.) will land in their own test classes alongside this profile as the user
|
||||
/// validates each behavior in ModbusPal; see <c>docs/v2/modbus-test-plan.md</c> §per-device
|
||||
/// validates each behavior in pymodbus; see <c>docs/v2/modbus-test-plan.md</c> §per-device
|
||||
/// quirk catalog for the checklist.
|
||||
/// </remarks>
|
||||
public static class DL205Profile
|
||||
{
|
||||
/// <summary>Holding register the smoke test reads. Address 100 sidesteps the DL205
|
||||
/// register-zero quirk (pending confirmation) — see modbus-test-plan.md.</summary>
|
||||
public const ushort SmokeHoldingRegister = 100;
|
||||
/// <summary>
|
||||
/// Holding register the smoke test writes + reads. Address 200 is the first cell of the
|
||||
/// scratch HR range in both <c>Pymodbus/standard.json</c> (HR[200..209] = 0) and
|
||||
/// <c>Pymodbus/dl205.json</c> (HR[4096..4103] added in PR 43 for the same purpose), so
|
||||
/// the smoke test runs identically against either simulator profile. Originally
|
||||
/// targeted HR[100] — moved to HR[200] when the standard profile claimed HR[100] as
|
||||
/// the auto-incrementing register that drives subscribe-and-receive tests.
|
||||
/// </summary>
|
||||
public const ushort SmokeHoldingRegister = 200;
|
||||
|
||||
/// <summary>Expected value the ModbusPal profile seeds into register 100. When running
|
||||
/// against a real DL205 (or a ModbusPal profile where this register is writable), the smoke
|
||||
/// test seeds this value first, then reads it back.</summary>
|
||||
/// <summary>Value the smoke test writes then reads back to assert round-trip integrity.</summary>
|
||||
public const short SmokeHoldingValue = 1234;
|
||||
|
||||
public static ModbusDriverOptions BuildOptions(string host, int port) => new()
|
||||
@@ -32,7 +36,7 @@ public static class DL205Profile
|
||||
Tags =
|
||||
[
|
||||
new ModbusTagDefinition(
|
||||
Name: "DL205_Smoke_HReg100",
|
||||
Name: "Smoke_HReg200",
|
||||
Region: ModbusRegion.HoldingRegisters,
|
||||
Address: SmokeHoldingRegister,
|
||||
DataType: ModbusDataType.Int16,
|
||||
|
||||
@@ -38,13 +38,13 @@ public sealed class DL205SmokeTests(ModbusSimulatorFixture sim)
|
||||
// zeroed at simulator start, and tests must not depend on prior-test state per the
|
||||
// test-plan conventions.
|
||||
var writeResults = await driver.WriteAsync(
|
||||
[new(FullReference: "DL205_Smoke_HReg100", Value: (short)DL205Profile.SmokeHoldingValue)],
|
||||
[new(FullReference: "Smoke_HReg200", Value: (short)DL205Profile.SmokeHoldingValue)],
|
||||
TestContext.Current.CancellationToken);
|
||||
writeResults.Count.ShouldBe(1);
|
||||
writeResults[0].StatusCode.ShouldBe(0u, "write must succeed against the ModbusPal DL205 profile");
|
||||
|
||||
var readResults = await driver.ReadAsync(
|
||||
["DL205_Smoke_HReg100"],
|
||||
["Smoke_HReg200"],
|
||||
TestContext.Current.CancellationToken);
|
||||
readResults.Count.ShouldBe(1);
|
||||
readResults[0].StatusCode.ShouldBe(0u);
|
||||
|
||||
@@ -0,0 +1,81 @@
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.DL205;
|
||||
|
||||
/// <summary>
|
||||
/// Verifies the DL205/DL260 low-byte-first ASCII string packing quirk against the
|
||||
/// <c>dl205.json</c> pymodbus profile. Standard Modbus packs the first char of each pair
|
||||
/// in the high byte of the register; DirectLOGIC packs it in the low byte instead. Without
|
||||
/// <see cref="ModbusStringByteOrder.LowByteFirst"/> the driver decodes "eHllo" garbage
|
||||
/// even though the bytes on the wire are identical.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// <para>
|
||||
/// Requires the dl205 profile (<c>Pymodbus\serve.ps1 -Profile dl205</c>). The standard
|
||||
/// profile does not seed HR[1040..1042] with string bytes, so running this against the
|
||||
/// standard profile returns <c>"\0\0\0\0\0"</c> and the test fails. Skip when the env
|
||||
/// var <c>MODBUS_SIM_PROFILE</c> is not set to <c>dl205</c>.
|
||||
/// </para>
|
||||
/// </remarks>
|
||||
[Collection(ModbusSimulatorCollection.Name)]
|
||||
[Trait("Category", "Integration")]
|
||||
[Trait("Device", "DL205")]
|
||||
public sealed class DL205StringQuirkTests(ModbusSimulatorFixture sim)
|
||||
{
|
||||
[Fact]
|
||||
public async Task DL205_string_low_byte_first_decodes_Hello_from_HR1040()
|
||||
{
|
||||
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
||||
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "dl205",
|
||||
StringComparison.OrdinalIgnoreCase))
|
||||
{
|
||||
Assert.Skip("MODBUS_SIM_PROFILE != dl205 — skipping (standard profile does not seed HR[1040..1042]).");
|
||||
}
|
||||
|
||||
var options = new ModbusDriverOptions
|
||||
{
|
||||
Host = sim.Host,
|
||||
Port = sim.Port,
|
||||
UnitId = 1,
|
||||
Timeout = TimeSpan.FromSeconds(2),
|
||||
Tags =
|
||||
[
|
||||
new ModbusTagDefinition(
|
||||
Name: "DL205_Hello_Low",
|
||||
Region: ModbusRegion.HoldingRegisters,
|
||||
Address: 1040,
|
||||
DataType: ModbusDataType.String,
|
||||
Writable: false,
|
||||
StringLength: 5,
|
||||
StringByteOrder: ModbusStringByteOrder.LowByteFirst),
|
||||
// Control: same address, HighByteFirst, to prove the driver would have decoded
|
||||
// garbage without the quirk flag.
|
||||
new ModbusTagDefinition(
|
||||
Name: "DL205_Hello_High",
|
||||
Region: ModbusRegion.HoldingRegisters,
|
||||
Address: 1040,
|
||||
DataType: ModbusDataType.String,
|
||||
Writable: false,
|
||||
StringLength: 5,
|
||||
StringByteOrder: ModbusStringByteOrder.HighByteFirst),
|
||||
],
|
||||
Probe = new ModbusProbeOptions { Enabled = false },
|
||||
};
|
||||
await using var driver = new ModbusDriver(options, driverInstanceId: "dl205-string");
|
||||
await driver.InitializeAsync(driverConfigJson: "{}", TestContext.Current.CancellationToken);
|
||||
|
||||
var results = await driver.ReadAsync(["DL205_Hello_Low", "DL205_Hello_High"],
|
||||
TestContext.Current.CancellationToken);
|
||||
|
||||
results.Count.ShouldBe(2);
|
||||
results[0].StatusCode.ShouldBe(0u);
|
||||
results[0].Value.ShouldBe("Hello", "DL205 low-byte-first ordering must produce 'Hello' from HR[1040..1042]");
|
||||
|
||||
// The high-byte-first read of the same wire bytes should differ — not asserting the
|
||||
// exact garbage string (that would couple the test to the ASCII byte math) but the two
|
||||
// decodes MUST disagree, otherwise the quirk flag is a no-op.
|
||||
results[1].StatusCode.ShouldBe(0u);
|
||||
results[1].Value.ShouldNotBe("Hello");
|
||||
}
|
||||
}
|
||||
@@ -1,30 +0,0 @@
|
||||
# ModbusPal simulator profiles
|
||||
|
||||
Drop device-specific `.xmpp` profiles here. The integration tests connect to the
|
||||
endpoint in `MODBUS_SIM_ENDPOINT` (default `localhost:502`) and expect the
|
||||
simulator to already be running — tests do not launch ModbusPal themselves,
|
||||
because its Java GUI + JRE requirement is heavier than the harness is worth.
|
||||
|
||||
## Getting started
|
||||
|
||||
1. Download ModbusPal from SourceForge (`modbuspal.jar`).
|
||||
2. `java -jar modbuspal.jar` to launch the GUI.
|
||||
3. Load a profile from this directory (or configure one manually) and start the
|
||||
simulator on TCP port 502.
|
||||
4. `dotnet test tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests` — tests
|
||||
auto-skip with a clear `SkipReason` if the TCP probe at the configured
|
||||
endpoint fails within 2 seconds.
|
||||
|
||||
## Profile files
|
||||
|
||||
- `DL205.xmpp` — _to be added_ — register map reflecting the AutomationDirect
|
||||
DL205 quirks tracked in `docs/v2/modbus-test-plan.md`. The scaffolded smoke
|
||||
test in `DL205/DL205SmokeTests.cs` needs holding register 100 writable and
|
||||
present; a minimal ModbusPal profile with a single holding-register bank at
|
||||
address 100 is sufficient.
|
||||
|
||||
## Environment variables
|
||||
|
||||
- `MODBUS_SIM_ENDPOINT` — override the simulator endpoint. Accepts `host:port`;
|
||||
defaults to `localhost:502`. Useful when pointing the suite at a real PLC on
|
||||
the bench.
|
||||
@@ -3,8 +3,9 @@ using System.Net.Sockets;
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests;
|
||||
|
||||
/// <summary>
|
||||
/// Reachability probe for a Modbus TCP simulator (ModbusPal or a real PLC). Parses
|
||||
/// <c>MODBUS_SIM_ENDPOINT</c> (default <c>localhost:502</c>) and TCP-connects once at
|
||||
/// Reachability probe for a Modbus TCP simulator (pymodbus-driven, see
|
||||
/// <c>Pymodbus/serve.ps1</c>) or a real PLC. Parses
|
||||
/// <c>MODBUS_SIM_ENDPOINT</c> (default <c>localhost:5020</c> per PR 43) and TCP-connects once at
|
||||
/// fixture construction. Each test checks <see cref="SkipReason"/> and calls
|
||||
/// <c>Assert.Skip</c> when the endpoint was unreachable, so a dev box without a running
|
||||
/// simulator still passes `dotnet test` cleanly — matches the Galaxy live-smoke pattern in
|
||||
@@ -25,7 +26,11 @@ namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests;
|
||||
/// </remarks>
|
||||
public sealed class ModbusSimulatorFixture : IAsyncDisposable
|
||||
{
|
||||
private const string DefaultEndpoint = "localhost:502";
|
||||
// PR 43: default port is 5020 (pymodbus convention) instead of 502 (Modbus standard).
|
||||
// Picking 5020 sidesteps the privileged-port admin requirement on Windows + matches the
|
||||
// port baked into the pymodbus simulator JSON profiles in Pymodbus/. Override with
|
||||
// MODBUS_SIM_ENDPOINT to point at a real PLC on its native port 502.
|
||||
private const string DefaultEndpoint = "localhost:5020";
|
||||
private const string EndpointEnvVar = "MODBUS_SIM_ENDPOINT";
|
||||
|
||||
public string Host { get; }
|
||||
@@ -41,18 +46,30 @@ public sealed class ModbusSimulatorFixture : IAsyncDisposable
|
||||
|
||||
try
|
||||
{
|
||||
using var client = new TcpClient();
|
||||
var task = client.ConnectAsync(Host, Port);
|
||||
// Force IPv4 family on the probe — pymodbus's TCP server binds 0.0.0.0 (IPv4 only)
|
||||
// while .NET's TcpClient default-resolves "localhost" → IPv6 ::1 first, fails to
|
||||
// connect, and only then tries IPv4. Under .NET 10 the IPv6 fail surfaces as a
|
||||
// 2s timeout (no graceful fallback by default), so the C# probe times out even
|
||||
// though a PowerShell probe of the same endpoint succeeds. Resolving + dialing
|
||||
// explicit IPv4 sidesteps the dual-stack ordering.
|
||||
using var client = new TcpClient(System.Net.Sockets.AddressFamily.InterNetwork);
|
||||
var task = client.ConnectAsync(
|
||||
System.Net.Dns.GetHostAddresses(Host)
|
||||
.FirstOrDefault(a => a.AddressFamily == System.Net.Sockets.AddressFamily.InterNetwork)
|
||||
?? System.Net.IPAddress.Loopback,
|
||||
Port);
|
||||
if (!task.Wait(TimeSpan.FromSeconds(2)) || !client.Connected)
|
||||
{
|
||||
SkipReason = $"Modbus simulator at {Host}:{Port} did not accept a TCP connection within 2s. " +
|
||||
$"Start ModbusPal (or override {EndpointEnvVar}) and re-run.";
|
||||
$"Start the pymodbus simulator (Pymodbus\\serve.ps1 -Profile standard) " +
|
||||
$"or override {EndpointEnvVar}, then re-run.";
|
||||
}
|
||||
}
|
||||
catch (Exception ex)
|
||||
{
|
||||
SkipReason = $"Modbus simulator at {Host}:{Port} unreachable: {ex.GetType().Name}: {ex.Message}. " +
|
||||
$"Start ModbusPal (or override {EndpointEnvVar}) and re-run.";
|
||||
$"Start the pymodbus simulator (Pymodbus\\serve.ps1 -Profile standard) " +
|
||||
$"or override {EndpointEnvVar}, then re-run.";
|
||||
}
|
||||
}
|
||||
|
||||
|
||||
@@ -0,0 +1,163 @@
|
||||
# pymodbus simulator profiles
|
||||
|
||||
Two JSON-config profiles for pymodbus's `ModbusSimulatorServer`. Replaces the
|
||||
ModbusPal `.xmpp` profiles that lived here in PR 42 — pymodbus is headless,
|
||||
maintained, semantic about register layout, and pip-installable on Windows.
|
||||
|
||||
| File | What it simulates | Test category |
|
||||
|---|---|---|
|
||||
| [`standard.json`](standard.json) | Generic Modbus TCP server — HR[0..31] = address-as-value, HR[100] declarative auto-increment via `"action": "increment"`, alternating coils, scratch ranges for write tests. | `Trait=Standard` |
|
||||
| [`dl205.json`](dl205.json) | AutomationDirect DirectLOGIC DL205 / DL260 quirks per [`docs/v2/dl205.md`](../../../docs/v2/dl205.md): low-byte-first string packing, CDAB Float32, BCD numerics, V-memory address markers, Y/C coil mappings. Inline `_quirk` comments per register name the behavior. | `Trait=DL205` |
|
||||
|
||||
Both bind TCP **5020** (pymodbus convention; sidesteps the Windows admin
|
||||
requirement for privileged port 502). The integration-test fixture
|
||||
(`ModbusSimulatorFixture`) defaults to `localhost:5020` to match — override
|
||||
via `MODBUS_SIM_ENDPOINT` to point at a real PLC on its native port 502.
|
||||
|
||||
Run only **one profile at a time** (they share TCP 5020).
|
||||
|
||||
## Install
|
||||
|
||||
```powershell
|
||||
pip install "pymodbus[simulator]==3.13.0"
|
||||
```
|
||||
|
||||
The `[simulator]` extra pulls in `aiohttp` for the optional web UI / REST API.
|
||||
Pinned to 3.13.0 for reproducibility — avoid 4.x dev releases until stabilized.
|
||||
Requires Python ≥ 3.10. Windows Firewall will prompt on first bind; allow
|
||||
Private network.
|
||||
|
||||
## Run
|
||||
|
||||
Foreground (Ctrl+C to stop). Use the `serve.ps1` wrapper:
|
||||
|
||||
```powershell
|
||||
.\serve.ps1 -Profile standard
|
||||
.\serve.ps1 -Profile dl205
|
||||
```
|
||||
|
||||
Or invoke pymodbus directly:
|
||||
|
||||
```powershell
|
||||
pymodbus.simulator `
|
||||
--modbus_server srv `
|
||||
--modbus_device dev `
|
||||
--json_file .\standard.json `
|
||||
--http_port 8080
|
||||
```
|
||||
|
||||
Web UI at `http://localhost:8080` lets you inspect + poke registers manually.
|
||||
Pass `--no_http` (or `-HttpPort 0` to `serve.ps1`) to disable.
|
||||
|
||||
## Run the integration tests
|
||||
|
||||
In a separate shell, with the simulator running:
|
||||
|
||||
```powershell
|
||||
cd C:\Users\dohertj2\Desktop\lmxopcua
|
||||
dotnet test tests\ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests
|
||||
```
|
||||
|
||||
Tests auto-skip with a clear `SkipReason` if `localhost:5020` isn't reachable
|
||||
within 2 seconds. Filter by trait when both profiles' tests coexist:
|
||||
|
||||
```powershell
|
||||
dotnet test ... --filter "Trait=Standard"
|
||||
dotnet test ... --filter "Trait=DL205"
|
||||
```
|
||||
|
||||
## What's encoded in each profile
|
||||
|
||||
### standard.json
|
||||
|
||||
- HR[0..31]: each register's value equals its address. Easy mental map.
|
||||
- HR[100]: `"action": "increment"` ticks 0..65535 on every register access — drives subscribe-and-receive tests so they have a register that changes without a write.
|
||||
- HR[200..209]: scratch range for write-roundtrip tests.
|
||||
- Coils[0..31]: alternating on/off (even=on).
|
||||
- Coils[100..109]: scratch.
|
||||
- All addresses 0..1023 are writable (`"write": [[0, 1023]]`).
|
||||
|
||||
### dl205.json (per `docs/v2/dl205.md`)
|
||||
|
||||
| HR address | Quirk demonstrated | Raw value | Decoded |
|
||||
|---|---|---|---|
|
||||
| `0` (V0) | Register 0 is valid (rejects-register-0 rumour disproved) | `51966` (0xCAFE) | marker |
|
||||
| `1024` (V2000 octal) | V-memory octal-to-decimal mapping | `8192` (0x2000) | marker |
|
||||
| `8448` (V40400 octal) | V40400 → PDU 0x2100 (NOT register 0) | `16448` (0x4040) | marker |
|
||||
| `1040..1042` | String "Hello" packed first-char-low-byte | `25928, 27756, 111` | `"Hello"` |
|
||||
| `1056..1057` | Float32 1.5f in CDAB word order | `0, 16320` | `1.5f` |
|
||||
| `1072` | Decimal 1234 in BCD encoding | `4660` (0x1234) | `1234` |
|
||||
| `1280..1407` | 128-register block (FC03 cap = 128 above spec's 125) | first/last/mid markers; rest defaults to 0 | for FC03 cap test |
|
||||
|
||||
| Coil address | Quirk demonstrated |
|
||||
|---|---|
|
||||
| `2048` | Y0 maps to coil 2048 (DL260 layout) |
|
||||
| `3072` | C0 maps to coil 3072 (DL260 layout) |
|
||||
| `4000..4007` | Scratch C-relay range for write-roundtrip tests |
|
||||
|
||||
The DL260 X-input markers (FC02 discrete inputs) **are not encoded separately**
|
||||
because the profile uses `shared blocks: true` (matches DL series memory
|
||||
model) — coils/DI/HR/IR overlay the same word address space. Tests that
|
||||
target FC02 against this profile end up reading the same bit positions as
|
||||
the coils they share with.
|
||||
|
||||
## What's IN pymodbus that wasn't in ModbusPal
|
||||
|
||||
- **All four standard tables** (HR, IR, coils, DI) configurable via `co size` / `di size` / `hr size` / `ir size` setup keys.
|
||||
- **Per-register raw uint16 seeding** — `{"addr": 1040, "value": 25928}` puts exactly that 16-bit value on the wire. No interpretation.
|
||||
- **Built-in actions**: `increment`, `random`, `timestamp`, `reset`, `uptime` for declarative dynamic registers. No Python script alongside the config required.
|
||||
- **Custom actions** — point `--custom_actions_module` at a `.py` file exposing callables to express anything more complex (per-second wall-clock ticks, BCD synthesis, etc.).
|
||||
- **Headless** — pure CLI process, no Java, no Swing. Pip-installable. Plays well with CI runners.
|
||||
- **Web UI / REST API** — `--http_port 8080` adds an aiohttp server for live inspection. Optional.
|
||||
- **Maintained** — current stable 3.13.0 (April 2026), active development on 4.0 dev branch.
|
||||
|
||||
## Trade-offs vs the hand-authored ModbusPal profiles
|
||||
|
||||
- pymodbus's built-in `float32` type stores in pymodbus's word order; for explicit DL205 CDAB control we seed two raw `uint16` entries instead. Documented inline in `dl205.json`.
|
||||
- `increment` action ticks per-access, not wall-clock. A 250ms-poll integration test sees variation either way; for strict 1Hz cadence add `--custom_actions_module my_actions.py` with a `time.time()`-based callable.
|
||||
- `dl205.json` uses `shared blocks: true` because it matches DL series memory model; `standard.json` uses `shared blocks: false` so coils and HR address spaces are independent (more like a textbook PLC).
|
||||
|
||||
## File format reference
|
||||
|
||||
```json
|
||||
{
|
||||
"server_list": {
|
||||
"<server-name>": {
|
||||
"comm": "tcp",
|
||||
"host": "0.0.0.0",
|
||||
"port": 5020,
|
||||
"framer": "socket",
|
||||
"device_id": 1
|
||||
}
|
||||
},
|
||||
"device_list": {
|
||||
"<device-name>": {
|
||||
"setup": {
|
||||
"co size": N, "di size": N, "hr size": N, "ir size": N,
|
||||
"shared blocks": false,
|
||||
"type exception": false,
|
||||
"defaults": { "value": {...}, "action": {...} }
|
||||
},
|
||||
"invalid": [],
|
||||
"write": [[<from>, <to>]],
|
||||
"bits": [{"addr": N, "value": 0|1}],
|
||||
"uint16": [{"addr": N, "value": <0..65535>, "action"?: "increment", "parameters"?: {...}}],
|
||||
"uint32": [{"addr": N, "value": <int>}],
|
||||
"float32": [{"addr": N, "value": <float>}],
|
||||
"string": [{"addr": N, "value": "<text>"}],
|
||||
"repeat": []
|
||||
}
|
||||
}
|
||||
}
|
||||
```
|
||||
|
||||
The CLI args `--modbus_server <server-name> --modbus_device <device-name>`
|
||||
pick which entries the simulator binds.
|
||||
|
||||
## References
|
||||
|
||||
- [pymodbus on PyPI](https://pypi.org/project/pymodbus/) — install, version pin
|
||||
- [Simulator config docs](https://pymodbus.readthedocs.io/en/dev/source/library/simulator/config.html) — full schema reference
|
||||
- [Simulator REST API](https://pymodbus.readthedocs.io/en/latest/source/library/simulator/restapi.html) — for the optional web UI
|
||||
- [`docs/v2/dl205.md`](../../../docs/v2/dl205.md) — what each DL205 profile entry simulates
|
||||
- [`docs/v2/modbus-test-plan.md`](../../../docs/v2/modbus-test-plan.md) — the `DL205_<behavior>` test naming convention
|
||||
@@ -0,0 +1,118 @@
|
||||
{
|
||||
"_comment": "DL205.json — DirectLOGIC DL205/DL260 quirk simulator. Models docs/v2/dl205.md as concrete register values. NOTE: pymodbus rejects unknown keys at device-list / setup level; explanatory comments live at top-level _comment + in README + git. Inline _quirk keys WITHIN individual register entries are accepted by pymodbus 3.13.0 (it only validates addr / value / action / parameters per entry). Each quirky uint16 is a pre-computed raw 16-bit value; pymodbus serves it verbatim. shared blocks=true matches DL series memory model. write list mirrors each seeded block — pymodbus rejects sweeping write ranges that include undefined cells.",
|
||||
|
||||
"server_list": {
|
||||
"srv": {
|
||||
"comm": "tcp",
|
||||
"host": "0.0.0.0",
|
||||
"port": 5020,
|
||||
"framer": "socket",
|
||||
"device_id": 1
|
||||
}
|
||||
},
|
||||
|
||||
"device_list": {
|
||||
"dev": {
|
||||
"setup": {
|
||||
"co size": 16384,
|
||||
"di size": 8192,
|
||||
"hr size": 16384,
|
||||
"ir size": 1024,
|
||||
"shared blocks": true,
|
||||
"type exception": false,
|
||||
"defaults": {
|
||||
"value": {"bits": 0, "uint16": 0, "uint32": 0, "float32": 0.0, "string": " "},
|
||||
"action": {"bits": null, "uint16": null, "uint32": null, "float32": null, "string": null}
|
||||
}
|
||||
},
|
||||
"invalid": [],
|
||||
"write": [
|
||||
[0, 0],
|
||||
[200, 209],
|
||||
[1024, 1024],
|
||||
[1040, 1042],
|
||||
[1056, 1057],
|
||||
[1072, 1072],
|
||||
[1280, 1282],
|
||||
[1343, 1343],
|
||||
[1407, 1407],
|
||||
[2048, 2050],
|
||||
[3072, 3074],
|
||||
[4000, 4007],
|
||||
[8448, 8448]
|
||||
],
|
||||
|
||||
"uint16": [
|
||||
{"_quirk": "V0 marker. HR[0]=0xCAFE proves register 0 is valid on DL205/DL260 (rejects-register-0 was a DL05/DL06 relative-mode artefact). 0xCAFE = 51966.",
|
||||
"addr": 0, "value": 51966},
|
||||
|
||||
{"_quirk": "Scratch HR range 200..209 — mirrors the standard.json scratch range so the smoke test (DL205Profile.SmokeHoldingRegister=200) round-trips identically against either profile.",
|
||||
"addr": 200, "value": 0},
|
||||
{"addr": 201, "value": 0},
|
||||
{"addr": 202, "value": 0},
|
||||
{"addr": 203, "value": 0},
|
||||
{"addr": 204, "value": 0},
|
||||
{"addr": 205, "value": 0},
|
||||
{"addr": 206, "value": 0},
|
||||
{"addr": 207, "value": 0},
|
||||
{"addr": 208, "value": 0},
|
||||
{"addr": 209, "value": 0},
|
||||
|
||||
{"_quirk": "V2000 marker. V2000 octal = decimal 1024 = PDU 0x0400. Marker 0x2000 = 8192.",
|
||||
"addr": 1024, "value": 8192},
|
||||
|
||||
{"_quirk": "V40400 marker. V40400 octal = decimal 8448 = PDU 0x2100 (NOT register 0). Marker 0x4040 = 16448.",
|
||||
"addr": 8448, "value": 16448},
|
||||
|
||||
{"_quirk": "String 'Hello' first char in LOW byte. HR[0x410] = 'H'(0x48) lo + 'e'(0x65) hi = 0x6548 = 25928.",
|
||||
"addr": 1040, "value": 25928},
|
||||
{"_quirk": "String 'Hello' second char-pair: 'l'(0x6C) lo + 'l'(0x6C) hi = 0x6C6C = 27756.",
|
||||
"addr": 1041, "value": 27756},
|
||||
{"_quirk": "String 'Hello' third char-pair: 'o'(0x6F) lo + null(0x00) hi = 0x006F = 111.",
|
||||
"addr": 1042, "value": 111},
|
||||
|
||||
{"_quirk": "Float32 1.5f in CDAB word order. IEEE 754 1.5 = 0x3FC00000. CDAB = low word first: HR[0x420]=0x0000, HR[0x421]=0x3FC0=16320.",
|
||||
"addr": 1056, "value": 0},
|
||||
{"_quirk": "Float32 1.5f CDAB high word.",
|
||||
"addr": 1057, "value": 16320},
|
||||
|
||||
{"_quirk": "BCD register. Decimal 1234 stored as BCD nibbles 0x1234 = 4660. NOT binary 1234 (= 0x04D2).",
|
||||
"addr": 1072, "value": 4660},
|
||||
|
||||
{"_quirk": "FC03 cap test marker — first cell of a 128-register span the FC03 cap test reads. Other cells in the span aren't seeded explicitly, so reads of HR[1283..1342] / 1344..1406 return the default 0; the seeded markers at 1280, 1281, 1282, 1343, 1407 prove the span boundaries.",
|
||||
"addr": 1280, "value": 0},
|
||||
{"addr": 1281, "value": 1},
|
||||
{"addr": 1282, "value": 2},
|
||||
{"addr": 1343, "value": 63},
|
||||
{"addr": 1407, "value": 127}
|
||||
],
|
||||
|
||||
"bits": [
|
||||
{"_quirk": "Y0 marker. DL260 maps Y0 to coil 2048 (0-based). Coil 2048 = ON proves the mapping.",
|
||||
"addr": 2048, "value": 1},
|
||||
{"addr": 2049, "value": 0},
|
||||
{"addr": 2050, "value": 1},
|
||||
|
||||
{"_quirk": "C0 marker. DL260 maps C0 to coil 3072 (0-based). Coil 3072 = ON proves the mapping.",
|
||||
"addr": 3072, "value": 1},
|
||||
{"addr": 3073, "value": 0},
|
||||
{"addr": 3074, "value": 1},
|
||||
|
||||
{"_quirk": "Scratch C-relays for write-roundtrip tests against the writable C range.",
|
||||
"addr": 4000, "value": 0},
|
||||
{"addr": 4001, "value": 0},
|
||||
{"addr": 4002, "value": 0},
|
||||
{"addr": 4003, "value": 0},
|
||||
{"addr": 4004, "value": 0},
|
||||
{"addr": 4005, "value": 0},
|
||||
{"addr": 4006, "value": 0},
|
||||
{"addr": 4007, "value": 0}
|
||||
],
|
||||
|
||||
"uint32": [],
|
||||
"float32": [],
|
||||
"string": [],
|
||||
"repeat": []
|
||||
}
|
||||
}
|
||||
}
|
||||
@@ -0,0 +1,60 @@
|
||||
<#
|
||||
.SYNOPSIS
|
||||
Launches the pymodbus simulator with one of the integration-test profiles
|
||||
(Standard or DL205). Foreground process — Ctrl+C to stop.
|
||||
|
||||
.PARAMETER Profile
|
||||
Which simulator profile to run: 'standard' or 'dl205'. Both bind TCP 5020 by
|
||||
default so they can't run simultaneously on the same box.
|
||||
|
||||
.PARAMETER HttpPort
|
||||
Port for pymodbus's optional web UI / REST API. Default 8080. Pass 0 to
|
||||
disable (passes --no_http).
|
||||
|
||||
.EXAMPLE
|
||||
.\serve.ps1 -Profile standard
|
||||
Starts the standard server on TCP 5020 with web UI on 8080.
|
||||
|
||||
.EXAMPLE
|
||||
.\serve.ps1 -Profile dl205 -HttpPort 0
|
||||
Starts the DL205 server on TCP 5020, no web UI.
|
||||
#>
|
||||
[CmdletBinding()]
|
||||
param(
|
||||
[Parameter(Mandatory)] [ValidateSet('standard', 'dl205')] [string]$Profile,
|
||||
[int]$HttpPort = 8080
|
||||
)
|
||||
|
||||
$ErrorActionPreference = 'Stop'
|
||||
$here = $PSScriptRoot
|
||||
|
||||
# Confirm pymodbus.simulator is on PATH — clearer message than the
|
||||
# 'CommandNotFoundException' dotnet style.
|
||||
$cmd = Get-Command pymodbus.simulator -ErrorAction SilentlyContinue
|
||||
if (-not $cmd) {
|
||||
Write-Error "pymodbus.simulator not found. Install with: pip install 'pymodbus[simulator]==3.13.0'"
|
||||
exit 1
|
||||
}
|
||||
|
||||
$jsonFile = Join-Path $here "$Profile.json"
|
||||
if (-not (Test-Path $jsonFile)) {
|
||||
Write-Error "Profile config not found: $jsonFile"
|
||||
exit 1
|
||||
}
|
||||
|
||||
$args = @(
|
||||
'--modbus_server', 'srv',
|
||||
'--modbus_device', 'dev',
|
||||
'--json_file', $jsonFile
|
||||
)
|
||||
|
||||
if ($HttpPort -gt 0) {
|
||||
$args += @('--http_port', $HttpPort)
|
||||
Write-Host "Web UI will be at http://localhost:$HttpPort"
|
||||
} else {
|
||||
$args += '--no_http'
|
||||
}
|
||||
|
||||
Write-Host "Starting pymodbus simulator: profile=$Profile TCP=localhost:5020"
|
||||
Write-Host "Ctrl+C to stop."
|
||||
& pymodbus.simulator @args
|
||||
@@ -0,0 +1,97 @@
|
||||
{
|
||||
"_comment": "Standard.json — generic Modbus TCP server for the integration suite. See ../README.md. NOTE: pymodbus rejects unknown keys at device-list / setup level; explanatory comments live in the README + git history. Layout: HR[0..31]=address-as-value, HR[100]=auto-increment, HR[200..209]=scratch, coils 1024..1055=alternating, coils 1100..1109=scratch. Coils live at 1024+ because pymodbus stores all 4 standard tables in ONE underlying cell array — bits and uint16 at the same address conflict (each cell can only be typed once).",
|
||||
|
||||
"server_list": {
|
||||
"srv": {
|
||||
"comm": "tcp",
|
||||
"host": "0.0.0.0",
|
||||
"port": 5020,
|
||||
"framer": "socket",
|
||||
"device_id": 1
|
||||
}
|
||||
},
|
||||
|
||||
"device_list": {
|
||||
"dev": {
|
||||
"setup": {
|
||||
"co size": 2048,
|
||||
"di size": 2048,
|
||||
"hr size": 2048,
|
||||
"ir size": 2048,
|
||||
"shared blocks": true,
|
||||
"type exception": false,
|
||||
"defaults": {
|
||||
"value": {"bits": 0, "uint16": 0, "uint32": 0, "float32": 0.0, "string": " "},
|
||||
"action": {"bits": null, "uint16": null, "uint32": null, "float32": null, "string": null}
|
||||
}
|
||||
},
|
||||
"invalid": [],
|
||||
"write": [
|
||||
[0, 31],
|
||||
[100, 100],
|
||||
[200, 209],
|
||||
[1024, 1055],
|
||||
[1100, 1109]
|
||||
],
|
||||
|
||||
"uint16": [
|
||||
{"addr": 0, "value": 0}, {"addr": 1, "value": 1},
|
||||
{"addr": 2, "value": 2}, {"addr": 3, "value": 3},
|
||||
{"addr": 4, "value": 4}, {"addr": 5, "value": 5},
|
||||
{"addr": 6, "value": 6}, {"addr": 7, "value": 7},
|
||||
{"addr": 8, "value": 8}, {"addr": 9, "value": 9},
|
||||
{"addr": 10, "value": 10}, {"addr": 11, "value": 11},
|
||||
{"addr": 12, "value": 12}, {"addr": 13, "value": 13},
|
||||
{"addr": 14, "value": 14}, {"addr": 15, "value": 15},
|
||||
{"addr": 16, "value": 16}, {"addr": 17, "value": 17},
|
||||
{"addr": 18, "value": 18}, {"addr": 19, "value": 19},
|
||||
{"addr": 20, "value": 20}, {"addr": 21, "value": 21},
|
||||
{"addr": 22, "value": 22}, {"addr": 23, "value": 23},
|
||||
{"addr": 24, "value": 24}, {"addr": 25, "value": 25},
|
||||
{"addr": 26, "value": 26}, {"addr": 27, "value": 27},
|
||||
{"addr": 28, "value": 28}, {"addr": 29, "value": 29},
|
||||
{"addr": 30, "value": 30}, {"addr": 31, "value": 31},
|
||||
|
||||
{"addr": 100, "value": 0,
|
||||
"action": "increment",
|
||||
"parameters": {"minval": 0, "maxval": 65535}},
|
||||
|
||||
{"addr": 200, "value": 0}, {"addr": 201, "value": 0},
|
||||
{"addr": 202, "value": 0}, {"addr": 203, "value": 0},
|
||||
{"addr": 204, "value": 0}, {"addr": 205, "value": 0},
|
||||
{"addr": 206, "value": 0}, {"addr": 207, "value": 0},
|
||||
{"addr": 208, "value": 0}, {"addr": 209, "value": 0}
|
||||
],
|
||||
|
||||
"bits": [
|
||||
{"addr": 1024, "value": 1}, {"addr": 1025, "value": 0},
|
||||
{"addr": 1026, "value": 1}, {"addr": 1027, "value": 0},
|
||||
{"addr": 1028, "value": 1}, {"addr": 1029, "value": 0},
|
||||
{"addr": 1030, "value": 1}, {"addr": 1031, "value": 0},
|
||||
{"addr": 1032, "value": 1}, {"addr": 1033, "value": 0},
|
||||
{"addr": 1034, "value": 1}, {"addr": 1035, "value": 0},
|
||||
{"addr": 1036, "value": 1}, {"addr": 1037, "value": 0},
|
||||
{"addr": 1038, "value": 1}, {"addr": 1039, "value": 0},
|
||||
{"addr": 1040, "value": 1}, {"addr": 1041, "value": 0},
|
||||
{"addr": 1042, "value": 1}, {"addr": 1043, "value": 0},
|
||||
{"addr": 1044, "value": 1}, {"addr": 1045, "value": 0},
|
||||
{"addr": 1046, "value": 1}, {"addr": 1047, "value": 0},
|
||||
{"addr": 1048, "value": 1}, {"addr": 1049, "value": 0},
|
||||
{"addr": 1050, "value": 1}, {"addr": 1051, "value": 0},
|
||||
{"addr": 1052, "value": 1}, {"addr": 1053, "value": 0},
|
||||
{"addr": 1054, "value": 1}, {"addr": 1055, "value": 0},
|
||||
|
||||
{"addr": 1100, "value": 0}, {"addr": 1101, "value": 0},
|
||||
{"addr": 1102, "value": 0}, {"addr": 1103, "value": 0},
|
||||
{"addr": 1104, "value": 0}, {"addr": 1105, "value": 0},
|
||||
{"addr": 1106, "value": 0}, {"addr": 1107, "value": 0},
|
||||
{"addr": 1108, "value": 0}, {"addr": 1109, "value": 0}
|
||||
],
|
||||
|
||||
"uint32": [],
|
||||
"float32": [],
|
||||
"string": [],
|
||||
"repeat": []
|
||||
}
|
||||
}
|
||||
}
|
||||
@@ -24,7 +24,7 @@
|
||||
</ItemGroup>
|
||||
|
||||
<ItemGroup>
|
||||
<None Update="ModbusPal\**\*" CopyToOutputDirectory="PreserveNewest"/>
|
||||
<None Update="Pymodbus\**\*" CopyToOutputDirectory="PreserveNewest"/>
|
||||
<None Update="DL205\**\*" CopyToOutputDirectory="PreserveNewest"/>
|
||||
</ItemGroup>
|
||||
|
||||
|
||||
@@ -172,4 +172,51 @@ public sealed class ModbusDataTypeTests
|
||||
wire[1].ShouldBe((byte)'i');
|
||||
for (var i = 2; i < 8; i++) wire[i].ShouldBe((byte)0);
|
||||
}
|
||||
|
||||
// --- DL205 low-byte-first strings (AutomationDirect DirectLOGIC quirk) ---
|
||||
|
||||
[Fact]
|
||||
public void String_LowByteFirst_decodes_DL205_packed_Hello()
|
||||
{
|
||||
// HR[1040] = 0x6548 (wire BE bytes [0x65, 0x48]) decodes first char from low byte = 'H',
|
||||
// second from high byte = 'e'. HR[1041] = 0x6C6C → 'l','l'. HR[1042] = 0x006F → 'o', nul.
|
||||
var tag = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.String,
|
||||
StringLength: 5, StringByteOrder: ModbusStringByteOrder.LowByteFirst);
|
||||
var wire = new byte[] { 0x65, 0x48, 0x6C, 0x6C, 0x00, 0x6F };
|
||||
ModbusDriver.DecodeRegister(wire, tag).ShouldBe("Hello");
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void String_LowByteFirst_decode_truncates_at_first_nul()
|
||||
{
|
||||
// Low-byte-first with only 2 real chars in register 0 (lo='H', hi='i') and the rest nul.
|
||||
var tag = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.String,
|
||||
StringLength: 6, StringByteOrder: ModbusStringByteOrder.LowByteFirst);
|
||||
var wire = new byte[] { 0x69, 0x48, 0x00, 0x00, 0x00, 0x00 };
|
||||
ModbusDriver.DecodeRegister(wire, tag).ShouldBe("Hi");
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void String_LowByteFirst_encode_round_trips_with_decode()
|
||||
{
|
||||
var tag = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.String,
|
||||
StringLength: 5, StringByteOrder: ModbusStringByteOrder.LowByteFirst);
|
||||
var wire = ModbusDriver.EncodeRegister("Hello", tag);
|
||||
// Expect exactly the DL205-documented byte sequence.
|
||||
wire.ShouldBe(new byte[] { 0x65, 0x48, 0x6C, 0x6C, 0x00, 0x6F });
|
||||
ModbusDriver.DecodeRegister(wire, tag).ShouldBe("Hello");
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void String_HighByteFirst_and_LowByteFirst_differ_on_same_wire()
|
||||
{
|
||||
// Same wire buffer, different byte order → first char switches 'H' vs 'e'.
|
||||
var wire = new byte[] { 0x48, 0x65 };
|
||||
var hi = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.String,
|
||||
StringLength: 2, StringByteOrder: ModbusStringByteOrder.HighByteFirst);
|
||||
var lo = new ModbusTagDefinition("T", ModbusRegion.HoldingRegisters, 0, ModbusDataType.String,
|
||||
StringLength: 2, StringByteOrder: ModbusStringByteOrder.LowByteFirst);
|
||||
ModbusDriver.DecodeRegister(wire, hi).ShouldBe("He");
|
||||
ModbusDriver.DecodeRegister(wire, lo).ShouldBe("eH");
|
||||
}
|
||||
}
|
||||
|
||||
@@ -0,0 +1,160 @@
|
||||
using System.Linq;
|
||||
using Opc.Ua;
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
|
||||
using ZB.MOM.WW.OtOpcUa.Server.OpcUa;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Server.Tests;
|
||||
|
||||
/// <summary>
|
||||
/// Unit coverage for the static helpers <see cref="DriverNodeManager"/> exposes to bridge
|
||||
/// driver-side history data (<see cref="HistoricalEvent"/> + <see cref="DataValueSnapshot"/>)
|
||||
/// to the OPC UA on-wire shape (<c>HistoryData</c> / <c>HistoryEvent</c> wrapped in an
|
||||
/// <see cref="ExtensionObject"/>). Fast, framework-only — no server fixture.
|
||||
/// </summary>
|
||||
[Trait("Category", "Unit")]
|
||||
public sealed class DriverNodeManagerHistoryMappingTests
|
||||
{
|
||||
[Theory]
|
||||
[InlineData(nameof(HistoryAggregateType.Average), HistoryAggregateType.Average)]
|
||||
[InlineData(nameof(HistoryAggregateType.Minimum), HistoryAggregateType.Minimum)]
|
||||
[InlineData(nameof(HistoryAggregateType.Maximum), HistoryAggregateType.Maximum)]
|
||||
[InlineData(nameof(HistoryAggregateType.Total), HistoryAggregateType.Total)]
|
||||
[InlineData(nameof(HistoryAggregateType.Count), HistoryAggregateType.Count)]
|
||||
public void MapAggregate_translates_each_supported_OPC_UA_aggregate_NodeId(
|
||||
string name, HistoryAggregateType expected)
|
||||
{
|
||||
// Resolve the ObjectIds.AggregateFunction_<name> constant via reflection so the test
|
||||
// keeps working if the stack ever renames them — failure means the stack broke its
|
||||
// naming convention, worth surfacing loudly.
|
||||
var field = typeof(ObjectIds).GetField("AggregateFunction_" + name);
|
||||
field.ShouldNotBeNull();
|
||||
var nodeId = (NodeId)field!.GetValue(null)!;
|
||||
|
||||
DriverNodeManager.MapAggregate(nodeId).ShouldBe(expected);
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void MapAggregate_returns_null_for_unknown_aggregate()
|
||||
{
|
||||
// AggregateFunction_TimeAverage is a valid OPC UA aggregate but not one the driver
|
||||
// surfaces. Null here means the service handler will translate to BadAggregateNotSupported
|
||||
// — the right behavior per Part 13 when the requested aggregate isn't implemented.
|
||||
DriverNodeManager.MapAggregate(ObjectIds.AggregateFunction_TimeAverage).ShouldBeNull();
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void MapAggregate_returns_null_for_null_input()
|
||||
{
|
||||
// Processed requests that omit the aggregate list (or pass a single null) must not crash.
|
||||
DriverNodeManager.MapAggregate(null).ShouldBeNull();
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void BuildHistoryData_wraps_samples_as_HistoryData_extension_object()
|
||||
{
|
||||
var samples = new[]
|
||||
{
|
||||
new DataValueSnapshot(Value: 42, StatusCode: StatusCodes.Good,
|
||||
SourceTimestampUtc: new DateTime(2024, 1, 1, 0, 0, 0, DateTimeKind.Utc),
|
||||
ServerTimestampUtc: new DateTime(2024, 1, 1, 0, 0, 1, DateTimeKind.Utc)),
|
||||
new DataValueSnapshot(Value: 99, StatusCode: StatusCodes.Good,
|
||||
SourceTimestampUtc: new DateTime(2024, 1, 1, 0, 0, 5, DateTimeKind.Utc),
|
||||
ServerTimestampUtc: new DateTime(2024, 1, 1, 0, 0, 6, DateTimeKind.Utc)),
|
||||
};
|
||||
|
||||
var ext = DriverNodeManager.BuildHistoryData(samples);
|
||||
|
||||
ext.Body.ShouldBeOfType<HistoryData>();
|
||||
var hd = (HistoryData)ext.Body;
|
||||
hd.DataValues.Count.ShouldBe(2);
|
||||
hd.DataValues[0].Value.ShouldBe(42);
|
||||
hd.DataValues[1].Value.ShouldBe(99);
|
||||
hd.DataValues[0].SourceTimestamp.ShouldBe(new DateTime(2024, 1, 1, 0, 0, 0, DateTimeKind.Utc));
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void BuildHistoryEvent_wraps_events_with_BaseEventType_field_ordering()
|
||||
{
|
||||
// BuildHistoryEvent populates a fixed field set in BaseEventType's conventional order:
|
||||
// EventId, SourceName, Message, Severity, Time, ReceiveTime. Pinning this so a later
|
||||
// "respect the client's SelectClauses" change can't silently break older clients that
|
||||
// rely on the default layout.
|
||||
var events = new[]
|
||||
{
|
||||
new HistoricalEvent(
|
||||
EventId: "e-1",
|
||||
SourceName: "Tank1.HiAlarm",
|
||||
EventTimeUtc: new DateTime(2024, 1, 1, 12, 0, 0, DateTimeKind.Utc),
|
||||
ReceivedTimeUtc: new DateTime(2024, 1, 1, 12, 0, 0, 5, DateTimeKind.Utc),
|
||||
Message: "High level reached",
|
||||
Severity: 750),
|
||||
};
|
||||
|
||||
var ext = DriverNodeManager.BuildHistoryEvent(events);
|
||||
|
||||
ext.Body.ShouldBeOfType<HistoryEvent>();
|
||||
var he = (HistoryEvent)ext.Body;
|
||||
he.Events.Count.ShouldBe(1);
|
||||
var fields = he.Events[0].EventFields;
|
||||
fields.Count.ShouldBe(6);
|
||||
fields[0].Value.ShouldBe("e-1"); // EventId
|
||||
fields[1].Value.ShouldBe("Tank1.HiAlarm"); // SourceName
|
||||
((LocalizedText)fields[2].Value).Text.ShouldBe("High level reached"); // Message
|
||||
fields[3].Value.ShouldBe((ushort)750); // Severity
|
||||
((DateTime)fields[4].Value).ShouldBe(new DateTime(2024, 1, 1, 12, 0, 0, DateTimeKind.Utc));
|
||||
((DateTime)fields[5].Value).ShouldBe(new DateTime(2024, 1, 1, 12, 0, 0, 5, DateTimeKind.Utc));
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void BuildHistoryEvent_substitutes_empty_string_for_null_SourceName_and_Message()
|
||||
{
|
||||
// Driver-side nulls are preserved through the wire contract by design (distinguishes
|
||||
// "system event with no source" from "source unknown"), but OPC UA Variants of type
|
||||
// String must not carry null — the stack serializes null-string as empty. This test
|
||||
// pins the choice so a nullable-Variant refactor doesn't break clients that display
|
||||
// the field without a null check.
|
||||
var events = new[]
|
||||
{
|
||||
new HistoricalEvent("sys", null, DateTime.UtcNow, DateTime.UtcNow, null, 1),
|
||||
};
|
||||
|
||||
var ext = DriverNodeManager.BuildHistoryEvent(events);
|
||||
var fields = ((HistoryEvent)ext.Body).Events[0].EventFields;
|
||||
fields[1].Value.ShouldBe(string.Empty);
|
||||
((LocalizedText)fields[2].Value).Text.ShouldBe(string.Empty);
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void ToDataValue_preserves_status_code_and_timestamps()
|
||||
{
|
||||
var snap = new DataValueSnapshot(
|
||||
Value: 123.45,
|
||||
StatusCode: StatusCodes.UncertainSubstituteValue,
|
||||
SourceTimestampUtc: new DateTime(2024, 5, 1, 10, 0, 0, DateTimeKind.Utc),
|
||||
ServerTimestampUtc: new DateTime(2024, 5, 1, 10, 0, 1, DateTimeKind.Utc));
|
||||
|
||||
var dv = DriverNodeManager.ToDataValue(snap);
|
||||
|
||||
dv.Value.ShouldBe(123.45);
|
||||
dv.StatusCode.Code.ShouldBe(StatusCodes.UncertainSubstituteValue);
|
||||
dv.SourceTimestamp.ShouldBe(new DateTime(2024, 5, 1, 10, 0, 0, DateTimeKind.Utc));
|
||||
dv.ServerTimestamp.ShouldBe(new DateTime(2024, 5, 1, 10, 0, 1, DateTimeKind.Utc));
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public void ToDataValue_leaves_SourceTimestamp_default_when_snapshot_has_no_source_time()
|
||||
{
|
||||
// Galaxy's raw-history rows often carry only a ServerTimestamp (the historian knows
|
||||
// when it wrote the row, not when the process sampled it). The mapping must not
|
||||
// synthesize a bogus SourceTimestamp from ServerTimestamp — that would lie to the
|
||||
// client about the measurement's actual time.
|
||||
var snap = new DataValueSnapshot(Value: 1, StatusCode: 0,
|
||||
SourceTimestampUtc: null,
|
||||
ServerTimestampUtc: new DateTime(2024, 5, 1, 10, 0, 1, DateTimeKind.Utc));
|
||||
|
||||
var dv = DriverNodeManager.ToDataValue(snap);
|
||||
dv.SourceTimestamp.ShouldBe(default);
|
||||
}
|
||||
}
|
||||
@@ -0,0 +1,356 @@
|
||||
using Microsoft.Extensions.Logging.Abstractions;
|
||||
using Opc.Ua;
|
||||
using Opc.Ua.Client;
|
||||
using Opc.Ua.Configuration;
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
|
||||
using ZB.MOM.WW.OtOpcUa.Core.Hosting;
|
||||
using ZB.MOM.WW.OtOpcUa.Server.OpcUa;
|
||||
using ZB.MOM.WW.OtOpcUa.Server.Security;
|
||||
// Core.Abstractions.HistoryReadResult (driver-side samples) collides with Opc.Ua.HistoryReadResult
|
||||
// (service-layer per-node result). Alias the driver type so the stub's interface implementations
|
||||
// are unambiguous.
|
||||
using DriverHistoryReadResult = ZB.MOM.WW.OtOpcUa.Core.Abstractions.HistoryReadResult;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Server.Tests;
|
||||
|
||||
/// <summary>
|
||||
/// End-to-end test that a real OPC UA client's HistoryRead service reaches a fake driver's
|
||||
/// <see cref="IHistoryProvider"/> via <see cref="DriverNodeManager"/>'s
|
||||
/// <c>HistoryReadRawModified</c> / <c>HistoryReadProcessed</c> / <c>HistoryReadAtTime</c> /
|
||||
/// <c>HistoryReadEvents</c> overrides. Boots the full OPC UA stack + a stub
|
||||
/// <see cref="IHistoryProvider"/> driver, opens a client session, issues each HistoryRead
|
||||
/// variant, and asserts the client receives the expected per-kind payload.
|
||||
/// </summary>
|
||||
[Trait("Category", "Integration")]
|
||||
public sealed class HistoryReadIntegrationTests : IAsyncLifetime
|
||||
{
|
||||
private static readonly int Port = 48600 + Random.Shared.Next(0, 99);
|
||||
private readonly string _endpoint = $"opc.tcp://localhost:{Port}/OtOpcUaHistoryTest";
|
||||
private readonly string _pkiRoot = Path.Combine(Path.GetTempPath(), $"otopcua-history-test-{Guid.NewGuid():N}");
|
||||
|
||||
private DriverHost _driverHost = null!;
|
||||
private OpcUaApplicationHost _server = null!;
|
||||
private HistoryDriver _driver = null!;
|
||||
|
||||
public async ValueTask InitializeAsync()
|
||||
{
|
||||
_driverHost = new DriverHost();
|
||||
_driver = new HistoryDriver();
|
||||
await _driverHost.RegisterAsync(_driver, "{}", CancellationToken.None);
|
||||
|
||||
var options = new OpcUaServerOptions
|
||||
{
|
||||
EndpointUrl = _endpoint,
|
||||
ApplicationName = "OtOpcUaHistoryTest",
|
||||
ApplicationUri = "urn:OtOpcUa:Server:HistoryTest",
|
||||
PkiStoreRoot = _pkiRoot,
|
||||
AutoAcceptUntrustedClientCertificates = true,
|
||||
};
|
||||
|
||||
_server = new OpcUaApplicationHost(options, _driverHost, new DenyAllUserAuthenticator(),
|
||||
NullLoggerFactory.Instance, NullLogger<OpcUaApplicationHost>.Instance);
|
||||
await _server.StartAsync(CancellationToken.None);
|
||||
}
|
||||
|
||||
public async ValueTask DisposeAsync()
|
||||
{
|
||||
await _server.DisposeAsync();
|
||||
await _driverHost.DisposeAsync();
|
||||
try { Directory.Delete(_pkiRoot, recursive: true); } catch { /* best-effort */ }
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task HistoryReadRaw_round_trips_driver_samples_to_the_client()
|
||||
{
|
||||
using var session = await OpenSessionAsync();
|
||||
var nsIndex = (ushort)session.NamespaceUris.GetIndex("urn:OtOpcUa:history-driver");
|
||||
var nodeId = new NodeId("raw.var", nsIndex);
|
||||
|
||||
// The Opc.Ua client exposes HistoryRead via Session.HistoryRead. We construct a
|
||||
// ReadRawModifiedDetails (IsReadModified=false → raw path) and a single
|
||||
// HistoryReadValueId targeting the driver-backed variable.
|
||||
var details = new ReadRawModifiedDetails
|
||||
{
|
||||
StartTime = new DateTime(2024, 1, 1, 0, 0, 0, DateTimeKind.Utc),
|
||||
EndTime = new DateTime(2024, 1, 1, 0, 0, 10, DateTimeKind.Utc),
|
||||
NumValuesPerNode = 100,
|
||||
IsReadModified = false,
|
||||
ReturnBounds = false,
|
||||
};
|
||||
var extObj = new ExtensionObject(details);
|
||||
var nodesToRead = new HistoryReadValueIdCollection { new() { NodeId = nodeId } };
|
||||
|
||||
session.HistoryRead(null, extObj, TimestampsToReturn.Both, false, nodesToRead,
|
||||
out var results, out _);
|
||||
|
||||
results.Count.ShouldBe(1);
|
||||
results[0].StatusCode.Code.ShouldBe(StatusCodes.Good, $"HistoryReadRaw returned {results[0].StatusCode}");
|
||||
var hd = (HistoryData)ExtensionObject.ToEncodeable(results[0].HistoryData);
|
||||
hd.DataValues.Count.ShouldBe(_driver.RawSamplesReturned, "one DataValue per driver sample");
|
||||
hd.DataValues[0].Value.ShouldBe(_driver.FirstRawValue);
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task HistoryReadProcessed_maps_Average_aggregate_and_routes_to_ReadProcessedAsync()
|
||||
{
|
||||
using var session = await OpenSessionAsync();
|
||||
var nsIndex = (ushort)session.NamespaceUris.GetIndex("urn:OtOpcUa:history-driver");
|
||||
var nodeId = new NodeId("proc.var", nsIndex);
|
||||
|
||||
var details = new ReadProcessedDetails
|
||||
{
|
||||
StartTime = new DateTime(2024, 1, 1, 0, 0, 0, DateTimeKind.Utc),
|
||||
EndTime = new DateTime(2024, 1, 1, 0, 1, 0, DateTimeKind.Utc),
|
||||
ProcessingInterval = 10_000, // 10s buckets
|
||||
AggregateType = [ObjectIds.AggregateFunction_Average],
|
||||
};
|
||||
var extObj = new ExtensionObject(details);
|
||||
var nodesToRead = new HistoryReadValueIdCollection { new() { NodeId = nodeId } };
|
||||
|
||||
session.HistoryRead(null, extObj, TimestampsToReturn.Both, false, nodesToRead,
|
||||
out var results, out _);
|
||||
|
||||
results[0].StatusCode.Code.ShouldBe(StatusCodes.Good);
|
||||
_driver.LastProcessedAggregate.ShouldBe(HistoryAggregateType.Average,
|
||||
"MapAggregate must translate ObjectIds.AggregateFunction_Average → driver enum");
|
||||
_driver.LastProcessedInterval.ShouldBe(TimeSpan.FromSeconds(10));
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task HistoryReadProcessed_returns_BadAggregateNotSupported_for_unmapped_aggregate()
|
||||
{
|
||||
using var session = await OpenSessionAsync();
|
||||
var nsIndex = (ushort)session.NamespaceUris.GetIndex("urn:OtOpcUa:history-driver");
|
||||
var nodeId = new NodeId("proc.var", nsIndex);
|
||||
|
||||
var details = new ReadProcessedDetails
|
||||
{
|
||||
StartTime = new DateTime(2024, 1, 1, 0, 0, 0, DateTimeKind.Utc),
|
||||
EndTime = new DateTime(2024, 1, 1, 0, 1, 0, DateTimeKind.Utc),
|
||||
ProcessingInterval = 10_000,
|
||||
// TimeAverage is a valid OPC UA aggregate NodeId but not one the driver implements —
|
||||
// the override returns BadAggregateNotSupported per Part 13 rather than coercing.
|
||||
AggregateType = [ObjectIds.AggregateFunction_TimeAverage],
|
||||
};
|
||||
var extObj = new ExtensionObject(details);
|
||||
var nodesToRead = new HistoryReadValueIdCollection { new() { NodeId = nodeId } };
|
||||
|
||||
session.HistoryRead(null, extObj, TimestampsToReturn.Both, false, nodesToRead,
|
||||
out var results, out _);
|
||||
|
||||
results[0].StatusCode.Code.ShouldBe(StatusCodes.BadAggregateNotSupported);
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task HistoryReadAtTime_forwards_timestamp_list_to_driver()
|
||||
{
|
||||
using var session = await OpenSessionAsync();
|
||||
var nsIndex = (ushort)session.NamespaceUris.GetIndex("urn:OtOpcUa:history-driver");
|
||||
var nodeId = new NodeId("atTime.var", nsIndex);
|
||||
|
||||
var t1 = new DateTime(2024, 3, 1, 10, 0, 0, DateTimeKind.Utc);
|
||||
var t2 = new DateTime(2024, 3, 1, 10, 0, 30, DateTimeKind.Utc);
|
||||
var details = new ReadAtTimeDetails { ReqTimes = new DateTimeCollection { t1, t2 } };
|
||||
var extObj = new ExtensionObject(details);
|
||||
var nodesToRead = new HistoryReadValueIdCollection { new() { NodeId = nodeId } };
|
||||
|
||||
session.HistoryRead(null, extObj, TimestampsToReturn.Both, false, nodesToRead,
|
||||
out var results, out _);
|
||||
|
||||
results[0].StatusCode.Code.ShouldBe(StatusCodes.Good);
|
||||
_driver.LastAtTimeRequestedTimes.ShouldNotBeNull();
|
||||
_driver.LastAtTimeRequestedTimes!.Count.ShouldBe(2);
|
||||
_driver.LastAtTimeRequestedTimes[0].ShouldBe(t1);
|
||||
_driver.LastAtTimeRequestedTimes[1].ShouldBe(t2);
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task HistoryReadEvents_returns_HistoryEvent_with_BaseEventType_field_list()
|
||||
{
|
||||
using var session = await OpenSessionAsync();
|
||||
// Events target the driver-root notifier (not a specific variable) which is the
|
||||
// conventional pattern for alarm-history browse.
|
||||
var nsIndex = (ushort)session.NamespaceUris.GetIndex("urn:OtOpcUa:history-driver");
|
||||
var nodeId = new NodeId("history-driver", nsIndex);
|
||||
|
||||
// EventFilter must carry at least one SelectClause or the stack rejects it as
|
||||
// BadEventFilterInvalid before our override runs — empty filters are spec-forbidden.
|
||||
// We populate the standard BaseEventType selectors any real client would send; my
|
||||
// override's BuildHistoryEvent ignores the specific clauses and emits the canonical
|
||||
// field list anyway (the richer "respect exact SelectClauses" behavior is on the PR 38
|
||||
// follow-up list).
|
||||
var filter = new EventFilter();
|
||||
filter.AddSelectClause(ObjectTypeIds.BaseEventType, BrowseNames.EventId);
|
||||
filter.AddSelectClause(ObjectTypeIds.BaseEventType, BrowseNames.SourceName);
|
||||
filter.AddSelectClause(ObjectTypeIds.BaseEventType, BrowseNames.Message);
|
||||
filter.AddSelectClause(ObjectTypeIds.BaseEventType, BrowseNames.Severity);
|
||||
filter.AddSelectClause(ObjectTypeIds.BaseEventType, BrowseNames.Time);
|
||||
filter.AddSelectClause(ObjectTypeIds.BaseEventType, BrowseNames.ReceiveTime);
|
||||
|
||||
var details = new ReadEventDetails
|
||||
{
|
||||
StartTime = new DateTime(2024, 1, 1, 0, 0, 0, DateTimeKind.Utc),
|
||||
EndTime = new DateTime(2024, 12, 31, 0, 0, 0, DateTimeKind.Utc),
|
||||
NumValuesPerNode = 10,
|
||||
Filter = filter,
|
||||
};
|
||||
var extObj = new ExtensionObject(details);
|
||||
var nodesToRead = new HistoryReadValueIdCollection { new() { NodeId = nodeId } };
|
||||
|
||||
session.HistoryRead(null, extObj, TimestampsToReturn.Both, false, nodesToRead,
|
||||
out var results, out _);
|
||||
|
||||
results[0].StatusCode.Code.ShouldBe(StatusCodes.Good);
|
||||
var he = (HistoryEvent)ExtensionObject.ToEncodeable(results[0].HistoryData);
|
||||
he.Events.Count.ShouldBe(_driver.EventsReturned);
|
||||
he.Events[0].EventFields.Count.ShouldBe(6, "BaseEventType default field layout is 6 entries");
|
||||
}
|
||||
|
||||
private async Task<ISession> OpenSessionAsync()
|
||||
{
|
||||
var cfg = new ApplicationConfiguration
|
||||
{
|
||||
ApplicationName = "OtOpcUaHistoryTestClient",
|
||||
ApplicationUri = "urn:OtOpcUa:HistoryTestClient",
|
||||
ApplicationType = ApplicationType.Client,
|
||||
SecurityConfiguration = new SecurityConfiguration
|
||||
{
|
||||
ApplicationCertificate = new CertificateIdentifier
|
||||
{
|
||||
StoreType = CertificateStoreType.Directory,
|
||||
StorePath = Path.Combine(_pkiRoot, "client-own"),
|
||||
SubjectName = "CN=OtOpcUaHistoryTestClient",
|
||||
},
|
||||
TrustedIssuerCertificates = new CertificateTrustList { StoreType = CertificateStoreType.Directory, StorePath = Path.Combine(_pkiRoot, "client-issuers") },
|
||||
TrustedPeerCertificates = new CertificateTrustList { StoreType = CertificateStoreType.Directory, StorePath = Path.Combine(_pkiRoot, "client-trusted") },
|
||||
RejectedCertificateStore = new CertificateTrustList { StoreType = CertificateStoreType.Directory, StorePath = Path.Combine(_pkiRoot, "client-rejected") },
|
||||
AutoAcceptUntrustedCertificates = true,
|
||||
AddAppCertToTrustedStore = true,
|
||||
},
|
||||
TransportConfigurations = new TransportConfigurationCollection(),
|
||||
TransportQuotas = new TransportQuotas { OperationTimeout = 15000 },
|
||||
ClientConfiguration = new ClientConfiguration { DefaultSessionTimeout = 60000 },
|
||||
};
|
||||
await cfg.Validate(ApplicationType.Client);
|
||||
cfg.CertificateValidator.CertificateValidation += (_, e) => e.Accept = true;
|
||||
|
||||
var instance = new ApplicationInstance { ApplicationConfiguration = cfg, ApplicationType = ApplicationType.Client };
|
||||
await instance.CheckApplicationInstanceCertificate(true, CertificateFactory.DefaultKeySize);
|
||||
|
||||
var selected = CoreClientUtils.SelectEndpoint(cfg, _endpoint, useSecurity: false);
|
||||
var endpointConfig = EndpointConfiguration.Create(cfg);
|
||||
var configuredEndpoint = new ConfiguredEndpoint(null, selected, endpointConfig);
|
||||
|
||||
return await Session.Create(cfg, configuredEndpoint, false, "OtOpcUaHistoryTestClientSession", 60000,
|
||||
new UserIdentity(new AnonymousIdentityToken()), null);
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// Stub driver that implements <see cref="IHistoryProvider"/> so the service dispatch
|
||||
/// can be verified without bringing up a real Galaxy or Historian. Captures the last-
|
||||
/// seen arguments so tests can assert what the service handler forwarded.
|
||||
/// </summary>
|
||||
private sealed class HistoryDriver : IDriver, ITagDiscovery, IReadable, IHistoryProvider
|
||||
{
|
||||
public string DriverInstanceId => "history-driver";
|
||||
public string DriverType => "HistoryStub";
|
||||
|
||||
public int RawSamplesReturned => 3;
|
||||
public int FirstRawValue => 100;
|
||||
public int EventsReturned => 2;
|
||||
|
||||
public HistoryAggregateType? LastProcessedAggregate { get; private set; }
|
||||
public TimeSpan? LastProcessedInterval { get; private set; }
|
||||
public IReadOnlyList<DateTime>? LastAtTimeRequestedTimes { get; private set; }
|
||||
|
||||
public Task InitializeAsync(string driverConfigJson, CancellationToken ct) => Task.CompletedTask;
|
||||
public Task ReinitializeAsync(string driverConfigJson, CancellationToken ct) => Task.CompletedTask;
|
||||
public Task ShutdownAsync(CancellationToken ct) => Task.CompletedTask;
|
||||
public DriverHealth GetHealth() => new(DriverState.Healthy, DateTime.UtcNow, null);
|
||||
public long GetMemoryFootprint() => 0;
|
||||
public Task FlushOptionalCachesAsync(CancellationToken ct) => Task.CompletedTask;
|
||||
|
||||
public Task DiscoverAsync(IAddressSpaceBuilder builder, CancellationToken ct)
|
||||
{
|
||||
// Every variable must be Historized for HistoryRead to route — the node-manager's
|
||||
// stack base class checks the bit before dispatching.
|
||||
builder.Variable("raw", "raw",
|
||||
new DriverAttributeInfo("raw.var", DriverDataType.Int32, false, null,
|
||||
SecurityClassification.FreeAccess, IsHistorized: true, IsAlarm: false));
|
||||
builder.Variable("proc", "proc",
|
||||
new DriverAttributeInfo("proc.var", DriverDataType.Float64, false, null,
|
||||
SecurityClassification.FreeAccess, IsHistorized: true, IsAlarm: false));
|
||||
builder.Variable("atTime", "atTime",
|
||||
new DriverAttributeInfo("atTime.var", DriverDataType.Int32, false, null,
|
||||
SecurityClassification.FreeAccess, IsHistorized: true, IsAlarm: false));
|
||||
return Task.CompletedTask;
|
||||
}
|
||||
|
||||
public Task<IReadOnlyList<DataValueSnapshot>> ReadAsync(
|
||||
IReadOnlyList<string> fullReferences, CancellationToken cancellationToken)
|
||||
{
|
||||
var now = DateTime.UtcNow;
|
||||
IReadOnlyList<DataValueSnapshot> r =
|
||||
[.. fullReferences.Select(_ => new DataValueSnapshot(0, 0u, now, now))];
|
||||
return Task.FromResult(r);
|
||||
}
|
||||
|
||||
public Task<DriverHistoryReadResult> ReadRawAsync(
|
||||
string fullReference, DateTime startUtc, DateTime endUtc, uint maxValuesPerNode,
|
||||
CancellationToken cancellationToken)
|
||||
{
|
||||
var samples = new List<DataValueSnapshot>();
|
||||
for (var i = 0; i < RawSamplesReturned; i++)
|
||||
{
|
||||
samples.Add(new DataValueSnapshot(
|
||||
Value: FirstRawValue + i,
|
||||
StatusCode: StatusCodes.Good,
|
||||
SourceTimestampUtc: startUtc.AddSeconds(i),
|
||||
ServerTimestampUtc: startUtc.AddSeconds(i)));
|
||||
}
|
||||
return Task.FromResult(new DriverHistoryReadResult(samples, null));
|
||||
}
|
||||
|
||||
public Task<DriverHistoryReadResult> ReadProcessedAsync(
|
||||
string fullReference, DateTime startUtc, DateTime endUtc, TimeSpan interval,
|
||||
HistoryAggregateType aggregate, CancellationToken cancellationToken)
|
||||
{
|
||||
LastProcessedAggregate = aggregate;
|
||||
LastProcessedInterval = interval;
|
||||
return Task.FromResult(new DriverHistoryReadResult(
|
||||
[new DataValueSnapshot(1.0, StatusCodes.Good, startUtc, startUtc)],
|
||||
null));
|
||||
}
|
||||
|
||||
public Task<DriverHistoryReadResult> ReadAtTimeAsync(
|
||||
string fullReference, IReadOnlyList<DateTime> timestampsUtc,
|
||||
CancellationToken cancellationToken)
|
||||
{
|
||||
LastAtTimeRequestedTimes = timestampsUtc;
|
||||
var samples = timestampsUtc
|
||||
.Select(t => new DataValueSnapshot(42, StatusCodes.Good, t, t))
|
||||
.ToArray();
|
||||
return Task.FromResult(new DriverHistoryReadResult(samples, null));
|
||||
}
|
||||
|
||||
public Task<HistoricalEventsResult> ReadEventsAsync(
|
||||
string? sourceName, DateTime startUtc, DateTime endUtc, int maxEvents,
|
||||
CancellationToken cancellationToken)
|
||||
{
|
||||
var events = new List<HistoricalEvent>();
|
||||
for (var i = 0; i < EventsReturned; i++)
|
||||
{
|
||||
events.Add(new HistoricalEvent(
|
||||
EventId: $"e{i}",
|
||||
SourceName: sourceName,
|
||||
EventTimeUtc: startUtc.AddHours(i),
|
||||
ReceivedTimeUtc: startUtc.AddHours(i).AddSeconds(1),
|
||||
Message: $"Event {i}",
|
||||
Severity: (ushort)(500 + i)));
|
||||
}
|
||||
return Task.FromResult(new HistoricalEventsResult(events, null));
|
||||
}
|
||||
}
|
||||
}
|
||||
Reference in New Issue