P8: on the native transport the bounded-parallel read window is also the cap
on services per Multiple Service Packet (the device's shared scheduler packs
whatever is queued, within the connection's request/reply byte budget), so the
default 8 cost a 1000-tag controller ~125 round trips per poll instead of ~10.
The effective window (AbCipDriver.ReadWindow) is now max(64, option) when the
native tag factory serves reads; libplctag and injected factories keep the
option exactly. Option doc + AdminUI help text updated (Razor: Wave 4 live
check).
P7 addendum: a work item now takes its window slot only after its runtime
exists. A cold create queues on its device's single-flight connect gate, and
holding a slot there let one dead device's backoff-expiry attempt occupy the
whole window for a full Timeout, stalling every other device's reads.
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
FocasDataType.String was authorable on any address, but no area read returns text: PMC
fell through to a byte read, PARAM to Int32, MACRO to a double, and the String node
received a boxed number at Good.
One rule, FocasTagDefinitionFactory.DescribeDataTypeMismatch, now backs every path:
- FromTagConfig rejects the pair, so the driver skips + reports it (BadNodeIdUnknown,
never a Good number) and Inspect names the reason at deploy;
- FocasTagConfigModel.Validate refuses it on the typed fields;
- the AdminUI editor only offers String where it is readable and shows the rule's text
inline (kept visible for a loaded blob that already carries it);
- the CLI read/subscribe/probe/write commands refuse it at the boundary.
String stays valid on FIXED: paths (Identity/Program name/mode text) and is ignored on
ALARM: tags; an unparseable address keeps its own diagnosis.
Razor change (FocasTagConfigEditor.razor) needs the Wave 4 live check.
Refs #740
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 2026-10-21 G-5, G-6, G-8 ("wire them all").
- G-5: GatewayGalaxyHierarchySource now pages the DiscoverHierarchy RPC
itself (DiscoverHierarchyRawAsync) at Repository.DiscoverPageSize. The
mxaccessgw client's typed DiscoverHierarchyAsync overloads hard-code a
5000-row page and DiscoverHierarchyOptions carries no page size, so the
authored knob reached nothing; the raw request takes page_size on the
wire, so it is honoured here (non-positive → 5000). The loop keeps the
client's repeated-page-token guard.
- G-6: GalaxyDriverProbe reads ProbeTimeoutSeconds from the config and
runs under min(caller budget, configured cap) — the knob can shorten a
probe, never extend it past the host's budget. The TCP preflight now
shares that deadline instead of hanging on the caller's token alone.
- G-8: GatewayGalaxyDataWriter runs a batch as one lane per distinct tag,
concurrently and bounded at 8 (MaxConcurrentWriteLanes); same-tag
writes keep their authored order inside one lane and results land at
their request's index. Acks stay serial by design.
- GalaxyDriverForm: help text now says what the two knobs actually do.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Clears CommentChecker findings in src/ (3,280 -> 209, the remainder being false
positives like PLC-5/IEEE-754/M0.0) by adding missing summaries/params/returns,
normalising inheritdoc usage, and removing Gitea/review tracking IDs while keeping
the rationale they annotated. Comment-only: comment-stripped sources are identical
to the parent commit.
- Endpoint rewrite: the driver now connects to the configured host AND port (scheme
match, advertised path kept) instead of the server-advertised URL — fixes NAT/port-map
upstreams and lets an in-test proxy carry the session (SDK SelectEndpoint rule).
- TcpStallProxy + OpcUaClientDriverStallWireTests: the in-place blip (#670) is now
wire-tested on loopback — one Bad, frozen read stamp, same session, identical value
republished Good, a post-recovery change arrives, no source-time regression after
the SDK's late backlog flush.
- Defect found by that test, fixed: a change published right after a stall rode a
Publish response the SDK timed out and never republished, leaving the node Good on
the pre-change value indefinitely. New trailing reconcile read (Timeout +
KeepAliveInterval after recovery) publishes any Good value newer than the last
accepted one, through the replay guard's mark.
- IDriverConnectionLossSource (Core.Abstractions): opt-in definitive-loss signal.
DriverInstanceActor attaches in PreStart / detaches in PostStop and turns a raise
into a disconnect only while Connected. OpcUaClient raises once per session on
keep-alive BadSessionIdInvalid/BadSessionClosed/BadSessionNotActivated/
BadServerHalted (measured: the SDK never re-opens a halted channel) or a dropped
subscription; ambiguous codes stay with the #527 watchdog.
- Replay guard: one Information summary per recovery when the window closes
("dropped N late notifications across M refs"), with a timer so quiet
subscriptions log it too.
- ReconnectPeriod deleted (options, AdminUI form, docs, tests); stored configs that
carry reconnectPeriod still parse in the factory, probe and browser.
- Docs: OpcUaClient.md, DriverLifecycle.md, driver-specs.md, CLAUDE.md.
HistoryRead is served server-side by IHistorianDataSource; nothing ever dispatched
to a driver's IHistoryProvider. Removes IHistoryProvider, the OpcUaClient history
passthrough, DriverCapability.HistoryRead (+ resilience tier rows and AdminUI row),
HistoryReadStatusException and its node-manager catches, and the tests that only
covered them. Shared result types and HistoryAggregateNotSupportedException stay
(moved to Historian/HistoryReadContracts.cs). A stored ResilienceConfig still
carrying a HistoryRead key parses (diagnostic only; new test).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
An ALARM: address (*, <Type>, <Type>/<n>, <Type>/<lo>-<hi>, T<code>, OTHER) on a raw tag that
also carries the cross-driver alarm object is ONE condition with ConditionId == RawPath and a
Kind (Raise / Retrigger / Clear), so DriverHostActor.ForwardNativeAlarm routes it and
NativeAlarmProjector activates it. Fixes all seven triage defects:
1. SubscribeAlarmsAsync treated the host's RawPaths as device hosts -> nothing polled.
2. Decorated "{host}#{Type}:{Number}" ConditionId -> every event dropped.
3. No Kind -> projector kept prior state.
4. WireFocasClient.ReadAlarmsAsync answered [] on failure -> mass clear + un-acked re-raise.
It now throws; a failed device read keeps every condition's state.
5. Acks lost on reconnect -> told-record dedup (MTConnect #626 pattern) held for the driver's
lifetime; same-set re-subscribe / re-init re-raise nothing; changed set prunes leavers only.
6. Subscribe threw while AlarmProjection.Enabled=false -> the tag is the opt-in; flag is a no-op.
7. Alarm tags could not be authored -> ALARM: grammar (FocasAlarmSelector, Contracts) backs the
editor, the address picker, the deploy-time inspector and driver init.
Severity: authored alarm.severity -> exact OpcUaSeverity; else the 16i-era type bucket. The type
table stays the only one (moved to Contracts, documented 16i-era; 30i codes not invented; raw
T<code> selector + raw code in every message). Read-only: ack is server-side. Also clears the
value table on a re-initialise (#630 gap that let a removed/moved tag keep reading).
E2E: Runtime.Tests FocasNativeAlarmEndToEndTests drives the real driver through the real
DriverHostActor and asserts the condition goes Active then inactive.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Strict width+kind eligibility for sum-batched scalars (others read singly); latch only on ADS
1793/1794, split 1792/1797/1798 without latching; 32 KiB per-command budget and 500-item ceiling;
short sum response handled per item. Diagnostics: opt-in diagnosticsEnabled (default off), reuse the
probe's ReadState, sample after the host-state transition, JitterMs renamed HeadroomMs, compact
per-device line so many devices fit the 16-entry cap, unavailable-symbol latch cleared on reconnect.
AdminUI: min/max on sum-read max, diagnostics checkbox. Pure planner extracted and unit-tested.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Sum-read (#310): batches a poll's reads per device into sum commands capped at sumReadMaxItems,
per-item ADS errors mapped per tag, falls back to individual reads when the target refuses the
command. Diagnostics (#314): ADS state, app name, online-change count, task cycle/exec/jitter via
IDriverDiagnostics. Re-implemented against the current raw-byte read path (stranded auto/driver-gaps
commits predate it). Sum-write not ported. Unit tests only; live gate pending a route.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Nothing read the mapping table beyond the startup validator; v3 UNS projection is
explicit via UnsTagReference. Legacy keys in stored DriverConfig are ignored (pinned).
Reverts the docker-dev opc-plc seed workaround from fdee129f.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
New S7DataType members WString/Char/WChar/Dtl/Date/Tod/Time/S5Time mapped onto existing
DriverDataType (String / DateTime / Int32 ms); writes refuse out-of-range with BadOutOfRange.
Optional localTsap/remoteTsap/connectionType through options, factory JSON, probe and AdminUI form.
NegotiatedPduSize snapshotted at connect and exposed via GetDiagnostics (DriverHealth has no bag).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
M1: PageErrorBoundary wraps the body of every InteractiveServer page; the inert layout boundary is removed.
m1: DisposeBridge cancels its CTS when the 5 s wait times out.
m2: a CSV import that commits after the modal closed still raises OnSaved.
m3: document SecurityMode=None no-fallback in Client.CLI.md / Client.UI.md.
m4: browsePageDelayMs written only when loaded or changed; negative flagged.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The old AdminUI cannot author the per-driver transport key (#576), so the
'pin before upgrading' recipe had no working path. A node-level appsetting
(env Drivers__AbCip__DefaultTransport) now supplies the default for AbCip
drivers with no key: explicit key > node default > compiled Native. Bound
and validated unconditionally (bad value fails host start); the driver
factory and the Test Connect probe both read it so they agree. AbCip.md
upgrade recipe rewritten around the key; Configuration.md documents it.
Also documents first-wins for AllowPacking/probe and host-alias throttles
(final review M6) and moves the status-bit note out of AbCip.md (M5).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
On a wire the native PCCC path is proven only for N-file reads/writes and
one F8 read (ab_server). An absent transport key now resolves to Libplctag
for every family; explicit Native still wins and still warns once per
instance on PLC-5/LogixPccc. AdminUI dropdown, CLI help, evidence claims
(PcccFileType, AbLegacy.md wire-evidence table, release note) corrected:
S:0 (default probe) and B/T/C/R/S/L/ST/A/O/I are unverified natively.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Task 22 (spec section 8 P5), with the controller rulings that exclude PLC-5 and LogixPccc.
- Transport is nullable on both option records; null (key absent) means "use the default" and is
never serialized. Factory DTO parse: absent -> null; a bad value still fails via ParseEnum.
- One resolver per driver (AbCipTransportResolver / AbLegacyTransportResolver), used by the driver
constructor, the Test Connect probe and (through the driver) the CLI.
AbCip: null -> Native. AbLegacy: null -> Native unless any device is Plc5 or LogixPccc, then the
whole driver resolves to Libplctag. Explicit values always win; explicit Native with a
Plc5/LogixPccc device logs one Warning at init.
- Init log shows configured vs effective, e.g. transport=Native (default).
- AdminUI forms: "Default (...)" / "Native (managed)" / "libplctag (fallback)". Default omits the
key on save (reverses Task 19's explicit re-emit, which would have pinned every edited driver).
- CLIs: --transport default|native|libplctag, default "default" via the resolver, so
--plc-type Plc5 with no --transport runs libplctag.
- Tests pinned to Libplctag where a default-path runtime was created: found by instrumenting the
native factories with the current xUnit test name (one unit test, AbLegacyReinitConfigAdoption;
plus the two fixture-gated AbCip probe E2E tests whose exact messages were proven on libplctag).
TransportMatrix and the differential harness already pass explicit transports.
- Switch/resolver/CLI/form tests are falsified by mutating the resolver (default -> Libplctag,
exclusion removed, AbLegacy default -> Libplctag): each mutation turns them red.
- Replaces the inline role-name literal in AbCipDriverFactoryExtensions' ParseEnum call with a named
constant; RoleAuthorityGuardTests was already red on the base commit for that line.
- Docs: AbCip.md / AbLegacy.md default + release note; CLAUDE.md AB section.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- AbCip/AbLegacy driver forms gain a Transport InputSelect; FromOptions/ToOptions now carry
Transport, so saving any other field no longer silently reverts Native to libplctag.
- Both drivers log the constructed transport once per init.
- AbCip factory now takes the host ILoggerFactory (it ran on NullLogger in production, hiding
every AbCip log line); DriverFactoryBootstrap passes it.
- Gate results: AdminUI /run (T19) native, inverted (dead port) and libplctag legs.
Sweep task 5 (Shared/Drivers + Acls):
- btn-group the Save/Cancel pair in DriverFormShell (all 13 driver forms),
CollectionEditor foot + per-row Edit/Delete, DriverConfigModal /
DeviceModal / DriverTagPicker / AclScopePickerModal feet,
DriverStatusPanel Reconnect+Restart and its inline restart confirm,
and the Refresh+Close browse toolbars on the FOCAS/AbCip/TwinCAT pickers.
- Replace the no-op inline border-color:var(--alert) tint with .notice-alert
in DriverFormShell, DriverConfigModal, DeviceModal, MqttDriverForm,
MTConnectDriverForm, MqttDeviceForm.
- Replace inline style="width:18px" expander sizing with .tree-twist in
DriverBrowseTree and AclScopeTree.
Markup only — every @onclick, binding, disabled and arm->confirm flow is
unchanged.
UI sweep task 4 (Shared/Raw). Markup-only; no behavior change.
- Wrap the Cancel+primary modal-footer pairs in a Bootstrap btn-group across
RawNameDialog, RawDriverTypeDialog, RawConfirmDialog, RawTagModal,
RawManualTagEntryModal, RawCsvImportModal, RawBrowseModal and
RawCsvExportModal (the last mixes a <button> with the download <a>, which
is valid btn-group membership; the download attribute is unchanged).
- RawBrowseModal: the rebirth confirm pair (Publish rebirth request + Cancel)
becomes a btn-group btn-group-sm in place of the d-flex gap-2 wrapper.
- RawCsvImportModal: drop the py-0 padding hack from the per-row remove
button; .btn-sm sizing covers it.
- RawTree: replace the expander's inline style="width:18px" (and the matching
leaf placeholder) with the shared .tree-twist class.
The CSV import all-or-nothing commit gating and RawTree's tree logic are
untouched.
Foundation task of the AdminUI UI sweep. CSS/link/doc only — no behavior change
beyond restoring styles that were built but never served.
- App.razor: link the RCL's scoped-CSS bundle
(_content/ZB.MOM.WW.OtOpcUa.AdminUI/ZB.MOM.WW.OtOpcUa.AdminUI.bundle.scp.css).
It is produced on every compile and served by the Host, but nothing referenced
it, so ContextMenu.razor.css was dead at runtime and context menus rendered
in-flow with no position:fixed.
- site.css: three additions.
* .btn / .btn-sm sizing as Bootstrap CSS-VARIABLE overrides (never box
properties — .btn-group depends on Bootstrap's own .btn rules for its seams
and end-cap radii). Theme 0.3.1 ships no .btn rule, so Bootstrap's 1rem
applied against the theme's 0.9rem body. Upstreaming candidate, same as the
ignitionoee router's app.css.
* .notice-alert — red variant of the kit's amber .notice, on the --bad/
--bad-bg/--bad-border tokens. The 13 existing call sites hack this with
style="border-color:var(--alert)", and no --alert token exists anywhere, so
the tint silently no-ops today. Call-site migration is a separate task.
* .tree-twist — shared 18px expander column for the tree components, replacing
repeated inline style="width:18px". Rows are d-flex, so flex-basis is what
actually holds the column. Adoption is a separate task.
- ContextMenu.razor.css: correct the header comment — the kit is light-only
(no dark block in Theme 0.3.1, site.css, or this file). No rule changes.
- docs/Telemetry.md: record that driver-health is keyed per driver instance
across the cluster, not per Akka member (the wire record carries no per-member
identity). The fact previously lived only in Hosts.razor page copy.
- docs/Configuration.md: new audit-log subsection recording that EventId gives
cross-restart dedup, enforced by the filtered unique index
UX_ConfigAuditLog_EventId, so a retried apply inserts no duplicate row;
CorrelationId joins a row to its originating workflow. Previously only in the
historical v2 rebuild plan and ClusterAudit page copy.
IWritable shipped behind write.enabled and docs/drivers/MTConnect.md told the operator to
set it, but MTConnectDriverForm — the only editor DriverFormMaps maps for this type, with
no raw-JSON escape hatch and no driver-instance API — exposed no write section, so the
documented enablement path was a hand edit of DriverInstance.DriverConfig in the config DB.
- Write-back section: switch + form text stating it is observation injection, that the
Agent's AllowPut is an independent second gate, and that it does not by itself make a
node writable over OPC UA (Tag.AccessLevel still composes CurrentWrite).
- Write added to the mirrored MTConnectConfigDto and to the form model, written in BOTH
states — an omitted block would leave a previously-authored true standing, so the switch
could never turn writing off again.
- The false 'MTConnect is read-only' header comment is gone; the doc names the new section.
No bUnit here, so the model/serialization seam is unit-tested both sides: the AdminUI test
pins the emitted bytes, and MTConnectFactoryTests parses that same document and asserts
MTConnectDriverOptions.Write.Enabled. Live page verification remains a rig step.
Blazor does not serialize OnParametersSetAsync against its own outstanding
task, and the modal's `_open` bool cannot tell two opens apart. ResetAndResolveAsync
awaits LoadMergedProbeConfigAsync and ResolveGroupContextAsync and then wrote
_driverType/_mergedConfig/_effectiveDeviceId/_groupPrefix/_canBrowse/_disabledReason
with no staleness re-check, so a close-reopen onto another device let the first
open's late continuation install its device's browse context under the displayed
modal — "Connect & browse" would silently dial the wrong controller and the commit
would land under the wrong tag-group.
Ports the per-open `_openGeneration` counter proven in the two sibling modals
(RawManualTagEntryModal, RawTagModal, 2026-08-05) to every post-await write here:
after both awaits, in the catch's error banner, and in the finally. The finally is
the one departure from the sibling shape and it is load-bearing — this modal resolves
inside a try/finally, so a stale `return` still runs the tail and would drop the LIVE
open's spinner mid-resolve.
Pinned by four RawBrowseModalStaleOpenTests facts, each observed red before the guard
and each re-falsified afterwards by reverting only its own guard. The modal calls
StateHasChanged on the open path, which throws without a render handle, so the test
attaches an inert Renderer subclass (file-local BL0006 pragma); [Parameter]s are set
by reflection per the BL0005 convention.
AdminUI suite 1117/1117 green.
The connect path was the one capability call the resilience pipeline never
saw, so a driver that could not connect contributed zero breaker input and
the /hosts resilience panel read 'All targets healthy' against a dead
endpoint. InitializeAsync now routes through the invoker as
DriverCapability.Initialize, keyed on the driver-instance id.
- No pipeline retry: the actor's RetryConnect timer is the retry loop
(parser forces retryCount overrides to 0, same funnel as write-shaped).
- Breaker threshold 2, not the Read-sized 5: the breaker samples 30 s and
the reconnect timer fires every 10 s, so at most three attempts fit one
window — threshold 5 could never open. Pinned by its own test.
- An open breaker fast-fails into the same InitializeFailed path as a real
connect failure; the 15 s break window costs at most one extra tick.
The best-effort teardown ShutdownAsync stays unwrapped.
- Companion fix: DriverCapabilityInvokerFactory.Create now invalidates the
instance's tracker snapshots with its pipelines — a respawn during an
outage discarded the only breaker whose OnClosed could clear the OPEN
flag, stranding a false 'Breaker OPEN' chip forever.
Live gate PASSED on docker-dev (image symbol-verified per container):
rtu-gate against dead 10.100.0.35:5021 opened its Initialize breaker on
both centrals with the red 'BREAKER OPEN' chip on /hosts; a socat
5021→5020 forwarder recovered it (both breakers closed within 1 s, panel
back to 'All targets healthy'); healthy MAIN-modbus recorded zero breaker
events. Full suite 50/50 green. Evidence:
docs/plans/2026-08-07-adminui-followups-and-live-gates.md §7.
Authoring FOCAS tags through /raw -> Browse device... produced tags the driver
could never read. Every committed tag read BadNodeIdUnknown forever, and the
failure was silent end to end: the AdminUI accepted it, the deploy gate sealed
green, and the driver reported Healthy with 0 errors while ignoring the tags.
Net effect: the whole fixed-tree surface could not be published through any v3
authoring path. Found cutting wonder-app-vd03 over to v3 against a real Makino
Pro 5 / Fanuc 30i, where 0 of 20 committed tags read while two hand-authored
MACRO: tags on the same device read Good.
A captured browse leaf's id IS its DriverAttributeInfo.FullName, and the fixed
tree emitted "{deviceHost}/{path}" there -- an internal cache key, not an
address. Both authoring paths wrote it verbatim into TagConfig.address, and
FocasAddress.TryParse accepts no such form, so the driver skipped the tags at
init.
Fixed at the emitter rather than by stripping the host at commit, which fixes
the browse-commit flow and the manual picker's tree-select together and leaves
one canonical address form:
- FocasAddress gains a fourth kind, FIXED:<path>, and moves to Contracts so the
AdminUI and ControlPlane can parse without referencing the runtime driver
(#526). A FIXED: read is served from the fixed-tree snapshot the poll loop
already maintains -- no area read, no connection. Writes refuse: nothing in
that tree is a writable location on the CNC.
- The address carries no device. A tag's device comes from its Device row, and
a second routing channel for one fact is what created this defect.
- An authored FIXED: tag arms the fixed-tree poll loop by itself. Enabled
defaults false and the browser force-enables it only for a browse, so the
operator would otherwise browse, commit, deploy, and land on a driver whose
loop never starts -- every tag Bad with a correct address.
- Fixed-tree values are now dated from the last answered poll and go
BadCommunicationError once it is stale (8 cadences, floored at 30s). The poll
loop swallows a failed tick by design, so a dead CNC would otherwise serve its
last snapshot as Good indefinitely -- harmless while nothing could bind to the
tree, not harmless now.
Guardrails, so this class cannot recur silently:
- FocasTagConfigModel.Validate() runs the real parser instead of a non-empty
check, and FocasTagDefinitionFactory.Inspect() warns at the deploy gate, which
covers CSV/API config that never touches the modal.
- The manual picker offered axis/spindle/program/status "parameter groups" --
none of which is a FOCAS addressing space -- and its own default value,
axis:5, was unusable. It now composes PMC / PARAM: / MACRO: through
FocasAddress, so what it emits is parseable by construction.
Tests assert addresses ROUND-TRIP through the parser rather than matching an
expected string: the previous FocasAddressBuilderTests pinned "axis:5" exactly,
which is how a green suite coexisted with a picker nobody could use. Verified
red-first against the old emitter. FOCAS 308, AdminUI 1095, ControlPlane 169,
Core 581 -- all pass, 0 warnings.
The remaining half of #540 -- a driver reporting Healthy/0 errors while
skipping tags at init -- is fleet-wide (eight drivers do this) and is filed
separately rather than patched per-driver.