Joseph Doherty 3de2cc3ba8 fix(opcuaclient): alarm index survives namespace reorder; match condition node first; ack with real EventId (#619 review)
The alarm index was keyed on ns=N strings resolved once at subscribe time, while an
in-place SDK reconnect transfers the subscription without re-running it - a remote
namespace reorder silently orphaned every alarm tag. Keys are now nsu= on both sides.
Events match the authored nodeId against the event's ConditionId first, then its
SourceNode, so several conditions on one source can be authored 1:1. Acknowledge
passes the EventId of the event that named the remembered condition (paired, so node
and EventId can never come from different conditions) instead of an empty one.