N2: pre-#741 rows carry region/address beside an addressString with no marker (the old driver never read the string, the old model preserved it as an unknown key). The r1 rule resolved those from the string - a silent remap or BadNodeIdUnknown on upgrade. The driver now loads from region+address whenever both are present (classic, editor-pinned, pre-lane); only a blob with NO keys is string-only and resolved through the parser. This is safe because the model no longer stamps keys onto a string-only tag. The model distinguishes string-only / legacy-string-beside-keys / pinned, and the editor hint says so. Test matrix over every persisted shape (keys only, pre-lane keys+string, pre-lane stamped HR/0+string, string only, marker+keys, marker no keys) under every family; the pre-lane row also through a model save and a CSV export->import. n5: a typed CSV address cell is an authored address - it drops addressString and the marker (new CsvTypedColumn.ClearsKeys) instead of being discarded. n6: Validate skips the region/dataType/byteOrder enum checks on a string-only tag (the driver ignores them). n7: docs/v2/modbus-addressing.md restates the key-presence rule. Refs #741 Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
OtOpcUa
OPC UA server (.NET 10 AnyCPU) that exposes a fleet of industrial drivers as a single OPC UA address space. Drivers ship in-process for AVEVA System Platform Galaxy (via the sibling mxaccessgw repo), Modbus TCP, Siemens S7, Allen-Bradley CIP (ControlLogix / CompactLogix), Allen-Bradley Legacy (SLC 500 / MicroLogix), Beckhoff TwinCAT (ADS), FANUC FOCAS, OPC UA Client (gateway), and MQTT (broker subscribe; Sparkplug B in progress).
A cross-platform client stack (.NET 10) — shared library, CLI, and Avalonia desktop app — connects to any OPC UA server.
Architecture
OPC UA Clients (CLI, Desktop UI, 3rd-party)
|
v
+-------------------------------------+
| OtOpcUa.Server (.NET 10 AnyCPU) |
| address space + capability fan-out|
+-------------------------------------+
| | | | | | | |
Galaxy Modbus S7 AbCip AbLeg TwinCAT FOCAS OpcUaClient MQTT
|
v
mxaccessgw (sibling repo, gRPC)
|
v
MXAccess COM (x86 worker, on AVEVA box)
Galaxy is the only driver with an external runtime: it speaks gRPC to a separately installed mxaccessgw server (sibling repo at c:\Users\dohertj2\Desktop\mxaccessgw\) which owns the MXAccess COM apartment and the x86/STA bitness constraint server-side. Everything in this repo is platform-agnostic .NET 10.
Prerequisites
- .NET 10 SDK (server, drivers, clients all target .NET 10)
- SQL Server reachable for the central config DB
- For Galaxy specifically: a running
mxaccessgwdeployment — see docs/v2/Galaxy.ParityRig.md - For historian read-back / alarm history / continuous historization: a running
ZB.MOM.WW.HistorianGatewaydeployment (the sole historian backend; consumed as theZB.MOM.WW.HistorianGateway.ClientgRPC package). It must runRuntimeDb:Enabled=true+RuntimeDb:EventReadsEnabled=true, and the API key must carryhistorian:read+historian:write+historian:tags:writescopes.
Quick Start
dotnet restore ZB.MOM.WW.OtOpcUa.slnx
dotnet build ZB.MOM.WW.OtOpcUa.slnx
dotnet test ZB.MOM.WW.OtOpcUa.slnx
# Run the server in dev (foreground)
dotnet run --project src/Server/ZB.MOM.WW.OtOpcUa.Host
The server starts on opc.tcp://localhost:4840 with the None security profile. Configure Security.Profiles in src/Server/ZB.MOM.WW.OtOpcUa.Host/appsettings.json to enable Basic256Sha256-Sign or Basic256Sha256-SignAndEncrypt. See docs/security.md.
Install as Windows Services
Production deployment is driven by scripts/install/Install-Services.ps1, which registers the OtOpcUa server service under a chosen service account. Historian support requires a separately deployed ZB.MOM.WW.HistorianGateway and Galaxy support a separately installed mxaccessgw — neither this repo nor the install script provisions them.
.\scripts\install\Install-Services.ps1 `
-InstallRoot 'C:\Program Files\OtOpcUa' `
-ServiceAccount 'DOMAIN\svc-otopcua'
The historian backend is the external ZB.MOM.WW.HistorianGateway (not installed by this script). See the script header and docs/ServiceHosting.md for full options.
Client CLI
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- connect -u opc.tcp://localhost:4840
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- browse -u opc.tcp://localhost:4840 -r -d 3
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- read -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode"
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- write -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -v 42
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- subscribe -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -i 500
See docs/Client.CLI.md and docs/Client.UI.md.
Documentation
Architecture deep-dives
| Topic | Doc |
|---|---|
| OPC UA server composition, namespace fan-out, Polly invoker | docs/OpcUaServer.md |
| Address space layout | docs/AddressSpace.md |
| Read / Write dispatch (driver vs virtual vs scripted-alarm) | docs/ReadWriteOperations.md |
| Incremental sync (driver-backend rediscovery + config publishes) | docs/IncrementalSync.md |
| Service hosting (Server + Admin; external HistorianGateway backend) | docs/ServiceHosting.md |
| Security (transport, LDAP, certificates) | docs/security.md |
| Redundancy | docs/Redundancy.md |
| Status dashboard | docs/StatusDashboard.md |
Drivers
| Topic | Doc |
|---|---|
| Driver specs (per-driver capability surface, config, addressing) | docs/v2/driver-specs.md |
| Galaxy driver | docs/drivers/Galaxy.md |
| Modbus / S7 / AbCip / AbLegacy / TwinCAT / FOCAS / OpcUaClient / MQTT | docs/drivers/ |
| Galaxy parity rig (mxaccessgw setup) | docs/v2/Galaxy.ParityRig.md |
| Galaxy performance + tracing | docs/v2/Galaxy.Performance.md |
Clients
| Topic | Doc |
|---|---|
| Client CLI | docs/Client.CLI.md |
| Client UI (Avalonia desktop) | docs/Client.UI.md |
v1 archive
The original v1 in-process MXAccess docs (Galaxy.Host topology, Configuration env vars, AlarmTracking, DataTypeMapping, HistoricalDataAccess, Subscriptions, etc.) are preserved under docs/v1/ — historical reference only. PR 7.2 retired the v1 architecture on 2026-04-30; current state is documented in the sections above.
License
Internal use only.