The gate closed both follow-ups on the docker-dev rig and found a third defect
that offline tests could not have found first: it lived behind the one being
fixed. Once 0.1.2 made back-fill work, a rebuilt node could be observed writing
for the first time — and its writes went nowhere, because the healthy node kept
the old peer's seq watermark. Library 0.1.1 -> 0.1.2 -> 0.1.3 over the course
of the gate; both consumers now pinned to 0.1.3.
Check 4 (was PARTIAL, now PASS): with SQL stopped and site-a-2's LocalDb volume
destroyed, a-1 logged "Snapshot sent (as_of_seq 0, 4 rows)" — a line that could
not appear on 0.1.1 — and a-2 came back with a row_version dump byte-identical
to a-1's, carrying a-1's origin node ids and its ORIGINAL applied_at_utc. It
then booted from cache and served 17 ns=2 nodes, diff-identical to its peer,
from a configuration it never applied and could not have fetched.
Check 8 (PASS): two restarts with an unchanged artifact left the oplog at 7 and
the pointer timestamp frozen — the re-cache was skipped outright. Positive
control: a real config change still wrote, 7 -> 10 -> 13.
Also records one unrelated pre-existing finding the gate's SQL flapping
surfaced: a transient ConfigDb error during artifact load empties the served
address space while logging "rebuild becomes no-op". The cache layer correctly
refused to store the bad artifact and the node recovered on restart, but the
two logs disagree and it is the same class as the Phase 1 gate's check-3
defect. Untouched by this work; wants its own issue.
Claude-Session: https://claude.ai/code/session_01GASWkNEi68FSCtvr6rLoEW
1. Wiped-node back-fill (live gate check 4). Fixed upstream in
ZB.MOM.WW.LocalDb 0.1.2 and pinned here. The gate's diagnosis was slightly
off: the oplog cap was not the gate. Snapshot detection measured the peer's
gap against the oldest surviving oplog row and read an empty oplog as "no
gap possible" — and an empty oplog is the steady state of a converged pair,
since ack-pruning deletes everything the peer confirmed. The healthy state
was the one state that could not heal a wiped peer. Now measured against
last_acked_seq when the oplog is empty.
Pinned at this level too, not just the library's: the pair harness grows a
WipePassiveAsync (a NEW database — a rebuilt node comes back with a new node
id and a zero watermark), and the new scenario asserts the emptied oplog as
its precondition before wiping, then requires the deployment artifact to
come back byte-identical with no new deploy. Verified RED against the pinned
0.1.1 (times out waiting for back-fill) and green on 0.1.2.
2. Oplog growth on default-OFF nodes (live gate check 8), fixed at the source:
StoreAsync now skips entirely when the pointer already names this
deployment/revision, the SHA matches the bytes, and the expected chunk count
is present. Re-caching an artifact the node already holds — every restart's
boot-from-cache, every RestoreApplied — writes nothing and mints no oplog
rows, where before it cost a delete plus an insert per chunk plus a pointer
update, all identical to what was already there.
Identity is over the bytes and the chunks are counted, both deliberately: a
re-composed artifact can carry the same ids with different bytes, and a
pointer can name a deployment whose chunks are missing, where skipping would
make an unreadable cache permanent. Both guards verified RED against a naive
pointer-only skip.
The gate's stated bound was also wrong and is corrected in the doc: growth
was never headed for the 1M row cap. AddZbLocalDbReplication is registered
unconditionally, so MaintenanceBackgroundService runs on default-OFF nodes
and the 7-day MaxOplogAge cap prunes.
Runtime.Tests 412/0/31, Host.IntegrationTests LocalDb 45/45. Pre-existing and
unrelated: AbCip_Green_AgainstSim (needs the AB CIP docker fixture, red on a
clean master too) and a flaky Roslyn race test (green 2/2 in isolation).
Claude-Session: https://claude.ai/code/session_01GASWkNEi68FSCtvr6rLoEW
Records the docker-dev live gate: 8/8 checks pass (check 4 with a documented
limitation). The gate caught four real defects every offline test missed — the
NU1101 packageSourceMapping gap, the ASPNETCORE_HTTP_PORTS re-bind, the empty
address space on boot-from-cache, and the cache not repopulating on
RestoreApplied — all fixed on-branch with regression tests. Two limitations
documented as follow-ups: no replication back-fill of a fully-wiped node, and
oplog growth on default-OFF nodes.
Offline sweep: full-solution build 0 errors (824 pre-existing OTOPCUA0001
analyzer warnings live in driver test projects, none in LocalDb files);
no LiteDB/LocalCache code references remain (2 explanatory doc-comment lines
allowed); Runtime.Tests 407/0/31 twice (flagged intermittent not reproduced);
Host.IntegrationTests LocalDb subset 40/0/0. Full-solution test suite with
stash-baseline deferred to CI/live gate — infra-gated suites cannot run offline
on macOS. Not merged to master; live gate (Task 16) awaits operator go-ahead.
New operations runbook (enable/disable, fail-closed ApiKey rule, stop/start-
together, tombstone-retention window, MaxBatchSize row-count-vs-4MB, never
sqlite3-a-live-WAL-DB cp-triplet recipe). Configuration.md gains a LocalDb
section; Redundancy.md gains a pair-local config cache section (what boot-from-
cache does and does not cover); CLAUDE.md gains the Phase 1 scope paragraph.
Never registered in DI and dead since Phase 6.1. Keeping two unwired cache designs
invites the next reader to wire the wrong one.
Deletes all three test files - LiteDbConfigCacheTests.cs was missing from the plan's
list and would have failed to compile (it calls new LiteDB.LiteDatabase directly).
StaleConfigFlagTests lives inside ResilientConfigReaderTests.cs, so it goes too.
The XML-doc reference in ILdapGroupRoleMappingService is rewritten rather than removed:
it now records that no sign-in fallback exists and that reviving one means an admin-side
cache on LocalDb.
Post-implementation review (HIGH finding) noted #478's mux-delivered
input-quality path does not cover a driver comms-loss: a poll driver
(Modbus/S7) whose device goes unreachable emits only ConnectivityChanged and
goes silent on the value feed, so a scripted alarm keeps the last Good value.
The code as shipped faithfully implements #478's written scope (worst of input
tags' qualities via the dependency mux). The comms-loss bridge for scripted
alarms (symmetric of native #477-L2, plus the null-value/cold-start asymmetry
and its VT-quality ripple) is tracked as #481. Docs updated in
AlarmTracking.md + the design doc.
Layer 3 of #477: a scripted alarm's condition Quality now reflects the WORST
quality across its input tags, mirroring the native OT semantic (#477 L2).
Plumbing (quality was silently discarded twice on the live path):
- VirtualTagActor.DependencyValueChanged gains Quality (defaulted Good); the
DependencyMuxActor forwards the published AttributeValuePublished.Quality it
already carried; ScriptedAlarmHostActor.OnDependencyChanged pushes the real
quality into the engine (was hardcoded 0u/Good).
Engine (Core.ScriptedAlarms):
- ScriptedAlarmEngine computes worst-of-input quality each eval (skipping
not-yet-published inputs, which are a readiness concern, not a quality signal)
and carries it on ScriptedAlarmEvent.WorstInputStatusCode.
- A real transition carries the current worst quality so ToSnapshot's full
snapshot doesn't clobber quality back to Good (e.g. transition while Uncertain).
- A Bad input freezes the condition (no transition), like a comms-lost native
driver; a quality-bucket change with no transition emits the new
EmissionKind.QualityChanged, routed to the existing #477-L2
AlarmQualityUpdate -> WriteAlarmQuality node path (quality only, no /alerts
row, no historian write). ScriptedAlarmSource skips QualityChanged so it never
fabricates a phantom IAlarmSource event.
Host: ToSnapshot maps WorstInputStatusCode -> OpcUaQuality; OnEngineEmission
routes QualityChanged out of band.
Tests (TDD, RED-first): engine worst-carry + Bad/restore QualityChanged +
unchanged-bucket-no-emit; source swallows QualityChanged; mux forwards quality;
host Bad-dep -> AlarmQualityUpdate(no alerts) + transition snapshot carries worst.
Docs: AlarmTracking.md Layer-3 section + design doc.
Closes#478
Part 9 ConditionType.Quality was never assigned; default(StatusCode)==Good
so every native + scripted condition reported Good unconditionally — a
comms-lost device still showed a healthy, inactive, Good condition (a
wrong-VALUE bug, distinct from the null-value #473/#475). Clients (and HMIs
bucketing on IsGood) could not tell "genuinely inactive" from "lost contact".
Layer 1 — make Quality a real, plumbed field:
- AlarmConditionSnapshot gains OpcUaQuality Quality (default Good).
- MaterialiseAlarmCondition sets it (native BadWaitingForInitialData, scripted Good).
- WriteAlarmCondition projects snapshot.Quality; the delta-gate gains a Quality
member so a quality-bucket change fires a Part 9 event.
Layer 2 — drive native quality from driver connectivity (a comms-lost driver
emits no alarm transitions, and an alarm-bearing raw tag has no value variable,
so quality can't come from either existing channel):
- DriverInstanceActor Tells parent ConnectivityChanged on Connected/Reconnecting.
- DriverHostActor fans it to every native condition the driver owns as
OpcUaPublishActor.AlarmQualityUpdate (Good on connect, Bad on disconnect).
- New dedicated IOpcUaAddressSpaceSink.WriteAlarmQuality sets ONLY Quality and
fires only on a bucket change — never touches Active/Acked/Retain (an active
alarm that loses comms stays active). Not a full-snapshot re-projection, so it
can't clobber severity/message and works for a never-fired condition.
Forwarded through DeferredAddressSpaceSink (F10b trap; auto-verified by the
reflection forwarding guard). Ungated by redundancy role; no /alerts row.
Scripted conditions stay Good; worst-of-input quality deferred to #478 (Layer 3).
Tests: node-level (materialise/project/no-clobber/unknown-node no-op),
NativeAlarmProjector, DriverInstanceActor connectivity emission, DriverHostActor
fan-out, OpcUaPublishActor routing, and the wire-level guard
(Condition_event_Quality_tracks_source_connectivity_on_the_wire) — RED-verified
against a simulated pre-fix always-Good server. Existing DriverInstanceActor
parent probes ignore the new ConnectivityChanged.
Docs: docs/AlarmTracking.md §"Condition source-data Quality (#477)";
design doc docs/plans/2026-07-17-alarm-condition-quality-477-design.md.
MaterialiseAlarmCondition never assigned the mandatory Part 9 ConditionType
classification fields, so every condition event — native and scripted — shipped
ConditionClassId = NodeId.Null (i=0) and ConditionClassName = empty text. Same
mechanism as #473: Create() builds the mandatory children from the type's
embedded definition but leaves them unset, and nothing downstream synthesises
them (ReportEvent / InstanceStateSnapshot copy children verbatim). An HMI
bucketing alarms by condition class dropped every OtOpcUa alarm as unclassified.
Report BaseConditionClassType — Part 9's "no condition class modelled" value.
This is the honest report: we hold no classification at the materialise seam.
Deliberately NOT ProcessConditionClassType (the SDK sample's pick), which would
assert a classification we cannot back and would be actively wrong for a Galaxy
alarm whose upstream category is Safety/Diagnostics — trading a detectable null
for an undetectable lie. Real per-alarm classification needs the driver's
AlarmCategory carried to this deploy-time seam (it lives only on the runtime
AlarmEventArgs transition today) and is a separate feature.
Guards, both observed RED against the pre-fix server:
- NativeAlarmEventIdentityFieldDeliveryTests: wire-level, its own select clause
(the #473 test's clause mirrors ScadaBridge's exactly and its indices are
load-bearing, so it is left untouched). The class fields are declared on
ConditionType, not BaseEventType, so they are selected against that type.
- NodeManagerAlarmSourceFieldsTests: node-level, native (Raw) + scripted (Uns).
Stacked on #473 (PR #474) — merge after it.
MaterialiseAlarmCondition never assigned the three mandatory BaseEventType
identity fields, so all three arrived null on every condition event — native
and scripted. The SDK does not synthesise them on this path: Create() builds
the children from the type definition but leaves them unset, the auto-filling
BaseEventState.Initialize overload is only used for transient events, and
ReportEvent / InstanceStateSnapshot copy children verbatim. A conforming
client could not attribute an alarm to its source.
EventType = the concrete materialised type (TypeDefinitionId)
SourceNode = the condition's own NodeId (== ConditionId) — the condition IS
the source; an alarm-bearing raw tag materialises only the
condition, with no sibling value variable
SourceName = the same identifying id string: RawPath (native) /
ScriptedAlarmId (scripted)
SourceName carries the unique id rather than the leaf name: the leaf collides
across devices (HR200 on two PLCs) and is already carried by ConditionName, so
nothing is lost. Documented in docs/AlarmTracking.md, including that clients
must key on ConditionId and must not compose SourceName with ConditionName,
and that SourceName is NOT a live<->history join key (the alarm-history writer
stamps it with the EquipmentPath — a pre-existing divergence, now called out).
Tests: NativeAlarmEventIdentityFieldDeliveryTests is the wire-level guard —
a real client subscription using the standard [EventType, SourceNode,
SourceName, Time, Message, Severity] select clause, verified to fail against
the pre-fix server. NodeManagerAlarmSourceFieldsTests guards the node across
both realms, the base-type fallback, and the kind-swap re-materialise.
The HistoryRead events projection is a separate path (it projects historian
rows, not node fields) and is unaffected — its EventType => Variant.Null
assertions still hold.
OtOpcUa is Akka-clustered and AddZbSecrets is registered unconditionally, so every
node (admin, driver, fused) resolves secrets and needs the SAME KEK + same store rows.
Ship G-5 as a production-posture runbook rather than hardcoding Source=File + shared
paths into the committed role-overlay appsettings (which dev + TwoNodeClusterHarness
also consume — that would break every dev/CI boot). Base appsettings stays on
Source=Environment. Documents the interim File-KEK + shared-SQLite posture and the
G-7 hand-off (ConfigDb-backed ISecretStore mirroring the existing DP
PersistKeysToDbContext<OtOpcUaConfigDbContext> key-ring sharing). Cross-linked from
docs/security.md. Mirrors the ScadaBridge G-5 resolution.
OtOpcUa commits no plaintext secrets — the only secret-shaped committed value is
ServerHistorian:ApiKey='' (empty, disabled by default). Because the pre-host expander
is fail-closed AND section-agnostic, hard-committing a ${secret:} token would break
every dev/CI/integration boot for zero at-rest benefit. Instead document the token
delivery convention for all five config secrets (jwt/ldap/deploy/configdb/historian)
in docs/security.md and note the token option in the ServerHistorian comments.
Mechanism proven live: unseeded token boot fails with SecretNotFoundException at
pre-host expansion; seeded token resolves and boot proceeds. Behavior-neutral
(comment + doc only).
Uns.md Tags section rewritten to the reference-only model (UnsTagReference list,
cluster-scoped picker, effective-name uniqueness, {{equip}}/RefName); CLAUDE.md
gains a v3 Batch 3 paragraph. ScriptEditor.md was updated by WP4.
Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
Live-verified on docker-dev: AbCip picker renders Browse button (full CanBrowse chain), clicking
it runs the universal-browser capture in production (central-2 logs) with PatchForBrowse
demonstrably applied (@tags walk ran without the authored config setting EnableControllerBrowse);
error surfaces gracefully. Modbus picker shows NO Browse button (negative). Populated tree-render
is fixture-blocked — ab_server returns ErrorUnsupported for the controller @tags walk (test sim
limitation, not a code defect). Two follow-ups recorded: (1) full tree-render needs a symbol-browse
capable AB backend; (2) driver-page pickers don't pass live config to the picker body.
Task 14/15/16: each picker body keeps its manual builder and appends a DriverOperator-gated
browse affordance (mirrors OpcUaClientAddressPickerBody) — Browse/Refresh/Close, DriverBrowseTree
over the universal DiscoveryDriverBrowser session, leaf-only commit (OnNodeSelected fires for
folders too), snapshot-at-open label, fire-and-forget close on dispose. _canBrowse evaluated once
in OnInitializedAsync (CanBrowse constructs a throwaway driver). FOCAS commits the leaf FullName
directly (the group/id builder can't reconstruct it). Editors pass DriverType + GetConfigJson
through. Razor-live-verified at Task 18.
Task 9: DiscoverTreeAsync UntilStable settle loop (FOCAS) — re-capture on a 1s interval until
the node set is non-empty and stable across two passes, bounded by open-timeout; on
timeout with a prior non-empty capture, return it (best-effort) instead of failing.
Task 11: BrowserSessionService resolves bespoke-first, falls back to IUniversalDriverBrowser
when no bespoke browser matches and CanBrowse is true; new CanBrowse on the service.
16 unit tests green (4 settle + 12 service).
Task 3/4/5: SupportsOnlineDiscovery => true on AbCipDriver, TwinCATDriver, FocasDriver
(their device enumeration is real, config-gated on EnableControllerBrowse / FixedTree.Enabled
which PatchForBrowse guarantees at open). One gate fact per driver test project.
Every concern the 7-agent review parked is now decided and integrated:
- universal browser: in-flight capture coalescing keyed (driverType,
config-hash) + global cap of 4 concurrent captures; CanBrowse catches a
throwing TryCreate and defensively shuts down the throwaway instance;
cleanup ShutdownAsync bounded at 10s (R2-01); picker Refresh = close +
re-capture. Coalesced sessions share an immutable tree, so DisposeAsync
drops the session's reference, not the tree.
- mtconnect: UNAVAILABLE pinned to BadNoCommunication (fleet's
BadCommunicationError stays reserved for the driver's own transport
failures); TIME_SERIES sampleCount flows into ArrayDim; Subscribe timeout
bounds only the stream-start handshake; library version/TFM folded into
the license checklist.
- mqtt: browse rebirth is an explicit DriverOperator-gated "Request rebirth"
button (RequestRebirthAsync(scope)) - never fired by open/root/expand;
hand-rolled reconnect loop committed for P1 (MQTTnet v5 dropped
ManagedMqttClient); Wave-2-start library re-verification checkbox;
implement from the Sparkplug v3.0 spec text.
- bacnet: P1 opens with a first-spike checklist (package TFM, BBMD/
segmented-RPM/COV API smoke, unicast-I-Am fixture behavior); AdminUI-node
browse registers a second foreign device - BBMD FD-table sizing note.
- sql-poll: split-node browse needs env parity for Sql__ConnectionStrings__
refs on admin nodes (actionable error + session-only pasted literal);
one-row-per-key query contract (last-wins + rate-limited warning);
absent key -> BadNoData; operationTimeout > commandTimeout authoring rule;
Browser->Driver.Sql SqlClient transitive on AdminUI accepted on record.
- omron: FINS framer gated on W227 + live golden vectors; CIP string layout
is the first P1 live-gate item; AbCip harness static-init anti-pattern
note; writable-defaults-true operator warning.
- modbus-rtu: first P1 step confirms pymodbus exposes framer=rtu on a TCP
server (custom-script fallback otherwise).
- program doc: new cross-cutting rule - driver ctors must be connection-free
(the universal browser's CanBrowse throwaway instances depend on it).
Per user decision 2026-07-15: the direct-serial transport (ModbusRtuTransport,
System.IO.Ports, serial config fields, socat live rig) is not being built.
Serial RS-485 buses are reached exclusively via serial->Ethernet gateways
(Moxa NPort etc.) using the new ModbusRtuOverTcpTransport — zero new package
deps, no container device mapping, reuses the hardened socket lifecycle.
ModbusTransportMode shrinks to Tcp|RtuOverTcp (Rtu member reserved). The
direct-serial design is kept in the RTU doc's §2b as a marked record,
including the R2-01 SerialPort-BaseStream-ignores-ReadTimeout trap.
Adds the driver-expansion program design (umbrella: universal Discover-backed
browser + MTConnect, MQTT/Sparkplug B, BACnet/IP, SQL poll, Omron, Modbus RTU;
MELSEC deferred) plus the per-driver research reports.
All docs went through a 7-agent parallel review against the codebase before
this commit. Highlights fixed in review:
- universal browser: FOCAS FixedTree fills post-connect -> UntilStable settle
+ FixedTree.Enabled patch; MQTT reconciled to bespoke (was contradicting the
program doc's SupportsOnlineDiscovery=false verdict)
- modbus-rtu: SerialPort.ReadTimeout doesn't bound async BaseStream reads ->
linked-CTS per-op deadline (R2-01 class); BCL enum reuse would leak
System.IO.Ports into Contracts
- bacnet: DiscoveryRediscoverPolicy enum name; UDP 47808 contention; live
suite rewritten around unicast Who-Is + BBMD (broadcast doesn't cross VMs)
- sql-poll: real tier registration via DriverFactoryRegistry.Register;
blackhole gate must not docker-pause the shared central SQL Server
- mqtt: Sparkplug v3.0 STATE topic form; first-in-repo proto codegen noted
- omron: host hardcodes isIdempotent:false today (retry seam unshipped);
v1 scopes UDTs to dotted-leaf access
- mtconnect: SecurityClassification.ViewOnly; factory ParseEnum<T> pattern
- program doc: both valid enum-serialization patterns; IRediscoverable is
change-signal-gated; RTU P2 adds System.IO.Ports; label is host-side
#420 (filed 2026-05-01 as '4 inert scaffolds + D.1 smoke') is stale. Current
master + the mxaccessgw sibling repo show the feature landed on both sides:
- mxaccessgw A.2/A.4: native alarms served via the wnwrap consumer
(WnWrapAlarmConsumer over WNWRAPCONSUMERLib.wwAlarmConsumerClass) +
FailoverAlarmConsumer + AlarmDispatcher; StreamAlarms active-alarm snapshot
(20 alarms verified live). The WM_APP-pump premise this issue was written
against was ruled out by the 2026-05-01 probes; the design pivoted to wnwrap.
- mxaccessgw A.3: NotWiredAlarmRpcDispatcher gone (only in generated proto);
ack routes MxGatewayClient.AcknowledgeAlarmAsync -> AlarmClient.AlarmAckByGUID.
- lmxopcua: GalaxyDriver : IAlarmSource wires GatewayGalaxyAlarmFeed
(-> OnAlarmEvent, native metadata incl. operator-comment) + inbound ack via
GatewayGalaxyAlarmAcknowledger; native feed live-proven by
GatewayGalaxyAlarmFeedLiveTests.
- C.1 (SdkAlarmHistorianWriteBackend / aahClientManaged): SUPERSEDED. The whole
Wonderware sidecar was retired; alarm-history writes cut over to the
HistorianGateway (GatewayAlarmHistorianWriter, SendEvent path), live-verified
2026-07-15 (R2-06/R2-08, 6/6). The target no longer exists in the tree.
Updated the alarms-over-gateway.md banner (final reconciliation) + the
alarms-d1-smoke-artifact.md status note. Sole residual = a Windows-parity-rig
running-server OPC UA A&C round-trip (needs live Galaxy + human IDE).
Corrects the #459 finding. 2-node keep-oldest recovery works fine (the ScadaBridge
sister project proves it); OtOpcUa was missing the supervision pieces that make it
automatic, and docs/Redundancy.md wrongly claimed in-place oldest-crash failover.
Mechanism (confirmed on a 2-container rig + by decompiling Akka KeepOldest.OldestDecision):
on an OLDEST-node crash keep-oldest downs the LONE survivor (DownReachable including
myself) — down-if-alone can't rescue a lone survivor (its branch needs >=2 survivors).
Recovery is exit-and-rejoin: run-coordinated-shutdown-when-down terminates the node and
the service supervisor restarts it. My earlier 'total outage' was a docker-dev artifact
(no restart policy); production Install-Services.ps1 already has sc.exe failure restart.
Changes (ScadaBridge parity):
- ActorSystemTerminationWatchdog (Host, registered after AddAkka): watches
ActorSystem.WhenTerminated and on an unexpected self-down calls StopApplication so the
process exits (supervisor restarts it) instead of idling with a dead actor system.
Distinguishes graceful shutdown via _stopRequested + ApplicationStopping. 3 unit tests.
- docker-dev: restart: unless-stopped on the host anchor (models production supervision) +
both redundancy peers in SeedNodes so a restarted node re-forms via either peer.
- docs/Redundancy.md: rewrote the split-brain recovery section — younger-loss = in-place
fast failover; oldest-loss = exit-and-rejoin under supervision (not in-place); the three
requirements (supervisor + watchdog + both-node seeds); flagged HardKillFailoverTests as
non-representative (Transport.Shutdown, not a real crash). Instant in-place takeover on
ANY single loss needs 3+ members.
Cluster.Tests 29/29 (SBR guards), watchdog tests 3/3, full solution builds.
Live re-verify of the watchdog image pending (host docker disk full).
The historian's Int1 analog-tag creation path is server-degenerate:
EnsureTags(Int1) stores an unusable stub (live-probed on the deployed
2023 R2 historian; root-caused + documented gateway-side in
HistorianGateway #11 / PR #16). HistorianTypeMapper mapped
DriverDataType.Boolean -> HistorianDataType.Int1, so Boolean historized
tags failed auto-provisioning.
Map Boolean -> Int2 instead (store 0/1). Int2 is a proven-creatable
analog type, and the value-write path already sends every value as a
double on WriteLiveValues regardless of tag type, so Boolean 0.0/1.0
round-trips cleanly. Both Float and Int2 are supported, so a
pre-existing Float Boolean tag retypes cleanly on its next deploy.
- HistorianTypeMapper: Boolean => Int2 (+ remarks)
- Unit pins: HistorianTypeMapperTests, GatewayTagProvisionerTests
(Boolean_definition_carries_explicit_Int2_presence)
- Live gate: EnsureTags_boolean_sandbox_provisions_as_Int2 (was _Int1);
retype probe reframed Float->Int2 (drops the dead Int1 leg)
- Docs: docs/Historian.md 'Boolean historization maps to Int2', CLAUDE.md,
archreview STATUS.md (R2-06 live gate -> 6/6)
Resolves#441.
- StorageRateMs bug found+fixed (PR #439); live suite 3/6 -> 5/6
- U-7: EnsureTags is a real upsert; supported-type retype ACCEPTED (Float->Double);
Int1 not creatable on this histsdk (ProtocolEvidenceMissingException, Int1-only)
- record the observed retype policy in docs/Historian.md (fills the placeholder)