Joseph Doherty e16146fa0c fix(adminui): close a browse session that opens after its picker is gone (R04 L4)
Every picker and RawBrowseModal stored the OpenAsync token after the await; if
the host was disposed (or the modal closed) meanwhile, its teardown had already
run with no token, so the plant-side session lived until the reaper's idle TTL.
BrowseOpenGuard.CloseIfOrphaned closes it at once; each host sets _disposed
first thing in DisposeAsync (RawBrowseModal also treats !Visible as gone).

Refs #745
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:51:34 -04:00
Joseph Doherty 1313b94097 fix(adminui): /alarms-historian says when the role runs no historian; Fleet-style lifecycle (R04 L3)
A bare catch {} turned every failure - including an admin-only node with no
historian actor - into 'Loading...' forever, and a tick queued after a sync
timer dispose still issued an Ask. HistorianSinkStatusReader classifies a poll
as Available / NotOnThisRole (permanent: shown once, polling stops) /
Unavailable (shown with the last good status and its read time). The page
follows Fleet.razor: IAsyncDisposable, _disposed, overlap guard, page CTS.

Refs #745
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:47:30 -04:00
Joseph Doherty 4b594ec525 fix(adminui): Test Connect honours the configured probe timeout; drain its clear timer (R04 L2, G1-F5, F-FU2)
DriverTestConnectButton always sent a fixed 10 s, and the Galaxy/OpcUaClient
probes run under min(caller, configured), so ProbeTimeoutSeconds - documented
on every driver as the Test Connect timeout - could shorten a probe but never
lengthen it (Galaxy's 30 s default was silently 10 s). TestConnectBudget reads
the root ProbeTimeoutSeconds from the merged config at click time, clamped to
the actor's [1, 60] s, falling back to TimeoutSeconds. DeviceModal (the only
host) needs no change. The Galaxy/OpcUaClient form hints are reworded.

The 30 s result-clear timer moves from System.Timers.Timer + an async void
Elapsed lambda to System.Threading.Timer, drained in DisposeAsync, with a
generation so a superseded fire cannot clear a newer result.

Refs #745
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:45:39 -04:00
Joseph Doherty b0959f697b perf(adminui): cache the modals' DynamicComponent parameter dictionaries (R04 H2)
DriverConfigModal, DeviceModal and RawTagModal built a new parameter dictionary
and new EventCallbacks every render. ParameterDictionaryCache reuses the
dictionary while the values it carries are unchanged and rebuilds it with the
current value when one changes (a build-once cache would strand edits); the
callbacks are created once. Blazor still re-sets an EventCallback-bearing
child's parameters per parent render, so the forms' _lastParsed guards stay.

Refs #745
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:43:01 -04:00
Joseph Doherty 36e6ab590b perf(adminui): virtualize the CSV import grid; download exports from an endpoint (R04 P6)
The import review grid rendered every parsed row and re-scanned all rows three
times per render for its counts; RawCsvReviewView recomputes rows + counts once
per change and the grid renders through Virtualize. The export modal embedded the
whole CSV twice (textarea + base64 data: URI); it now shows a 50-line preview
and links to GET /api/raw/tags.csv (ConfigEditor, like /raw), which runs the same
RawTagCsvExport builder and sends it as an attachment.

Refs #745
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:40:40 -04:00
Joseph Doherty ce9679b671 feat(adminui): GET /api/deployments/{id}, the status resource the 202 Location names (R04 S5)
The deploy API's 202 pointed at a route that did not exist. The GET reads the
deployment (projected, no artifact blob) and its per-node apply states, and
carries the POST's own gate: API key in X-Api-Key, AllowAnonymous against the
cookie fallback, 503 while Security:DeployApiKey is unset.

Refs #745
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:36:54 -04:00
Joseph Doherty 2a788ed8ac perf(adminui): RawTree renders a flat Virtualize list, pages 500 per level, caches menus (R04 P5)
The recursive RenderNode rendered every row of an expanded device, and built a
fresh context-menu list + closures per node per render. RawTreeRows flattens the
expanded tree (explicit stack) into rows rendered by one Virtualize; each level
shows 500 children, then a 'Show more' row. RawNodeMenuCache keys menus weakly
on the node instance and rebuilds on a picker-mode or Enabled change.

Refs #745
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:33:45 -04:00
Joseph Doherty 10b83d69c5 perf(adminui): /scripts lists a projection and loads source per dialog (R04 P8)
The list loaded every script entity including SourceCode to render names and
hashes. ScriptListQueries projects {ScriptId, Name, Language, SourceHash} for
the list and fetches one script's source when its Source dialog opens, with a
generation guard against a superseded open.

Refs #745
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:30:50 -04:00
Joseph Doherty 8e69118200 perf(adminui): coalesce /script-log and /alerts renders with a ring buffer (R04 P7)
Each received event used to Insert(0) into a List and render the full page.
LiveTailBuffer queues events from the bridge thread into a bounded newest-first
ring; CoalescingRenderScheduler (TimeProvider-driven, drained on dispose)
flushes and renders at most once per 200 ms window. ScriptLog's filtered rows
are recomputed on flush/filter change instead of three times per render.

Refs #745
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:28:23 -04:00
Joseph Doherty 348ffaec1c perf(adminui): /hosts rebuilds driver rows on the tick, not per health publish (R04 P4)
OnSnapshotChanged used to re-project every cluster group and re-render the
whole page for each driver publish, per open tab. It now only marks a
CoalescingDirtyFlag; the 5 s tick rebuilds when the flag is set or the config
load changed (or evicted) anything.

Refs #745
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:28:23 -04:00
Joseph Doherty a04196d725 fix(adminui): evict unconfigured drivers from status stores; isolate throwing subscribers (R04 L1, L5)
The driver-status and resilience stores had no removal path, so a deleted
driver stayed on /hosts as a frozen row until restart. Both stores gain
RetainOnly, which /hosts calls after each successful config load (never on a
failed one).

The stores and InProcessBroadcaster now raise their events one subscriber at a
time, so a throwing handler cannot starve later subscribers or escape onto the
bridge actor. The alert/script-log bridges publish inside their try, and the
resilience bridge catches a store failure instead of restarting.

Refs #745
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:24:04 -04:00
Joseph Doherty 82380d2bee Merge lane G1: OpcUaClient + MTConnect driver remediation (#743)
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:16:20 -04:00
Joseph Doherty 92749402b5 fix(modbus): review r3 - one address authority (ModbusTagAddressResolution)
N3: a keyless blob carrying the addressResolved marker was served from its
string by the driver but saved as HR[0] by the editor model / CSV path. The
precedence rule now lives in ONE pure resolver in Driver.Modbus.Contracts
(ModbusTagAddressResolution.Classify/Resolve): keys when region+address are
both present, else a string-only addressString resolved with the driver's
family (refused when it cannot parse), else refused. The marker never decides.

Consumers that now ask it instead of restating it: the driver's tag reader
(ModbusTagDefinitionFactory.FromTagConfig), the deploy gate (Inspect /
DescribeRejection), the editor model (AddressShape / IsStringOnly /
HasKeyAddress / ResolveWith, ToJson stamping, Validate), the CSV export cells
and the editor hint. The model writes keys only when it loaded them or a field
was authored - never defaults it did not resolve (also closes two divergences
the new matrix found: malformed-string+marker and non-string addressString were
saved as HR[0]).

One table-driven test (ModbusAddressAuthorityAgreementTests) runs 15 persisted
shapes through driver, deploy gate, model load/save/Validate and the real CSV
export->import under all four families; breaking the CSV export or reverting
the model to the marker rule fails it.

Minors: m1 CSV address cells keep the string+marker while it still describes
them (lossless unchanged round trip), drop it when contradicted, and the review
grid reports the drop; m2 the pre-lane test uses the real export residual; m3
unmarked string-only + typed-cell case added; m4 stale docs/summary and the
unused factory parameter removed.

Refs #741

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 16:46:21 -04:00
Joseph Doherty f0d807e7b7 fix(opcuaclient): review r0 minors m1-m10
- m1: the form hint now says ProbeTimeoutSeconds can only shorten Test Connect's
  10 s budget (passing the configured value as the button's budget is shared code -
  follow-up).
- m2: a superseded init no longer overwrites _options (generation-checked under
  _probeLock) or the cert-validation handler (handed back and published with the
  session; detached when not installed; a previous one detached on replace).
- m3: an ack none of whose condition ids resolves throws BadNodeIdUnknown + Warning.
- m4: an ack with no reply (transport failure / non-caller timeout) degrades.
- m5: no session before the gate is the same ServiceResultException(BadNotConnected).
- m6: the caller-cancelled-write deviation is documented.
- m7: a reply during a published outage advances the stamp but does not write
  Healthy; the keep-alive recovery ends the outage.
- m8: test for a non-caller OperationCanceledException write -> Degraded.
- m9: the browse session owns and disposes the user certificate it loaded
  (OpcUaUserIdentityFactory.LoadCertificate; a key-less cert is disposed before the
  throw); AdminUI-host certificate path documented.
- m10: a subscribe overtaken by a shutdown / re-init removes its half-built
  subscription instead of registering it (data and alarm).
- Sync Dispose drains each gate for 500 ms (was 2 s).

Refs #743

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 16:42:29 -04:00
Joseph Doherty 0200619322 fix(modbus): review r2 - region+address keys always win; string-only means no keys
N2: pre-#741 rows carry region/address beside an addressString with no marker
(the old driver never read the string, the old model preserved it as an
unknown key). The r1 rule resolved those from the string - a silent remap or
BadNodeIdUnknown on upgrade. The driver now loads from region+address whenever
both are present (classic, editor-pinned, pre-lane); only a blob with NO keys
is string-only and resolved through the parser. This is safe because the model
no longer stamps keys onto a string-only tag. The model distinguishes
string-only / legacy-string-beside-keys / pinned, and the editor hint says so.
Test matrix over every persisted shape (keys only, pre-lane keys+string,
pre-lane stamped HR/0+string, string only, marker+keys, marker no keys) under
every family; the pre-lane row also through a model save and a CSV
export->import.
n5: a typed CSV address cell is an authored address - it drops addressString
and the marker (new CsvTypedColumn.ClearsKeys) instead of being discarded.
n6: Validate skips the region/dataType/byteOrder enum checks on a string-only
tag (the driver ignores them). n7: docs/v2/modbus-addressing.md restates the
key-presence rule.

Refs #741
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 16:23:37 -04:00
Joseph Doherty 1f82ecfc0d Merge commit '7feffc96' into remed/lane-Modbus 2026-10-22 16:19:17 -04:00
Joseph Doherty 7feffc963a Merge lane S7: S7 driver remediation (#742)
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 16:11:24 -04:00
Joseph Doherty 3531834cce fix(modbus): review r1 - resolved address keys win only when the editor pinned them
N1: the m2 precedence trusted region/address whenever the keys were present,
but the AdminUI model stamps defaulted HoldingRegisters/0 on every save, so a
string-only tag (CSV import, or any editor toggle) silently became HR[0] -
reads AND writes. The resolved keys are now authoritative only when the editor
marked them ("addressResolved": true, written by Resolve); an unmarked
addressString is always resolved through the parser with the driver's family.
The model no longer stamps address fields for a string-only tag, CSV export
leaves its address cells blank, and the editor hint distinguishes string-only
from pinned tags. Tests: CSV import and editor save of a string-only tag, a
stamped-default blob, and the pinned positive control across families.
n1: docs/v2/modbus-addressing.md updated (FC23 opt-in, maxReadGap semantics,
coalescing scope, addressString/family rules, coil coercion, refusals).
n2: form round-trip tests for UseFC23ForMultiRegisterWrites /
DisableReadCoalescing. n4: the editor keeps unresolved address text when the
parent echoes back its own emit. n3: noted, no change.

Refs #741
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 16:06:02 -04:00
Joseph Doherty 081fa693af fix(s7): access-denied is an answer; review round-1 minors (R07:H4 follow-through)
I-1: a PUT/GET-disabled CPU (every read denied) stayed Faulted with
LastSuccessfulRead frozen, so the comms-loss watchdog reconnected and
re-subscribed it every 90 s forever. Both access-denied arms now also record
an answer: Faulted is kept (worst state wins), the stamp advances, and the
sticky write fault still clears only on a real success. Pinned end to end in
Runtime.Tests: the real S7Driver under the real DriverInstanceActor watchdog
is not reconnected across 2x the threshold; the control (every read timing
out) is.

Minors:
- m-1: injectable pass clock (UtcNow); "LastSuccessfulRead advanced" is now
  asserted strictly, including the write-refusal case.
- m-2: the editor uses S7TagShapeRules.IsByteAnchored instead of its own list.
- m-3: a release that races an init publish also cancels the probe loop the
  publish started after the release took its snapshot.
- m-4: a retained poll failing during a lifecycle operation writes no health.
- m-5: a multi-var chunk that fell back memoises its members refused alone.
- m-7: access-denied needs S7.Net's exact wording and no transport fault in
  the chain.
- m-8: sync teardown clears the write-side Degraded owner; a sync Dispose
  racing a running shutdown is tested.

Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:57:53 -04:00
Joseph Doherty fd6ecf8293 fix(modbus): review r0 - FC23 opt-in, explicit maxReadGap 0 = off, legacy coil types load, one health writer
Coordinator rulings and Important findings from review r0:
1. FC23 is opt-in (new UseFC23ForMultiRegisterWrites, default false); a config
   without it - including the persisted "disableFC23": false every form-saved
   config carries - keeps the FC16 wire. DisableFC23 stays the hard kill-switch.
2. An explicit maxReadGap 0 means coalescing off again (its pre-lane meaning);
   the gap-8 default applies only to an absent key.
3. Coils/DiscreteInputs tags persisted with a register dataType (the old
   editor saved Int16) are coerced to Bool, never refused, with no deploy
   warning (a warning can be promoted to a blocking error). The editor loads
   them as Bool. Register region + Bool is still refused.
4. One comms-fault slot for reads and writes: a good read clears a write's
   transport fault and vice versa.
Minors: Dispose writes its own Unknown health (m1); persisted region/address
are authoritative over addressString so a Family change cannot remap a live
tag (m2); a malformed-but-delivered reply no longer fails the unit fast (m3);
a fresh socket published after a concurrent dispose is torn down (m4); the
editor resets address text per tag (m5); master merged (m6); the FC23 latch
log says re-init restores it (m7). Back-compat tests use the old persisted
JSON shapes and fail without the fixes.

Refs #741
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:55:32 -04:00
Joseph Doherty c12269c221 Merge commit '5135a036' into remed/lane-Modbus 2026-10-22 15:47:50 -04:00
Joseph Doherty 04ad774235 Merge commit '5135a036' into remed/lane-S7 2026-10-22 15:46:38 -04:00
Joseph Doherty 8a5b4434a4 Merge local master 5135a036 into remed/lane-AbLegacy
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:36:12 -04:00
Joseph Doherty 4a3d7a9361 feat(modbus): wire Family / MelsecSubFamily / DisableFC23, and the form's timing keys
U1: a tag's addressString (Modicon / mnemonic / DL205 V-memory / MELSEC
D-X-Y grammar) now resolves through ModbusAddressParser with the DRIVER's
Family and MelsecSubFamily at every initialize and is authoritative; the
family-unaware gates (deploy Inspect, AdminUI parse consult) accept what
some family resolves. The tag editor gets an address-text field that
resolves with the owning driver's family and persists both the string and
the resolved region/offset/type fields; a hand edit drops the string.
DisableFC23 now gates FC23: by default a 2..121-register holding write is
one FC23 write + read-back (a unit answering exception 01, or failing FC23 at
the transport, moves to FC16 for the rest of the generation); RTU framing
deframes the FC23 reply. Live-checked: the pymodbus fixture implements FC23.
Also: the AdminUI driver form serialises ModbusDriverOptions (TimeSpan
strings), which the factory DTO never read - every timing field on the form
was dead. The DTO now accepts both shapes (*Ms keys win).

Refs #741
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:35:58 -04:00
Joseph Doherty 5135a0366e Merge Wave-1 integration: cross-lane scripting/runtime follow-ups (#731, #734)
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:25:43 -04:00
Joseph Doherty 2ef3cd0df2 feat(modbus): block-read coalescing on by default; coils/DI/BitInRegister/String fold
U2: MaxReadGap defaults to 8 and 0 now means adjacent-only rather than
off; a new DisableReadCoalescing switch (factory DTO + AdminUI form) turns it
off entirely. The planner also merges Coils/DiscreteInputs (FC01/FC02, gap in
bits), String scalars and BitInRegister tags - sixteen bit tags on one status
word are one FC03 instead of sixteen. Auto-prohibition and its re-probe /
bisection use the region's own function code (a coil range was re-probed
with FC04).

Refs #741
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:24:38 -04:00
Joseph Doherty efa040813a fix(ablegacy): coalesceReads absent means default; the form never pins it
Review r0 M9. The AdminUI form wrote coalesceReads:true on every save, pinning
today's default into every edited driver. AbLegacyDriverOptions.CoalesceReads
is now bool? (null = default ON, never serialised, same encoding as
Transport); the form omits the key when the switch is on and writes only an
explicit false. Persisted coalesceReads:true keeps loading as on.

Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:24:30 -04:00
Joseph Doherty d758dd1e16 fix(ablegacy): encode array writes at the data file's element width
Review r0 I3. The array encoder used the AUTHORED dataType's width while both
runtimes size their buffer from the FILE: an Int array on F8 wrote four shorts
into a 16-byte float buffer and sent it all (garbage neighbours, answered
Good); Long/Float on N overran it.

- The write path resolves the element width from the data file the address
  names (N/B/A/I/O/S 16-bit word, L 32-bit, F float) and encodes at THAT width.
- An authored type that does not match its file is refused BadTypeMismatch
  before any runtime exists (warned once, no health write).
- The same rule (AbLegacyTagDefinitionFactory.ArrayFileMismatch) backs an
  Inspect deploy warning and the AdminUI model's Validate error; FromTagConfig
  still accepts the tag so persisted configs keep loading.
- M6: the skipped F1 parity test gains the shapes the write path refuses
  (/bit, .sub, indirect, type/file mismatch, PLC-5 native).

Tests: one case per file type, a mismatch per pairing with nothing created,
and a positive control.

Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:20:10 -04:00
Joseph Doherty f827b3a134 fix(modbus): enforce region/type compatibility at the tag factory
P6: Coils/DiscreteInputs carry only Bool and register regions never Bool;
the factory (and so the deploy-gate Inspect and the AdminUI parse consult)
refuses a mismatch, and an absent dataType defaults per region (Bool for a
bit region). A HoldingRegisters+Bool tag used to throw out of the coalescing
planner and stall every tag of the subscription; the planner also skips any
incompatible pair defensively. The tag editor keeps the type compatible when
the region changes; the CLI refuses the pair up front. The array-write parity
test records the Coils divergence from DriverArrayWriteSupport (owned outside
this lane) as follow-up F1.

Refs #741
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:19:28 -04:00
Joseph Doherty f5a392c684 docs(scripting): note that dot-completion walks the base chain for every receiver
Review m-5. The ctx.CancellationToken completion fix (d2cc0715) made
TryGetDotMembers include inherited instance members for EVERY receiver,
not only ctx. The visible side effect beyond the item's scope: struct
and enum receivers now also complete the System.ValueType / System.Enum
instance members they inherit (CompareTo, HasFlag, ...). These are
valid, compilable members, so the change is kept. This commit records
it here and in the code comment.

Refs #731 #734
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:15:41 -04:00
Joseph Doherty 9c0f59a3ab Merge lane AbCip: AbCip driver remediation (#737)
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:09:58 -04:00
Joseph Doherty 20875ea939 Merge local master 0d49eaf7 into remed/lane-AbLegacy
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:06:32 -04:00
Joseph Doherty 87a7414df7 fix(s7): refuse unservable tag shapes per tag at every gate (R07:H3, R07:U4)
The init-time tag guards THREW: one mis-authored tag (DB1.DBZ0, DB1.DBW0 typed
Float64, T5 typed Int32, a writable Bool array) faulted the whole driver and the
actor retried the same init every 10 s forever, darkening every tag on the PLC.
Neither the editor nor the deploy gate checked any of it.

- S7AddressParser moves to S7.Contracts (same namespace) and a new
  S7TagShapeRules there is the single authority on servable shapes.
- S7TagDefinitionFactory.FromTagConfig applies it, so the AdminUI editor, the
  deploy gate (Inspect, with the specific reason) and the driver init refuse
  the same tags. Init now skips a refused tag (ISkippedTagReporter) instead of
  throwing; the throwing RejectUnsupportedTagConfigs is gone.
- New rules on top of the old guards: a narrow type at the wrong access width
  (every read failed) and a Bool array not starting at bit 0 (U4: DB1.DBX0.3
  silently read bit 0 of bytes 0..n).
- AdminUI test fixtures that used addresses the driver could never serve
  (DB1.DBS0, a browse "SomeAddress", Int32/Float32 on DBW) now use real ones.

Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:04:19 -04:00
Joseph Doherty 6636de1199 refactor(runtime): delete the per-value AttributeValuePublished message
It had no production sender: every driver data change is already a
batch, and the comms-loss fan was converted earlier. DependencyMuxActor
drops its per-value receive, DriverInstanceActor drops the record, and
DependencyMuxActorTests' 13 sends move to the ValuePublishes.Single
one-item batch (same semantics through the batch path). XML docs and
the living docs (DriverLifecycle, VirtualTags, ScriptEditor) are
reworded; historical plan docs are left as written.

Refs #731 #734
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 14:42:08 -04:00
Joseph Doherty 530f4bdcd4 perf(ablegacy): coalesce adjacent N/B/F/L scalar reads into one PCCC request
Review 07 P7 (rest): adjacent words on one data file were never coalesced
(one round trip per tag) although the array path proves the transport can read
a span. Within a device pass, scalar tags on one N/B/F/L file within 8
elements of each other (block <= 200 data bytes, under the 236-byte typed-read
limit) now ride one multi-element read and are decoded from their offsets with
exactly the CLR types the single-tag path returns (int / float / bool).

Only shapes the single path decodes identically are coalesced: indirect,
sub-element, array, file-number-less (S:/I:/O:) and width-mismatched tags keep
the single path. A block the device refuses (an authored element past the end
of the file, a native PLC-5 non-N file) falls back to per-tag reads for its
members and its shape is remembered; a comms fault fails the members together.

New driver-config key coalesceReads (default true) with an AdminUI switch
(Razor change: AbLegacyDriverForm, for the Wave 4 live check). Adds an
env-gated ab_server parity case (coalesced == per-tag values).

Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 14:41:20 -04:00
Joseph Doherty d2cc071517 feat(scripting): expose the run token to scripts as ctx.CancellationToken
ScriptContext.CancellationToken is backed by an AsyncLocal that
ScriptEvaluator.RunAsync scopes around the compiled delegate, so it is
exactly the token ScriptRunGuard cancels on timeout. A polling script
can now end its own abandoned run and free the slot. AsyncLocal rather
than a field because the scripted-alarm engine reuses one context per
alarm: an orphan keeps seeing its own cancelled token. The scoping
entry point is internal (IVT to Core.Scripting) so a script cannot
replace its own token.

Editor parity: ScriptAnalysisService dot-completion now walks the
receiver's base chain (instance members only, stopping before
System.Object). Before this, a member declared only on ScriptContext
compiled and published but never completed. DiagnoseTests pins the
member as allow-listed; CompletionTests pins the completion.

Refs #731 #734
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 14:31:03 -04:00
Joseph Doherty 8b50b43048 fix(ablegacy): deterministic NotSupported refusals are BadNotSupported with no health write
Review 07 H16: an array of String/Timer/Counter/Control passed the mapper, so
every poll created a handle (one init read), the decode threw
NotSupportedException, the generic catch evicted the handle and latched
Degraded. FromTagConfig now rejects that combination (the skip carries the
reason, Inspect/deploy gate and the AdminUI model state it), and a runtime
NotSupportedException on read or write is BadNotSupported: handle kept, no
health write, one Warning per tag and operation. Write refusals (native PLC-5
and status-bit writes, libplctag translated addresses) now warn once per tag too.

Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 14:20:17 -04:00
Joseph Doherty 4e9bd9d966 perf(abcip): native read window >= 64; cold waiters hold no window slot
P8: on the native transport the bounded-parallel read window is also the cap
on services per Multiple Service Packet (the device's shared scheduler packs
whatever is queued, within the connection's request/reply byte budget), so the
default 8 cost a 1000-tag controller ~125 round trips per poll instead of ~10.
The effective window (AbCipDriver.ReadWindow) is now max(64, option) when the
native tag factory serves reads; libplctag and injected factories keep the
option exactly. Option doc + AdminUI help text updated (Razor: Wave 4 live
check).

P7 addendum: a work item now takes its window slot only after its runtime
exists. A cold create queues on its device's single-flight connect gate, and
holding a slot there let one dead device's backoff-expiry attempt occupy the
whole window for a full Timeout, stalling every other device's reads.

Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 14:19:38 -04:00
Joseph Doherty cc140593a0 fix(focas): refuse String on PMC/PARAM/MACRO in the factory, editor and CLI (R07:U8)
FocasDataType.String was authorable on any address, but no area read returns text: PMC
fell through to a byte read, PARAM to Int32, MACRO to a double, and the String node
received a boxed number at Good.

One rule, FocasTagDefinitionFactory.DescribeDataTypeMismatch, now backs every path:
- FromTagConfig rejects the pair, so the driver skips + reports it (BadNodeIdUnknown,
  never a Good number) and Inspect names the reason at deploy;
- FocasTagConfigModel.Validate refuses it on the typed fields;
- the AdminUI editor only offers String where it is readable and shows the rule's text
  inline (kept visible for a loaded blob that already carries it);
- the CLI read/subscribe/probe/write commands refuse it at the boundary.
String stays valid on FIXED: paths (Identity/Program name/mode text) and is ignored on
ALARM: tags; an unparseable address keeps its own diagnosis.

Razor change (FocasTagConfigEditor.razor) needs the Wave 4 live check.

Refs #740
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 14:15:35 -04:00
Joseph Doherty 8a0acc4649 Merge master into remed/lane-F
Refs #735

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 13:29:15 -04:00
Joseph Doherty d8c39933ed Merge lane A: runtime driver lifecycle (#731)
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 10:44:22 -04:00
Joseph Doherty a01f5e6705 build: pin patched System.Security.Cryptography.* / SignalR to clear fresh-restore NuGet audit
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 10:38:07 -04:00
Joseph Doherty 953bd27533 fix(runtime,adminui): per-tag write ordering, pessimistic init bound, unique generations, PostStop budget (fix round 1)
- Writes: a second write to a tag already inside the driver waits in the
  queue behind it (_tagsInFlight) while other tags still run under the
  cap of 4; queued writes are stamped and failed BadTimeout at dequeue
  once older than the 8 s host Ask budget (Props queuedWriteBudget)
  instead of being written late.
- Initialise attempts are bounded pessimistically (initializeTimeout,
  default 30 s = 2x Tier C) on top of the invoker's token-only timeout:
  an overrun is logged as abandoned, reported InitializeFailed so the
  retry loop continues, and its late result is dropped by generation.
  Generations come from a process-wide Interlocked counter so a prior
  incarnation's late result cannot collide (F6).
- PostStop shares one shutdownTimeout budget across shutdown + dispose.
- TelemetryDialSupervisor cancels the establishment deadline on
  StreamStopped; FleetDiagnosticsClient builds the ActorSelection inside
  the try (a malformed node degrades to "unavailable"); the diagnostics
  page labels the column "Last health publish".
- Tests: same-tag serialisation with a distinct-tag positive control;
  stale queued write BadTimeout; token-ignoring hung init -> later
  attempt connects; stopwatch assertion demoted to a ceiling.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 10:36:30 -04:00
Joseph Doherty 59b72fe385 fix(runtime): diagnostics Name stays the string instance id; order-tolerant write-cap test (A6 follow-through)
DriverInstanceDiagnostics.Name carries the string driver-instance id
(what /hosts, telemetry and the artifact key on) and DriverInstanceId
the DB row Guid; the wire record has no slot for the authored display
name. The write-cap test asserts entry order per slot pair instead of
completion order of two concurrent writes.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 10:15:01 -04:00
Joseph Doherty d1cc9e2cfc feat(runtime,adminui): real GetDiagnostics from child health + /fleet/diagnostics consumer (A6)
DriverHostActor wraps the health publisher it hands its children in a
ChildHealthLedger (last snapshot per driver id, forwarded to the real
publisher), so GetDiagnostics now answers with each child's row id,
authored name, last-published state, device counts (host statuses when
the driver probes hosts, else one device) and last-change time — instead
of Guid.Empty / "Spawned" / 0 / now. Entries are forgotten on StopChild
and operator Restart.

IFleetDiagnosticsClient gains its first consumer: the new
/fleet/diagnostics page (node selector + ?node= query, revision,
running-from-cache notice, per-driver table). FleetDiagnosticsClient
logs the degrade-to-empty path at Warning.

Review ref: 02/U1.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 06:44:38 -04:00
Joseph Doherty 6dedf5158f feat(galaxy): wire DiscoverPageSize and ProbeTimeoutSeconds; concurrent first-touch write lanes
Review 2026-10-21 G-5, G-6, G-8 ("wire them all").

- G-5: GatewayGalaxyHierarchySource now pages the DiscoverHierarchy RPC
  itself (DiscoverHierarchyRawAsync) at Repository.DiscoverPageSize. The
  mxaccessgw client's typed DiscoverHierarchyAsync overloads hard-code a
  5000-row page and DiscoverHierarchyOptions carries no page size, so the
  authored knob reached nothing; the raw request takes page_size on the
  wire, so it is honoured here (non-positive → 5000). The loop keeps the
  client's repeated-page-token guard.
- G-6: GalaxyDriverProbe reads ProbeTimeoutSeconds from the config and
  runs under min(caller budget, configured cap) — the knob can shorten a
  probe, never extend it past the host's budget. The TCP preflight now
  shares that deadline instead of hanging on the caller's token alone.
- G-8: GatewayGalaxyDataWriter runs a batch as one lane per distinct tag,
  concurrently and bounded at 8 (MaxConcurrentWriteLanes); same-tag
  writes keep their authored order inside one lane and results land at
  their request's index. Acks stay serial by design.
- GalaxyDriverForm: help text now says what the two knobs actually do.

Refs #735

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 06:41:47 -04:00
Joseph Doherty c6d4b14c93 feat(telemetry): wire TelemetryDial:CallTimeoutSeconds as the dial-establishment deadline (A5)
CallTimeoutSeconds was bound, defaulted and documented but consumed
nowhere. TelemetryDialSupervisor now arms a per-generation deadline on
every dial: a dial that has delivered no event by the deadline is
cancelled and treated as a transport failure (reconnect with a failure
streak). A live node replays its snapshots on subscribe, so this bites
only a dial that never connects (a black-holed host, where the socket
connect has no timeout). An established stream is deliberately not
bounded — the wire has no heartbeat, keepalive pings own its liveness.

Review ref: 02/U2.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 06:38:32 -04:00
Joseph Doherty 826312befe docs: fill missing XML docs and strip tracking IDs from src comments
Clears CommentChecker findings in src/ (3,280 -> 209, the remainder being false
positives like PLC-5/IEEE-754/M0.0) by adding missing summaries/params/returns,
normalising inheritdoc usage, and removing Gitea/review tracking IDs while keeping
the rationale they annotated. Comment-only: comment-stripped sources are identical
to the parent commit.
2026-10-15 06:14:58 -04:00
Joseph Doherty fccffd0a0f feat(opcuaclient): #676 follow-ups — endpoint rewrite, stall wire test, fast definitive-loss recovery
- Endpoint rewrite: the driver now connects to the configured host AND port (scheme
  match, advertised path kept) instead of the server-advertised URL — fixes NAT/port-map
  upstreams and lets an in-test proxy carry the session (SDK SelectEndpoint rule).
- TcpStallProxy + OpcUaClientDriverStallWireTests: the in-place blip (#670) is now
  wire-tested on loopback — one Bad, frozen read stamp, same session, identical value
  republished Good, a post-recovery change arrives, no source-time regression after
  the SDK's late backlog flush.
- Defect found by that test, fixed: a change published right after a stall rode a
  Publish response the SDK timed out and never republished, leaving the node Good on
  the pre-change value indefinitely. New trailing reconcile read (Timeout +
  KeepAliveInterval after recovery) publishes any Good value newer than the last
  accepted one, through the replay guard's mark.
- IDriverConnectionLossSource (Core.Abstractions): opt-in definitive-loss signal.
  DriverInstanceActor attaches in PreStart / detaches in PostStop and turns a raise
  into a disconnect only while Connected. OpcUaClient raises once per session on
  keep-alive BadSessionIdInvalid/BadSessionClosed/BadSessionNotActivated/
  BadServerHalted (measured: the SDK never re-opens a halted channel) or a dropped
  subscription; ambiguous codes stay with the #527 watchdog.
- Replay guard: one Information summary per recovery when the window closes
  ("dropped N late notifications across M refs"), with a timer so quiet
  subscriptions log it too.
- ReconnectPeriod deleted (options, AdminUI form, docs, tests); stored configs that
  carry reconnectPeriod still parse in the factory, probe and browser.
- Docs: OpcUaClient.md, DriverLifecycle.md, driver-specs.md, CLAUDE.md.
2026-10-11 11:35:52 -04:00
Joseph Doherty 2ef8ee3ade feat(historian): OPC UA HistoryUpdate in the node manager + HistoryUpdate authorization (T6)
- OtOpcUaNodeManager overrides HistoryUpdateData / HistoryDeleteRawModified / HistoryDeleteAtTime,
  block-bridging to the optional IHistorianDataUpdater under the shared HistoryRead batch limiter +
  deadline. Insert/Replace/Update map to HistoryUpdateMode; Remove, IsDeleteModified, events and
  structure data are BadHistoryOperationUnsupported. Per-item codes stitched back in request order
  (MinValue SourceTimestamp => BadInvalidTimestamp, untypeable value => BadTypeMismatch); success
  clears the base's pre-seeded Unsupported error.
- HistoryWrite AccessLevel bit OR-ed in for historized nodes when an updater is wired (raw + UNS);
  it is dispatch-load-bearing in the SDK base. OtOpcUaSdkServer.SetHistorianDataUpdater; the hosted
  service assigns it from an optional HistorianUpdaterHolder before SetSink, clears it on stop.
- AuthorizeHistoryUpdate: ACL on => scoped OpcUaOperation.HistoryUpdate decision (replaces the role
  check); ACL off => #563 key re-check + new OpcUaDataPlaneRoles.HistoryUpdate role, conferred by
  ApiKeyInterimRoleMapper only from a Cluster-scoped HistoryUpdate grant (WriteOperate does not).
- AdminUI ACL editor offers NodePermissions.HistoryUpdate.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe