Commit Graph

400 Commits

Author SHA1 Message Date
Joseph Doherty 5de1d661bb fix(runtime): evict a stopped driver's retained values from the dependency mux
DriverHostActor now tells the mux SourceRemoved(driverInstanceId)
wherever a driver object ends: StopChild (deploy removal and the stop
half of a config-change respawn) and an operator Restart. It is not
sent on a supervision restart, which re-uses the same driver. Before
this nothing sent it, so a removed driver's last Good stayed in the
mux and replayed to the next replay-opting subscriber as current.

DriverHostActorSourceRemovedTests drives a real mux with two real
driver children: after a deploy drops DI-1 only DI-2's value replays
(positive control: both replay before the removal), and a supervision
restart of DI-1 leaves its value replayable.

Residual (documented on EvictRetainedValues): a burst the old child
enqueued just before it stopped can still be forwarded after the
eviction; the next publish, a comms-loss fan or the grace sweep
bounds it.

Refs #731 #734
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 14:36:54 -04:00
Joseph Doherty 3e0606af58 Merge lane E: script runtime safety + scripted alarms (#734)
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 14:03:54 -04:00
Joseph Doherty ef2eebe6b6 fix(scripting): review minors: configured limit in summaries, dispose gate/CTS, validator, docs (fix round 1)
- ScriptLogRateLimiter.LimitPerWindow. The ScriptLogTopicSink and
  VirtualTagActor summaries now print the configured limit, not
  DefaultLimitPerWindow. Tests assert "limit N/window" for a non-default
  N.
- CalculationDriver.Dispose cancels, then takes _evalGate (bounded 2 s)
  and disposes the gate and _evalCts. The pump and timer ticks enter the
  gate through TryEnterEvalGateAsync, which stops cleanly once the
  driver is disposed. Test: Dispose with a 6 s runaway run in flight
  returns promptly, disposes both, and a late trigger is harmless.
- ScriptedAlarmEngine captures _shutdownToken once and disposes
  _shutdownCts in Dispose when every drained task has completed. A task
  stuck past the grace leaves the CTS to the GC. Lifecycle tests assert
  the disposal.
- DraftValidator: CalculationNoEffectiveTrigger is skipped for a
  change-triggered tag whose scriptId does not resolve. That case is
  already CalculationScriptMissing or CalculationScriptNotFound, and
  there are no reads to count. Both existing tests now assert the
  absence (red before the change).
- docs/VirtualTags.md: System.Threading is denied as a whole namespace,
  with an allow-list; the type list is now accurate (Unsafe,
  RuntimeHelpers, and the ForbiddenMembers on System.Type); the resource
  limits section covers the run guard and the allocation budget.
  docs/ScriptEditor.md: accurate deny-list and a new "Runtime safety"
  section covering timeout, refusal, quarantine after 3 timeouts,
  allocation budget, lifting, and rate-limit summaries that appear only
  on the source's next entry after a burst then quiet.

Refs #734

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 13:41:15 -04:00
Joseph Doherty 9e180b72a3 test(runtime): de-flake the hung-write release test; name the real write bound
The fixture wedged EVERY write on one shared token-ignoring release gate, so
the later same-tag write was also hung, and the 300 ms pessimistic bound
abandoned it while the test was still polling before ReleaseWrites(). Its
reason was "write did not complete within" (the bound), not "queued for" (the
queue budget), and it had already entered the driver, so the tag had been
released. The release path is correct. Only the first write now hangs, and
later writes complete at once.

The abandon reason formatted the bound with TotalSeconds:F0, which printed a
300 ms bound as "0s". It now uses milliseconds, and the test asserts it.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 13:39:33 -04:00
Joseph Doherty ad6be56850 fix(runtime): bound DependencyMux last-value retention to replay-opting refs (fix round 1 I2)
DependencyMuxActor retained the last value of every ref ever registered,
and never removed the entries. The continuous-historization recorder
registers every historized ref, so on a historizing node the map grew
with the historized address space and never shrank. The class remark
claimed a bound that did not hold.

- Retain only refs that at least one subscriber registered with
  ReplayRetained: true names (VT actors, the Calculation mux adapter, the
  scripted-alarm host). A non-opting subscriber is still delivered to but
  retains nothing.
- When a ref's last replay-opting subscriber leaves, its value is kept
  for a grace (default 2 min, Props(retentionGrace)) so a restart
  (old adapter gone, new one not yet registered) still replays. A
  periodic sweep then drops it along with the entry. Entries with no
  subscriber and nothing retained are removed.
- New SourceRemoved(DriverInstanceId) evicts the values a removed driver
  produced, so its last Good is never replayed. The mux records the
  publishing driver per retained ref. No production sender exists yet:
  DriverHostActor is outside this lane (follow-up).
- Remark rewritten. Tests: retention bounded to replay-opting refs,
  release after grace (with an in-grace replay as the positive control),
  SourceRemoved eviction, and the restart-replay scenario still green.

Refs #734

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 13:31:41 -04:00
Joseph Doherty 909b061d3a Merge branch 'master' into remed/lane-E 2026-10-22 10:48:41 -04:00
Joseph Doherty d8c39933ed Merge lane A: runtime driver lifecycle (#731)
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 10:44:22 -04:00
Joseph Doherty 7ae74ef147 fix(runtime): pessimistic write bound, incarnation-stamped write completions (fix round 2)
- RunWriteAsync wraps the invoker call in WaitAsync(writeTimeout) (Props,
  default 10 s = 2x the 5 s write cap): a token-ignoring hung write now
  answers BadTimeout, releases its slot and tag, and its orphan outcome
  is observed and discarded - later writes to that tag reach the device.
- WriteCompleted carries the launching incarnation (from the process-wide
  generation source); a late completion from a previous incarnation after
  a supervision restart is ignored instead of freeing the new
  incarnation's slot/tag.
- Test: a hung token-ignoring tag-a write is abandoned and a later tag-a
  write reaches the device while the abandoned one is still inside it.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 10:43:45 -04:00
Joseph Doherty 953bd27533 fix(runtime,adminui): per-tag write ordering, pessimistic init bound, unique generations, PostStop budget (fix round 1)
- Writes: a second write to a tag already inside the driver waits in the
  queue behind it (_tagsInFlight) while other tags still run under the
  cap of 4; queued writes are stamped and failed BadTimeout at dequeue
  once older than the 8 s host Ask budget (Props queuedWriteBudget)
  instead of being written late.
- Initialise attempts are bounded pessimistically (initializeTimeout,
  default 30 s = 2x Tier C) on top of the invoker's token-only timeout:
  an overrun is logged as abandoned, reported InitializeFailed so the
  retry loop continues, and its late result is dropped by generation.
  Generations come from a process-wide Interlocked counter so a prior
  incarnation's late result cannot collide (F6).
- PostStop shares one shutdownTimeout budget across shutdown + dispose.
- TelemetryDialSupervisor cancels the establishment deadline on
  StreamStopped; FleetDiagnosticsClient builds the ActorSelection inside
  the try (a malformed node degrades to "unavailable"); the diagnostics
  page labels the column "Last health publish".
- Tests: same-tag serialisation with a distinct-tag positive control;
  stale queued write BadTimeout; token-ignoring hung init -> later
  attempt connects; stopwatch assertion demoted to a ceiling.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 10:36:30 -04:00
Joseph Doherty 4d3fc9c816 fix(runtime): restart-safe alarm host, mux last-value replay, VT log rate limit, Calculation remediation (E4)
- R02:H1 ScriptedAlarmHostActor gains a factory Props
  (Func<(upstream, engine)>) so every incarnation builds and owns its own
  engine; a supervision restart no longer re-creates the actor around a
  disposed engine. The legacy instance-taking Props stays source-compatible
  and is now restart-safe in the weaker sense (PreRestart marks the stop as
  a restart, PostStop then detaches instead of disposing). DriverHostActor
  still spawns through the legacy overload (not owned by this lane — F3).
- R02:H3 OnAlarmCommand runs every engine op under a 10 s token linked to
  the actor's lifetime (DefaultCommandTimeout / Props commandTimeout) and
  logs a Warning on timeout instead of suspending the mailbox on a stalled
  store.
- R02:L3 DependencyMuxTagUpstreamSource.RetainOnly(loaded dep-ref union),
  called after every successful load.
- R02:P6 VirtualTagActor's per-failure ScriptLogEntry is rate-limited per
  tag (ScriptLogRateLimiter, 20/min + one summary); the Bad publish and the
  metric are untouched.
- R07:H6 DependencyMuxActor retains the last (value, status, ts) per
  ever-registered ref (through unregisters) and replays them in one batch to
  a RegisterInterest(ReplayRetained: true) — VirtualTagActor, the Calculation
  mux adapter and the alarm host opt in; the historization recorder does not
  (a replay there would record a stale sample per deploy). CalculationDriver
  records inputs regardless of _running so a replay landing before
  InitializeAsync still satisfies the change-gate.
- R07:P4 CalculationEvaluator negative-caches compile failures by source
  hash (one Roslyn attempt + one Warning per source until redeploy); the
  driver's script-log entry fires on the Good→Bad transition or a change of
  reason, matching the once-per-transition Bad publish.
- R07:H8 array results dedup structurally.
- R07:L2 ShutdownAsync drops the compiled scripts (collectible ALCs).
- R07:U5 DraftValidator rule CalculationNoEffectiveTrigger: a tag with no
  timer whose change trigger is off or whose script has no literal
  ctx.GetTag read can never evaluate.

Refs #734

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 10:27:49 -04:00
Joseph Doherty 7e8941fbdc test(historian): paged-vs-unpaged raw-cap fuzz, MaxReturnDataValues advertisement, cap floor of 3
- NodeManagerHistoryReadRawCapFuzzTests: 10k seeds (env OTOPCUA_PAGING_FUZZ_ITERATIONS)
  through a real SDK node manager against wire-faithful fakes of SqlServer / QuestDB /
  Gateway that enforce the backend half of the cap; random series with ties, random
  windows (empty, on/past a tie, between samples, forward/reverse/end-only, bounds),
  N in {0,1,2,small,huge}, cap in {off,3..1000}, tie budget {3,8,65536}. Pages must
  concatenate to the cap-off one-shot answer (checked against the series), terminate
  within values + 2 (+ one empty step per oversized boundary cluster), never exceed
  the cap, never ask the backend for 0 / over-cap; refusals only past the budget.
- HistoryPaging.AdvertiseMaxReturnDataValues writes HistoryServerCapabilities/
  MaxReturnDataValues (i=11273), read back through the SDK master node manager.
- MinMaxRawValuesPerRead raised to 3: at 2 a resumed page has no room (value + its
  boundary tie + lookahead) and every value cost an empty page + CP (seed 15).
- RawPageLimit rows pin the default-cap arithmetic (9 999 first page, 9 998 resumed).

Fuzz findings recorded as follow-ups: a bounded read whose data fits one page
returns cap + 1 (end bound fitted against N, not the cap; node manager, F2);
the Gateway walk-back's cost on a sparse series under a tiny tie budget is
pre-existing (seed 320: 82 reads uncapped, 93 capped).

Refs #736

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 10:15:21 -04:00
Joseph Doherty 59b72fe385 fix(runtime): diagnostics Name stays the string instance id; order-tolerant write-cap test (A6 follow-through)
DriverInstanceDiagnostics.Name carries the string driver-instance id
(what /hosts, telemetry and the artifact key on) and DriverInstanceId
the DB row Guid; the wire record has no slot for the authored display
name. The write-cap test asserts entry order per slot pair instead of
completion order of two concurrent writes.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 10:15:01 -04:00
Joseph Doherty d1cc9e2cfc feat(runtime,adminui): real GetDiagnostics from child health + /fleet/diagnostics consumer (A6)
DriverHostActor wraps the health publisher it hands its children in a
ChildHealthLedger (last snapshot per driver id, forwarded to the real
publisher), so GetDiagnostics now answers with each child's row id,
authored name, last-published state, device counts (host statuses when
the driver probes hosts, else one device) and last-change time — instead
of Guid.Empty / "Spawned" / 0 / now. Entries are forgotten on StopChild
and operator Restart.

IFleetDiagnosticsClient gains its first consumer: the new
/fleet/diagnostics page (node selector + ?node= query, revision,
running-from-cache notice, per-driver table). FleetDiagnosticsClient
logs the degrade-to-empty path at Warning.

Review ref: 02/U1.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 06:44:38 -04:00
Joseph Doherty 79d6b0a4b2 fix(runtime): lifecycle housekeeping — reprovision stamp, Stale drops, off-thread DB probe, tombstone sweep (A4)
- DriverHostActor.StopChild removes the driver's _lastReprovisionUtc stamp
  (and its deferred-reprovision timer): the map grew per removed id and a
  re-added driver inherited a backoff it never earned (02/L2).
- Stale now registers explicit drops for AttributeValueBatchPublished,
  AttributeAlarmPublished, ArtifactForApply and ApplyWedged instead of
  letting them hit Unhandled (02/H5).
- DbHealthProbeActor runs its SELECT on the thread pool and pipes the
  outcome back (single-flight), with a 2 s command timeout on relational
  providers, so a hung SQL Server no longer pins the actor thread and the
  cached GetStatus answer stays reachable (02/P7).
- TelemetryLocalHub eviction tombstones are timestamped and swept past a
  10 min TTL on the next Evict; a TimeProvider ctor is the test seam (02/L4).
- Tests: ValuePublishes.Single helper replaces the per-value
  AttributeValuePublished in CalculationDependencyFlowTests (02/U4, test
  half; the production receive is owned by Lane E).
- R05/8 audit: PollGroupEngine.Unsubscribe has no production caller; every
  driver already uses UnsubscribeAsync (no change).

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 06:36:12 -04:00
Joseph Doherty 6e2febbf3d fix(runtime): run driver writes off the mailbox under an in-flight cap (A3)
WriteAttribute was a ReceiveAsync, suspending the child's mailbox for the
whole device round-trip (up to 5 s): writes serialised, the second of two
operator writes to a slow device missed the host's 8 s Ask and was
reverted although the device took it, and every data change queued behind
the write. Writes are now a synchronous Receive that launches the device
call on the thread pool (sender captured, reply from the task, slot freed
by a self-sent WriteCompleted) under a per-driver cap (default 4; excess
writes queue in order). Queued writes fail fast on every exit from
Connected. Subscribe/unsubscribe stay ReceiveAsync.

Review ref: 02/P2.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 06:30:57 -04:00
Joseph Doherty 6669fae7e5 feat(historian): ServerHistorian:MaxRawValuesPerRead caps raw pages and backend reads
Review R08:1.1: an uncapped HistoryRead-Raw (NumValuesPerNode = 0) read a
tag's whole window into memory on every backend (SQL TOP(int.MaxValue),
QuestDB LIMIT, Gateway max_values = int.MaxValue + a second snapshot copy).

New ServerHistorian:MaxRawValuesPerRead (default 10 000; <= 0 unbounded with
a Validate() warning; 1 raised to 2). Each backend data source takes it,
reports it as IHistorianDataSource.MaxRawValuesPerRead (the Gateway: min
with a strict gateway's learned ceiling), so the node manager's existing
RawPageLimit paging serves N = 0 and N > cap as pages of at most the cap
with a continuation point. Independently, a backend raw read asking for 0
or more than the cap reads cap + 1 rows and is REFUSED
(HistoryReadLimitExceededException => BadTooManyOperations) when the window
holds more - never answered truncated, since the server's paging reads a
short answer as the last page. Bound through the Host registry, the
SqlServer/QuestDb providers and GatewayHistorian.CreateDataSource.

Tests: options (default/binding/warnings), provider binding, Gateway unit +
through a real SDK node manager (uncapped -> 999/998/998/605 + CPs), and a
conformance case for the SQL backends.

Refs #736

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 06:29:10 -04:00
Joseph Doherty bfd5b7b015 fix(runtime): single-flight reconnect attempts, bounded pre-reconnect teardown (A2)
The Reconnecting retry timer started a new ShutdownAsync + InitializeAsync
pair on every tick whether or not the previous attempt had finished; the
generation token only discarded the older RESULT, so with an Initialize
bound longer than the cadence the teardown ran underneath an attempt still
inside the driver (the dispose-before-overwrite race). An _initInFlight
gate, cleared by the piped InitializeSucceeded/Failed, skips a tick while
an attempt is running; the pre-reconnect teardown is bounded by the
shutdown timeout; PostStop cancels an in-flight attempt before shutting
the driver down.

Review ref: 02/H2.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 06:26:45 -04:00
Joseph Doherty eb23053700 fix(runtime): dispose drivers on final stop, bound PostStop shutdown (A1)
DriverInstanceActor.PostStop now bounds IDriver.ShutdownAsync by a
shutdownTimeout (default 5 s, logged on overrun) and then disposes the
driver (IAsyncDisposable preferred, else IDisposable) — but only on a
real stop. PreRestart flags the restart so the PostStop it triggers
skips the dispose, because a supervision restart re-uses the same
driver object (Props closure) and the host re-initialises it.

DiscoveryDriverBrowser disposes its throwaway capture/probe driver
after the bounded shutdown, including after a failed or timed-out one.

Review refs: 02/L1, 02/P4, 06/G-1 (host context), 07/L2.

Refs #731

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 06:23:39 -04:00
Joseph Doherty c4b4046832 test: verify missing-snapshot ServiceLevel timer behavior
v2-ci / unit-tests (pull_request) Successful in 1h0m42s
2026-10-13 17:19:50 -04:00
Joseph Doherty bc80b53e0e Merge ServiceLevel replay fixes for freshness integration 2026-10-13 15:11:20 -04:00
Joseph Doherty 1e71a25e3d fix: age DB-less ServiceLevel snapshots periodically 2026-10-13 14:29:00 -04:00
Joseph Doherty c8e3e279b4 Retain and replay ServiceLevel across publisher binding and failures
v2-ci / unit-tests (pull_request) Waiting to run
2026-10-13 13:26:27 -04:00
Joseph Doherty 3c3513ea3e fix(historian): #694 page raw reads at a strict gateway's learned ceiling; opt-in EventReadHorizon
Item 1: IHistorianDataSource.MaxRawValuesPerRead (Gateway: learned ceiling - 16 = L; 0 elsewhere, guard-tested).
RawPageLimit plans every raw page on top of #692's lookahead: with L > 0 the read (page P + boundary ties k
+ lookahead) is <= L, P = min(N, L - k - 1) (uncapped: L - k - 1); no room => straight to the tie-cluster
over-fetch (never an uncapped or underflowing request). One re-plan + re-read when the read taught a new
limit or was refused for crowding pre-window rows (HistoryReadLimitExceededException.PreWindowRows): the
page shrinks by them. Over-fetch bound min(MaxTieClusterOverfetch, L - 1); slice size never 0.
Review fixes: F1 a window starting at/before the epoch counts AVEVA's synthetic row as pre-window (a
ceiling-truncated read was reported complete); F2 the page path disables ReverseRawReader's own re-run
(cold end-only ceiling 20/N=3000 cost 3,023 reads, now <= 40); F3 crowded look-back re-read around, not
refused; F4 the #687 crowding re-read room at least doubles (up to 8 re-reads), so a cluster of hundreds
just before a resume point no longer fails on a default gateway; a crowding refusal that leaves no room
is BadTooManyOperations, never a tick-by-tick cursor.

Item 2: ServerHistorian:EventReadHorizon (default 00:00:00 = exact, unchanged). When set, every fresh
HistoryReadEvents window's earlier bound is raised to now - horizon (both directions, all backends).
Lossy by design; documented.

Item 3 (native TimeAverage/Total re-check) stays blocked on historiangw#27.
2026-10-13 01:39:32 -04:00
Joseph Doherty 934909b430 fix(historian): #691 review — clamp Gateway at-or-after read, GoodNoData when nothing exists, HonorReturnBounds kill switch
1. The at-or-after bound read on a forward-only backend (Gateway) ends at
   now + ReverseRawReader.LookAhead instead of DateTime.MaxValue (the gateway
   only checks start <= end, so a year-9999 end reached AVEVA); a bound beyond
   the horizon is not found without a read. SqlServer/QuestDB keep MaxValue:
   they bind it safely and may hold samples further ahead. The Gateway fake now
   refuses far-future ends, so the missing-end-bound test is no longer vacuous.
3. No data and no bound found (whole read empty) => GoodNoData, no values —
   the pre-bounds answer (6.5.3.2: success only if one or both bounds exist).
   A one-value page whose start bound is missing first checks there is data or
   a found end bound.
4. ServerHistorian:HonorReturnBounds (default true); false ignores ReturnBounds
   as before #691, including the modified-read Bad_InvalidArgument.
2026-10-12 17:52:34 -04:00
Joseph Doherty 50c09e21d5 Merge feat/676-opcuaclient-followups: endpoint host+port rewrite, TCP-stall wire test, ReconnectPeriod removed, IDriverConnectionLossSource fast recovery, trailing re-read, replay summary (#676) 2026-10-11 11:45:26 -04:00
Joseph Doherty 232c03ed1b fix(historian): #674 review follow-ups — HistoryUpdate boot-window gate, node-level v1 refusal, plan-before-gate, UTC skew compare
- HistoryUpdate Primary gate now reads IHistoryUpdateRoleView (PrimaryGatePolicy.ShouldServeHistoryUpdate):
  the data-plane verdict but CLOSED until this node's first redundancy snapshot, so both pair nodes cannot
  accept in the pre-join boot window. Single nodes open on their own singleton's first snapshot; admin-only
  nodes register no view => no gate. DriverHostActor publishes it at every Primary-verdict publish point.
- SqlServer v1: the updater throws NotSupportedException on every arm; the node manager maps it to a
  node-level BadHistoryOperationUnsupported (was per-item under a Good node for UpdateData/DeleteAtTime).
  HistoryWrite bit still advertised on v1 (not knowable at materialise time) — documented.
- The update plan is evaluated before the Primary gate: an unservable request (Remove, IsDeleteModified,
  not historized, no updater) is BadHistoryOperationUnsupported off-Primary, not BadInvalidState.
- Local-kind SourceTimestamp converted to UTC before the future-skew compare and sent as UTC.
- Hosted-service wiring extracted to BuildHistoryUpdatePosture and tested (gate source, skew, clock).
- Docs: Historian.md (boot window, ordering, node-level v1, HistoryWrite bit), CLAUDE.md.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-10-11 11:41:11 -04:00
Joseph Doherty 30a9d5f094 fix(opcuaclient): #676 review fix-ups (port-less rewrite, full reconcile, delivery lock, timers)
1. RewriteEndpointUrl keeps the advertised port when the configured URL names none
   (Uri.Port -1 would have sent the session to 4840); port-less + IPv6 tests.
2. The trailing re-read repairs any (value, status) difference that is not older than
   the last delivered value — Good->Bad/Uncertain included; a read without a source
   timestamp counts as newer; an equal source time with different content is published
   (repairs the replay guard's by-design equal-timestamp drop).
3. One driver-wide delivery lock makes decide+publish atomic across live notifications,
   the recovery read and the trailing read, so an older value can never land after a
   newer one (deterministic race test via a seam).
4. Known gap documented: a ConnectionLost raised while the host is not Connected is
   swallowed and that session falls back to the watchdog.
5. Only a SERVER-reported subscription loss raises ConnectionLost; the publishing-stall
   heuristic stays with the #527 watchdog.
6. Post-recovery timers run on Task.Delay(…, Clock, ct) with a session-work CTS
   cancelled on session release and dispose.
7. Replay summary at Information only when something was dropped (Debug otherwise);
   a re-arm reports the superseded window's drops and counts afresh.
8. DriverInstanceActor: AttachHostStatusSource doc comment restored; Reconnecting
   swallows a stray DisconnectObserved (test).
9. Stall wire test: 120 s session timeout, 3000-cycle subscription lifetime, one further
   bad keep-alive tick, 60 s headroom on the post-recovery waits (5/5 green).
2026-10-11 11:35:53 -04:00
Joseph Doherty fccffd0a0f feat(opcuaclient): #676 follow-ups — endpoint rewrite, stall wire test, fast definitive-loss recovery
- Endpoint rewrite: the driver now connects to the configured host AND port (scheme
  match, advertised path kept) instead of the server-advertised URL — fixes NAT/port-map
  upstreams and lets an in-test proxy carry the session (SDK SelectEndpoint rule).
- TcpStallProxy + OpcUaClientDriverStallWireTests: the in-place blip (#670) is now
  wire-tested on loopback — one Bad, frozen read stamp, same session, identical value
  republished Good, a post-recovery change arrives, no source-time regression after
  the SDK's late backlog flush.
- Defect found by that test, fixed: a change published right after a stall rode a
  Publish response the SDK timed out and never republished, leaving the node Good on
  the pre-change value indefinitely. New trailing reconcile read (Timeout +
  KeepAliveInterval after recovery) publishes any Good value newer than the last
  accepted one, through the replay guard's mark.
- IDriverConnectionLossSource (Core.Abstractions): opt-in definitive-loss signal.
  DriverInstanceActor attaches in PreStart / detaches in PostStop and turns a raise
  into a disconnect only while Connected. OpcUaClient raises once per session on
  keep-alive BadSessionIdInvalid/BadSessionClosed/BadSessionNotActivated/
  BadServerHalted (measured: the SDK never re-opens a halted channel) or a dropped
  subscription; ambiguous codes stay with the #527 watchdog.
- Replay guard: one Information summary per recovery when the window closes
  ("dropped N late notifications across M refs"), with a timer so quiet
  subscriptions log it too.
- ReconnectPeriod deleted (options, AdminUI form, docs, tests); stored configs that
  carry reconnectPeriod still parse in the factory, probe and browser.
- Docs: OpcUaClient.md, DriverLifecycle.md, driver-specs.md, CLAUDE.md.
2026-10-11 11:35:52 -04:00
Joseph Doherty e59ab69398 Merge feat/674-historyupdate-posture: future-skew bound, Primary-only HistoryUpdate, SqlServer v1 accepted with modified trail disabled, QuestDB TTL pin (#674) 2026-10-11 11:21:30 -04:00
Joseph Doherty 0658d244d0 feat(historian): #674 HistoryUpdate posture — future-skew bound, Primary gate, SqlServer v1 accepted, QuestDB TTL pin
- HistoryUpdate items with SourceTimestamp > now + ServerHistorian:HistoryUpdateMaxFutureSkew
  (default 1 day, <=0 disables) => BadOutOfRange in the node manager (every backend, never sent);
  clock injected via OtOpcUaNodeManager.Clock (host TimeProvider).
- HistoryUpdate is Primary-only: off-Primary => BadInvalidState per node, after authorization,
  same IDriverPrimaryRoleSource verdict as the native-ack gate; HistoryRead ungated.
- SqlServer: base schema requirement back to v1; SupportsModifiedTrail (v>=2). On v1 with
  AutoCreateSchema=false: writes/reads/events/retention work, modified reads + HistoryUpdate =>
  BadHistoryOperationUnsupported with nothing sent, retention skips SampleModified, one Warning per boot.
- QuestDB integration test pinning wall-clock TTL (far-future row evicts only partitions older
  than the TTL by the wall clock), with a positive control.
- Docs: Historian.md, Configuration.md, security.md, CLAUDE.md (incl. QuestDB retry duplicates,
  #674.4 anonymous-readable trail with ACL off, #674.5 not implemented).

Co-Authored-By: Claude <noreply@anthropic.com>
2026-10-11 11:18:44 -04:00
Joseph Doherty 42eb96af9e test(runtime): #678.2 #672 initial-state unreachable peer + strengthen Self_unreachable_is_ignored 2026-10-11 10:43:15 -04:00
Joseph Doherty 3b739b982b Merge feat/671-time-weighted-aggregates: Part 13 time-weighted aggregates (#671) 2026-10-11 09:10:52 -04:00
Joseph Doherty 56bb4855bb fix(historian): #671 review — raw-row cap, reverse Interpolative, SDK status rule, Partial bit
M1: the time-weighted family (incl. Total, formerly a pushed-down SUM) streams
raw window rows into the C# evaluator. New shared knob
ServerHistorian:MaxTimeWeightedRawRows (default 1,000,000; <=0 unbounded with a
Validate warning) flows through HistorianBackendRegistry into both providers.
The window query is capped at cap+1 (SQL Server TOP (@maxRows), QuestDB LIMIT $4);
one row past the cap throws the new Core.Abstractions
HistoryReadLimitExceededException, which the node manager maps to
BadTooManyOperations for that node. Not counted as a backend health failure;
bound rows are not counted; per-sample aggregates are not capped.

M2: reverse Interpolative is anchored at the later time (Part 13): points at
End - i*interval, emitted latest first. 10:00->09:00 @1h yields 10:00.

L1: Partial bit (0x4, = Opc.Ua.AggregateBits.Partial) on non-Bad results of a
truncated last interval (time-weighted family; per-sample family is a follow-up).

L2/L3: aligned with the SDK AggregateCalculator.GetTimeBasedStatusCode
(decompiled from Opc.Ua.Server 1.5.378.106): TreatUncertainAsBad=false counts
Uncertain time (Uncertain samples, held-into-outage, extrapolation) as Good
time; data but no non-Bad time => generic Bad (0x80000000); BadNoData only
when there is no data at all. Consequence: a live tag's latest interval reads
Good (documented).

L5: release note no longer claims Total matches the Gateway Integral exactly
(AVEVA's divisor is unverified); it notes Total is now evaluated in C# and
subject to the cap.

Tests: unit (reverse Interpolative x3, Partial, Bad vs BadNoData incl. an
open-ended outage, cap helpers, SDK bit oracles); conformance (reverse
Interpolative, raw-row cap at/over/0, bounds not counted, health unaffected);
node manager BadTooManyOperations; options default + warning. Each new
behaviour falsified by mutation (aggregator x9, data-source cap checks on
both backends against the real DBs, node-manager catch).
2026-10-11 09:10:26 -04:00
Joseph Doherty 91434e7f61 Merge fix/672-capture-gap: capture while the recording Primary is unreachable (#672) 2026-10-11 08:29:59 -04:00
Joseph Doherty 1b2c36eb87 fix(historian): capture while the recording Primary is unreachable (#672)
A SIGKILLed Primary stays an unreachable-but-not-downed member until
auto-down, and the redundancy singleton usually dies with it, so the
standby's cached snapshot kept naming it Primary and nobody captured for
~30 s. DriverHostActor now holds its own ReachabilityEvent (+MemberUp)
subscription, caches the last snapshot, and excludes unreachable peers
from the historization peer-is-Primary predicate only, republishing just
the capture verdict on a reachability change. Alarm drain and the Primary
data-plane verdict are unchanged. Gated by
ContinuousHistorization:CaptureWhilePrimaryUnreachable (default true).

Tests: message-driven cases with real ReachabilityEvents (incl. a
falsification control on the drain/data-plane verdicts) plus a real
two-node cluster crash test with downing disabled.
2026-10-11 08:26:39 -04:00
Joseph Doherty 924eff8d3c feat(historian): SQL Server retention purge (RetentionDays, Primary-gated, applock) (#667) 2026-10-11 08:21:30 -04:00
Joseph Doherty 96ec751a0b fix(historian): latch the recorder's dropped-kind Debug log per run; pin the outbox.unreadable gauge
The DroppedUnsupportedKind counter still counts every value; only the Debug
line is latched (cleared by the next captured value), so a Gateway-backend
comms loss no longer logs one line per tag.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 14:23:42 -04:00
Joseph Doherty 1c822eeeed fix(historian): document comms-loss outage markers; freeze DefaultSupportedKinds
Review round 1: the #481 FanCommsLossToDependencyMux fan-out DOES reach the recorder. Per the
controller ruling it is historized as an Empty/BadNoCommunication outage marker when the backend
supports Empty and counted in DroppedUnsupportedKind otherwise; remarks and the counter doc now say
so. DefaultSupportedKinds is a FrozenSet. The drop-leg test now runs under the default (gateway)
kinds, and the Empty leg pins status 0x80310000.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 12:52:32 -04:00
Joseph Doherty 04b882f5c6 fix(historian): record the real status code and typed values; backend-supported kinds gate capture
The recorder now appends the typed HistorianValue and the mux's own StatusCode instead of a
double + hard-coded Good, and drops any kind not in the backend's SupportedKinds (resolved
optionally from IHistorianBackendProvider; absent => {Double, Int64, Boolean}, today's behaviour).
RecorderStatus.DroppedNonNumeric -> DroppedUnsupportedKind; GoodQuality const removed; stale
"mux carries no quality" remarks rewritten (comms-loss node stamps are not historized).

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 12:49:05 -04:00
Joseph Doherty ff7c6c531a feat(historian): typed HistorianValue contracts, IHistorianDataUpdater, IHistorianBackendProvider (no behaviour change)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 12:44:19 -04:00
Joseph Doherty 1ea1da8236 refactor(runtime): delete the dead in-place ApplyDelta seam; config change = respawn only (#665)
Since #516 a DriverConfig change is stop + respawn, so DriverSpawnPlan.ToApplyDelta
was always empty and the in-place path had no producer. #663 and #664 were both
latent bugs in it. This deletes it:
- host: ApplyChildDelta, _pendingDelta, HandleApplyResult and HandleDeltaApplied
- plan: DriverSpawnPlan.ToApplyDelta
- actor: the ApplyDelta, ApplyResult and DeltaApplied messages, the Connected
  reinit handler and the mid-connect AdoptConfigDuringInit
- tests: the actor tests that drove the seam

IDriver.ReinitializeAsync and each driver's implementation and unit tests stay.
Comments and docs that cited AdoptConfigDuringInit as the reason a driver must
release prior state at init now cite the IDriver contract and overlapping
retries, which still apply.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 11:23:16 -04:00
Joseph Doherty 97fcf624ae fix(drivers): mid-connect ApplyDelta adopts config in Calculation, refuses it in Galaxy (#664)
AdoptConfigDuringInit re-runs InitializeAsync(newConfig) and acks success, but
Calculation and Galaxy ignored the JSON there: Calculation kept its old tag
set, and Galaxy connected on its old endpoint. Calculation now rebuilds its tag
table from a config with a body (sharing AdoptConfig with ReinitializeAsync and
stopping any running timer scheduler first). Galaxy, which cannot hot-swap its
options, refuses a non-equivalent one the way ReinitializeAsync does. The actor
now sends DeltaApplied once the adopted init succeeds, so a dependency
consumer's mux interest is re-registered. Unreachable from deploys since #516.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 11:05:58 -04:00
Joseph Doherty 39c5af3d7f fix(runtime): in-place ApplyDelta releases and re-subscribes data + alarms (#663)
A Connected ApplyDelta called ReinitializeAsync and kept the actor's data and
native-alarm handles, though every driver's reinit drops the driver-side
subscriptions behind them (#630). The reconcile only re-subscribes a missing
handle, so the driver went silent until a reconnect. Release both at the
driver before the reinit and re-subscribe both in a finally. Unreachable from
deploys since #516; pinned by a two-case test, each case failing against a
different wrong fix.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 07:49:56 -04:00
Joseph Doherty 28ca04e466 fix(#662 review): back off alarm retries, contain failed OpcUaClient alarm subscribes
- Reconcile retries of a failing alarm subscribe back off (skip 2^(n-1)-1
  ticks, cap 7 => >= every 4 min at the 30 s tick) so a hanging subscribe
  cannot hold the mailbox every tick; the stack is logged once per streak.
- The unreachable handler re-attach logs at Warning (it only fires on a
  regression).
- OpcUaClient: a failed SubscribeAlarmsAsync detaches its notification
  handler and bounds the session cleanup to 5 s under _gate;
  OnEventNotification drops events from subscriptions not registered in
  _alarmSubscriptions, so a stray that survives cleanup cannot deliver.
- The retry test also covers 3 failures (crosses the backoff); its tick
  positive control documents its dependence on the stub's changing health.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 07:35:50 -04:00
Joseph Doherty 5067509dd4 fix(runtime): keep native-alarm feed across data re-subscribes; reconcile retries alarms (#662)
A data re-subscribe (every deploy's bulk SetDesiredSubscriptions push to a
kept driver) dropped the prior data subscription through the full
DetachSubscription, which also unhooked OnAlarmEvent and forgot the alarm
handle. On any deploy that did not respawn the driver, the alarm
subscription kept logging "established" while every event reached nobody
until a reconnect or respawn. The data path now uses DetachDataSubscription;
only a lost connection and PostStop detach both.

The #488 health-poll reconcile only looked at data, so an alarm subscribe
that failed on (re)connect gated the feed for the life of the connection.
ReconcileAlarmSubscription now re-attaches a missing handler and
re-subscribes a stale/missing alarm handle every tick.

OpcUaClient removes a half-built alarm subscription from its session when
SubscribeAlarmsAsync throws, so the new retries cannot accumulate.

Tests: actor-level data-resubscribe + reconcile-retry tests and an
end-to-end NativeAlarmFeedSurvivesDeployTests through DriverHostActor; all
three fail against the unfixed actor.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 07:30:25 -04:00
Joseph Doherty 48a80b5962 fix(alarms): atomic InactiveUnacknowledged + flagged Clear/Acknowledge first sight for OpcUaClient (#657)
After an OpcUaClient respawn an upstream inactive+unacked condition went out as
Retrigger+Clear (duplicate Activated+Cleared rows, Active flicker), and a
first-sight inactive+acked one as Unspecified (an Activated row for an inactive
alarm; a retained-Active host condition never cleared).

- New AlarmTransitionKind.InactiveUnacknowledged: one projection, rows only for
  what changed (Activated+Cleared from acked, Cleared from active+unacked, none
  when already inactive+unacked).
- OpcUaClient uses it for moves into inactive+unacked; first sight of an
  inactive condition is InactiveUnacknowledged or Clear+Acknowledge, flagged.
- Projector: a flagged Acknowledge on an already-acked condition writes no row.
- E2E tests through DriverHostActor.ForwardNativeAlarm (red-proven).

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 06:08:39 -04:00
Joseph Doherty 83d8de303c fix(abcip): ALMA review round 1 + ALMD polls InAlarm (not InFaulted)
M1 drop-out is a no-row Unspecified+IsRestatement update (projector case); M2 ack judged over every declared
limit; L1 ActiveAcknowledged for an already-acked new limit; L2 Bad Acked/severity carried/skipped; L3 host
end-to-end test; L4 BOOL member-by-member tests + mixed ALMD/ALMA; L5 detection requires no plain Acked.
ALMD active bit is InAlarm per Rockwell's ALMD reference; InFaulted is input health.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 04:22:45 -04:00
Joseph Doherty b39bb6794d fix(alarms): native-alarm re-statements no longer duplicate history or hide acked alarms (#656)
- AlarmTransitionKind.ActiveAcknowledged (appended): active AND acked applied as ONE projection.
  Galaxy ActiveAcked snapshot entries and OpcUaClient inactive->(active,acked) use it; the
  projector writes 'Activated' only if not already active, 'Acknowledged' only if not acked.
- AlarmEventArgs.IsRestatement (optional, default false): set only by Galaxy snapshot entries
  and OpcUaClient first sight. A flagged Retrigger on an Active+unacked condition with the same
  message and severity, or a flagged Clear on an inactive condition, writes no /alerts row.
- NativeAlarmProjector reports the history rows per transition; ForwardNativeAlarm writes one
  row per entry. Unflagged sources (FOCAS/MTConnect/AbCip, live Galaxy) are unchanged.
- Tests: projector rules each with a must-write control; OpcUaClient transition table;
  Galaxy feed/driver mapping; Galaxy + OpcUaClient end-to-end through DriverHostActor.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 23:35:50 -04:00
Joseph Doherty f02067d295 test: retry OPC UA host start on a port bind race (TOCTOU in AllocateFreePort)
The tests probe a free port (bind 0, release) and start the SDK server later; under a
highly parallel run another test can take the port in between and the SDK fails with
'Failed to establish tcp listener sockets for Ipv4 and IPv6.'. OpcUaHostStart.StartAsync
builds a fresh host + server on a fresh port per attempt (up to 5) when the failure is a
bind failure; all 45 start sites in OpcUaServer.Tests, OpcUaServer.IntegrationTests and
Runtime.Tests use it. Per-attempt GUID ApplicationUris are hoisted out of the host factory
because a changed URI against a reused PKI store fails with 'Cannot access private key'.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 22:30:55 -04:00
Joseph Doherty e7dd742541 Merge b647-focas-alarms: FOCAS native alarms reach Part 9 conditions (ALARM: address) + respawn keeps acks host-side (#647)
v2-ci / build (push) Successful in 4m57s
v2-ci / unit-tests (push) Failing after 21m6s
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 20:46:13 -04:00