Follow-ups from the fleet-wide read-timeout audit that the S7 R2-01 read-leg
fix (PR #453) prompted. The audit confirmed S7 was the ONLY driver with the
async-read-ignores-socket-timeout hang; these are the two adjacent (non-hang)
findings it surfaced.
1. FOCAS TimeoutMs:0 footgun (the risky one): a non-positive Timeout made
SynchronizedFocasClient DISABLE its per-call wall-clock ceiling, reverting to
the caller's long-lived poll token — reintroducing exactly the frozen-peer
wedge S7 just eliminated, under misconfig. Clamp non-positive TimeoutMs to the
2s default at the config boundary so the deadline can never be authored away.
2. TimeoutMs validation symmetry: apply the same clamp in the AbCip + AbLegacy
factories. libplctag's Tag.Timeout setter throws on <=0, faulting tag creation
on every read/write; clamping keeps a misconfigured TimeoutMs:0 running on the
default bound instead. (Shared PositiveTimeoutOrDefault helper per factory.)
3. AbLegacy reconnect parity with AbCip: AbLegacy evicted the cached libplctag
runtime on neither the non-zero-status nor transport-exception read/write path
(AbCip evicts on both), so a data-path fault recovered only via the probe loop
/ libplctag internals. Added EvictRuntime + wired it into both read and write
failure paths so a fresh handle is created on the next call.
Tests: FOCAS 265->269 (clamp theory + positive), AbCip 336->339 (clamp theory +
positive), AbLegacy 209->212 (read-nonzero / read-exception / write-nonzero evict).
No production regressions; all three driver suites green.
The R2-01 live gate (S7_1500ConnectTimeoutOutageTests, docker-pause blackhole)
surfaced a real gap the offline fakes couldn't: S7.Net's ReadTimeout/WriteTimeout
map to the TcpClient's ReceiveTimeout/SendTimeout, which govern only SYNCHRONOUS
socket calls — the async read/write paths S7.Net uses ignore them. On an
established-but-frozen peer (frozen PLC / firewall DROP / cable pulled mid-flow,
TCP session still open) a read blocked until the OS TCP stack gave up (minutes),
silently wedging the poll loop: no Bad tick, no reconnect. STAB-14 fixed only the
CONNECT leg (EnsureConnectedAsync CancelAfter); this is its READ-leg sibling.
- New S7OperationDeadline: bounds every data-plane wire op with a wall-clock
ceiling (= _options.Timeout), surfacing an overrun as TimeoutException. Applied
in S7PlcAdapter to Read/ReadBytes/Write/WriteBytes/ReadStatus. OpenAsync is left
to EnsureConnectedAsync's own CancelAfter (not double-bounded).
- IsS7ConnectionFatal now classifies TimeoutException fatal → handle marked dead →
next EnsureConnectedAsync reopens (connect-timeout fix takes over from there).
- Tests: 5 S7OperationDeadline unit tests (deadline / token-honouring / caller-
cancel-passthrough / resultless), 1 driver-reaction test (read TimeoutException
→ reopen). Driver.S7.Tests 260/260.
- Live gate S7_1500ConnectTimeoutOutageTests now GREEN against the real snap7 sim
(8s: baseline Good -> pause blackhole -> Bad tick -> unpause -> recovered Good).
The 9cad9ed0 'strip tracking-ID comments' XML-doc sweep collaterally
removed the comment explaining why the S7 subscribe command routes
OnDataChange through the CliFx IConsole (not System.Console), leaving
SubscribeCommandConsoleHandlerCommentTests red. The Modbus copy still
carries the comment verbatim and the test guards S7-mirrors-Modbus
parity, so restore it (matching the Modbus wording) rather than weaken
the guard.
S7.Cli tests 49/49.
The historian's Int1 analog-tag creation path is server-degenerate:
EnsureTags(Int1) stores an unusable stub (live-probed on the deployed
2023 R2 historian; root-caused + documented gateway-side in
HistorianGateway #11 / PR #16). HistorianTypeMapper mapped
DriverDataType.Boolean -> HistorianDataType.Int1, so Boolean historized
tags failed auto-provisioning.
Map Boolean -> Int2 instead (store 0/1). Int2 is a proven-creatable
analog type, and the value-write path already sends every value as a
double on WriteLiveValues regardless of tag type, so Boolean 0.0/1.0
round-trips cleanly. Both Float and Int2 are supported, so a
pre-existing Float Boolean tag retypes cleanly on its next deploy.
- HistorianTypeMapper: Boolean => Int2 (+ remarks)
- Unit pins: HistorianTypeMapperTests, GatewayTagProvisionerTests
(Boolean_definition_carries_explicit_Int2_presence)
- Live gate: EnsureTags_boolean_sandbox_provisions_as_Int2 (was _Int1);
retype probe reframed Float->Int2 (drops the dead Int1 leg)
- Docs: docs/Historian.md 'Boolean historization maps to Int2', CLAUDE.md,
archreview STATUS.md (R2-06 live gate -> 6/6)
Resolves#441.
GatewayTagProvisioner built HistorianTagDefinition without a StorageRateMs, so
the proto uint32 defaulted to 0. The gateway's EnsureTags maps StorageRateMs
straight to the AVEVA SDK's storageRateMs, which requires a positive value —
0 makes the SDK throw ArgumentOutOfRangeException ('Storage rate must be > 0 ms'),
so EVERY historized-tag auto-provision (the deploy-time IHistorianProvisioning
hook) silently failed at the gateway with failed=N.
Stamp DefaultStorageRateMs=1000 (matches the gateway's own live provisioner
convention; quantized 1000/5000/10000). Add a regression unit test asserting the
definition carries a positive rate, and set StorageRateMs on the live-suite's
inline definitions so the retype probe reaches a real EnsureTags.
Found via the R2-06 live gate against a real 0.2.0 gateway + AVEVA historian:
with this fixed, Float/Int2/UInt2/Int4/UInt4/Double all provision and the live
suite goes 3/6 -> 5/6. (Int1/Boolean remains blocked by the gateway histsdk's
ProtocolEvidenceMissingException for Int1 — a gateway-side type-support gap, not
this bug.)
Gateway driver unit 103/103.
Four continuous-historization types (IHistorizationOutbox, HistorizationOutboxEntry,
IHistorianValueWriter/HistorizationValue, HistorizationCommitMode) drifted into a
ZB.MOM.WW.OtOpcUa.Core.Abstractions.Historian sub-namespace while the other six files
in the same folder correctly use the root namespace. This violated decision #59's
flat-public-surface rule and left InterfaceIndependenceTests.AllPublicTypes_LiveInRootNamespace
red on master (pre-existing, predates round-2 remediation).
Move all four to the root namespace and drop/retarget the now-redundant
'using ...Core.Abstractions.Historian;' in the ~11 consumers. No behavioral change.
Verified: Core.Abstractions.Tests 129/129 (was 128/129), Runtime.Tests Historian+DI 72/72,
Gateway driver unit 102/102, full solution build 0 errors.
- CapabilityInvoker: 3 methods that implement IDriverCapabilityInvoker now use
<inheritdoc /> instead of duplicating the interface docs (MissingInheritDoc).
- TwinCAT NativeRegistration ctor: added the 8 missing <param> tags (MissingParam).
- Stripped the arch-review bookkeeping IDs STAB-1 (IS7Plc, S7Driver) + STAB-2
(TwinCATDriver x4) from comments, keeping the descriptive text.
Left the other 86 flagged items untouched — they are checker false positives on
legitimate technical content: interface-implemented events / IEqualityComparer /
IDisposable members whose <inheritdoc/> IS correct (10 InheritDocMisused), and domain
terms the heuristic misreads as tracking IDs (IEEE-754, S7-1200/300/400/1500, PLC-5,
D2-260, S7/Melsec memory addresses, OPC UA Part 9, phase-N design-doc filename refs,
UNS level-N descriptions, and prose like 'the #1 bug source' / failover 'pick #3').
Inject the custom UnwrappedCapabilityCallAnalyzer as an OutputItemType=Analyzer
ProjectReference from Directory.Build.props (excluding the analyzer + its test
project) so OTOPCUA0001 runs on every src/ and tests/ compilation — it previously
enforced its CapabilityInvoker-wrapping rule against nothing but its own 31 unit
tests (the 'built-but-never-wired' failure mode).
Triage of the ~280 surfaced hits, three categories:
1. RESILIENCE-DISPATCH-GAP (7 sites, DriverInstanceActor x6 + GenericDriverNodeManager
x1): a REAL, previously-untracked gap the analyzer caught on first wiring — the
Phase 6.1 CapabilityInvoker resilience pipeline (retry/breaker/bulkhead/telemetry)
is constructed ONLY in tests and was never wired into the production dispatch
layer. Scoped per-site #pragma with a greppable RESILIENCE-DISPATCH-GAP marker
explicitly noting these are tracked-but-not-intentional, pending the dispatch-wiring
remediation (filed as a follow-up). Keeps the analyzer live everywhere else in
those projects so a NEW unwrapped call still fails the build.
2. Driver-INTERNAL self-calls (3 sites, AbCipAlarmProjection x2 + S7Driver x1):
a driver's own poll/ack path calling its own capability method. The invoker wraps
the driver from the dispatch layer OUTWARD; a driver re-wrapping its own internal
calls would double-wrap. Genuinely intentional — scoped #pragma with that rationale.
3. Wire-level test suites + manual-testing CLIs (12 projects): invoke drivers directly
by design — the analyzer's own documented intentional case. Project-level NoWarn
with a comment.
Verified: full solution build green, 0 OTOPCUA0001 hits; analyzer's 31 tests pass;
negative control — dropping one dispatch-gap pragma re-fires OTOPCUA0001 and fails
the Runtime build, proving the analyzer is genuinely live tree-wide, not disabled.