fix(r2-01): cancellation observed mid-PDU marks the connection dead before propagating (STAB-15a, task 8)
This commit is contained in:
@@ -52,7 +52,7 @@
|
||||
{
|
||||
"id": 8,
|
||||
"subject": "RED->GREEN: cancellation-during-I/O marks handle dead (T6 read + T7 write; per-item OCE catches set _plcDead before propagating)",
|
||||
"status": "pending",
|
||||
"status": "completed",
|
||||
"blockedBy": [7]
|
||||
},
|
||||
{
|
||||
|
||||
@@ -521,6 +521,17 @@ public sealed class S7Driver
|
||||
results[i] = new DataValueSnapshot(value, 0u, now, now);
|
||||
_health = new DriverHealth(DriverState.Healthy, now, null);
|
||||
}
|
||||
catch (OperationCanceledException)
|
||||
{
|
||||
// Cancellation observed mid-PDU abandons a half-read ISO-on-TCP response on the
|
||||
// single gated stream — the handle must be reopened, not reused (STAB-15a). Mark
|
||||
// dead (we hold _gate) and propagate: the caller cancelled, nobody consumes the
|
||||
// batch. Marking is unconditional on OCE (not routed through the type classifier):
|
||||
// whether bytes moved is unknowable, and a false positive costs one cheap reopen
|
||||
// versus permanent desync for a false negative.
|
||||
_plcDead = true;
|
||||
throw;
|
||||
}
|
||||
catch (NotSupportedException)
|
||||
{
|
||||
results[i] = new DataValueSnapshot(null, StatusBadNotSupported, null, now);
|
||||
@@ -1057,8 +1068,12 @@ public sealed class S7Driver
|
||||
}
|
||||
catch (OperationCanceledException)
|
||||
{
|
||||
// Let cancellation propagate rather than turning it into
|
||||
// a status code — the gate is still held so Release() runs in finally.
|
||||
// Cancellation observed mid-PDU abandons a half-written ISO-on-TCP request on
|
||||
// the single gated stream — the handle must be reopened, not reused (STAB-15a).
|
||||
// Mark dead (we hold _gate) and propagate: the caller cancelled, nobody consumes
|
||||
// the batch, and Release() still runs in finally. Marking is unconditional on
|
||||
// OCE — a false positive costs one cheap reopen versus permanent desync.
|
||||
_plcDead = true;
|
||||
throw;
|
||||
}
|
||||
catch (NotSupportedException)
|
||||
|
||||
@@ -291,6 +291,66 @@ public sealed class S7DriverReconnectTests
|
||||
factory.Created[0].Disposed.ShouldBeTrue();
|
||||
}
|
||||
|
||||
// ---- STAB-15a: cancellation observed mid-I/O must mark the handle dead ----
|
||||
|
||||
/// <summary>
|
||||
/// T6 (STAB-15a). Cancellation observed WHILE a read is in flight abandons a half-read
|
||||
/// ISO-on-TCP response on the single gated stream — the handle can't be reused. The OCE
|
||||
/// must propagate (caller cancelled; nobody consumes the batch) AND mark the handle dead so
|
||||
/// the next read reopens. Before the fix the read path converted the OCE to a Bad snapshot
|
||||
/// and kept the desynced handle.
|
||||
/// </summary>
|
||||
[Fact]
|
||||
public async Task Cancelled_read_marks_handle_dead_and_next_read_reopens()
|
||||
{
|
||||
var factory = new FakeS7PlcFactory();
|
||||
using var drv = new S7Driver(Options(), "s7-cancel-read", factory);
|
||||
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
|
||||
factory.Created[0].ReadHangsUntilCancelled = true;
|
||||
using var cts = new CancellationTokenSource();
|
||||
cts.CancelAfter(50);
|
||||
await Should.ThrowAsync<OperationCanceledException>(
|
||||
async () => await drv.ReadAsync(["W0"], cts.Token));
|
||||
|
||||
// Fresh-token read reopens a fresh connection.
|
||||
var recovered = await drv.ReadAsync(["W0"], TestContext.Current.CancellationToken);
|
||||
recovered[0].StatusCode.ShouldBe(0u);
|
||||
factory.Created.Count.ShouldBe(2);
|
||||
factory.Created[0].Disposed.ShouldBeTrue();
|
||||
}
|
||||
|
||||
/// <summary>
|
||||
/// T7 (STAB-15a). Cancellation observed while a WRITE is in flight likewise marks the
|
||||
/// handle dead before propagating (the OCE already propagated pre-fix; the reopen is what
|
||||
/// was missing).
|
||||
/// </summary>
|
||||
[Fact]
|
||||
public async Task Cancelled_write_marks_handle_dead_and_next_read_reopens()
|
||||
{
|
||||
var opts = new S7DriverOptions
|
||||
{
|
||||
Host = "192.0.2.1",
|
||||
Timeout = TimeSpan.FromMilliseconds(250),
|
||||
Probe = new S7ProbeOptions { Enabled = false },
|
||||
Tags = [new S7TagDefinition("WW0", "DB1.DBW0", S7DataType.UInt16, Writable: true)],
|
||||
};
|
||||
var factory = new FakeS7PlcFactory();
|
||||
using var drv = new S7Driver(opts, "s7-cancel-write", factory);
|
||||
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
|
||||
factory.Created[0].WriteHangsUntilCancelled = true;
|
||||
using var cts = new CancellationTokenSource();
|
||||
cts.CancelAfter(50);
|
||||
await Should.ThrowAsync<OperationCanceledException>(
|
||||
async () => await drv.WriteAsync([new WriteRequest("WW0", (ushort)1)], cts.Token));
|
||||
|
||||
var recovered = await drv.ReadAsync(["WW0"], TestContext.Current.CancellationToken);
|
||||
recovered[0].StatusCode.ShouldBe(0u);
|
||||
factory.Created.Count.ShouldBe(2);
|
||||
factory.Created[0].Disposed.ShouldBeTrue();
|
||||
}
|
||||
|
||||
// ---- fakes ----
|
||||
|
||||
private sealed class FakeS7PlcFactory : IS7PlcFactory
|
||||
|
||||
Reference in New Issue
Block a user