I1: the U11 Bits[n] -> Bits[n/32] rewrite was unconditional. The native
runtime now keeps the original element path until the first reply settles the
layout: 0xD3 confirms DWORD addressing (bit n%32); any other reply type (e.g.
a 0xC1 per-element BOOL array) or a refusal of the DWORD index falls back to
Bits[n] and re-reads, and a write settles the layout by a read first, so it can
never decode or write element n/32 of an element-addressed array.
I2: libplctag ErrorNoMatch/ErrorBadDevice no longer fold into NotFound (they
now read as BadConnection: comms, Degraded, LastSuccessfulRead preserved).
ErrorNotImplemented - and the native runtime's own pre-send refusals - raise
AbCipLocalRefusalException: BadNotSupported, no health, LastSuccessfulRead NOT
advanced, no backoff record, not reachable for the probe or Test Connect.
M1: the bit RMW's parent read/write status words follow the health contract
(refusal: per-tag Bad + Warning; comms: evict the parent + Degraded).
M2: device Unsupported read refusals return Refused (advance
LastSuccessfulRead); device write refusals call RecordWriteAnswered (not the
pre-send native type gate).
M3: a good write clears a Degraded a write comms fault recorded (a read-side
Degraded is still left for the read path).
M4: a superseded init throws AbCipInitializationSupersededException (not an
OCE); ShutdownAsync stamps Unknown only if no newer init published meanwhile.
M5: the sync-Dispose timing assert is 2 s against a 4 s probe read; the
unencodable-array test asserts health.
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
F10 follow-through: removing IDisposable outright broke a synchronous
drv.Dispose() call site outside this lane (Runtime.Tests
AbCipAlmaNativeAlarmEndToEndTests). The sync Dispose() is back, but it starts
the same teardown as DisposeAsync and returns instead of parking the caller on
DisposeAsync().AsTask().GetAwaiter().GetResult(); a background fault is
logged. The runtime still takes the IAsyncDisposable path (preferred, never
both).
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
U10 (user decision: implement array encode now): config, the AdminUI and
discovery all advertised array tags Operate-writable, but both runtimes encoded
a scalar - an int[] threw InvalidCastException (BadTypeMismatch AND Degraded),
a scalar wrote element 0 natively, and libplctag re-sent its whole last-read
buffer with element 0 patched (stale elements 1..n-1).
- AbCipArrayCodec encodes count elements little-endian at the element width,
CONVERTING each element (ScadaBridge writes int[] to INT arrays; overflow is
BadOutOfRange, unconvertible BadTypeMismatch, both before anything is sent).
- The driver checks the shape before any runtime exists: not a list ->
BadTypeMismatch, length != elementCount -> BadOutOfRange, BOOL/STRING/
structure element types -> BadNotSupported; and, before sending, a controller
buffer that is not width x count -> BadTypeMismatch. Refusals warn once and
write no health.
- Native: ONE Write Tag of count elements with the controller's type code (the
client fragments a large one); libplctag: the codec's bytes copied into the
elem_count-sized buffer, refused TooSmall if it does not fit.
- IAbCipTagRuntime.EncodeArray (default: NotSupportedException).
Real-controller proof is a hardware userGate (see the lane report recipe).
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
U11: a scalar BOOL authored over Bits[n] requested element n and decoded
"any of bits 0-7 of the reply set", so Bits[n] read Good with the subscript
ignored. A Logix BOOL array is stored as DWORDs (0xD3) and its element segment
addresses them, so the native runtime now requests DWORD n / 32 and decodes bit
n % 32 when the controller answers 0xD3 (a plain BOOL reply still decodes its
byte). libplctag exposes no type code and so cannot say which DWORD it read: a
4-byte reply for such a tag is refused BadNotSupported (warned once) instead of
publishing a wrong value as Good. Real-controller proof is a hardware gate.
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
H19: Format/InvalidCast/Overflow on a client value never touched the wire but
latched Degraded; a good write set Healthy and so undid a Degraded the poll
loop had just recorded for other tags (the batch read path is worst-wins for
exactly this reason).
- The three conversion failures map to BadTypeMismatch/BadOutOfRange with a
once-per-tag Warning and no health write (AbLegacy's rule).
- A good write (scalar or bit RMW) advances LastSuccessfulRead only - the
device answered - and leaves the state alone.
- A write comms fault (thrown, or a non-refusal status word, which used to
write no health at all) is Degraded with LastSuccessfulRead preserved and
never downgrades Faulted.
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
H17: the .n read-modify-write hard-coded a DINT parent. On an INT or SINT host
(both legal in Logix, and reads of Flags.3 there already worked) the DINT
decode of a 2-byte buffer threw OutOfBounds, the generic catch evicted the BIT
tag's (non-existent) runtime and reported BadCommunicationError + Degraded.
The parent width now comes from the parent read's size (1 SINT / 2 INT /
4 DINT / 8 LINT; unknown keeps the DINT assumption). Narrow hosts use unsigned
arithmetic so a set top bit encodes without overflow; a bit past the host's
width is BadOutOfRange and a non-integer width BadTypeMismatch, both refused
before anything is written, warned once, no health write. A transport failure
in the RMW now evicts the parent runtime it actually used. Native end-to-end:
an INT host is written as ONE INT (type 0xC3, 2 bytes).
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
P8: on the native transport the bounded-parallel read window is also the cap
on services per Multiple Service Packet (the device's shared scheduler packs
whatever is queued, within the connection's request/reply byte budget), so the
default 8 cost a 1000-tag controller ~125 round trips per poll instead of ~10.
The effective window (AbCipDriver.ReadWindow) is now max(64, option) when the
native tag factory serves reads; libplctag and injected factories keep the
option exactly. Option doc + AdminUI help text updated (Razor: Wave 4 live
check).
P7 addendum: a work item now takes its window slot only after its runtime
exists. A cold create queues on its device's single-flight connect gate, and
holding a slot there let one dead device's backoff-expiry attempt occupy the
whole window for a full Timeout, stalling every other device's reads.
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Found by the H13 stress test (200 re-inits under a concurrent reader): a read
that resolved the device just before the table swap could cold-create a
runtime into the retired state after its teardown had disposed it (leaked
native handle / lease), and could hit a per-tag SemaphoreSlim the teardown had
disposed, which the generic catch reported as a comms fault (Degraded).
- DeviceState.Retire marks the state retired before disposing handles; each
handle is removed-then-disposed exactly once. A creator re-checks the flag
after its TryAdd (fenced, Dekker-paired with Retire) and disposes the orphan.
- A failure on a retired device is the teardown's doing: BadCommunicationError
for that one call, no evict, no health signal.
- Per-tag/RMW gates are no longer disposed (async-only waits hold no handle),
matching the ConnectGate rationale.
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
H10: the probe loop recorded EVERY exception - including the controller
answering NotFound for a typo'd or download-deleted Probe.ProbeTagPath - as a
Forward-Open failure. At a 5 s tick against a 30 s backoff cap ShouldAttempt
was never true again, so every cold or evicted data tag on a reachable device
read BadCommunicationError indefinitely and the host showed Stopped.
The probe now decides the backoff verdict and the host state separately:
- a device refusal (thrown or as a status word) is backoff success + host
Running + one Warning per device naming the probe tag; an initialised probe
runtime is kept so its lease is not re-opened every tick;
- a malformed probe tag name (AbCipTagConfigurationException) never reached
the device: no backoff signal, no host transition, one Warning;
- a genuine transport failure is unchanged (backoff failure, host Stopped).
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
H1/L4: one classification (AbCipRefusals.IsDeviceRefusal) of the statuses
that prove the controller answered - NotFound, OutOfBounds, NotAllowed,
TooLarge, TooSmall, TypeMismatch, Unsupported - shared by the data path, the
Test-Connect probe (IsReachableStatus widened) and the native runtime.
- A refused read/write (thrown or as a status word) is per-tag Bad with a
once-per-tag Warning, keeps the runtime (no evict, so no lease/Forward-Open
churn for a sole lease holder), writes no Degraded and, since the device
answered, advances LastSuccessfulRead without touching the state.
- A refused cold create records the backoff as reachable, so siblings are no
longer throttled for up to 30 s by one Arr[999].
- The native runtime completes InitializeAsync on any refusal (it used to on
TypeMismatch/Unsupported only) and reports it on every later read.
- A refused READ of NotAllowed reads BadNotReadable, not BadNotWritable.
- Test Connect names the refusal ("probe tag refused: OutOfBounds").
0x1C/0x20/0xFF-0x2104 still fold into BadReply inside Driver.Ab.Transport
(Lane K follow-up); they remain comms faults until mapped there.
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
H13: _devices/_devicesByRoutingKey are published by reference swap under a
lifecycle lock and never mutated after publish, so the retained poll engine,
discovery and the actor's GetHostStatuses pull never read a table mid-Clear.
Every retire (init's own release, shutdown, dispose) takes the table it
replaces, so ShutdownAsync racing DisposeAsync tears each state down once, and
a generation check makes an InitializeAsync overtaken by a shutdown publish
nothing (it throws OperationCanceledException) instead of resurrecting probe
loops behind the shutdown. Probe join is one bounded 5 s wait independent of
the caller token.
H21: _health is volatile and read-modify-write updates go through a CAS.
F10: the sync Dispose() (sync-over-async) is removed; DisposeAsync is the
complete, idempotent teardown the runtime calls after ShutdownAsync.
Refs #737
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Clears CommentChecker findings in src/ (3,280 -> 209, the remainder being false
positives like PLC-5/IEEE-754/M0.0) by adding missing summaries/params/returns,
normalising inheritdoc usage, and removing Gitea/review tracking IDs while keeping
the rationale they annotated. Comment-only: comment-stripped sources are identical
to the parent commit.
Since #516 a DriverConfig change is stop + respawn, so DriverSpawnPlan.ToApplyDelta
was always empty and the in-place path had no producer. #663 and #664 were both
latent bugs in it. This deletes it:
- host: ApplyChildDelta, _pendingDelta, HandleApplyResult and HandleDeltaApplied
- plan: DriverSpawnPlan.ToApplyDelta
- actor: the ApplyDelta, ApplyResult and DeltaApplied messages, the Connected
reinit handler and the mid-connect AdoptConfigDuringInit
- tests: the actor tests that drove the seam
IDriver.ReinitializeAsync and each driver's implementation and unit tests stay.
Comments and docs that cited AdoptConfigDuringInit as the reason a driver must
release prior state at init now cite the IDriver contract and overlapping
retries, which still apply.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- L2: WriteWidthRefusal leaves a BOOL over a wider value to a runtime that sees the CIP
type (native): mistyped integer member -> BadTypeMismatch (as its read), 0xD3 BOOL-array
DWORD -> BadNotSupported; libplctag keeps BadNotSupported for both (size only).
- L4: direct theory over WriteWidthRefusal (1/2/4/8 widths incl LINT/ULINT/LREAL, String/Dt,
unknown size) + array/bit-selector exemptions with a non-vacuous control.
- L1: CLAUDE.md member/BIT-member writes are ab_server-proven only.
- L3: patch 0003 blind spots documented (Docker README, AbServer-Test-Fixture.md); nits.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Item 2 — controller-discovered UDT members are writable on both transports once
browse-committed and authored ReadWrite (writability is the operator's: the commit
lands AccessLevel Read with no writable key). The write names the member (one CIP
symbolic segment per member), its own type, its own bytes. BIT members are supported:
Z-35162 (read-only probe) exposes a UDT BIT member as a 1-byte 0xC1 BOOL, so the
controller applies the bit and the hidden host's other bits are never in the request.
- AbCipDriver: pre-write width check on BOTH transports (libplctag patched part of
its read buffer and sent it all): BadTypeMismatch, Bool over a wider value
BadNotSupported; nothing sent, handle kept, health untouched, warn once.
- A runtime NotSupportedException is a refusal: no longer latches Degraded.
Item 3 — whole-UDT writes refused BadNotSupported before any runtime exists, by
decision (a structure write overwrites hidden hosts + padding), documented.
ab_server patch 0003: serve member paths from dotted flat tags (UdtSeg.*), and
accept libplctag's pad byte on 1-byte writes (stock ab_server refused every
libplctag BOOL/SINT write with 0x03). New AbCipUdtMemberWriteTests (both
transports), AbCipDiscoveredMemberWriteTests, native request-byte theory, and a
browse-commit mapper pin. Docs: AbCip.md Member writes / Whole-UDT writes / Known
gaps, fixture docs, CLAUDE.md AB section.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
M1 drop-out is a no-row Unspecified+IsRestatement update (projector case); M2 ack judged over every declared
limit; L1 ActiveAcknowledged for an already-acked new limit; L2 Bad Acked/severity carried/skipped; L3 host
end-to-end test; L4 BOOL member-by-member tests + mixed ALMD/ALMA; L5 detection requires no plain Acked.
ALMD active bit is InAlarm per Rockwell's ALMD reference; InFaulted is input health.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Detect ALMA by declared *InAlarm members; one condition per tag keyed on RawPath; severity/message from
the most severe active limit; Raise/ActiveAcknowledged/Retrigger/Clear/Acknowledge; ack writes OperAckAll.
Unit-tested over fake runtimes only (no ab_server ALMA support, Z35162 has none).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Now that ALMD transitions route, a re-subscribe (every reconnect, every alarm-set change)
started from an empty per-subscription record and re-RAISED every still-faulted alarm,
which the host projects as Active+unacked - un-acknowledging a condition the server had
just carried across the rebuild with its client ack. The record is now driver-owned and
pruned to the new set, mirroring MTConnect's _deliveredConditions.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
FOCAS, AbLegacy, AbCip, TwinCAT, S7 and OpcUaClient orphaned the previous
probe/recycle/fixed-tree loops and clients when re-initialised on a live driver.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
#570
- STRING: the built-in 88-byte Logix STRING holds 82 characters (LEN + DATA[82] + 2 pad), not 84; the
write still sends the whole 88-byte structure and a read never decodes the pad as characters.
- Mistype churn: a type refusal (CIP 0xFF/0x2107) on the existence read no longer throws from
InitializeAsync, so the runtime is not disposed/re-created (and re-Forward-Opened) every poll; the driver
also keeps a runtime that throws TypeMismatch from init and records the device as reachable.
- Malformed tag name: a TagPath that does not parse, or a name the CIP symbolic encoder refuses (now also
non-ASCII, empty member, >255-char member, unterminated subscript), is AbCipTagConfigurationException ->
per-tag BadConfigurationError (named const in AbCipStatusMapper), warned once, never feeding the device
backoff or health; siblings keep reading. A malformed probe tag no longer feeds the backoff either.
- Micro800 BYTE/WORD/LWORD (0xD1/0xD2/0xD4) are type-checked as integers of their width: REAL/LREAL or a
narrower integer over LWORD is TypeMismatch, not decoded garbage.
#579
- ConnectionLease.ReleaseInBackground: one non-blocking release shape for both native AB runtimes. The
AbCip runtime's Dispose no longer waits up to 2 s under the per-tag lock; the pool still registers the
close synchronously so a re-create cannot overlap it. Offline soak tests (25 cycles, AbCip + AbLegacy)
prove no leaked connection; FakeEipServer gains OpenConnections.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
#572: listing continues at max(instance in page)+1 (no ascending-order assumption, no-progress guard kept);
browsePageDelayMs (default 5 ms) paces pages; DiscoverAsync reads templates through one batch reader
(IAbCipTemplateReaderFactory.CreateBatch) holding one lease.
#575: differential harness reports a same-status template refusal as an equal refusal; offline test pins the
open-attempt budget without relying on the abort ending the phase.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A native TypeMismatch (read status, write gate, or CIP 0xFF/0x2107) used
to evict the runtime and degrade health on every poll; for a sole lease
holder that meant Forward Close + Forward Open per poll, and an all-
mismatched driver tripped the comms-loss watchdog. It now reports
BadTypeMismatch, keeps the handle, leaves health alone and warns once per
tag per instance — reads, whole-UDT reads and writes, plus the libplctag
width check. Tests (red against the pre-fix driver): single create over N
polls, unchanged health, one warning, and one Forward Open / zero Forward
Close over the real native runtime against FakeCipTarget. AbLegacy has no
TypeMismatch path (its native runtime has no type check).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The old AdminUI cannot author the per-driver transport key (#576), so the
'pin before upgrading' recipe had no working path. A node-level appsetting
(env Drivers__AbCip__DefaultTransport) now supplies the default for AbCip
drivers with no key: explicit key > node default > compiled Native. Bound
and validated unconditionally (bad value fails host start); the driver
factory and the Test Connect probe both read it so they agree. AbCip.md
upgrade recipe rewritten around the key; Configuration.md documents it.
Also documents first-wins for AllowPacking/probe and host-alias throttles
(final review M6) and moves the status-bit note out of AbCip.md (M5).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Native is the default, so a locally refused write must not look like a comms fault.
- AbLegacy: an AbTransportException with AbStatus.Unsupported (status-bit sub-element writes, PLC-5
non-N reads, all PLC-5 writes; libplctag's ErrorUnsupported maps here too) now returns
BadNotSupported on both the read and the write path (incl. the bit-RMW path). The tag handle is
not evicted and driver health is not touched. A native runtime whose init read is refused locally
is CACHED rather than disposed, so a poll of a refused tag does not re-create (and re-lease the
pooled connection) every cycle.
- AbCip: the same mapping on the write path and both read paths (single + whole-UDT).
- Uses the existing named BadNotSupported constants (StatusCodeParityTests guard).
- Tests (falsified by disabling the mapping, and separately the keep-on-refusal): status-bit
writes and PLC-5 read/write through the driver over the native runtime — BadNotSupported, zero
wire requests, one create, health unchanged; AbCip refused read/write via a refusing fake plus a
control that a non-refusal failure still evicts and degrades.
- Docs/CLAUDE.md: BadNotSupported; #571 known-gap wording removed.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- I1: the upgrade restart itself moves every no-key AbCip/AbLegacy driver to Native (every process
start constructs drivers, incl. boot-from-cache). Docs + CLAUDE.md now say so and tell operators
to set "transport": "Libplctag" BEFORE upgrading (older builds ignore the unknown key).
- I2: AbLegacy release note leads with the status-bit write refusal (T4:0.DN, C5:0.CU, R6:0.EN, ...)
on defaulted SLC/MicroLogix drivers and the fallback. The real client status is
BadCommunicationError, not BadNotSupported (the driver's write catch-all maps the runtime's
AbTransportException like any transport failure, as #571 does for PLC-5), with handle eviction
and Degraded health; pinned by a driver-level test (no 0xAA write on the wire, with a positive
control). ST string byte order stated as unverified. Also corrects the docs' "T4:0/DN" examples:
the driver's address grammar is "T4:0.DN" ("/DN" is a malformed address).
- I3: DriverProbeHandshakeE2eTests' two AbCip probe tests are a [Theory] over Native and
Libplctag. Run against ab_server controllogix: all 4 rows pass with identical exact messages.
- M1: documented (docs + resolver XML doc): the AdminUI merges only the probed device, so a
mixed-family defaulted AbLegacy driver can probe Native while running Libplctag.
- M2: factory ParseEnum rejects undefined integer strings ("7") via Enum.IsDefined (both drivers).
- M3: AbCip driver-level bad value reads "AB CIP config in '<id>' has unknown Transport ..."; the
named constant is gone (tagName: null now means driver-level).
- M4: the explicit-Native limited-family Warning is once per instance, not per (re)init.
- Nit: EffectiveTransport docs note that injected factories bypass it.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Task 22 (spec section 8 P5), with the controller rulings that exclude PLC-5 and LogixPccc.
- Transport is nullable on both option records; null (key absent) means "use the default" and is
never serialized. Factory DTO parse: absent -> null; a bad value still fails via ParseEnum.
- One resolver per driver (AbCipTransportResolver / AbLegacyTransportResolver), used by the driver
constructor, the Test Connect probe and (through the driver) the CLI.
AbCip: null -> Native. AbLegacy: null -> Native unless any device is Plc5 or LogixPccc, then the
whole driver resolves to Libplctag. Explicit values always win; explicit Native with a
Plc5/LogixPccc device logs one Warning at init.
- Init log shows configured vs effective, e.g. transport=Native (default).
- AdminUI forms: "Default (...)" / "Native (managed)" / "libplctag (fallback)". Default omits the
key on save (reverses Task 19's explicit re-emit, which would have pinned every edited driver).
- CLIs: --transport default|native|libplctag, default "default" via the resolver, so
--plc-type Plc5 with no --transport runs libplctag.
- Tests pinned to Libplctag where a default-path runtime was created: found by instrumenting the
native factories with the current xUnit test name (one unit test, AbLegacyReinitConfigAdoption;
plus the two fixture-gated AbCip probe E2E tests whose exact messages were proven on libplctag).
TransportMatrix and the differential harness already pass explicit transports.
- Switch/resolver/CLI/form tests are falsified by mutating the resolver (default -> Libplctag,
exclusion removed, AbLegacy default -> Libplctag): each mutation turns them red.
- Replaces the inline role-name literal in AbCipDriverFactoryExtensions' ParseEnum call with a named
constant; RoleAuthorityGuardTests was already red on the base commit for that line.
- Docs: AbCip.md / AbLegacy.md default + release note; CLAUDE.md AB section.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- AbCip/AbLegacy driver forms gain a Transport InputSelect; FromOptions/ToOptions now carry
Transport, so saving any other field no longer silently reverts Native to libplctag.
- Both drivers log the constructed transport once per init.
- AbCip factory now takes the host ILoggerFactory (it ran on NullLogger in production, hiding
every AbCip log line); DriverFactoryBootstrap passes it.
- Gate results: AdminUI /run (T19) native, inverted (dead port) and libplctag legs.
libplctag decodes whatever bytes the controller returns as the authored type and never
checks the CIP type code. Live read-only check on a production press: WW_ActualVacuum is a
REAL (L5X + the controller's symbol table agree) but the legacy Kepware export in the
ignitionoee repo types it Short; read as INT it returned Good -17346 while the real value
was 5.37. A scalar atomic read (not an array, not a bit-in-DINT) whose buffer size is not
the authored type's width now reads BadTypeMismatch with a warning naming both. Widths
observed live: SINT/BOOL 1, INT 2, DINT/REAL 4, LINT 8. IAbCipTagRuntime.GetSize() is a
default-interface member (-1 = unknown, never checked). Same-width mismatches (DINT vs
REAL) stay undetectable without the type code libplctag strips.
Live read-only check against a production CompactLogix press: with one nonexistent tag
first in the read list, libplctag's create threw LibPlcTagException("ErrorNotFound"); the
driver counted it as a failed Forward-Open, opened the device's 05/STAB-8 connect-backoff
window, and every other cold tag on the device - all real (WW_InCycle, WW_ActualPress,
WW_WorkOrderNum) - read BadCommunicationError. In steady polling the bad tag re-opens
the window each attempt, so siblings ordered after it may never connect.
- A create that fails with a "controller answered" status (NotFound/NoMatch/BadDevice,
the probe's existing reachable classification) records backoff SUCCESS, not failure.
Genuine connection failures still open the window (falsification control test).
- Read exceptions map through the libplctag Status they carry: unknown tag ->
BadNodeIdUnknown, decode past the buffer -> BadOutOfRange, timeout -> BadTimeout,
instead of a blanket BadCommunicationError. One status-name parser
(AbCipStatusMapper.TryGetStatus) now serves both the read path and the probe.
Live read-only check against production CompactLogix 5069-L320ERS2 rev 34.11 presses
(Z-35162 / 10.209.70.160): every @udt/<id> template the controller returned decoded to
null, so controller-discovered UDTs never fanned out. The decoder assumed a 12-byte
header led by the member count and [info][array][offset] blocks with ';'-terminated
names; libplctag actually returns a 14-byte header (u16 id, u32 def words, u32 instance
size, u16 member count, u16 handle), [info][type][offset] blocks, and NUL-terminated
names after a 'Name;<tail>' type name. All three test builders restated the old
assumption, so the unit suite agreed with itself (the #468 trap again); they now share a
TemplateBufferBuilder pinned by real captures (CipTemplateObjectWireCaptureTests).
Discovery follow-ons that the working decoder exposed:
- STRING (and user string types, LEN DINT + DATA SINT[n]) browse as one String variable,
top-level and nested, not as a LEN/DATA folder.
- Controller-generated members (ZZZZZZZZZZ* BOOL hosts, __* AOI backing) are not browsed.
- A UDT array is not fanned out into element-free Tag.Member paths.
Found on the docker-dev live gate, not in tests. Two drivers that faulted
during initialise (rtu-gate, opcua1) each rendered "0 tags" on /hosts against
two authored tags apiece, because a ledger that had never committed returned
SkippedTagReport.Empty.
A zero report is a positive claim -- "this driver skipped nothing" -- and
making it on behalf of a driver that never got as far as looking is exactly
the quiet inaccuracy #541 exists to remove. GetSkippedTags() and
SkippedTagLedger.Snapshot() now return null until the first committed build,
so the column renders the same em-dash it already used for a driver that
cannot report at all. Both are 'no answer'; neither is 'nothing skipped'.
Knock-on: a FOCAS driver whose only init threw now reports null rather than a
zero report, which is strictly more honest than the assertion the test
originally made.
A driver builds its RawPath -> definition table at init and tolerates a
per-tag miss: an unmappable TagConfig, an unparseable address, a
capability-matrix rejection. That tolerance is right -- one bad tag must not
take down the other few thousand. What was missing is any statement of the
fact afterwards. A skip is not an error and happens before any read, so the
driver stays Healthy, errors/5 min stays 0, Last error stays empty, and Last
read advances live off the tags that did map. On the wonder Makino in #540
that reading held while focas-z-34184 ignored 20 of its 22 tags.
New optional capability ISkippedTagReporter, backed by a shared
SkippedTagLedger so the reset/commit/cap rules are one implementation rather
than one per driver. The report -- authored count, exact skipped count, and a
capped sample of RawPath + reason -- rides DriverHealthChanged to a new Tags
column on /hosts, over the Phase 5 telemetry stream. No table: a driver-only
node has no ConfigDb to write to, the lesson from #521.
The issue named eight drivers. It is twelve -- every driver in
DriverTypeNames.All has an authored-tag skip path. Calculation (no scriptId),
MTConnect (no readable DataItem id), Galaxy (no attributeRef) and OpcUaClient
(no nodeId) were unlisted, and OpcUaClient's was the quietest of the twelve:
NamespaceMap drops such an entry with a bare `continue` and not even a log
line. SkippedTagReporterFleetTests pins the invariant reflectively over every
IDriver in src/Drivers/, so a thirteenth cannot re-introduce the silence.
Sql drops a tag at TWO points and its report is the union of both: a blob
that does not map, AND an identifier the 8.1 catalog gate rejects against the
live catalog. The second is what schema drift produces -- a renamed column, a
dropped view -- months after a deployment sealed green, and reporting only
the first would have that driver claim "0 skipped" while polling half its
tags, which is worse than reporting nothing because the column would then be
actively reassuring.
Deliberately additive to driver state, never a change of it. Latching
non-Healthy for a config problem would satisfy both halves of the #527
comms-loss conjunction -- 90 s without a successful read AND non-Healthy --
and a driver whose tags were ALL skipped has no successful reads by
construction, so it would reconnect-loop forever against a healthy device.
Three details that are load-bearing rather than incidental:
- The skip digest is part of the publish fingerprint. A skipped tag leaves
every other fingerprint component identical to a clean driver's, so without
it PublishHealthSnapshot's dedup swallows exactly the publish carrying the
signal -- the trap that already bit the rediscovery and host-status
channels. The digest covers the sample, not just the counts: a redeploy
that fixes one tag and breaks another leaves both counts unchanged.
- The count is exact; only the sample is capped, and the tooltip says so when
it is showing fewer than it counted. A truncated list that looked complete
would have an operator fix twenty tags and believe the job done.
- The ledger stages and commits, so an init that throws part-way leaves the
previous report standing. A partial snapshot would read as "we now skip
fewer tags", the opposite of the truth.
The proto field needs no companion presence flag, unlike host_statuses: a
singular message field carries real presence in proto3, and a has_ flag would
collide with protoc's generated HasSkippedTags.
Verified red-first three ways: dropping SkippedTagDigest from the fingerprint
fails the two dedup tests, removing the seam from one driver fails the fleet
guard, and dropping the catalog-gate leg fails the Sql union test. Full
solution builds with zero new warnings against 4e22f024.
A browse-committed AB CIP / TwinCAT / FOCAS tag bound with its model's DEFAULT
data type, not the one the device reported. A browsed REAL committed as
`{"tagPath":"Pump_1_Speed","dataType":"DInt"}` — and those three drivers decode
the wire bytes by that field, not by the raw row's OPC UA DataType — so the tag
read four bytes of a float through an integer decoder and published a plausible
wrong number with no error raised anywhere. FOCAS was missed when #536 was filed.
The type is CARRIED, not derived. Reverse-mapping the leaf's driver-agnostic
DriverDataType looks like the smaller fix and is wrong: SInt/Int/DInt/USInt/UInt
all collapse into Int32 on the way out of the driver, so that version would bind
a 16-bit INT as a 32-bit DINT while appearing to fix the REAL. Drivers now state
their own type name on DriverAttributeInfo.NativeDataType, which reaches the
picker as AttributeInfo.AddressFields["dataType"] and the commit mapper from
there. A leaf that states nothing keeps the model default — the pre-#536
behaviour, kept deliberately as the fallback rather than a guess.
Numeric strings are refused before parsing: Enum.TryParse accepts "9" for any
enum and Enum.IsDefined then confirms it, so an unguarded parse would bind a tag
to a type nobody named. A test caught this in the first version of the guard.
--- and the other half, which the fixture was hiding ---
Test Connect on a device with NO authored tags — every AB CIP device at the
moment an operator first presses the button — reported "CIP handshake failed"
against a healthy controller. That was written down as a fixture limitation
("ab_server doesn't implement @raw_cpu_type"). Both halves of that were wrong:
* @raw_cpu_type is not a libplctag special tag at all (only @raw, @tags and
@udt/ are), so it goes out as an ordinary symbolic name that no controller
defines, and the controller's "tag does not exist" IS the successful answer.
* ab_server answered an unresolvable tag path with CIP 0x03 where a Logix
controller answers 0x04 — ErrorBadParam vs ErrorNotFound, which the probe
classifies oppositely. Fixed in vendored patch 0002.
* With the fixture then telling the truth, the real defect surfaced:
AbCipDriverProbe.IsReachableException matched the native C status spellings
("STATUS_NOT_FOUND"), but libplctag.NET throws with the MANAGED enum name
("ErrorNotFound"). Those substrings can never match, so the reachable
classification could not fire on the exception path — which is the path every
no-authored-tags probe takes. This was failing on real hardware too, not just
against the sim. It now recovers the Status and defers to IsReachableStatus,
so there is one classification rather than two that can drift.
Rejected: switching the fallback to @tags. libplctag builds a tag-listing tag
with NO network I/O, so it reports OK against any TCP listener — measured green
against a Mosquitto broker.
Verification: full solution suite green. Falsification runs confirm exactly the
intended tests go red — 9 for the type carry, 3 (the reachable statuses only) for
the probe classification. Live on docker-dev: browse-committed TestString/
Motor_Run/TestSINT now store String/Bool/SInt, alongside last session's
Pump_1_Speed still holding the wrong DInt. TestSINT is the falsifier — its row
DataType is Int32, identical to TestDINT's, so no reverse map could have produced
"SInt".
Known consequence: pre-existing browse-committed tags keep their wrong dataType;
the fix applies to new commits only.
Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo