1f983d610f
A. #566 on a real CompactLogix (Z-35162, read-only): a class-3 connection idled 60 s past its 16 s timeout is closed at the TCP level, not with CIP 0x0107/0x0203; the next request fails on its write (Broken pipe -> BadConnection) in 9 ms and the one after reopens. The transport already handles this, so no production behaviour changed; the shape is pinned offline by CipConnectionTests.A_target_that_resets_an_idle_session_... (FakeEipServer.ResetAllConnections), proven red with a reconnect-skipping mutation. The diagnostics-only exchange tap now also sees Forward Open replies (granted RPIs). B. Native STRING write through the driver on Program:ES03_TemperatureControl._StrTmp: write, read back, restored byte-exact (user-approved). Array write NOT run: the census's unreferenced DINT[32] _SEQ_EP arrays are aliased sequencer step registers (raw L5X grep), so none qualifies. #567 still impossible (a 128 B array / 88 B STRING never fragments). New env-gated harness: AbCip.IntegrationTests/HardwareGate (IdleConnectionEvidenceTests, StringWriteGateTests). Docs: gate results (hw5 section + raw output), AbCip.md, CLAUDE.md. Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
16 lines
2.3 KiB
Plaintext
16 lines
2.3 KiB
Plaintext
# hw5 native STRING write gate, Z-35162, 2026-10-09 10:10:54Z-10:11:29Z UTC (user-approved; restored)
|
|
# AB_HW_WRITE_GATEWAY=ab://10.209.70.160/1,0 AB_HW_WRITE_APPROVED=1 AB_HW_WRITE_STRING_TAG=Program:ES03_TemperatureControl._StrTmp -> HardwareGate/StringWriteGateTests
|
|
Passed ZB.MOM.WW.OtOpcUa.Driver.AbCip.IntegrationTests.HardwareGate.StringWriteGateTests.A_native_STRING_write_reads_back_and_restores_the_exact_original [32 s]
|
|
Gateway ab://10.209.70.160/1,0; tag 'Program:ES03_TemperatureControl._StrTmp'; transport Native; snapshot gap 30 s
|
|
snapshot 1: status 0x00000000, value 'ES03_TemperatureControl:Fault', raw (92 B) A002CE0F1D000000455330335F54656D7065726174757265436F6E74726F6C3A4661756C7400000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
|
|
snapshot 2: status 0x00000000, value 'ES03_TemperatureControl:Fault', raw (92 B) A002CE0F1D000000455330335F54656D7065726174757265436F6E74726F6C3A4661756C7400000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
|
|
Preflight OK: type/handle A002CE0F, LEN 29, tail zero; original 'ES03_TemperatureControl:Fault'
|
|
write test value: 'OTOPCUA-TEST' (ASCII 4F544F504355412D54455354) -> status 0x00000000
|
|
read back test value: status 0x00000000, value 'OTOPCUA-TEST', raw (92 B) A002CE0F0C0000004F544F504355412D54455354000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
|
|
restore original: 'ES03_TemperatureControl:Fault' (ASCII 455330335F54656D7065726174757265436F6E74726F6C3A4661756C74) -> status 0x00000000
|
|
read back restored: status 0x00000000, value 'ES03_TemperatureControl:Fault', raw (92 B) A002CE0F1D000000455330335F54656D7065726174757265436F6E74726F6C3A4661756C7400000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
|
|
Test-value raw LEN 12; restored raw equals original: True
|
|
final snapshot: status 0x00000000, value 'ES03_TemperatureControl:Fault', raw (92 B) A002CE0F1D000000455330335F54656D7065726174757265436F6E74726F6C3A4661756C7400000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
|
|
RESULT: write, read-back, exact restore — PASS
|
|
Total time: 34.8142 Seconds
|