fix(galaxy): picker-form alarm ack waits for the feed snapshot instead of dialling bare tag.Attr (#904)
A picker-form native alarm (attributeRef tag.Attr) only learns the provider-qualified reference
Galaxy!<Area>.tag.Attr from the alarm feed. After a host restart the condition can be restored from
LocalDb before the feed's first snapshot reached the new driver, and an ack in that window dialled the
bare tag.Attr, which the gateway's AcknowledgeAlarm refuses.

The feed now exposes InitialSnapshotCompleted (set on snapshot_complete, after every snapshot entry has
been raised). AcknowledgeAsync resolves the reference through ResolveAlarmAckReferenceAsync: when a
picker-form tag has learned nothing yet and the feed is running, it waits for that snapshot (2 s, and the
caller's token) and dials the reference the snapshot names, so the area always comes from the feed and a
re-areaed object acks under its current area. No reference is guessed: if the snapshot does not name the
alarm, or does not arrive in time, the authored reference is dialled as before and refused visibly.

Chosen over the alternatives in the issue: a GR-browse area lookup can be stale against the runtime
area and is not loaded for authored tags, and a gateway-side tag.Attr resolution needs a cross-repo
deploy and would resolve from the same monitor cache the snapshot already carries.

Tests: 5 driver cases + 1 feed case (fail with the call site / sentinel reverted), and a skip-gated live
gate GalaxyPickerAckBeforeSnapshotLiveTests, run against windev's TEST Galaxy (TestMachine_015.TestAlarm003):
an ack issued before the snapshot dials Galaxy!TestArea.TestMachine_015.TestAlarm003 and is confirmed; with
the call site reverted it fails with the gateway's InvalidRequest refusal.

Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi