Files
lmxopcua/tests/Drivers
Joseph Doherty 875b82175d fix(galaxy): #866 grade OK-status data changes by the item's OPC DA quality
The gateway fills Statuses on every data change (live OnDataChange, value-cache
replay and session snapshot all carry Quality too), and EventPump used the status
row whenever one was present, so Quality was never read: an off-scan, Bad or
Uncertain attribute with an OK status row was published Good. A failure status
row still wins; otherwise the quality byte grades the value (legacy parity:
quality >= 192 Good).

Live, read-only on VD03 (DEV): healthy ScanState and _TestArea attributes stay
Good (0x00000000) via quality 192; the stopped JoePlatform/JoeAppEngine ScanState
now publish BadCommunicationError (0x80050000) instead of generic Bad, with no
"unrecognised quality byte" warning.

Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
2026-11-11 15:14:11 -05:00
..