U2: MaxReadGap defaults to 8 and 0 now means adjacent-only rather than off; a new DisableReadCoalescing switch (factory DTO + AdminUI form) turns it off entirely. The planner also merges Coils/DiscreteInputs (FC01/FC02, gap in bits), String scalars and BitInRegister tags - sixteen bit tags on one status word are one FC03 instead of sixteen. Auto-prohibition and its re-probe / bisection use the region's own function code (a coil range was re-probed with FC04). Refs #741 Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT