Joseph Doherty 0200619322 fix(modbus): review r2 - region+address keys always win; string-only means no keys
N2: pre-#741 rows carry region/address beside an addressString with no marker
(the old driver never read the string, the old model preserved it as an
unknown key). The r1 rule resolved those from the string - a silent remap or
BadNodeIdUnknown on upgrade. The driver now loads from region+address whenever
both are present (classic, editor-pinned, pre-lane); only a blob with NO keys
is string-only and resolved through the parser. This is safe because the model
no longer stamps keys onto a string-only tag. The model distinguishes
string-only / legacy-string-beside-keys / pinned, and the editor hint says so.
Test matrix over every persisted shape (keys only, pre-lane keys+string,
pre-lane stamped HR/0+string, string only, marker+keys, marker no keys) under
every family; the pre-lane row also through a model save and a CSV
export->import.
n5: a typed CSV address cell is an authored address - it drops addressString
and the marker (new CsvTypedColumn.ClearsKeys) instead of being discarded.
n6: Validate skips the region/dataType/byteOrder enum checks on a string-only
tag (the driver ignores them). n7: docs/v2/modbus-addressing.md restates the
key-presence rule.

Refs #741
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 16:23:37 -04:00

265 lines
11 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Modbus tag-addressing reference
Foundational doc for the Modbus addressing grammar shipped across #136–#144.
Covers the address-string parser (`ModbusAddressParser`) that the wire driver
and the Admin UI both consume, the per-tag suffix modifiers, and the family-
native branch.
## Grammar
```
<region><offset>[.<bit>][:<type>[<len>]][:<order>][:<count>]
```
Each field is optional from left to right; the parser fills defaults.
### Region + offset
Three accepted forms — pick whichever matches your tag spreadsheet's
convention. All three resolve to the same `(Region, ushort PduOffset)`
on the wire.
| Form | Example | Means |
|---|---|---|
| Modicon 5-digit | `40001` | Holding register 1 (PDU 0) |
| Modicon 6-digit | `400001` | Holding register 1 (PDU 0); supports up to `465536` (PDU 65535) |
| Mnemonic | `HR1`, `IR1`, `C100`, `DI1` | Same regions; `1`-based register number |
Modicon leading-digit → region:
| Digit | Region | OPC UA wire FC |
|---|---|---|
| `0` | Coils | FC01 / FC05 / FC15 |
| `1` | DiscreteInputs | FC02 (read-only) |
| `3` | InputRegisters | FC04 (read-only) |
| `4` | HoldingRegisters | FC03 / FC06 / FC16 |
### Bit suffix `.N`
`40001.5` = bit 5 (LSB-first) of HR[0]. Implies `DataType=BitInRegister`;
mixing with an explicit type or array-count is rejected.
### Type code `:T`
Codes verified 2026-04-25 against [Wonderware DASMBTCP user
guide](https://cdn.logic-control.com/media/DASMBTCP.pdf) and the
[Ignition Modbus addressing
manual](https://www.docs.inductiveautomation.com/docs/8.1/ignition-modules/opc-ua/opc-ua-drivers/modbus/modbus-addressing).
The `I` / `UI` / `I_64` / `UI_64` / `BCD_32` shapes match Wonderware's
suffix convention and Ignition's underscore-N prefix variants where
those vendors agree.
| Code | Type | Registers | Vendor reference |
|---|---|---|---|
| `BOOL` | Boolean | 1 (region must be Coils / DiscreteInputs) | universal |
| `S` | Int16 | 1 | Wonderware DASMBTCP `S` = 16-bit signed |
| `US` | UInt16 | 1 | Ignition `HRUS` = Unsigned Short |
| `I` | Int32 | 2 | Wonderware DASMBTCP `I` = 32-bit signed; Ignition `HRI` |
| `UI` | UInt32 | 2 | Ignition `HRUI` |
| `I_64` | Int64 | 4 | Ignition `HRI_64` |
| `UI_64` | UInt64 | 4 | Ignition `HRUI_64` |
| `F` | Float32 | 2 | Wonderware `F`; Ignition `HRF` |
| `D` | Float64 | 4 | Ignition `HRD` |
| `BCD` | 16-bit BCD | 1 | Ignition `HRBCD` |
| `BCD_32` | 32-bit BCD | 2 | Ignition `HRBCD_32` |
| `STR<len>` | ASCII string, `len` chars (2 chars / register) | `ceil(len/2)` | analogous to Ignition `HRS<addr>:<len>` |
Default when omitted:
- Coils / DiscreteInputs → `BOOL`
- HoldingRegisters / InputRegisters → `S` (Int16) — matches Ignition's bare-`HR` default
**Codes removed in #146** (silent wrong-data risk, never compatible with the
two reference vendors): `:DI`, `:L`, `:UDI`, `:UL`, `:LI`, `:ULI`, `:LBCD`.
Pre-#146 configs that use these get a clear "Unknown type code" diagnostic at
parse time; rewrite to the post-#146 codes per the table above.
### Byte order `:O`
| Mnemonic | Meaning | Wire |
|---|---|---|
| `ABCD` | Big-endian (Modbus spec default) | `[A,B,C,D]` |
| `CDAB` | Word swap (Siemens, several AB) | `[C,D,A,B]` |
| `BADC` | Byte swap (legacy little-endian-internal devices) | `[B,A,D,C]` |
| `DCBA` | Full reverse (some EtherNet/IP gateways) | `[D,C,B,A]` |
For 8-byte values (Int64 / Float64) the same labels apply pairwise.
### Array count `:N`
`40001:F:5` = `Float32[5]` (consumes HR[0..9]). Array + bit suffix is
rejected. Strings are not arrays.
### Composition
The 3-field shorthand `40001:F:5` is parsed as `(type=F, count=5)` because
`5` isn't a valid byte-order mnemonic. Use the explicit 4-field form
`40001:F:CDAB:5` when you need a non-default order.
## Family-native syntax (#144)
When the driver instance has `Family != Generic`, the parser tries the
family's native syntax FIRST, then falls back to Modicon / mnemonic.
### DL205 (AutomationDirect DirectLOGIC)
| Form | Example | Mapping |
|---|---|---|
| `Vnnnn` (octal) | `V2000` | HoldingRegisters[1024] (octal 2000 = decimal 1024) |
| `Ynn` (octal) | `Y17` | Coils[2048 + 15] (Y-output base + offset) |
| `Cnn` (octal) | `C100` | Coils[3072 + 64] (C-relay base + offset) |
| `Xnn` (octal) | `X17` | DiscreteInputs[15] |
| `SPnn` (octal) | `SP10` | DiscreteInputs[1024 + 8] |
**Cross-family ambiguity**: `C100` means Coils[99] under `Generic`
(mnemonic) but Coils[3136] under `DL205`. Per-driver Family choice
disambiguates.
### MELSEC (Mitsubishi)
| Form | Example | Mapping (sub-family Q_L_iQR / F_iQF) |
|---|---|---|
| `Dnnn` (decimal) | `D100` | HoldingRegisters[100] |
| `Mnnn` (decimal) | `M50` | Coils[50] |
| `Xnn` | `X20` | DiscreteInputs[32 hex / 16 octal] |
| `Ynn` | `Y20` | Coils[32 hex / 16 octal] |
X / Y digit interpretation depends on `MelsecSubFamily`:
- `Q_L_iQR` → hex (default)
- `F_iQF` → octal
Bank-base offsets default to 0 in the grammar string. Sites with non-zero
"Modbus Device Assignment" bases use the structured tag form.
## Driver-instance options
Beyond per-tag addressing, `ModbusDriverOptions` exposes (#139–#143):
### Connection (#139)
- `KeepAlive { Enabled, Time, Interval, RetryCount }` — TCP-level probes.
Defaults match the historical PR 53 wire output (Enabled=true, Time=30s,
Interval=10s, RetryCount=3).
- `IdleDisconnectTimeout` — proactively close + reconnect after this much
socket idle time. Default null = disabled.
- `Reconnect { InitialDelay, MaxDelay, BackoffMultiplier }` — geometric
backoff for the post-drop reconnect loop. Default
`(0, 30s, 2.0)` = immediate first retry, geometric thereafter.
### Protocol (#140)
- `MaxCoilsPerRead` (default 2000) — separate cap for FC01/FC02 coil reads.
- `UseFC15ForSingleCoilWrites` — force FC15 (write multiple coils
qty=1) for single-coil writes. Safety/audit PLCs may require this.
- `UseFC16ForSingleRegisterWrites` — same for FC16 vs FC06.
- `UseFC23ForMultiRegisterWrites` (default `false`) — opt-in: a 2–121-register
holding write is sent as one FC23 (write + read-back). A unit answering
exception 01 moves to FC16 until the next re-init. Without the key the
wire stays FC16 (#741).
- `DisableFC23` — hard kill switch: never send FC23, even when opted in.
### Subscribe (#141)
- Per-tag `Deadband` — suppress sub-threshold publishes on numeric tags.
- `WriteOnChangeOnly` (driver-level) — short-circuit identical-value
writes. Cache invalidates on read-divergence.
### Multi-unit (#142)
- Per-tag `UnitId` — overrides the driver-level UnitId in the MBAP
header. Required for one-Ethernet-gateway / N-RTU-slave deployments.
- `IPerCallHostResolver.ResolveHost` returns `host:port/unitN` per tag so
per-PLC circuit breakers fire per slave.
- Per-tag `CoalesceProhibited` — escape hatch for #143's planner (read
this tag in isolation regardless of `MaxReadGap`).
### Block-read coalescing (#143)
- `MaxReadGap` — gap budget the planner is willing to bridge between
adjacent tags of one (unit, region). With `MaxReadGap=10`, three tags at
HR 100/102/110 collapse into one FC03 of quantity 11. An explicit `0` =
coalescing off (its historical meaning); the default `8` applies only when
the key is absent (#741). Coils / DiscreteInputs (gap in bits), `String`
scalars and same-word `BitInRegister` tags coalesce too.
- `DisableReadCoalescing` — turn coalescing off regardless of the gap.
### Coalescing auto-recovery (#148 / #150 / #151 / #152)
- A coalesced read that fails with a Modbus exception (write-only or
protected register mid-block) records the failed range as
auto-prohibited. The planner stops re-coalescing across the range; the
per-tag fallback path keeps healthy members working in the same scan.
- **Bisection (#150)**: every re-probe pass narrows multi-register
prohibitions by trying the two halves separately. Over log2(span)
ticks the prohibition pins at the actual offending register(s);
intermediate halves that succeed get cleared.
- **Periodic re-probe (#151)**: opt in via
`AutoProhibitReprobeInterval` (TimeSpan?). Default null = disabled
(prohibitions persist for the driver lifetime; clear on
`ReinitializeAsync`).
- **Per-tag escape hatch**: `CoalesceProhibited` (bool, default false)
on `ModbusTagDefinition`. The planner reads such tags in isolation
regardless of `MaxReadGap`. Use for known-bad addresses you want to
exclude from the auto-discovery loop.
- **Diagnostics (#152)**: `ModbusDriver.GetAutoProhibitedRanges()`
returns a snapshot of every active prohibition as
`ModbusAutoProhibition` records (UnitId / Region / StartAddress /
EndAddress / LastProbedUtc / BisectionPending). Surface in the
driver-diagnostics RPC channel when that wiring lands; for now
consumable by in-process callers (Server health endpoints, log
aggregation).
## JSON DTO shape
The factory accepts both the structured form (legacy) and the new
`AddressString` form per-tag. Mix freely — newer pasted rows use the
grammar string; legacy rows keep the structured fields.
```json
{
"host": "10.1.2.3",
"port": 502,
"unitId": 1,
"family": "DL205",
"keepAlive": { "enabled": true, "timeMs": 30000, "intervalMs": 10000, "retryCount": 3 },
"idleDisconnectMs": 120000,
"reconnect": { "initialDelayMs": 0, "maxDelayMs": 30000, "backoffMultiplier": 2.0 },
"maxCoilsPerRead": 2000,
"writeOnChangeOnly": false,
"maxReadGap": 8,
"tags": [
{ "name": "Temp", "addressString": "V2000:F:CDAB" },
{ "name": "Setpoint", "addressString": "40001:I" },
{ "name": "Outputs", "addressString": "Y0:5" },
{ "name": "AlarmCount", "region": "HoldingRegisters", "address": 200, "dataType": "Int16", "deadband": 5.0 }
]
}
```
## Vendor compatibility caveat
The exact spelling of type codes (e.g. `I` vs `INT`, `BCD` vs `L_BCD`) and
the byte-order mnemonics were synthesised from training-era vendor docs
(Wonderware DASMBTCP, Kepware KEPServerEX, Ignition, Matrikon, OAS).
Before locking the grammar for a production deployment, verify against
the current Kepware "Modbus Ethernet Driver Help" PDF and Ignition's
"Modbus Addressing" user-manual page — if a critical tool's mnemonics
have shifted, add aliases in `ModbusAddressParser.TryParseType` rather
than asking users to rewrite spreadsheets.
## Address strings, families and region/type rules (#741)
- **Whenever a tag carries both `region` and `address`, those keys are its
address** — a classic tag, an editor-pinned tag, and a pre-#741 row that
carried an `addressString` beside its keys (the old driver never read the
string) all load from the keys, exactly as before, and a family change never
remaps them. Only a **string-only** blob (an `addressString` with NO
`region`/`address` — CSV / API authoring) is resolved through
`ModbusAddressParser` with the **driver's** `Family` / `MelsecSubFamily`; the
AdminUI never stamps default keys onto it, so it cannot collapse onto HR[0],
and a family that cannot parse it refuses the tag (BadNodeIdUnknown).
- The editor's "Resolve with driver family" persists the resolved
`region`/`address`/type fields plus `"addressResolved": true` (the pinned
state). Editing a resolved field by hand — in the editor or a typed CSV
address cell — drops the string and the marker.
- Coils / DiscreteInputs carry only Bool. A bit-region tag persisted with a
register `dataType` (the pre-#741 editor saved `Int16`) is coerced to Bool,
never refused. A register region with `Bool` is refused (use
`BitInRegister`).
- Exception 01/02/03 are device refusals: per-tag Bad, one Warning per tag,
no driver Degraded; reads and writes share one comms-fault health slot.