Compare commits
6 Commits
phase-3-pr
...
phase-3-pr
| Author | SHA1 | Date | |
|---|---|---|---|
|
|
f52b7d8979 | ||
|
|
b54724a812 | ||
|
|
10c724b5b6 | ||
| 8c89d603e8 | |||
| 299bd4a932 | |||
|
|
c506ea298a |
1
_p54.json
Normal file
1
_p54.json
Normal file
@@ -0,0 +1 @@
|
||||
{"title":"Phase 3 PR 54 -- Siemens S7 Modbus TCP quirks research doc","body":"## Summary\n\nAdds `docs/v2/s7.md` (485 lines) covering Siemens SIMATIC S7 family Modbus TCP behavior. Mirrors the `docs/v2/dl205.md` template for future per-quirk implementation PRs.\n\n## Key findings for the implementation track\n\n- **No fixed memory map** — every S7 Modbus server is user-wired via `MB_SERVER`/`MODBUSCP`/`MODBUSPN` library blocks. Driver must accept per-site config, not assume a vendor layout.\n- **MB_SERVER requires non-optimized DBs** (STATUS `0x8383` if optimized). Most common field bug.\n- **Word order default = ABCD** (opposite of DL260). Driver's S7 profile default must be `ByteOrder.BigEndian`, not `WordSwap`.\n- **One port per MB_SERVER instance** — multi-client requires parallel FBs on 503/504/… Most clients assume port 502 multiplexes (wrong on S7).\n- **CP 343-1 Lean is server-only**, requires the `2XV9450-1MB00` license.\n- **FC20/21/22/23/43 all return Illegal Function** on every S7 variant — driver must not attempt FC23 bulk-read optimization for S7.\n- **STOP-mode behavior non-deterministic** across firmware bands — treat both read/write STOP-mode responses as unavailable.\n\nTwo items flagged as unconfirmed rumour (V2.0+ float byte-order claim, STOP-mode caching location).\n\nNo code, no tests — implementation lands in PRs 56+.\n\n## Test plan\n- [x] Doc renders as markdown\n- [x] 31 citations present\n- [x] Section structure matches dl205.md template","head":"phase-3-pr54-s7-research-doc","base":"v2"}
|
||||
1
_p55.json
Normal file
1
_p55.json
Normal file
@@ -0,0 +1 @@
|
||||
{"title":"Phase 3 PR 55 -- Mitsubishi MELSEC Modbus TCP quirks research doc","body":"## Summary\n\nAdds `docs/v2/mitsubishi.md` (451 lines) covering MELSEC Q/L/iQ-R/iQ-F/FX3U Modbus TCP behavior. Mirrors `docs/v2/dl205.md` template for per-quirk implementation PRs.\n\n## Key findings for the implementation track\n\n- **Module naming trap** — `QJ71MB91` is SERIAL RTU, not TCP. TCP module is `QJ71MT91`. Surface clearly in driver docs.\n- **No canonical mapping** — per-site 'Modbus Device Assignment Parameter' block (up to 16 entries). Treat mapping as runtime config.\n- **X/Y hex vs octal depends on family** — Q/L/iQ-R use HEX (X20 = decimal 32); FX/iQ-F use OCTAL (X20 = decimal 16). Helper must take a family selector.\n- **Word order CDAB default** across all MELSEC families (opposite of Siemens S7). Driver Mitsubishi profile default: `ByteOrder.WordSwap`.\n- **D-registers binary by default** (opposite of DL205's BCD default). Caller opts in to `Bcd16`/`Bcd32` when ladder uses BCD.\n- **FX5U needs firmware ≥ 1.060** for Modbus TCP server — older is client-only.\n- **FX3U-ENET vs FX3U-ENET-P502 vs FX3U-ENET-ADP** — only the middle one binds port 502; the last has no Modbus at all. Common operator mis-purchase.\n- **QJ71MT91 does NOT support FC22 / FC23** — iQ-R / iQ-F do. Bulk-read optimization must gate on capability.\n- **STOP-mode writes configurable** on Q/L/iQ-R/iQ-F (default accept), always rejected on FX3U-ENET.\n\nThree unconfirmed rumours flagged separately.\n\nNo code, no tests — implementation lands in PRs 58+.\n\n## Test plan\n- [x] Doc renders as markdown\n- [x] 17 citations present\n- [x] Per-model test naming matrix included (`Mitsubishi_QJ71MT91_*`, `Mitsubishi_FX5U_*`, `Mitsubishi_FX3U_ENET_*`, shared `Mitsubishi_Common_*`)","head":"phase-3-pr55-mitsubishi-research-doc","base":"v2"}
|
||||
451
docs/v2/mitsubishi.md
Normal file
451
docs/v2/mitsubishi.md
Normal file
@@ -0,0 +1,451 @@
|
||||
# Mitsubishi Electric MELSEC — Modbus TCP quirks
|
||||
|
||||
Mitsubishi's MELSEC family speaks Modbus TCP through a patchwork of add-on modules
|
||||
and built-in Ethernet ports, not a single unified stack. The module names are
|
||||
confusingly similar (`QJ71MB91` is *serial* RTU, `QJ71MT91` is the TCP/IP module
|
||||
[9]; `LJ71MT91` is the L-series equivalent; `RJ71EN71` is the iQ-R Ethernet module
|
||||
with a MODBUS/TCP *slave* mode bolted on [8]; `FX3U-ENET`, `FX3U-ENET-P502`,
|
||||
`FX3U-ENET-ADP`, `FX3GE` built-in, and `FX5U` built-in are all different code
|
||||
paths) — and every one of the categories below has at least one trap a textbook
|
||||
Modbus client gets wrong: hex-numbered X/Y devices colliding with decimal Modbus
|
||||
addresses, a user-defined "device assignment" parameter block that means *no two
|
||||
sites are identical*, CDAB-vs-ABCD word order driven by how the ladder built the
|
||||
32-bit value, sub-spec FC16 caps on the older QJ71MT91, and an FX3U port-502
|
||||
licensing split that makes `FX3U-ENET` and `FX3U-ENET-P502` different SKUs.
|
||||
This document catalogues each quirk, cites primary sources, and names the
|
||||
ModbusPal integration test we'd write for it (convention from
|
||||
`docs/v2/modbus-test-plan.md`: `Mitsubishi_<model>_<behavior>`).
|
||||
|
||||
## Models and server/client capability
|
||||
|
||||
| Model | Family | Modbus TCP server | Modbus TCP client | Source |
|
||||
|------------------------|----------|-------------------|-------------------|--------|
|
||||
| `QJ71MT91` | MELSEC-Q | Yes (slave) | Yes (master) | [9] |
|
||||
| `QJ71MB91` | MELSEC-Q | **Serial only** — RS-232/422/485 RTU, *not TCP* | — | [1][3] |
|
||||
| `LJ71MT91` | MELSEC-L | Yes (slave) | Yes (master) | [10] |
|
||||
| `RJ71EN71` / `RnENCPU` | MELSEC iQ-R | Yes (slave) | Yes (master) | [8] |
|
||||
| `RJ71C24` / `RJ71C24-R2` | MELSEC iQ-R | RTU (serial) | RTU (serial) | [13] |
|
||||
| iQ-R built-in Ethernet | CPU | Yes (slave) | Yes (master) | [7] |
|
||||
| iQ-F `FX5U` built-in Ethernet | CPU | Yes, firmware ≥ 1.060 [11] | Yes | [7][11][12] |
|
||||
| `FX3U-ENET` | FX3U bolt-on | Yes (slave), but **not on port 502** [5] | Yes | [4][5] |
|
||||
| `FX3U-ENET-P502` | FX3U bolt-on | Yes (slave), port 502 enabled | Yes | [5] |
|
||||
| `FX3U-ENET-ADP` | FX3U adapter | **No MODBUS** [5] | No MODBUS | [5] |
|
||||
| `FX3GE` built-in | FX3GE CPU | No MODBUS (needs ENET module) [6] | No | [6] |
|
||||
| `FX3G` + `FX3U-ENET` | FX3G | Yes via ENET module | Yes | [6] |
|
||||
|
||||
- A common integration mistake is to buy `FX3U-ENET-ADP` expecting MODBUS —
|
||||
that adapter speaks only MC protocol / SLMP. Our driver should surface a clear
|
||||
capability error, not "connection refused", when the operator's device tag
|
||||
says `FX3U-ENET-ADP` [5].
|
||||
- Older forum threads assert the FX5U is "client only" [12] — that was true on
|
||||
firmware ≤ 1.040. Firmware 1.060 and later ship the parameter-driven MODBUS
|
||||
TCP server built-in and need no function blocks [11].
|
||||
|
||||
## Modbus device assignment (the parameter block)
|
||||
|
||||
Unlike a DL260 where the CPU exposes a *fixed* V-memory-to-Modbus mapping, every
|
||||
MELSEC MODBUS-TCP module exposes a **Modbus Device Assignment Parameter** block
|
||||
that the engineer configures in GX Works2 / GX Configurator-MB / GX Works3.
|
||||
Each of the four Modbus tables (Coil, Input, Input Register, Holding Register)
|
||||
can be split into up to 16 independent "assignment" entries, each binding a
|
||||
contiguous Modbus address range to a MELSEC device head (`M0`, `D0`, `X0`,
|
||||
`Y0`, `B0`, `W0`, `SM0`, `SD0`, `R0`, etc.) and a point count [3][7][8][9].
|
||||
|
||||
- **There is no canonical "MELSEC Modbus mapping"**. Two sites running the same
|
||||
QJ71MT91 module can expose completely different Modbus layouts. Our driver
|
||||
must treat the mapping as site-data (config-file-driven), not as a device
|
||||
profile constant.
|
||||
- **Default values do exist** — both GX Configurator-MB (for Q/L series) and
|
||||
GX Works3 (for iQ-R / iQ-F / FX5) ship a "dedicated pattern" default that is
|
||||
applied when the engineer does not override the assignment. Per the FX5
|
||||
MODBUS Communication manual (JY997D56101) and the QJ71MT91 manual, the FX5
|
||||
dedicated default is [3][7][11]:
|
||||
|
||||
| Modbus table | Modbus range (0-based) | MELSEC device | Head |
|
||||
|--------------------|------------------------|---------------|------|
|
||||
| Coil (FC01/05/15) | 0 – 7679 | M | M0 |
|
||||
| Coil | 8192 – 8959 | Y | Y0 |
|
||||
| Input (FC02) | 0 – 7679 | M | M0 |
|
||||
| Input | 8192 – 8959 | X | X0 |
|
||||
| Input Register (FC04) | 0 – 6143 | D | D0 |
|
||||
| Holding Register (FC03/06/16) | 0 – 6143 | D | D0 |
|
||||
|
||||
This matches the widely circulated "FC03 @ 0 = D0" convention that shows up
|
||||
in Ubidots / Ignition / AdvancedHMI integration guides [6][12].
|
||||
|
||||
- **X/Y in the default mapping occupy a second, non-zero Modbus range** (8192+
|
||||
on FX5; similar on Q/L/iQ-R). Driver users who expect "X0 = coil 0" will be
|
||||
reading M0 instead. Document this clearly.
|
||||
- **Assignment-range collisions silently disable the slave.** The QJ71MT91
|
||||
manual states explicitly that if any two of assignments 1-16 duplicate the
|
||||
head Modbus device number, the slave function is inactive with no clear
|
||||
error — the module just won't respond [9]. The driver probe will look like a
|
||||
simple timeout; the site engineer has to open GX Configurator-MB to diagnose.
|
||||
|
||||
Test names:
|
||||
`Mitsubishi_FX5U_default_mapping_coil_0_is_M0`,
|
||||
`Mitsubishi_FX5U_default_mapping_holding_0_is_D0`,
|
||||
`Mitsubishi_QJ71MT91_duplicate_assignment_head_disables_slave`.
|
||||
|
||||
## X/Y addressing — hex on MELSEC, decimal on Modbus
|
||||
|
||||
**MELSEC X (input) and Y (output) device numbers are hexadecimal on Q / L /
|
||||
iQ-R** and **octal** on FX / iQ-F (with a GX Works3 toggle) [14][15].
|
||||
|
||||
- On a Q CPU, `X20` means decimal **32**, not 20. On an FX5U in default (octal)
|
||||
mode, `X20` means decimal **16**. GX Works3 exposes a project-level option to
|
||||
display FX5U X/Y in hex to match Q/L/iQ-R convention — the same physical
|
||||
input is then called `X10` [14].
|
||||
- The Modbus Device Assignment Parameter block takes the *head device* as a
|
||||
MELSEC-native number, which is interpreted in the CPU's native base
|
||||
(hex for Q/L/iQ-R, octal for FX/iQ-F). After that, **Modbus offsets from
|
||||
the head are plain decimal** — the module does not apply a second hex
|
||||
conversion [3][9].
|
||||
- Example (QJ71MT91 on a Q CPU): assignment "Coil 0 = X0, 512 points" exposes
|
||||
physical `X0` through `X1FF` (hex) as coils 0-511. A client reading coil 32
|
||||
gets the bit `X20` (hex) — i.e. the 33rd input, not the value at "input 20"
|
||||
that the operator wrote on the wiring diagram in decimal.
|
||||
- **Driver bug source**: if the operator's tag configuration says "read X20" and
|
||||
the driver helpfully converts "20" to decimal 20 → coil offset 20, the
|
||||
returned bit is actually `X14` (hex) — off by twelve. Our config layer must
|
||||
preserve the MELSEC-native base that the site engineer sees in GX Works.
|
||||
- Timers/counters (`T`, `C`, `ST`) are always decimal in MELSEC notation.
|
||||
Internal relays (`M`, `B`, `L`), data registers (`D`, `W`, `R`, `ZR`),
|
||||
and special relays/registers (`SM`, `SD`) also decimal. **Only `X` and `Y`
|
||||
(and on Q/L/iQ-R, `B` link relays and `W` link registers) use hex**, and
|
||||
the X/Y decision is itself family-dependent [14][15].
|
||||
|
||||
Test names:
|
||||
`Mitsubishi_Q_X_address_is_hex_X20_equals_coil_offset_32`,
|
||||
`Mitsubishi_FX5U_X_address_is_octal_X20_equals_coil_offset_16`,
|
||||
`Mitsubishi_W_link_register_is_hex_W10_equals_holding_offset_16`.
|
||||
|
||||
## Word order for 32-bit values
|
||||
|
||||
MELSEC stores 32-bit ladder values (`DINT`, `DWORD`, `REAL` / single-precision
|
||||
float) across **two consecutive D-registers, low word first** — i.e., `CDAB`
|
||||
when viewed as a Modbus register pair [2][6].
|
||||
|
||||
```
|
||||
D100 (low word) : 0xCC 0xDD (big-endian bytes within the word)
|
||||
D101 (high word) : 0xAA 0xBB
|
||||
```
|
||||
|
||||
A Modbus master reading D100/D101 as a `float` with default (ABCD) word order
|
||||
gets garbage. Ignition's built-in Modbus driver notes Mitsubishi as a "CDAB
|
||||
device" specifically for this reason [2].
|
||||
|
||||
- **Q / L / iQ-R / iQ-F all agree** — this is a CPU-level convention, not a
|
||||
module choice. Both the QJ71MT91 manual and the FX5 MODBUS Communication
|
||||
manual describe 32-bit access by "reading the lower 16 bits from the start
|
||||
address and the upper 16 bits from start+1" [6][11].
|
||||
- **Byte order within each register is big-endian** (Modbus standard). The
|
||||
module does not byte-swap.
|
||||
- **Configurable?** The MODBUS modules themselves do **not** expose a word-
|
||||
order toggle; the behavior is fixed to how the CPU laid out the value in the
|
||||
two D-registers. If the ladder programmer used an `SWAP` instruction or a
|
||||
union-style assignment, the word order can be whatever they made it — but
|
||||
for values produced by the standard `D→DBL` and `FLT`/`FLT2` instructions
|
||||
it is always CDAB [2].
|
||||
- **FX5U quirk**: the FX5 MODBUS Communication manual tells the programmer to
|
||||
use the `SWAP` instruction *if* the remote Modbus peer requires
|
||||
little-endian *byte* ordering (BADC) [11]. This is only relevant when the
|
||||
FX5U is the Modbus *client*, but it confirms the FX5U's native wire layout
|
||||
is big-endian-byte / little-endian-word (CDAB) on the server side too.
|
||||
- **Rumoured exception**: a handful of MrPLC forum threads report iQ-R
|
||||
RJ71EN71 firmware < 1.05 returning DWORDs in `ABCD` order when accessed via
|
||||
the built-in Ethernet port's MODBUS slave [8]. _Unconfirmed_; treat as a
|
||||
per-site test.
|
||||
|
||||
Test names:
|
||||
`Mitsubishi_Float32_word_order_is_CDAB`,
|
||||
`Mitsubishi_Int32_word_order_is_CDAB`,
|
||||
`Mitsubishi_FX5U_SWAP_instruction_changes_byte_order_not_word_order`.
|
||||
|
||||
## BCD vs binary encoding
|
||||
|
||||
**MELSEC stores integer values in D-registers as plain binary two's-complement**,
|
||||
not BCD [16]. This is the opposite of AutomationDirect DirectLOGIC, where
|
||||
V-memory defaults to BCD and the ladder must explicitly request binary.
|
||||
|
||||
- A ladder `MOV K1234 D100` stores `0x04D2` (1234 decimal) in D100, not
|
||||
`0x1234`. The Modbus master reads `0x04D2` and decodes it as an integer
|
||||
directly — no BCD conversion needed [16].
|
||||
- **Timer / counter current values** (`T0` current value, `C0` count) are
|
||||
stored in binary as word devices on Q/L/iQ-R/iQ-F. The ladder preset
|
||||
(`K...`) is also binary [16][17].
|
||||
- **Timer / counter preset `K` operand in FX3U / earlier FX**: also binary when
|
||||
loaded from a D-register or a `K` constant. The older A-series CPUs had BCD
|
||||
presets on some timer types, but MELSEC-Q, L, iQ-R, iQ-F, and FX3U all use
|
||||
binary presets by default [17].
|
||||
- The FX3U programming manual dedicates `FNC 18 BCD` and `FNC 19 BIN` to
|
||||
explicit conversion — their existence confirms that anything in D-registers
|
||||
that came from a `BCD` instruction output is BCD, but nothing is BCD by
|
||||
default [17].
|
||||
- **7-segment display registers** are a common site-specific exception — many
|
||||
ladders pack `BCD D100` into a D-register so the operator panel can drive
|
||||
a display directly. Our driver should not assume; expose a per-tag
|
||||
"encoding = binary | BCD" knob.
|
||||
|
||||
Test names:
|
||||
`Mitsubishi_D_register_stores_binary_not_BCD`,
|
||||
`Mitsubishi_FX3U_timer_current_value_is_binary`.
|
||||
|
||||
## Max registers per request
|
||||
|
||||
From the FX5 MODBUS Communication manual Chapter 11 [11]:
|
||||
|
||||
| FC | Name | FX5U (built-in) | QJ71MT91 | iQ-R (RJ71EN71 / built-in) | FX3U-ENET |
|
||||
|----|----------------------------|-----------------|--------------|-----------------------------|-----------|
|
||||
| 01 | Read Coils | 1-2000 | 1-2000 [9] | 1-2000 [8] | 1-2000 |
|
||||
| 02 | Read Discrete Inputs | 1-2000 | 1-2000 | 1-2000 | 1-2000 |
|
||||
| 03 | Read Holding Registers | **1-125** | 1-125 [9] | 1-125 [8] | 1-125 |
|
||||
| 04 | Read Input Registers | 1-125 | 1-125 | 1-125 | 1-125 |
|
||||
| 05 | Write Single Coil | 1 | 1 | 1 | 1 |
|
||||
| 06 | Write Single Register | 1 | 1 | 1 | 1 |
|
||||
| 0F | Write Multiple Coils | 1-1968 | 1-1968 | 1-1968 | 1-1968 |
|
||||
| 10 | Write Multiple Registers | **1-123** | 1-123 | 1-123 | 1-123 |
|
||||
| 16 | Mask Write Register | 1 | not supported | 1 | not supported |
|
||||
| 17 | Read/Write Multiple Regs | R:1-125, W:1-121 | not supported | R:1-125, W:1-121 | not supported |
|
||||
|
||||
- **The FX5U / iQ-R native-port limits match the Modbus spec**: 125 for FC03/04,
|
||||
123 for FC16 [11]. No sub-spec caps like DL260's 100-register ceiling.
|
||||
- **QJ71MT91 does not support FC16 (0x16, Mask Write Register) or FC17
|
||||
(0x17, Read/Write Multiple)** — requesting them returns exception `01`
|
||||
Illegal Function [9]. FX5U and iQ-R *do* support both.
|
||||
- **QJ71MT91 device size**: 64k points (65,536) for each of Coil / Input /
|
||||
Input Register / Holding Register, plus up to 4086k points for Extended
|
||||
File Register via a secondary assignment range [9].
|
||||
- **FX3U-ENET / -P502 function code list is a strict subset** of the common
|
||||
eight (FC01/02/03/04/05/06/0F/10). FC16 and FC17 not supported [4].
|
||||
|
||||
Test names:
|
||||
`Mitsubishi_FX5U_FC03_126_registers_returns_IllegalDataValue`,
|
||||
`Mitsubishi_FX5U_FC16_124_registers_returns_IllegalDataValue`,
|
||||
`Mitsubishi_QJ71MT91_FC16_MaskWrite_returns_IllegalFunction`,
|
||||
`Mitsubishi_QJ71MT91_FC23_ReadWrite_returns_IllegalFunction`.
|
||||
|
||||
## Exception codes
|
||||
|
||||
MELSEC MODBUS modules return **only the standard Modbus exception codes 01-04**;
|
||||
no proprietary exception codes are exposed on the wire [8][9][11]. Module-
|
||||
internal diagnostics (buffer-memory error codes like `7380H`) are logged but
|
||||
not returned as Modbus exceptions.
|
||||
|
||||
| Code | Name | MELSEC trigger |
|
||||
|------|----------------------|---------------------------------------------------------|
|
||||
| 01 | Illegal Function | FC17 or FC16 on QJ71MT91/FX3U; FC08 (Diagnostics); FC43 |
|
||||
| 02 | Illegal Data Address | Modbus address outside any assignment range |
|
||||
| 03 | Illegal Data Value | Quantity out of per-FC range (see table above); odd coil-byte count |
|
||||
| 04 | Server Device Failure | See below |
|
||||
|
||||
- **04 (Server Failure) triggers on MELSEC**:
|
||||
- CPU in STOP or PAUSE during a write to an assignment whose "Access from
|
||||
External Device" permission is set to "Disabled in STOP" [9][11].
|
||||
*With the default "always enabled" setting the write succeeds in STOP
|
||||
mode* — another common trap.
|
||||
- CPU errors (parameter error, watchdog) during any access.
|
||||
- Assignment points to a device range that is not configured (e.g. write
|
||||
to `D16384` when CPU D-device size is 12288).
|
||||
- **Write to a "System Area" device** (e.g., `SD` special registers that are
|
||||
CPU-reserved read-only) returns `04`, not `02`, on QJ71MT91 and iQ-R — the
|
||||
assignment is valid, the device exists, but the CPU rejects the write [8][9].
|
||||
- **FX3U-ENET / -P502** returns `04` on any write attempt while the CPU is in
|
||||
STOP, regardless of permission settings — the older firmware does not
|
||||
implement the "Access from External Device" granularity that Q/L/iQ-R/iQ-F
|
||||
expose [4].
|
||||
- **No rumour of proprietary codes 05-0B** from MELSEC; operators sometimes
|
||||
report "exception 0A" but those traces all came from a third-party gateway
|
||||
sitting between the master and the MELSEC module.
|
||||
|
||||
Test names:
|
||||
`Mitsubishi_QJ71MT91_STOP_mode_write_with_Disabled_permission_returns_ServerFailure`,
|
||||
`Mitsubishi_QJ71MT91_STOP_mode_write_with_default_permission_succeeds`,
|
||||
`Mitsubishi_SD_system_register_write_returns_ServerFailure`,
|
||||
`Mitsubishi_FX3U_STOP_mode_write_always_returns_ServerFailure`.
|
||||
|
||||
## Connection behavior
|
||||
|
||||
Max simultaneous Modbus TCP clients, per module [7][8][9][11]:
|
||||
|
||||
| Model | Max TCP connections | Port 502 | Keepalive | Source |
|
||||
|----------------------|---------------------|----------|-----------|--------|
|
||||
| `QJ71MT91` | 16 (shared with master role) | Yes | No | [9] |
|
||||
| `LJ71MT91` | 16 | Yes | No | [10] |
|
||||
| iQ-R built-in / `RJ71EN71` | 16 | Yes | Configurable (KeepAlive = ON in parameter) | [8] |
|
||||
| iQ-F `FX5U` built-in | 8 | Yes | Configurable | [7][11] |
|
||||
| `FX3U-ENET` | 8 TCP, but **not port 502** | No (port < 1024 blocked) | No | [4][5] |
|
||||
| `FX3U-ENET-P502` | 8, port 502 enabled | Yes | No | [5] |
|
||||
|
||||
- **QJ71MT91's 16 is total connections shared between slave-listen and
|
||||
master-initiated sockets** [9]. A site that uses the same module as both
|
||||
master to downstream VFDs and slave to upstream SCADA splits the 16 pool.
|
||||
- **FX3U-ENET port-502 gotcha**: if the engineer loads a configuration with
|
||||
port 502 into a non-P502 ENET module, GX Works shows the download as
|
||||
successful; on next power cycle the module enters error state and the
|
||||
MODBUS listener never starts. This is documented on third-party FX3G
|
||||
integration guides [6].
|
||||
- **CPU STOP → RUN transition**: does **not** drop Modbus connections on any
|
||||
MELSEC family. Existing sockets stay open; outstanding requests during the
|
||||
transition may see exception 04 for a few scans but then resume [8][9].
|
||||
- **CPU reset (power cycle or `SM1255` forced reset)** drops all Modbus
|
||||
connections and the module re-listens after typically 5-10 seconds.
|
||||
- **Idle timeout**: QJ71MT91 and iQ-R have a per-connection "Alive-Check"
|
||||
(idle timer) parameter, default 0 (disabled). If enabled, default 10 s
|
||||
probe interval, 3 retries before close [8][9]. FX5U similar defaults.
|
||||
- **Keep-alive (TCP-level)**: only iQ-R / iQ-F expose a TCP keep-alive option
|
||||
(parameter "KeepAlive" in the Ethernet settings); QJ71MT91 and FX3U-ENET
|
||||
do not — so NAT/firewall idle drops require driver-side pinging.
|
||||
|
||||
Test names:
|
||||
`Mitsubishi_QJ71MT91_17th_connection_refused`,
|
||||
`Mitsubishi_FX5U_9th_connection_refused`,
|
||||
`Mitsubishi_STOP_to_RUN_transition_preserves_socket`,
|
||||
`Mitsubishi_CPU_reset_closes_all_sockets`.
|
||||
|
||||
## Behavioral oddities
|
||||
|
||||
- **Transaction ID echo**: QJ71MT91 and iQ-R reliably echo the MBAP TxId on
|
||||
every response across firmware revisions; no reports of TxId drops under
|
||||
load [8][9]. FX3U-ENET has an older, less-tested TCP stack; at least one
|
||||
MrPLC thread reports out-of-order TxId echoes under heavy polling on
|
||||
firmware < 1.14 [4]. _Unconfirmed_ on current firmware.
|
||||
- **Per-connection request serialization**: all MELSEC slaves serialize
|
||||
requests within a single TCP connection — a new request is not processed
|
||||
until the prior response has been sent. Pipelining multiple requests on one
|
||||
socket causes the module to queue them in buffer memory and respond in
|
||||
order, but **the queue depth is 1** on QJ71MT91 (a second in-flight request
|
||||
is held on the TCP receive buffer, not queued) [9]. Driver should treat
|
||||
Mitsubishi slaves as strictly single-flight per socket.
|
||||
- **Partial-frame handling**: QJ71MT91 and iQ-R close the socket on malformed
|
||||
MBAP length fields. FX5U resynchronises at the next valid MBAP header
|
||||
within 100 ms but will emit an error to `SD` diagnostics [11]. Driver must
|
||||
reconnect on half-close and replay.
|
||||
- **FX3U UDP vs TCP**: `FX3U-ENET` supports both UDP and TCP MODBUS transports;
|
||||
UDP is lossy and reorders under load. Default is TCP. Some legacy SCADA
|
||||
configurations pinned the module to UDP for multicast discovery — do not
|
||||
select UDP unless the site requires it [4].
|
||||
- **Known firmware-revision variants**:
|
||||
- QJ71MT91 ≤ firmware 10052000000 (year-month format): FC15 with coil
|
||||
count that forces byte-count to an odd value silently truncates the
|
||||
last coil. Fixed in later revisions [9]. _Operator-reported_.
|
||||
- FX5U firmware < 1.060: no native MODBUS TCP server — only accessible via
|
||||
a predefined-protocol function block hack. Firmware ≥ 1.060 ships
|
||||
parameter-based server. Our capability probe should read `SD203`
|
||||
(firmware version) and flag < 1.060 as unsupported for server mode [11][12].
|
||||
- iQ-R RJ71EN71 early firmware: possible ABCD word order (rumoured,
|
||||
unconfirmed) [8].
|
||||
- **SD (special-register) reads during assignment-parameter load**: while
|
||||
the CPU is loading a new MODBUS device assignment parameter (~1-2 s), the
|
||||
slave returns exception 04 Server Failure on every request. Happens after
|
||||
a parameter write from GX Configurator-MB [9].
|
||||
- **iQ-R "Station-based block transfer" collision**: if the RJ71EN71 is also
|
||||
running CC-Link IE Control on the same module, a MODBUS/TCP request that
|
||||
arrives during a CCIE cyclic period is delayed to the next scan — visible
|
||||
as jittery response time, not a failure [8].
|
||||
|
||||
Test names:
|
||||
`Mitsubishi_QJ71MT91_single_flight_per_socket`,
|
||||
`Mitsubishi_FX5U_malformed_MBAP_resync_within_100ms`,
|
||||
`Mitsubishi_FX3U_TxId_preserved_across_burst`,
|
||||
`Mitsubishi_FX5U_firmware_below_1_060_reports_no_server_mode`.
|
||||
|
||||
## Model-specific differences for test coverage
|
||||
|
||||
Summary of which quirks differ per model, so test-class naming can reflect them:
|
||||
|
||||
| Quirk | QJ71MT91 | LJ71MT91 | iQ-R (RJ71EN71 / built-in) | iQ-F (FX5U) | FX3U-ENET(-P502) |
|
||||
|------------------------------------------|----------|----------|----------------------------|-------------|------------------|
|
||||
| FC16 Mask-Write supported | No | No | Yes | Yes | No |
|
||||
| FC17 Read/Write Multiple supported | No | No | Yes | Yes | No |
|
||||
| Max connections | 16 | 16 | 16 | 8 | 8 |
|
||||
| X/Y numbering base | hex | hex | hex | octal (default) | octal |
|
||||
| 32-bit word order | CDAB | CDAB | CDAB (firmware-dependent rumour of ABCD) | CDAB | CDAB |
|
||||
| Port 502 supported | Yes | Yes | Yes | Yes | P502 only |
|
||||
| STOP-mode write permission configurable | Yes | Yes | Yes | Yes | No (always blocks) |
|
||||
| TCP keep-alive parameter | No | No | Yes | Yes | No |
|
||||
| Modbus device assignment — max entries | 16 | 16 | 16 | 16 | 8 |
|
||||
| Server via parameter (no FB) | Yes | Yes | Yes | Yes (fw ≥ 1.060) | Yes |
|
||||
|
||||
- **Test file layout**: `Mitsubishi_QJ71MT91_*`, `Mitsubishi_LJ71MT91_*`,
|
||||
`Mitsubishi_iQR_*`, `Mitsubishi_FX5U_*`, `Mitsubishi_FX3U_ENET_*`,
|
||||
`Mitsubishi_FX3U_ENET_P502_*`. iQ-R built-in Ethernet and the RJ71EN71
|
||||
behave identically for MODBUS/TCP slave purposes and can share a file
|
||||
`Mitsubishi_iQR_*`.
|
||||
- **Cross-model shared tests** (word order CDAB, binary not BCD, standard
|
||||
exception codes, 125-register FC03 cap) can live in a single
|
||||
`Mitsubishi_Common_*` fixture.
|
||||
|
||||
## References
|
||||
|
||||
1. Mitsubishi Electric, *MODBUS Interface Module User's Manual — QJ71MB91*
|
||||
(SH-080578ENG), RS-232/422/485 MODBUS RTU serial module for MELSEC-Q —
|
||||
https://dl.mitsubishielectric.com/dl/fa/document/manual/plc/sh080578eng/sh080578engk.pdf
|
||||
2. Inductive Automation, *Ignition Modbus Driver — Mitsubishi Q / iQ-R word
|
||||
order*, documents CDAB convention —
|
||||
https://docs.inductiveautomation.com/docs/8.1/ignition-modules/opc-ua/drivers/modbus-v2
|
||||
and forum discussion https://forum.inductiveautomation.com/t/modbus-tcp-device-word-byte-order/65984
|
||||
3. Mitsubishi Electric, *Programmable Controller User's Manual QJ71MB91 MODBUS
|
||||
Interface Module*, Chapter 7 "Parameter Setting" describing the Modbus
|
||||
Device Assignment Parameter block (assignments 1-16, head-device
|
||||
configuration) —
|
||||
https://www.lcautomation.com/dbdocument/29156/QJ71MB91%20Users%20manual.pdf
|
||||
4. Mitsubishi Electric, *FX3U-ENET User's Manual* (JY997D18101), Chapter on
|
||||
MODBUS/TCP communication; function code support and connection limits —
|
||||
https://dl.mitsubishielectric.com/dl/fa/document/manual/plc_fx/jy997d18101/jy997d18101h.pdf
|
||||
5. Venus Automation, *Mitsubishi FX3U-ENET-P502 Module — Open Port 502 for
|
||||
Modbus TCP/IP* —
|
||||
https://venusautomation.com.au/mitsubishi-fx3u-enet-p502-module-open-port-502-for-modbus-tcp-ip/
|
||||
and FX3U-ENET-ADP user manual (JY997D45801), which confirms the -ADP
|
||||
variant does not support MODBUS —
|
||||
https://dl.mitsubishielectric.com/dl/fa/document/manual/plc_fx/jy997d45801/jy997d45801h.pdf
|
||||
6. XML Control / Ubidots integration notes, *FX3G Modbus* — port-502 trap,
|
||||
D-register mapping default, word order reference —
|
||||
https://sites.google.com/site/xmlcontrol/archive/fx3g-modbus
|
||||
and https://ubidots.com/blog/mitsubishi-plc-as-modbus-tcp-server/
|
||||
7. FA Support Me, *Modbus TCP on Built-in Ethernet port in iQ-F and iQ-R* —
|
||||
confirms 16-connection limit on iQ-R, 8 on iQ-F, parameter-driven
|
||||
configuration via GX Works3 —
|
||||
https://www.fasupportme.com/portal/en/kb/articles/modbus-tcp-on-build-in-ethernet-port-in-iq-f-and-iq-r-en
|
||||
8. Mitsubishi Electric, *MELSEC iQ-R Ethernet User's Manual (Application)*
|
||||
(SH-081259ENG) and *MELSEC iQ-RJ71EN71 User's Manual* Chapter on
|
||||
"Communications Using Modbus/TCP" —
|
||||
https://www.allied-automation.com/wp-content/uploads/2015/02/MITSUBISHI_manual_plc_iq-r_ethernet_users.pdf
|
||||
and https://www.manualslib.com/manual/1533351/Mitsubishi-Electric-Melsec-Iq-Rj71en71.html?page=109
|
||||
9. Mitsubishi Electric, *MODBUS/TCP Interface Module User's Manual — QJ71MT91*
|
||||
(SH-080446ENG), exception codes page 248, device assignment parameter
|
||||
pages 116-124, duplicate-assignment-disables-slave note —
|
||||
https://dl.mitsubishielectric.com/dl/fa/document/manual/plc/sh080446eng/sh080446engj.pdf
|
||||
10. Mitsubishi Electric, *MELSEC-L Network Features* — LJ71MT91 documented as
|
||||
L-series equivalent of QJ71MT91 with identical MODBUS/TCP behavior —
|
||||
https://us.mitsubishielectric.com/fa/en/products/cnt/programmable-controllers/melsec-l-series/network/features/
|
||||
11. Mitsubishi Electric, *MELSEC iQ-F FX5 User's Manual (MODBUS Communication)*
|
||||
(JY997D56101), Chapter 11 "Modbus/TCP Communication Specifications" —
|
||||
function code max-quantity table, frame specification, device assignment
|
||||
defaults —
|
||||
https://dl.mitsubishielectric.com/dl/fa/document/manual/plcf/jy997d56101/jy997d56101h.pdf
|
||||
12. MrPLC forum, *FX5U Modbus-TCP Server (Slave)*, firmware ≥ 1.60 enables
|
||||
native server via parameter; earlier firmware required function block —
|
||||
https://mrplc.com/forums/topic/31883-fx5u-modbus-tcp-server-slave/
|
||||
and Industrial Monitor Direct's "FX5U MODBUS TCP Server Workaround"
|
||||
article (reflects older firmware behavior) —
|
||||
https://industrialmonitordirect.com/blogs/knowledgebase/mitsubishi-fx5u-modbus-tcp-server-configuration-workaround
|
||||
13. Mitsubishi Electric, *MELSEC iQ-R MODBUS and MODBUS/TCP Reference Manual —
|
||||
RJ71C24 / RJ71C24-R2* (BCN-P5999-1060) — RJ71C24 is serial RTU only,
|
||||
not TCP —
|
||||
https://dl.mitsubishielectric.com/dl/fa/document/manual/plc/bcn-p5999-1060/bcnp59991060b.pdf
|
||||
14. HMS Industrial Networks, *eWON and Mitsubishi FX5U PLC* (KB-0264-00) —
|
||||
documents that FX5U X/Y are octal in GX Works3 but hex when viewed as a
|
||||
Q-series PLC through eWON; the project-level hex/octal toggle —
|
||||
https://hmsnetworks.blob.core.windows.net/www/docs/librariesprovider10/downloads-monitored/manuals/knowledge-base/kb-0264-00-en-ewon-and-mitsubishi-fx5u-plc.pdf
|
||||
15. Fernhill Software, *Mitsubishi Melsec PLC Data Address* — documents
|
||||
hex-vs-octal device numbering split across MELSEC families —
|
||||
https://www.fernhillsoftware.com/help/drivers/mitsubishi-melsec/data-address-format.html
|
||||
16. Inductive Automation support, *Understanding Mitsubishi PLCs* — D registers
|
||||
store signed 16-bit binary, not BCD; DINT combines two consecutive D
|
||||
registers —
|
||||
https://support.inductiveautomation.com/hc/en-us/articles/16517576753165-Understanding-Mitsubishi-PLCs
|
||||
17. Mitsubishi Electric, *FXCPU Structured Programming Manual [Device &
|
||||
Common]* (JY997D26001) — FNC 18 BCD and FNC 19 BIN explicit-conversion
|
||||
instructions confirm binary-by-default storage —
|
||||
https://dl.mitsubishielectric.com/dl/fa/document/manual/plc_fx/jy997d26001/jy997d26001l.pdf
|
||||
@@ -0,0 +1,43 @@
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.Mitsubishi;
|
||||
|
||||
/// <summary>
|
||||
/// Tag map for the Mitsubishi MELSEC device class with a representative Modbus Device
|
||||
/// Assignment block mapping D0..D1023 → HR[0..1023]. Mirrors the behaviors in
|
||||
/// <c>mitsubishi.json</c> pymodbus profile and <c>docs/v2/mitsubishi.md</c>.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// MELSEC Modbus sites all have *different* device-assignment parameter blocks; this profile
|
||||
/// models the conventional default. Per-model differences (FX5U needs firmware ≥ 1.060 for
|
||||
/// Modbus server; QJ71MT91 lacks FC22/FC23; FX/iQ-F use octal X/Y while Q/L/iQ-R use hex)
|
||||
/// are handled in <see cref="MelsecAddress"/> (PR 59) and the per-model test files.
|
||||
/// </remarks>
|
||||
public static class MitsubishiProfile
|
||||
{
|
||||
/// <summary>
|
||||
/// Scratch HR the smoke test writes + reads. Address 200 mirrors the
|
||||
/// dl205/s7_1500/standard scratch range so one smoke test pattern works across every
|
||||
/// device profile the simulator supports.
|
||||
/// </summary>
|
||||
public const ushort SmokeHoldingRegister = 200;
|
||||
|
||||
/// <summary>Value the smoke test writes then reads back.</summary>
|
||||
public const short SmokeHoldingValue = 7890;
|
||||
|
||||
public static ModbusDriverOptions BuildOptions(string host, int port) => new()
|
||||
{
|
||||
Host = host,
|
||||
Port = port,
|
||||
UnitId = 1,
|
||||
Timeout = TimeSpan.FromSeconds(2),
|
||||
Tags =
|
||||
[
|
||||
new ModbusTagDefinition(
|
||||
Name: "Smoke_HReg200",
|
||||
Region: ModbusRegion.HoldingRegisters,
|
||||
Address: SmokeHoldingRegister,
|
||||
DataType: ModbusDataType.Int16,
|
||||
Writable: true),
|
||||
],
|
||||
Probe = new ModbusProbeOptions { Enabled = false },
|
||||
};
|
||||
}
|
||||
@@ -0,0 +1,45 @@
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.Mitsubishi;
|
||||
|
||||
/// <summary>
|
||||
/// End-to-end smoke against the MELSEC <c>mitsubishi.json</c> pymodbus profile (or a real
|
||||
/// MELSEC QJ71MT91 / iQ-R / FX5U when <c>MODBUS_SIM_ENDPOINT</c> points at one). Drives
|
||||
/// the full <see cref="ModbusDriver"/> + real <see cref="ModbusTcpTransport"/> stack.
|
||||
/// Success proves the driver initializes against the MELSEC sim, writes a known value,
|
||||
/// and reads it back — the baseline every Mitsubishi-specific test (PR 59+) builds on.
|
||||
/// </summary>
|
||||
[Collection(ModbusSimulatorCollection.Name)]
|
||||
[Trait("Category", "Integration")]
|
||||
[Trait("Device", "Mitsubishi")]
|
||||
public sealed class MitsubishiSmokeTests(ModbusSimulatorFixture sim)
|
||||
{
|
||||
[Fact]
|
||||
public async Task Mitsubishi_roundtrip_write_then_read_of_holding_register()
|
||||
{
|
||||
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
||||
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "mitsubishi",
|
||||
StringComparison.OrdinalIgnoreCase))
|
||||
{
|
||||
Assert.Skip("MODBUS_SIM_PROFILE != mitsubishi — skipping.");
|
||||
}
|
||||
|
||||
var options = MitsubishiProfile.BuildOptions(sim.Host, sim.Port);
|
||||
await using var driver = new ModbusDriver(options, driverInstanceId: "melsec-smoke");
|
||||
await driver.InitializeAsync(driverConfigJson: "{}", TestContext.Current.CancellationToken);
|
||||
|
||||
var writeResults = await driver.WriteAsync(
|
||||
[new(FullReference: "Smoke_HReg200", Value: (short)MitsubishiProfile.SmokeHoldingValue)],
|
||||
TestContext.Current.CancellationToken);
|
||||
writeResults.Count.ShouldBe(1);
|
||||
writeResults[0].StatusCode.ShouldBe(0u, "write must succeed against the MELSEC pymodbus profile");
|
||||
|
||||
var readResults = await driver.ReadAsync(
|
||||
["Smoke_HReg200"],
|
||||
TestContext.Current.CancellationToken);
|
||||
readResults.Count.ShouldBe(1);
|
||||
readResults[0].StatusCode.ShouldBe(0u);
|
||||
readResults[0].Value.ShouldBe((short)MitsubishiProfile.SmokeHoldingValue);
|
||||
}
|
||||
}
|
||||
@@ -0,0 +1,83 @@
|
||||
{
|
||||
"_comment": "mitsubishi.json -- Mitsubishi MELSEC Modbus TCP quirk simulator covering QJ71MT91, iQ-R, iQ-F/FX5U, and FX3U-ENET-P502 behaviors documented in docs/v2/mitsubishi.md. MELSEC CPUs store multi-word values in CDAB order (opposite of S7 ABCD, same family as DL260). The Modbus-module 'Modbus Device Assignment Parameter' block is per-site, so this profile models one *representative* assignment mapping D-register D0..D1023 -> HR 0..1023, M-relay M0..M511 -> coil 0..511, X-input X0..X15 -> DI 0..15 (X-addresses are HEX on Q/L/iQ-R, so X10 = decimal 16; on FX/iQ-F they're OCTAL like DL260). pymodbus bit-address semantics are the same as dl205.json and s7_1500.json (FC01/02/05/15 address N maps to cell index N/16).",
|
||||
|
||||
"server_list": {
|
||||
"srv": {
|
||||
"comm": "tcp",
|
||||
"host": "0.0.0.0",
|
||||
"port": 5020,
|
||||
"framer": "socket",
|
||||
"device_id": 1
|
||||
}
|
||||
},
|
||||
|
||||
"device_list": {
|
||||
"dev": {
|
||||
"setup": {
|
||||
"co size": 4096,
|
||||
"di size": 4096,
|
||||
"hr size": 4096,
|
||||
"ir size": 1024,
|
||||
"shared blocks": true,
|
||||
"type exception": false,
|
||||
"defaults": {
|
||||
"value": {"bits": 0, "uint16": 0, "uint32": 0, "float32": 0.0, "string": " "},
|
||||
"action": {"bits": null, "uint16": null, "uint32": null, "float32": null, "string": null}
|
||||
}
|
||||
},
|
||||
"invalid": [],
|
||||
"write": [
|
||||
[0, 0],
|
||||
[10, 10],
|
||||
[100, 101],
|
||||
[200, 209],
|
||||
[300, 301],
|
||||
[500, 500]
|
||||
],
|
||||
|
||||
"uint16": [
|
||||
{"_quirk": "D0 fingerprint marker. MELSEC D0 is the first data register; Modbus Device Assignment typically maps D0..D1023 -> HR 0..1023. 0x1234 is the fingerprint operators set in GX Works to prove the mapping parameter block is in effect.",
|
||||
"addr": 0, "value": 4660},
|
||||
|
||||
{"_quirk": "Scratch HR range 200..209 -- mirrors the dl205/s7_1500/standard scratch range so smoke tests (MitsubishiProfile.SmokeHoldingRegister=200) round-trip identically against any profile.",
|
||||
"addr": 200, "value": 0},
|
||||
{"addr": 201, "value": 0},
|
||||
{"addr": 202, "value": 0},
|
||||
{"addr": 203, "value": 0},
|
||||
{"addr": 204, "value": 0},
|
||||
{"addr": 205, "value": 0},
|
||||
{"addr": 206, "value": 0},
|
||||
{"addr": 207, "value": 0},
|
||||
{"addr": 208, "value": 0},
|
||||
{"addr": 209, "value": 0},
|
||||
|
||||
{"_quirk": "Float32 1.5f in CDAB word order (MELSEC Q/L/iQ-R/iQ-F default, same as DL260). HR[100]=0x0000=0 low word, HR[101]=0x3FC0=16320 high word. Decode with ByteOrder.WordSwap returns 1.5f; BigEndian decode returns a denormal.",
|
||||
"addr": 100, "value": 0},
|
||||
{"addr": 101, "value": 16320},
|
||||
|
||||
{"_quirk": "Int32 0x12345678 in CDAB word order. HR[300]=0x5678=22136 low word, HR[301]=0x1234=4660 high word. Contrasts with the S7 profile's ABCD encoding at the same address.",
|
||||
"addr": 300, "value": 22136},
|
||||
{"addr": 301, "value": 4660},
|
||||
|
||||
{"_quirk": "D10 = decimal 1234 stored as BINARY (NOT BCD like DL205). 0x04D2 = 1234 decimal. Caller reading with Bcd16 data type would decode this as binary 1234's BCD nibbles which are non-BCD and throw InvalidDataException -- proves MELSEC is binary-by-default, opposite of DL205's BCD-by-default quirk.",
|
||||
"addr": 10, "value": 1234},
|
||||
|
||||
{"_quirk": "Modbus Device Assignment boundary marker. HR[500] represents the last register in an assigned D-range D500. Beyond this (HR[501..4095]) would be Illegal Data Address on a real QJ71MT91 with this specific parameter block; pymodbus returns default 0 because its shared cell array has space -- real-PLC parity is documented in docs/v2/mitsubishi.md §device-assignment, not enforced here.",
|
||||
"addr": 500, "value": 500}
|
||||
],
|
||||
|
||||
"bits": [
|
||||
{"_quirk": "M-relay marker cell at cell 32 = Modbus coil 512 = MELSEC M512 (coils 0..15 collide with the D0 uint16 marker cell, so we place the M marker above that). Cell 32 bit 0 = 1 and bit 2 = 1 (value = 0b101 = 5) = M512=ON, M513=OFF, M514=ON. Matches the Y0/Y2 marker pattern in dl205 and s7_1500 profiles.",
|
||||
"addr": 32, "value": 5},
|
||||
|
||||
{"_quirk": "X-input marker cell at cell 33 = Modbus DI 528 (= MELSEC X210 hex on Q/L/iQ-R). Cell 33 bit 0 = 1 and bit 3 = 1 (value = 0x9 = 9). Chosen above cell 1 so it doesn't collide with any uint16 D-register. Proves the hex-parsing X-input helper on Q/L/iQ-R family; FX/iQ-F families use octal X-addresses tested separately.",
|
||||
"addr": 33, "value": 9}
|
||||
],
|
||||
|
||||
"uint32": [],
|
||||
"float32": [],
|
||||
"string": [],
|
||||
"repeat": []
|
||||
}
|
||||
}
|
||||
}
|
||||
@@ -0,0 +1,77 @@
|
||||
{
|
||||
"_comment": "s7_1500.json -- Siemens SIMATIC S7-1500 + MB_SERVER quirk simulator. Models docs/v2/s7.md behaviors as concrete register values. Unlike DL260 (CDAB word order default) or Mitsubishi (CDAB default), S7 MB_SERVER uses ABCD word order by default because Siemens native CPU types are big-endian top-to-bottom both within the register pair and byte pair. This profile exists so the driver's S7 profile default ByteOrder.BigEndian can be validated end-to-end. pymodbus bit-address semantics are the same as dl205.json (FC01/02/05/15 address X maps to cell index X/16); seed bits at the appropriate cell-indexed positions.",
|
||||
|
||||
"server_list": {
|
||||
"srv": {
|
||||
"comm": "tcp",
|
||||
"host": "0.0.0.0",
|
||||
"port": 5020,
|
||||
"framer": "socket",
|
||||
"device_id": 1
|
||||
}
|
||||
},
|
||||
|
||||
"device_list": {
|
||||
"dev": {
|
||||
"setup": {
|
||||
"co size": 4096,
|
||||
"di size": 4096,
|
||||
"hr size": 4096,
|
||||
"ir size": 1024,
|
||||
"shared blocks": true,
|
||||
"type exception": false,
|
||||
"defaults": {
|
||||
"value": {"bits": 0, "uint16": 0, "uint32": 0, "float32": 0.0, "string": " "},
|
||||
"action": {"bits": null, "uint16": null, "uint32": null, "float32": null, "string": null}
|
||||
}
|
||||
},
|
||||
"invalid": [],
|
||||
"write": [
|
||||
[0, 0],
|
||||
[25, 25],
|
||||
[100, 101],
|
||||
[200, 209],
|
||||
[300, 301]
|
||||
],
|
||||
|
||||
"uint16": [
|
||||
{"_quirk": "DB1 header marker. On an S7-1500 with MB_SERVER pointing at DB1, operators often reserve DB1.DBW0 for a fingerprint word so clients can verify they're talking to the right DB. 0xABCD = 43981.",
|
||||
"addr": 0, "value": 43981},
|
||||
|
||||
{"_quirk": "Scratch HR range 200..209 -- mirrors the standard.json scratch range so the smoke test (S7_1500Profile.SmokeHoldingRegister=200) round-trips identically against either profile.",
|
||||
"addr": 200, "value": 0},
|
||||
{"addr": 201, "value": 0},
|
||||
{"addr": 202, "value": 0},
|
||||
{"addr": 203, "value": 0},
|
||||
{"addr": 204, "value": 0},
|
||||
{"addr": 205, "value": 0},
|
||||
{"addr": 206, "value": 0},
|
||||
{"addr": 207, "value": 0},
|
||||
{"addr": 208, "value": 0},
|
||||
{"addr": 209, "value": 0},
|
||||
|
||||
{"_quirk": "Float32 1.5f in ABCD word order (Siemens big-endian default, OPPOSITE of DL260 CDAB). IEEE-754 1.5 = 0x3FC00000. ABCD = high word first: HR[100]=0x3FC0=16320, HR[101]=0x0000=0.",
|
||||
"addr": 100, "value": 16320},
|
||||
{"_quirk": "Float32 1.5f ABCD low word.",
|
||||
"addr": 101, "value": 0},
|
||||
|
||||
{"_quirk": "Int32 0x12345678 in ABCD word order. HR[300]=0x1234=4660, HR[301]=0x5678=22136. Demonstrates the contrast with DL260 CDAB Int32 encoding.",
|
||||
"addr": 300, "value": 4660},
|
||||
{"addr": 301, "value": 22136}
|
||||
],
|
||||
|
||||
"bits": [
|
||||
{"_quirk": "Coil bank marker cell. S7 MB_SERVER doesn't fix coil addresses; this simulates a user-wired DB where coil 400 (=bit 0 of cell 25) represents a latched digital output. Cell 25 bit 0 = 1 proves the wire-format round-trip works for coils on S7 profile.",
|
||||
"addr": 25, "value": 1},
|
||||
|
||||
{"_quirk": "Discrete-input bank marker cell. DI 500 (=bit 0 of cell 31) = 1. Like coils, discrete inputs on S7 MB_SERVER are per-site; we assert the end-to-end FC02 path only.",
|
||||
"addr": 31, "value": 1}
|
||||
],
|
||||
|
||||
"uint32": [],
|
||||
"float32": [],
|
||||
"string": [],
|
||||
"repeat": []
|
||||
}
|
||||
}
|
||||
}
|
||||
@@ -21,7 +21,7 @@
|
||||
#>
|
||||
[CmdletBinding()]
|
||||
param(
|
||||
[Parameter(Mandatory)] [ValidateSet('standard', 'dl205')] [string]$Profile,
|
||||
[Parameter(Mandatory)] [ValidateSet('standard', 'dl205', 's7_1500', 'mitsubishi')] [string]$Profile,
|
||||
[int]$HttpPort = 8080
|
||||
)
|
||||
|
||||
|
||||
@@ -0,0 +1,44 @@
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.S7;
|
||||
|
||||
/// <summary>
|
||||
/// Tag map for the Siemens SIMATIC S7-1500 device class with the <c>MB_SERVER</c> library
|
||||
/// block mapping HR[0..] to DB1.DBW0+. Mirrors <c>s7_1500.json</c> in <c>Pymodbus/</c>.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// Unlike DL205, S7 has no fixed Modbus memory map — every site wires MB_SERVER to a
|
||||
/// different DB. The profile here models the *default* user layout documented in
|
||||
/// <c>docs/v2/s7.md</c> §per-model-matrix: DB1.DBW0 = fingerprint marker, a scratch HR
|
||||
/// range 200..209 for write-roundtrip tests, and ABCD-order Float32 / Int32 markers at
|
||||
/// HR[100..101] and HR[300..301] to prove the driver's S7 profile default is correct.
|
||||
/// </remarks>
|
||||
public static class S7_1500Profile
|
||||
{
|
||||
/// <summary>
|
||||
/// Scratch HR the smoke test writes + reads. Address 200 mirrors the DL205 /
|
||||
/// standard scratch range so one smoke test pattern works across all device profiles.
|
||||
/// </summary>
|
||||
public const ushort SmokeHoldingRegister = 200;
|
||||
|
||||
/// <summary>Value the smoke test writes then reads back.</summary>
|
||||
public const short SmokeHoldingValue = 4321;
|
||||
|
||||
public static ModbusDriverOptions BuildOptions(string host, int port) => new()
|
||||
{
|
||||
Host = host,
|
||||
Port = port,
|
||||
UnitId = 1,
|
||||
Timeout = TimeSpan.FromSeconds(2),
|
||||
Tags =
|
||||
[
|
||||
new ModbusTagDefinition(
|
||||
Name: "Smoke_HReg200",
|
||||
Region: ModbusRegion.HoldingRegisters,
|
||||
Address: SmokeHoldingRegister,
|
||||
DataType: ModbusDataType.Int16,
|
||||
Writable: true),
|
||||
],
|
||||
// Disable the background probe loop — integration tests drive reads explicitly and
|
||||
// the probe would race with assertions.
|
||||
Probe = new ModbusProbeOptions { Enabled = false },
|
||||
};
|
||||
}
|
||||
@@ -0,0 +1,54 @@
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.S7;
|
||||
|
||||
/// <summary>
|
||||
/// End-to-end smoke against the S7-1500 <c>MB_SERVER</c> pymodbus profile (or a real
|
||||
/// S7-1500 + MB_SERVER deployment when <c>MODBUS_SIM_ENDPOINT</c> points at one). Drives
|
||||
/// the full <see cref="ModbusDriver"/> + real <see cref="ModbusTcpTransport"/> stack —
|
||||
/// no fake transport. Success proves the driver initializes against the S7 simulator,
|
||||
/// writes a known value, and reads it back with the correct status and value, which is
|
||||
/// the baseline every S7-specific test (PR 57+) builds on.
|
||||
/// </summary>
|
||||
/// <remarks>
|
||||
/// S7-specific quirk tests (MB_SERVER requires non-optimized DBs, ABCD word order
|
||||
/// default, port-per-connection, FC23 Illegal Function, STOP-mode behaviour, etc.) land
|
||||
/// as separate test classes in this directory as each quirk is validated in pymodbus.
|
||||
/// Keep this smoke test deliberately narrow — filtering by device class
|
||||
/// (<c>--filter DisplayName~S7</c>) should surface the quirk-specific failure mode when
|
||||
/// something goes wrong, not a blanket smoke failure that could mean anything.
|
||||
/// </remarks>
|
||||
[Collection(ModbusSimulatorCollection.Name)]
|
||||
[Trait("Category", "Integration")]
|
||||
[Trait("Device", "S7")]
|
||||
public sealed class S7_1500SmokeTests(ModbusSimulatorFixture sim)
|
||||
{
|
||||
[Fact]
|
||||
public async Task S7_1500_roundtrip_write_then_read_of_holding_register()
|
||||
{
|
||||
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
||||
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "s7_1500",
|
||||
StringComparison.OrdinalIgnoreCase))
|
||||
{
|
||||
Assert.Skip("MODBUS_SIM_PROFILE != s7_1500 — skipping (other profiles don't seed the S7 scratch range identically).");
|
||||
}
|
||||
|
||||
var options = S7_1500Profile.BuildOptions(sim.Host, sim.Port);
|
||||
await using var driver = new ModbusDriver(options, driverInstanceId: "s7-smoke");
|
||||
await driver.InitializeAsync(driverConfigJson: "{}", TestContext.Current.CancellationToken);
|
||||
|
||||
var writeResults = await driver.WriteAsync(
|
||||
[new(FullReference: "Smoke_HReg200", Value: (short)S7_1500Profile.SmokeHoldingValue)],
|
||||
TestContext.Current.CancellationToken);
|
||||
writeResults.Count.ShouldBe(1);
|
||||
writeResults[0].StatusCode.ShouldBe(0u, "write must succeed against the S7-1500 MB_SERVER profile");
|
||||
|
||||
var readResults = await driver.ReadAsync(
|
||||
["Smoke_HReg200"],
|
||||
TestContext.Current.CancellationToken);
|
||||
readResults.Count.ShouldBe(1);
|
||||
readResults[0].StatusCode.ShouldBe(0u);
|
||||
readResults[0].Value.ShouldBe((short)S7_1500Profile.SmokeHoldingValue);
|
||||
}
|
||||
}
|
||||
@@ -0,0 +1,132 @@
|
||||
using Shouldly;
|
||||
using Xunit;
|
||||
|
||||
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.S7;
|
||||
|
||||
/// <summary>
|
||||
/// Verifies the Siemens S7 big-endian (<c>ABCD</c>) word-order default for Float32 and
|
||||
/// Int32 against the <c>s7_1500.json</c> pymodbus profile. S7's native CPU types are
|
||||
/// big-endian end-to-end, so <c>MB_SERVER</c> places the high word at the lower register
|
||||
/// address — <b>opposite</b> of DL260's CDAB. The driver's S7-family tag config must
|
||||
/// therefore default to <see cref="ModbusByteOrder.BigEndian"/>; selecting
|
||||
/// <see cref="ModbusByteOrder.WordSwap"/> against an S7 would decode garbage.
|
||||
/// </summary>
|
||||
[Collection(ModbusSimulatorCollection.Name)]
|
||||
[Trait("Category", "Integration")]
|
||||
[Trait("Device", "S7")]
|
||||
public sealed class S7_ByteOrderTests(ModbusSimulatorFixture sim)
|
||||
{
|
||||
[Fact]
|
||||
public async Task S7_Float32_ABCD_decodes_1_5f_from_HR100()
|
||||
{
|
||||
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
||||
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "s7_1500",
|
||||
StringComparison.OrdinalIgnoreCase))
|
||||
{
|
||||
Assert.Skip("MODBUS_SIM_PROFILE != s7_1500 — skipping (s7_1500 profile is the only one seeding HR[100..101] ABCD).");
|
||||
}
|
||||
|
||||
var options = new ModbusDriverOptions
|
||||
{
|
||||
Host = sim.Host,
|
||||
Port = sim.Port,
|
||||
UnitId = 1,
|
||||
Timeout = TimeSpan.FromSeconds(2),
|
||||
Tags =
|
||||
[
|
||||
new ModbusTagDefinition("S7_Float_ABCD",
|
||||
ModbusRegion.HoldingRegisters, Address: 100,
|
||||
DataType: ModbusDataType.Float32, Writable: false,
|
||||
ByteOrder: ModbusByteOrder.BigEndian),
|
||||
// Control: same address with WordSwap should decode garbage — proves the
|
||||
// two code paths diverge on S7 wire bytes.
|
||||
new ModbusTagDefinition("S7_Float_CDAB_control",
|
||||
ModbusRegion.HoldingRegisters, Address: 100,
|
||||
DataType: ModbusDataType.Float32, Writable: false,
|
||||
ByteOrder: ModbusByteOrder.WordSwap),
|
||||
],
|
||||
Probe = new ModbusProbeOptions { Enabled = false },
|
||||
};
|
||||
await using var driver = new ModbusDriver(options, driverInstanceId: "s7-float-abcd");
|
||||
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
|
||||
var results = await driver.ReadAsync(
|
||||
["S7_Float_ABCD", "S7_Float_CDAB_control"],
|
||||
TestContext.Current.CancellationToken);
|
||||
|
||||
results[0].StatusCode.ShouldBe(0u);
|
||||
results[0].Value.ShouldBe(1.5f, "S7 MB_SERVER stores Float32 in ABCD word order; BigEndian decode returns 1.5f");
|
||||
|
||||
results[1].StatusCode.ShouldBe(0u);
|
||||
results[1].Value.ShouldNotBe(1.5f, "applying CDAB swap to S7 ABCD bytes must produce a different value — confirms the flag is not a no-op and S7 profile default must be BigEndian");
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task S7_Int32_ABCD_decodes_0x12345678_from_HR300()
|
||||
{
|
||||
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
||||
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "s7_1500",
|
||||
StringComparison.OrdinalIgnoreCase))
|
||||
{
|
||||
Assert.Skip("MODBUS_SIM_PROFILE != s7_1500 — skipping.");
|
||||
}
|
||||
|
||||
var options = new ModbusDriverOptions
|
||||
{
|
||||
Host = sim.Host,
|
||||
Port = sim.Port,
|
||||
UnitId = 1,
|
||||
Timeout = TimeSpan.FromSeconds(2),
|
||||
Tags =
|
||||
[
|
||||
new ModbusTagDefinition("S7_Int32_ABCD",
|
||||
ModbusRegion.HoldingRegisters, Address: 300,
|
||||
DataType: ModbusDataType.Int32, Writable: false,
|
||||
ByteOrder: ModbusByteOrder.BigEndian),
|
||||
],
|
||||
Probe = new ModbusProbeOptions { Enabled = false },
|
||||
};
|
||||
await using var driver = new ModbusDriver(options, driverInstanceId: "s7-int-abcd");
|
||||
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
|
||||
var results = await driver.ReadAsync(["S7_Int32_ABCD"], TestContext.Current.CancellationToken);
|
||||
results[0].StatusCode.ShouldBe(0u);
|
||||
results[0].Value.ShouldBe(0x12345678,
|
||||
"S7 Int32 stored as HR[300]=0x1234, HR[301]=0x5678 with ABCD order decodes to 0x12345678 — DL260 would store the reverse order");
|
||||
}
|
||||
|
||||
[Fact]
|
||||
public async Task S7_DB1_fingerprint_marker_at_HR0_reads_0xABCD()
|
||||
{
|
||||
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
||||
if (!string.Equals(Environment.GetEnvironmentVariable("MODBUS_SIM_PROFILE"), "s7_1500",
|
||||
StringComparison.OrdinalIgnoreCase))
|
||||
{
|
||||
Assert.Skip("MODBUS_SIM_PROFILE != s7_1500 — skipping.");
|
||||
}
|
||||
|
||||
// Real-world MB_SERVER deployments typically reserve DB1.DBW0 as a fingerprint so
|
||||
// clients can verify they're pointing at the right DB (protects against typos in
|
||||
// the MB_SERVER.MB_HOLD_REG.DB_number parameter). 0xABCD is the convention.
|
||||
var options = new ModbusDriverOptions
|
||||
{
|
||||
Host = sim.Host,
|
||||
Port = sim.Port,
|
||||
UnitId = 1,
|
||||
Timeout = TimeSpan.FromSeconds(2),
|
||||
Tags =
|
||||
[
|
||||
new ModbusTagDefinition("S7_Fingerprint",
|
||||
ModbusRegion.HoldingRegisters, Address: 0,
|
||||
DataType: ModbusDataType.UInt16, Writable: false),
|
||||
],
|
||||
Probe = new ModbusProbeOptions { Enabled = false },
|
||||
};
|
||||
await using var driver = new ModbusDriver(options, driverInstanceId: "s7-fingerprint");
|
||||
await driver.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
||||
|
||||
var results = await driver.ReadAsync(["S7_Fingerprint"], TestContext.Current.CancellationToken);
|
||||
results[0].StatusCode.ShouldBe(0u);
|
||||
results[0].Value.ShouldBe((ushort)0xABCD);
|
||||
}
|
||||
}
|
||||
@@ -26,6 +26,8 @@
|
||||
<ItemGroup>
|
||||
<None Update="Pymodbus\**\*" CopyToOutputDirectory="PreserveNewest"/>
|
||||
<None Update="DL205\**\*" CopyToOutputDirectory="PreserveNewest"/>
|
||||
<None Update="S7\**\*" CopyToOutputDirectory="PreserveNewest"/>
|
||||
<None Update="Mitsubishi\**\*" CopyToOutputDirectory="PreserveNewest"/>
|
||||
</ItemGroup>
|
||||
|
||||
<ItemGroup>
|
||||
|
||||
Reference in New Issue
Block a user