Files
lmxopcua/tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/S7/S7_1500Profile.cs
Joseph Doherty 10c724b5b6 Phase 3 PR 56 -- Siemens S7-1500 pymodbus profile + smoke integration test. Adds tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/Pymodbus/s7_1500.json modelling the SIMATIC S7-1500 + MB_SERVER default deployment documented in docs/v2/s7.md: DB1.DBW0 = 0xABCD fingerprint marker (operators reserve this so clients can verify they're talking to the right DB), scratch HR range 200..209 for write-roundtrip tests mirroring dl205.json + standard.json, Float32 1.5f at HR[100..101] in ABCD word order (high word first -- OPPOSITE of DL260 CDAB), Int32 0x12345678 at HR[300..301] in ABCD. Also seeds a coil at bit-addr 400 (= cell 25 bit 0) and a discrete input at bit-addr 500 (= cell 31 bit 0) so future S7-specific tests for FC01/FC02 have stable markers. shared blocks=true to match the proven dl205.json pattern (pymodbus's bits/uint16 cells coexist cleanly when addresses don't collide). Write list references cells (0, 25, 100-101, 200-209, 300-301), not bit addresses -- pymodbus's write-range entries are cell-indexed, not bit-indexed. Adds tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/S7/ directory with S7_1500Profile.cs (mirrors DL205Profile pattern: SmokeHoldingRegister=200, SmokeHoldingValue=4321, BuildOptions tags + probe-disabled + 2s timeout) and S7_1500SmokeTests.cs (single fact S7_1500_roundtrip_write_then_read_of_holding_register that writes SmokeHoldingValue then reads it back, asserting both write status 0 and read status 0 + value equality). Gates on MODBUS_SIM_PROFILE=s7_1500 so the test skips cleanly against other profiles. csproj updated to copy S7/** to test output as PreserveNewest (pattern matching DL205/**). Pymodbus/serve.ps1 ValidateSet extended from {standard,dl205} to {standard,dl205,s7_1500,mitsubishi} -- mitsubishi.json lands in PR 58 but the validator slot is claimed now so the serve.ps1 diff is one line in this PR and zero lines in future PRs. Verified end-to-end: smoke test 1/1 passes against the running pymodbus s7_1500 profile (localhost:5020 FC06 write of 4321 at HR[200] + FC03 read back). 143/143 Modbus.Tests pass, no regression in driver code because this PR is purely test-asset. Per-quirk S7 integration tests (ABCD word order default, FC23 IllegalFunction, MB_SERVER STATUS 0x8383 behaviour, port-per-connection semantics) land in PR 57+.
2026-04-18 22:57:03 -04:00

45 lines
1.9 KiB
C#

namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests.S7;
/// <summary>
/// Tag map for the Siemens SIMATIC S7-1500 device class with the <c>MB_SERVER</c> library
/// block mapping HR[0..] to DB1.DBW0+. Mirrors <c>s7_1500.json</c> in <c>Pymodbus/</c>.
/// </summary>
/// <remarks>
/// Unlike DL205, S7 has no fixed Modbus memory map — every site wires MB_SERVER to a
/// different DB. The profile here models the *default* user layout documented in
/// <c>docs/v2/s7.md</c> §per-model-matrix: DB1.DBW0 = fingerprint marker, a scratch HR
/// range 200..209 for write-roundtrip tests, and ABCD-order Float32 / Int32 markers at
/// HR[100..101] and HR[300..301] to prove the driver's S7 profile default is correct.
/// </remarks>
public static class S7_1500Profile
{
/// <summary>
/// Scratch HR the smoke test writes + reads. Address 200 mirrors the DL205 /
/// standard scratch range so one smoke test pattern works across all device profiles.
/// </summary>
public const ushort SmokeHoldingRegister = 200;
/// <summary>Value the smoke test writes then reads back.</summary>
public const short SmokeHoldingValue = 4321;
public static ModbusDriverOptions BuildOptions(string host, int port) => new()
{
Host = host,
Port = port,
UnitId = 1,
Timeout = TimeSpan.FromSeconds(2),
Tags =
[
new ModbusTagDefinition(
Name: "Smoke_HReg200",
Region: ModbusRegion.HoldingRegisters,
Address: SmokeHoldingRegister,
DataType: ModbusDataType.Int16,
Writable: true),
],
// Disable the background probe loop — integration tests drive reads explicitly and
// the probe would race with assertions.
Probe = new ModbusProbeOptions { Enabled = false },
};
}