A capped events read now pages: the source's truncation flag triggers a
session-bound cursor (time inclusive + tie skip), oversized tie clusters
are paged within via a bounded half-open over-fetch, and release/unknown/
cross-kind points behave as for Raw.
- I-1: QuestDbConnection caps Npgsql Maximum Pool Size at 24 (DefaultMaxPoolSize)
when the connection string does not set it; an explicit value is kept. The
effective value is logged once at Information.
- M-1: QuestDbTagCatalog.EnsureAsync waits for the tag table's sequenced commits
and re-checks before inserting, so it no longer overwrites a provisioner row
(unit/description) that is committed but not yet applied. Integration test
reproduces the clobber against real QuestDB (falsified).
- M-3: the pre-1970 drop Warning is rate-limited per tag (once per 10 min);
DroppedPre1970 still counts every sample.
- M-5: QuestDbHistorianProvider is IAsyncDisposable/IDisposable and disposes the
shared Npgsql pool; Program.cs registers the provider through a factory and
every seam resolves it from the container, so DI disposes it at shutdown.
- M-8, M-9: docs fixes (HistoryUpdate transaction wording; folded duplicate
HistoryUpdate paragraph). Pool-size docs updated for the new default cap.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Gate: Primary-only typed recording with real status, raw+UNS HistoryRead/Processed parity, HistoryUpdate
insert/duplicate/replace/delete + WriteOperate-only and anonymous denied, failover at 1x, Modbus device loss
stored as BadCommunicationError then a BadNoCommunication outage marker. Gate found the CLI hid the
node-level refusal code (fixed + pinned) and a pre-existing OpcUaClient comms-loss gap (filed separately).
docker-dev compose gains ServerHistorian__Backend / __SqlServer__ConnectionString (default Gateway).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- Historian.md: Empty samples always Bad (writer/updater/read clamp),
long-name refusal, 5 s bootstrap failure cache, AtTime after now, info-bit
masking, HistoryUpdate does NOT type-check (M-1 decision), DeleteRaw
needs both bounds, reverse Raw paging, the historian/historization metric
prefixes, and provisioning numeric-only lines qualified as Gateway.
- CLAUDE.md numeric-only lines qualified as Gateway backend.
- Stale 'sole historian' lines in DriverLifecycle, ServiceHosting and the
retired Wonderware stub; Client.CLI exit-code contract.
- ServerHistorianOptions: Endpoint/Backend XML docs untangled, Validate()
indented; Program.cs comments are backend-neutral; T10 week-test day count.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Since #516 a DriverConfig change is stop + respawn, so DriverSpawnPlan.ToApplyDelta
was always empty and the in-place path had no producer. #663 and #664 were both
latent bugs in it. This deletes it:
- host: ApplyChildDelta, _pendingDelta, HandleApplyResult and HandleDeltaApplied
- plan: DriverSpawnPlan.ToApplyDelta
- actor: the ApplyDelta, ApplyResult and DeltaApplied messages, the Connected
reinit handler and the mid-connect AdoptConfigDuringInit
- tests: the actor tests that drove the seam
IDriver.ReinitializeAsync and each driver's implementation and unit tests stay.
Comments and docs that cited AdoptConfigDuringInit as the reason a driver must
release prior state at init now cite the IDriver contract and overlapping
retries, which still apply.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
AdoptConfigDuringInit re-runs InitializeAsync(newConfig) and acks success, but
Calculation and Galaxy ignored the JSON there: Calculation kept its old tag
set, and Galaxy connected on its old endpoint. Calculation now rebuilds its tag
table from a config with a body (sharing AdoptConfig with ReinitializeAsync and
stopping any running timer scheduler first). Galaxy, which cannot hot-swap its
options, refuses a non-equivalent one the way ReinitializeAsync does. The actor
now sends DeltaApplied once the adopted init succeeds, so a dependency
consumer's mux interest is re-registered. Unreachable from deploys since #516.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A Connected ApplyDelta called ReinitializeAsync and kept the actor's data and
native-alarm handles, though every driver's reinit drops the driver-side
subscriptions behind them (#630). The reconcile only re-subscribes a missing
handle, so the driver went silent until a reconnect. Release both at the
driver before the reinit and re-subscribe both in a finally. Unreachable from
deploys since #516; pinned by a two-case test, each case failing against a
different wrong fix.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A data re-subscribe (every deploy's bulk SetDesiredSubscriptions push to a
kept driver) dropped the prior data subscription through the full
DetachSubscription, which also unhooked OnAlarmEvent and forgot the alarm
handle. On any deploy that did not respawn the driver, the alarm
subscription kept logging "established" while every event reached nobody
until a reconnect or respawn. The data path now uses DetachDataSubscription;
only a lost connection and PostStop detach both.
The #488 health-poll reconcile only looked at data, so an alarm subscribe
that failed on (re)connect gated the feed for the life of the connection.
ReconcileAlarmSubscription now re-attaches a missing handler and
re-subscribes a stale/missing alarm handle every tick.
OpcUaClient removes a half-built alarm subscription from its session when
SubscribeAlarmsAsync throws, so the new retries cannot accumulate.
Tests: actor-level data-resubscribe + reconcile-retry tests and an
end-to-end NativeAlarmFeedSurvivesDeployTests through DriverHostActor; all
three fail against the unfixed actor.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- HardwareGateGuardTests: only StringWriteGateTests may name a write path in HardwareGate/; the
allow-list is exactly the two Z-35162 (10.209.70.160) STRING tags; the opt-in, the (host, tag)
check and the AB_DIFF_ENDPOINT refusal are present. Proven red by a WriteAsync mutation.
- StringWriteGateTests: allow-list entries are (host, tag); any other endpoint is refused; skips
while AB_DIFF_ENDPOINT is set, like IntegrationWriteGate.
- AbCip.md #566: the close happened somewhere in the 16-60 s window; RST vs FIN not captured.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
A. #566 on a real CompactLogix (Z-35162, read-only): a class-3 connection idled 60 s past its
16 s timeout is closed at the TCP level, not with CIP 0x0107/0x0203; the next request fails on
its write (Broken pipe -> BadConnection) in 9 ms and the one after reopens. The transport already
handles this, so no production behaviour changed; the shape is pinned offline by
CipConnectionTests.A_target_that_resets_an_idle_session_... (FakeEipServer.ResetAllConnections),
proven red with a reconnect-skipping mutation. The diagnostics-only exchange tap now also sees
Forward Open replies (granted RPIs).
B. Native STRING write through the driver on Program:ES03_TemperatureControl._StrTmp: write,
read back, restored byte-exact (user-approved). Array write NOT run: the census's unreferenced
DINT[32] _SEQ_EP arrays are aliased sequencer step registers (raw L5X grep), so none qualifies.
#567 still impossible (a 128 B array / 88 B STRING never fragments).
New env-gated harness: AbCip.IntegrationTests/HardwareGate (IdleConnectionEvidenceTests,
StringWriteGateTests). Docs: gate results (hw5 section + raw output), AbCip.md, CLAUDE.md.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
After an OpcUaClient respawn an upstream inactive+unacked condition went out as
Retrigger+Clear (duplicate Activated+Cleared rows, Active flicker), and a
first-sight inactive+acked one as Unspecified (an Activated row for an inactive
alarm; a retained-Active host condition never cleared).
- New AlarmTransitionKind.InactiveUnacknowledged: one projection, rows only for
what changed (Activated+Cleared from acked, Cleared from active+unacked, none
when already inactive+unacked).
- OpcUaClient uses it for moves into inactive+unacked; first sight of an
inactive condition is InactiveUnacknowledged or Clear+Acknowledge, flagged.
- Projector: a flagged Acknowledge on an already-acked condition writes no row.
- E2E tests through DriverHostActor.ForwardNativeAlarm (red-proven).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Review M1: round 1 refused only the rewritten status bits, so S:/O:/I: writes - which
never worked on libplctag because tag creation failed - would have started reaching
the PLC (outputs, status-file words) on the default transport. WriteRefusal now keys
on LibplctagLegacyName.IsTranslated: file number supplied (S/O/I, incl. bit writes
like O:0/3, refused ahead of the parent-word RMW) or status bit rewritten. Reads
unaffected. Docs/comments now true; gate doc notes R bit-number wire evidence is
non-discriminating (L1). 12 new cases fail with the round-1 predicate.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
The read translation R6:0.DN -> R6:0.CON/13 made those names parse in libplctag, which
would have turned a write - previously impossible, tag creation failed - into a masked
write to the control word. LibplctagLegacyTagRuntime.WriteRefusal (via
IAbLegacyTagFactory.WriteRefusal, same plumbing as native) now refuses writes to every
rewritten status bit (R EN/EU/DN/EM/ER/UL/IN/FD, C UA) with BadNotSupported before a
runtime is created; the runtime also refuses as defence in depth. Reads stay
translated. T/C status bits libplctag parses itself keep their pre-existing behaviour.
13 new tests fail with the predicate disabled.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
libplctag 2.6.0 (bundled by libplctag 1.5.2 / NativeImport 1.0.41) pccc.c needs an
explicit file number (parse_pccc_file_num; S is only the status file when a digit
follows) and has no R-file status-bit mnemonics (sub_element_lookup: con/len/pos only;
a /bit is refused on a 6-byte element). So the canonical S:0 (the default probe),
O:0/3, I:0/0 and R6:0.DN failed with BadCommunicationError on a real MicroLogix 1400
while native read them.
LibplctagLegacyName (libplctag adapter only) now emits S2:/O0:/I1: (the native
encoder's implicit file numbers) and R6:0.CON/<bit> for status bits libplctag lacks
(R EN/EU/DN/EM/ER/UL/IN/FD, C UA), bit numbers taken from the native table. The
authored grammar is unchanged. Unit tests pin the translation per family and check,
through a model of the pccc.c parser, that the translated name addresses exactly
what the native encoder does (46 fail without the fix). Live: Z-33323 idle, reads
only - libplctag now equals native for S/O/I/R status bits; controls unchanged.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- L2: WriteWidthRefusal leaves a BOOL over a wider value to a runtime that sees the CIP
type (native): mistyped integer member -> BadTypeMismatch (as its read), 0xD3 BOOL-array
DWORD -> BadNotSupported; libplctag keeps BadNotSupported for both (size only).
- L4: direct theory over WriteWidthRefusal (1/2/4/8 widths incl LINT/ULINT/LREAL, String/Dt,
unknown size) + array/bit-selector exemptions with a non-vacuous control.
- L1: CLAUDE.md member/BIT-member writes are ab_server-proven only.
- L3: patch 0003 blind spots documented (Docker README, AbServer-Test-Fixture.md); nits.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Item 2 — controller-discovered UDT members are writable on both transports once
browse-committed and authored ReadWrite (writability is the operator's: the commit
lands AccessLevel Read with no writable key). The write names the member (one CIP
symbolic segment per member), its own type, its own bytes. BIT members are supported:
Z-35162 (read-only probe) exposes a UDT BIT member as a 1-byte 0xC1 BOOL, so the
controller applies the bit and the hidden host's other bits are never in the request.
- AbCipDriver: pre-write width check on BOTH transports (libplctag patched part of
its read buffer and sent it all): BadTypeMismatch, Bool over a wider value
BadNotSupported; nothing sent, handle kept, health untouched, warn once.
- A runtime NotSupportedException is a refusal: no longer latches Degraded.
Item 3 — whole-UDT writes refused BadNotSupported before any runtime exists, by
decision (a structure write overwrites hidden hosts + padding), documented.
ab_server patch 0003: serve member paths from dotted flat tags (UdtSeg.*), and
accept libplctag's pad byte on 1-byte writes (stock ab_server refused every
libplctag BOOL/SINT write with 0x03). New AbCipUdtMemberWriteTests (both
transports), AbCipDiscoveredMemberWriteTests, native request-byte theory, and a
browse-commit mapper pin. Docs: AbCip.md Member writes / Whole-UDT writes / Known
gaps, fixture docs, CLAUDE.md AB section.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
M1 drop-out is a no-row Unspecified+IsRestatement update (projector case); M2 ack judged over every declared
limit; L1 ActiveAcknowledged for an already-acked new limit; L2 Bad Acked/severity carried/skipped; L3 host
end-to-end test; L4 BOOL member-by-member tests + mixed ALMD/ALMA; L5 detection requires no plain Acked.
ALMD active bit is InAlarm per Rockwell's ALMD reference; InFaulted is input health.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Detect ALMA by declared *InAlarm members; one condition per tag keyed on RawPath; severity/message from
the most severe active limit; Raise/ActiveAcknowledged/Retrigger/Clear/Acknowledge; ack writes OperAckAll.
Unit-tested over fake runtimes only (no ab_server ALMA support, Z35162 has none).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe