A. #566 on a real CompactLogix (Z-35162, read-only): a class-3 connection idled 60 s past its
16 s timeout is closed at the TCP level, not with CIP 0x0107/0x0203; the next request fails on
its write (Broken pipe -> BadConnection) in 9 ms and the one after reopens. The transport already
handles this, so no production behaviour changed; the shape is pinned offline by
CipConnectionTests.A_target_that_resets_an_idle_session_... (FakeEipServer.ResetAllConnections),
proven red with a reconnect-skipping mutation. The diagnostics-only exchange tap now also sees
Forward Open replies (granted RPIs).
B. Native STRING write through the driver on Program:ES03_TemperatureControl._StrTmp: write,
read back, restored byte-exact (user-approved). Array write NOT run: the census's unreferenced
DINT[32] _SEQ_EP arrays are aliased sequencer step registers (raw L5X grep), so none qualifies.
#567 still impossible (a 128 B array / 88 B STRING never fragments).
New env-gated harness: AbCip.IntegrationTests/HardwareGate (IdleConnectionEvidenceTests,
StringWriteGateTests). Docs: gate results (hw5 section + raw output), AbCip.md, CLAUDE.md.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Review M1: round 1 refused only the rewritten status bits, so S:/O:/I: writes - which
never worked on libplctag because tag creation failed - would have started reaching
the PLC (outputs, status-file words) on the default transport. WriteRefusal now keys
on LibplctagLegacyName.IsTranslated: file number supplied (S/O/I, incl. bit writes
like O:0/3, refused ahead of the parent-word RMW) or status bit rewritten. Reads
unaffected. Docs/comments now true; gate doc notes R bit-number wire evidence is
non-discriminating (L1). 12 new cases fail with the round-1 predicate.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
libplctag 2.6.0 (bundled by libplctag 1.5.2 / NativeImport 1.0.41) pccc.c needs an
explicit file number (parse_pccc_file_num; S is only the status file when a digit
follows) and has no R-file status-bit mnemonics (sub_element_lookup: con/len/pos only;
a /bit is refused on a 6-byte element). So the canonical S:0 (the default probe),
O:0/3, I:0/0 and R6:0.DN failed with BadCommunicationError on a real MicroLogix 1400
while native read them.
LibplctagLegacyName (libplctag adapter only) now emits S2:/O0:/I1: (the native
encoder's implicit file numbers) and R6:0.CON/<bit> for status bits libplctag lacks
(R EN/EU/DN/EM/ER/UL/IN/FD, C UA), bit numbers taken from the native table. The
authored grammar is unchanged. Unit tests pin the translation per family and check,
through a model of the pccc.c parser, that the translated name addresses exactly
what the native encoder does (46 fail without the fix). Live: Z-33323 idle, reads
only - libplctag now equals native for S/O/I/R status bits; controls unchanged.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Pass 2 (2026-10-08 00:21Z, df776170): 17/17. Browse 3162=3162 tags, 20 UDT
templates identical, 200 tags read with 0 unexpected divergences (6 live
values compared structurally + every still element), 1 Forward Open and 1
acked Forward Close per native phase. Latency native p95 105.8 ms vs
libplctag 139.5 ms (limit 153.4) PASS. Pass 1 failures and their fixes are
recorded in the gate-results doc; pass 2 had no independent pcap.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- AbCip/AbLegacy driver forms gain a Transport InputSelect; FromOptions/ToOptions now carry
Transport, so saving any other field no longer silently reverts Native to libplctag.
- Both drivers log the constructed transport once per init.
- AbCip factory now takes the host ILoggerFactory (it ran on NullLogger in production, hiding
every AbCip log line); DriverFactoryBootstrap passes it.
- Gate results: AdminUI /run (T19) native, inverted (dead port) and libplctag legs.