Live run against ab_server (slc500/micrologix/plc5 x libplctag/native): with
coalescing on, the blackholed device's 20 tags are one block, i.e. one comms
fault per poll, so its backoff window opens on the second poll rather than the
first. The gate now asserts the actual contract: at most two timeouts across
three polls, the live device Good on every poll, and the third poll fast.
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
DriverArrayWriteSupport (Core.Abstractions, not this lane's) still lists
AbLegacy as scalar-only, so every AbLegacy array node is materialised
read-only and the new array encoder is unreachable from OPC UA. Adds the
Modbus/S7-style parity test, skipped until follow-up F1 adds the AbLegacy row
(Int/AnalogInt/Long/Float with a declared length), plus an active test pinning
exactly which element types the encoder accepts.
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 07 U7 (AbLegacy part): probe/read/write had no OperationCanceledException
arm, so cancelling a slow read printed an unhandled-exception stack trace. The
driver work now runs through AbLegacyCommandBase.RunCancellableAsync, which
reports an operator cancellation as "Cancelled." and still propagates anything
else. (The AbCip subscribe lock and SnapshotFormatter array rendering are
other lanes' files.)
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Dead config field (user decision: wire them all): the AdminUI form authors
probeTimeoutSeconds ("Admin UI probe timeout", default 5) but AbLegacyDriverProbe
never read it, so Test Connect always ran on the caller's budget. It now
tightens that budget (never raises it), the same rule as the Galaxy probe; a
non-positive value keeps the caller's budget.
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 02 P1 / Wave 2 rule (d): AbLegacy runs PollGroupEngine but raised only
the per-tag OnDataChange, so every changed tag paid its own trip through the
actor chain. The engine's per-cycle batch is now raised as OnDataChangeBatch
(one per poll cycle), alongside the per-tag event for legacy consumers.
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 07 P7 (rest): adjacent words on one data file were never coalesced
(one round trip per tag) although the array path proves the transport can read
a span. Within a device pass, scalar tags on one N/B/F/L file within 8
elements of each other (block <= 200 data bytes, under the 236-byte typed-read
limit) now ride one multi-element read and are decoded from their offsets with
exactly the CLR types the single-tag path returns (int / float / bool).
Only shapes the single path decodes identically are coalesced: indirect,
sub-element, array, file-number-less (S:/I:/O:) and width-mismatched tags keep
the single path. A block the device refuses (an authored element past the end
of the file, a native PLC-5 non-N file) falls back to per-tag reads for its
members and its shape is remembered; a comms fault fails the members together.
New driver-config key coalesceReads (default true) with an AdminUI switch
(Razor change: AbLegacyDriverForm, for the Wave 4 live check). Adds an
env-gated ab_server parity case (coalesced == per-tag values).
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 07 P7 (High): reads walked every reference of every device serially
with no backoff, so a dead device cost Timeout per tag per poll (50 tags x 2 s
= 100 s) and starved every healthy device long enough to trip the comms-loss
watchdog against a reachable one.
- ReadAsync buckets references by device and reads up to 8 devices
concurrently; each device's tags are still read in order.
- Each device has a ConnectionBackoff (1 s doubling to 30 s). Two consecutive
comms faults mark it down: the rest of that pass and every later pass fail
fast with BadCommunicationError and touch no wire until the window expires or
any answer (data path or probe) resets it. One timing-out tag does not
blacken its answering siblings.
- Cold connects are single-flight per device (ConnectGate), replacing the
per-key creation locks; a cached handle never touches the gate.
- A status/exception proving the device ANSWERED with a deterministic refusal
(not found, not allowed, out of bounds, type/size mismatch) is per-tag Bad,
keeps its handle, warns once per tag and advances LastSuccessfulRead instead
of evicting and degrading. Writes classify the same way.
- Health is written once per read: Degraded if any device faulted, Healthy if
anything read Good, LastSuccessfulRead advanced when any device answered.
Adds an env-gated ab_server case with a blackholed sibling device.
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 07 U10 (user decision: implement array encode now). Both runtimes
encoded a scalar for an array tag: an int[] threw InvalidCastException into
BadTypeMismatch + Degraded, a scalar wrote element 0 natively, and libplctag's
SetInt32(0, ..) re-sent the stale last-read buffer for elements 1..n-1.
IAbLegacyTagRuntime gains EncodeArray; both runtimes write every element at
the element width (Int/AnalogInt 2 bytes, Long/Float 4). The driver converts
the written value before any runtime exists: each element is converted, not
exact-matched (ScadaBridge writes int[] to Int16 nodes), a length other than
the tag's element count is BadOutOfRange, an overflowing element is
BadOutOfRange, a non-array or non-numeric payload is BadTypeMismatch, and a Bit
array (bit-packed words; an encode would clobber neighbour bits) is
BadNotSupported. None of these touch health or the wire. Adds an env-gated
ab_server round trip for an N-file array write.
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 07 H16: an array of String/Timer/Counter/Control passed the mapper, so
every poll created a handle (one init read), the decode threw
NotSupportedException, the generic catch evicted the handle and latched
Degraded. FromTagConfig now rejects that combination (the skip carries the
reason, Inspect/deploy gate and the AdminUI model state it), and a runtime
NotSupportedException on read or write is BadNotSupported: handle kept, no
health write, one Warning per tag and operation. Write refusals (native PLC-5
and status-bit writes, libplctag translated addresses) now warn once per tag too.
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 07 L7: each index value an indirect tag (N7:[N7:0]) swept through left a
per-runtime and a creation SemaphoreSlim in the device's gate tables until
shutdown. A moved index now drops the stale resolution's gates along with its
handle, and sweeps any other stale resolution of the same tag a concurrent
reader cached, so the tables stay bounded by the authored set.
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 07 H13: _devices and _tagsByRawPath were plain dictionaries cleared and
refilled in place while the retained poll loop, the actor's GetHostStatuses and
server reads enumerated them. Both are now built locally and published by
reference under a lifecycle lock; teardown swaps in empty tables.
Lane A contract: ShutdownAsync and Dispose each retire a disjoint set of device
states, so Dispose running concurrently with a still-joining ShutdownAsync is
safe. A lifecycle epoch makes an InitializeAsync that the runtime abandoned
(overlapping the next ShutdownAsync) refuse to publish its tables, start probe
loops or write health. A runtime cached on an already-retired device state by an
in-flight read is disposed instead of leaked, and late reads/writes no longer
overwrite shutdown's health. Per-key semaphores are no longer disposed under
callers that may still hold them.
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
GalaxyTelemetryTests (ActivityListener) and GatewayGalaxyDataWriterFailClosedTests
(MeterListener, filtered only by meter and instrument name) observe every Galaxy span or
measurement in the process. They now run in a collection with parallelization disabled
(F-FU6), because a parallel driver test, or its background probe seed, polluted their counts.
The stream-cancel assertion in GalaxyDriverShutdownTests goes back to a bounded wait: the
instantaneous IsCompleted check introduced in round 1 was racy.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review fix round 2 for lane F:
- N1: the init platform seed no longer runs inline under the init token. Galaxy's Tier-A
Initialize budget is 5 s, and a cold gateway DiscoverHierarchy can spend all of it, so the
OperationCanceledException rethrow failed init, opened the Initialize breaker and cost a full
rebuild per retry. InitializeAsync now only resolves the platform source (no network) and
queues a background seed tied to a per-runtime CTS that the teardown cancels. A result that
lands after its runtime was torn down is discarded.
- N2: the seed worker serves the runtime that is live when each pass STARTS, so a request made
under a new runtime while a stale pass is in flight always gets a pass of its own.
- N3: SubscribeAsync and the subscribe-once read capture the runtime generation before
SubscribeBulk and register only if it is unchanged, atomically with the teardown's registry
Clear (_registryGate). On a mismatch they release the handles and fail the call. Re-subscribe
Rebind uses the same gate, and the production rebuild clears the registry unconditionally.
- PerPlatformProbeWatcher re-checks its stop after the SubscribeBulk await, atomically with
the record and publish. A pass that straddles StopAsync releases the handles it acquired
instead of writing the probe entry back into a cleared registry.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The fixture wedged EVERY write on one shared token-ignoring release gate, so
the later same-tag write was also hung, and the 300 ms pessimistic bound
abandoned it while the test was still polling before ReleaseWrites(). Its
reason was "write did not complete within" (the bound), not "queued for" (the
queue budget), and it had already entered the driver, so the tag had been
released. The release path is correct. Only the first write now hangs, and
later writes complete at once.
The abandon reason formatted the bound with TotalSeconds:F0, which printed a
300 ms bound as "0s". It now uses milliseconds, and the test asserts it.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The writer concurrency fake parks on its release signal (the 300 ms delay could release the
gate early on a starved pool), the supervisor test's cross-thread hold flag is Volatile, and
the EffectiveTimeout doc now states the 1 s floor the code and tests implement.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review fix round 1 for lane F:
- The ScanState probe watcher is seeded at InitializeAsync from a platform-only
DiscoverHierarchy query (IGalaxyPlatformSource / GatewayGalaxyPlatformSource over the owned
repository client) and re-seeded on every deploy-watcher rediscovery. The runtime never
calls DiscoverAsync on a live driver, so per-platform host status was unreachable in
production. A failed fetch logs a Warning and never fails init; re-seeds coalesce so a
deploy during an in-flight pass still gets a pass that starts after it.
- EnsureEventPumpStarted refuses while the runtime is stopping, BEFORE reusing the live pump
(that pump belongs to the dying subscriber), and the production rebuild disposes any stale
pump before wiring the new subscriber.
- TeardownRuntimeAsync closes the MX session under the caller's token linked with a 5 s
SessionCloseDeadline, so a blackholed gateway cannot hold DriverInstanceActor.PostStop for 30 s.
- A runtime generation counter, bumped by every teardown, is re-checked before each Rebind
in ResubscribeAllAsync, so a replay-gap re-snapshot that straddles a teardown cannot
resurrect handles into the cleared registry.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The SDK's DisposeAsync closes with no token, i.e. under the 30 s DefaultCallTimeout, so a
blackholed gateway parked the driver's teardown for the whole of it. CloseAsync(ct) runs the
close under the caller's token, drops the channel on a cancelled/failed close (the gateway
reaps the session on its idle lease) and leaves the session re-openable. A close followed by
the final dispose closes the gateway session once.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- RunWriteAsync wraps the invoker call in WaitAsync(writeTimeout) (Props,
default 10 s = 2x the 5 s write cap): a token-ignoring hung write now
answers BadTimeout, releases its slot and tag, and its orphan outcome
is observed and discarded - later writes to that tag reach the device.
- WriteCompleted carries the launching incarnation (from the process-wide
generation source); a late completion from a previous incarnation after
a supervision restart is ignored instead of freeing the new
incarnation's slot/tag.
- Test: a hung token-ignoring tag-a write is abandoned and a later tag-a
write reaches the device while the abandoned one is still inside it.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- GatewayHistorianDataSource.ReadRawWindowAsync keeps the cap + 1 probe budget
(budgetCap) separate from the client's cap: a strict-ceiling or crowding
refusal now reports Limit = the server cap that applied and advises setting
NumValuesPerNode at or below it (it said "lower NumValuesPerNode" with
Limit = cap + 1 to a client that sent 0).
- Fuzz: the oracle-source over-cap assertion was vacuous (cap 0 never counts);
it now checks no reverse window reached the forward-only shape. Class docs
name the post-floor cap set (3 ... 1000) and distinguish NumValuesPerNode
1 / 2 from the smallest server cap.
- HistoryPaging.IsFullPage doc says it judges the REQUEST cap (page + ties +
lookahead), which is finite under any limit; AdvertiseMaxReturnDataValues
swallows any exception (returns false for the caller to log), as its doc
promised.
Refs #736
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- Writes: a second write to a tag already inside the driver waits in the
queue behind it (_tagsInFlight) while other tags still run under the
cap of 4; queued writes are stamped and failed BadTimeout at dequeue
once older than the 8 s host Ask budget (Props queuedWriteBudget)
instead of being written late.
- Initialise attempts are bounded pessimistically (initializeTimeout,
default 30 s = 2x Tier C) on top of the invoker's token-only timeout:
an overrun is logged as abandoned, reported InitializeFailed so the
retry loop continues, and its late result is dropped by generation.
Generations come from a process-wide Interlocked counter so a prior
incarnation's late result cannot collide (F6).
- PostStop shares one shutdownTimeout budget across shutdown + dispose.
- TelemetryDialSupervisor cancels the establishment deadline on
StreamStopped; FleetDiagnosticsClient builds the ActorSelection inside
the try (a malformed node degrades to "unavailable"); the diagnostics
page labels the column "Last health publish".
- Tests: same-tag serialisation with a distinct-tag positive control;
stale queued write BadTimeout; token-ignoring hung init -> later
attempt connects; stopwatch assertion demoted to a ceiling.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- NodeManagerHistoryReadRawCapFuzzTests: 10k seeds (env OTOPCUA_PAGING_FUZZ_ITERATIONS)
through a real SDK node manager against wire-faithful fakes of SqlServer / QuestDB /
Gateway that enforce the backend half of the cap; random series with ties, random
windows (empty, on/past a tie, between samples, forward/reverse/end-only, bounds),
N in {0,1,2,small,huge}, cap in {off,3..1000}, tie budget {3,8,65536}. Pages must
concatenate to the cap-off one-shot answer (checked against the series), terminate
within values + 2 (+ one empty step per oversized boundary cluster), never exceed
the cap, never ask the backend for 0 / over-cap; refusals only past the budget.
- HistoryPaging.AdvertiseMaxReturnDataValues writes HistoryServerCapabilities/
MaxReturnDataValues (i=11273), read back through the SDK master node manager.
- MinMaxRawValuesPerRead raised to 3: at 2 a resumed page has no room (value + its
boundary tie + lookahead) and every value cost an empty page + CP (seed 15).
- RawPageLimit rows pin the default-cap arithmetic (9 999 first page, 9 998 resumed).
Fuzz findings recorded as follow-ups: a bounded read whose data fits one page
returns cap + 1 (end bound fitted against N, not the cap; node manager, F2);
the Gateway walk-back's cost on a sparse series under a tiny tie budget is
pre-existing (seed 320: 82 reads uncapped, 93 capped).
Refs #736
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
DriverInstanceDiagnostics.Name carries the string driver-instance id
(what /hosts, telemetry and the artifact key on) and DriverInstanceId
the DB row Guid; the wire record has no slot for the authored display
name. The write-cap test asserts entry order per slot pair instead of
completion order of two concurrent writes.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
DriverHostActor wraps the health publisher it hands its children in a
ChildHealthLedger (last snapshot per driver id, forwarded to the real
publisher), so GetDiagnostics now answers with each child's row id,
authored name, last-published state, device counts (host statuses when
the driver probes hosts, else one device) and last-change time — instead
of Guid.Empty / "Spawned" / 0 / now. Entries are forgotten on StopChild
and operator Restart.
IFleetDiagnosticsClient gains its first consumer: the new
/fleet/diagnostics page (node selector + ?node= query, revision,
running-from-cache notice, per-driver table). FleetDiagnosticsClient
logs the degrade-to-empty path at Warning.
Review ref: 02/U1.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 2026-10-21 G-5, G-6, G-8 ("wire them all").
- G-5: GatewayGalaxyHierarchySource now pages the DiscoverHierarchy RPC
itself (DiscoverHierarchyRawAsync) at Repository.DiscoverPageSize. The
mxaccessgw client's typed DiscoverHierarchyAsync overloads hard-code a
5000-row page and DiscoverHierarchyOptions carries no page size, so the
authored knob reached nothing; the raw request takes page_size on the
wire, so it is honoured here (non-positive → 5000). The loop keeps the
client's repeated-page-token guard.
- G-6: GalaxyDriverProbe reads ProbeTimeoutSeconds from the config and
runs under min(caller budget, configured cap) — the knob can shorten a
probe, never extend it past the host's budget. The TCP preflight now
shares that deadline instead of hanging on the caller's token alone.
- G-8: GatewayGalaxyDataWriter runs a batch as one lane per distinct tag,
concurrently and bounded at 8 (MaxConcurrentWriteLanes); same-tag
writes keep their authored order inside one lane and results land at
their request's index. Acks stay serial by design.
- GalaxyDriverForm: help text now says what the two knobs actually do.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
CallTimeoutSeconds was bound, defaulted and documented but consumed
nowhere. TelemetryDialSupervisor now arms a per-generation deadline on
every dial: a dial that has delivered no event by the deadline is
cancelled and treated as a transport failure (reconnect with a failure
streak). A live node replays its snapshots on subscribe, so this bites
only a dial that never connects (a black-holed host, where the socket
connect has no timeout). An established stream is deliberately not
bounded — the wire has no heartbeat, keepalive pings own its liveness.
Review ref: 02/U2.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
- DriverHostActor.StopChild removes the driver's _lastReprovisionUtc stamp
(and its deferred-reprovision timer): the map grew per removed id and a
re-added driver inherited a backoff it never earned (02/L2).
- Stale now registers explicit drops for AttributeValueBatchPublished,
AttributeAlarmPublished, ArtifactForApply and ApplyWedged instead of
letting them hit Unhandled (02/H5).
- DbHealthProbeActor runs its SELECT on the thread pool and pipes the
outcome back (single-flight), with a 2 s command timeout on relational
providers, so a hung SQL Server no longer pins the actor thread and the
cached GetStatus answer stays reachable (02/P7).
- TelemetryLocalHub eviction tombstones are timestamped and swept past a
10 min TTL on the next Evict; a TimeProvider ctor is the test seam (02/L4).
- Tests: ValuePublishes.Single helper replaces the per-value
AttributeValuePublished in CalculationDependencyFlowTests (02/U4, test
half; the production receive is owned by Lane E).
- R05/8 audit: PollGroupEngine.Unsubscribe has no production caller; every
driver already uses UnsubscribeAsync (no change).
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 2026-10-21 G-4, G-7, G-11, G-10.
- G-4: PerPlatformProbeWatcher publishes its probe handles into the
driver's SubscriptionRegistry under the reserved ProbeSubscriptionId
(-1), so the EventPump's fan-out finally reaches the watcher — every
ScanState event used to be dropped as "stale after unsubscribe" and
per-platform host status never updated. ResubscribeAllAsync delegates
the reserved entry to the watcher's new ResubscribeAsync, so the probe
survives a reconnect; StopAsync removes the entry. Probe traffic is
routed by the reserved handle and never reaches the public OnDataChange.
The watcher is also built on the seam path (subscriber only), which is
what makes the wiring testable without a gateway.
- G-7: GalaxyDiscoverer.DiscoverAsync returns the hierarchy it fetched and
the driver selects its $WinPlatform/$AppEngine probe targets from that
same sweep instead of asking the gateway for the whole galaxy twice.
- G-11: OnPumpDataChange stamps LastSuccessfulRead from inbound stream
data, throttled (1 s default), so the comms-loss watchdog has honest
liveness evidence under a Degraded supervisor.
- G-10: an EventPump dispatch-loop exit that is not a cancellation now
reports a stream fault so the supervisor recreates the pump, instead of
leaving a deaf pump reporting Healthy.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
WriteAttribute was a ReceiveAsync, suspending the child's mailbox for the
whole device round-trip (up to 5 s): writes serialised, the second of two
operator writes to a slow device missed the host's 8 s Ask and was
reverted although the device took it, and every data change queued behind
the write. Writes are now a synchronous Receive that launches the device
call on the thread pool (sender captured, reply from the task, slot freed
by a self-sent WriteCompleted) under a per-driver cap (default 4; excess
writes queue in order). Queued writes fail fast on every exit from
Connected. Subscribe/unsubscribe stay ReceiveAsync.
Review ref: 02/P2.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
GalaxyDriver.ShutdownAsync was a no-op: the MX session, both owned gRPC
channels, the EventPump, the alarm feed, the DeployWatcher, the probe
watcher and the reconnect supervisor were released only by DisposeAsync,
which the host never calls — one leaked gateway session per respawn,
removal and /raw browse, and a watchdog Shutdown→Initialize that neither
tore down nor rebuilt anything (review 2026-10-21 G-1, G-2, G-9, G-3).
- ShutdownAsync and DisposeAsync share one ordered TeardownRuntimeAsync
(supervisor first, then deploy/probe watchers, pump, alarm feed,
session, channels); owned seams are nulled so the next InitializeAsync
rebuilds; injected seams survive a shutdown and drop only on the final
dispose. Lifecycle calls are serialised behind a gate.
- A failed production connect releases its partial runtime (no orphaned
client per watchdog retry) and lands Faulted before and after.
- StartDeployWatcherAsync stops the previous watcher before starting a
replacement, and now starts on a production instance's FIRST
InitializeAsync (the old guard returned whenever discovery had not run
here, which on a runtime instance is always).
- ReconnectSupervisor releases each cycle's CancellationTokenSource when
its loop exits and gains an awaitable StopAsync; PerPlatformProbeWatcher
gains an awaitable StopAsync.
- EventPump treats any exception under cancellation as a clean stop, so a
teardown never wakes the supervisor.
- Internal seams for tests: an IGalaxyDeployWatchSource ctor parameter and
a session-open override forwarded to the owned GalaxyMxSession.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review R08:1.1: an uncapped HistoryRead-Raw (NumValuesPerNode = 0) read a
tag's whole window into memory on every backend (SQL TOP(int.MaxValue),
QuestDB LIMIT, Gateway max_values = int.MaxValue + a second snapshot copy).
New ServerHistorian:MaxRawValuesPerRead (default 10 000; <= 0 unbounded with
a Validate() warning; 1 raised to 2). Each backend data source takes it,
reports it as IHistorianDataSource.MaxRawValuesPerRead (the Gateway: min
with a strict gateway's learned ceiling), so the node manager's existing
RawPageLimit paging serves N = 0 and N > cap as pages of at most the cap
with a continuation point. Independently, a backend raw read asking for 0
or more than the cap reads cap + 1 rows and is REFUSED
(HistoryReadLimitExceededException => BadTooManyOperations) when the window
holds more - never answered truncated, since the server's paging reads a
short answer as the last page. Bound through the Host registry, the
SqlServer/QuestDb providers and GatewayHistorian.CreateDataSource.
Tests: options (default/binding/warnings), provider binding, Gateway unit +
through a real SDK node manager (uncapped -> 999/998/998/605 + CPs), and a
conformance case for the SQL backends.
Refs #736
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The Reconnecting retry timer started a new ShutdownAsync + InitializeAsync
pair on every tick whether or not the previous attempt had finished; the
generation token only discarded the older RESULT, so with an Initialize
bound longer than the cadence the teardown ran underneath an attempt still
inside the driver (the dispose-before-overwrite race). An _initInFlight
gate, cleared by the piped InitializeSucceeded/Failed, skips a tick while
an attempt is running; the pre-reconnect teardown is bounded by the
shutdown timeout; PostStop cancels an in-flight attempt before shutting
the driver down.
Review ref: 02/H2.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
DriverInstanceActor.PostStop now bounds IDriver.ShutdownAsync by a
shutdownTimeout (default 5 s, logged on overrun) and then disposes the
driver (IAsyncDisposable preferred, else IDisposable) — but only on a
real stop. PreRestart flags the restart so the PostStop it triggers
skips the dispose, because a supervision restart re-uses the same
driver object (Props closure) and the host re-initialises it.
DiscoveryDriverBrowser disposes its throwaway capture/probe driver
after the bounded shutdown, including after a failed or timed-out one.
Review refs: 02/L1, 02/P4, 06/G-1 (host context), 07/L2.
Refs #731
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The #687/F4 crowding re-read doubled its room up to 8 re-reads with no cap, so a pathological single-ms
cluster on a streaming gateway was streamed several times over for one page. The room is now capped at
ServerHistorian:MaxTieClusterOverfetch (plumbed into GatewayHistorianDataSource as maxPreWindowRows,
default 65536); past it, or once a read has already seen more, the read is BadTooManyOperations with
PreWindowRows set.