#838 review of 91e28e87:
1. Ghost events. The deferred report ran the SDK walk off Lock with no
liveness check, so an event waiting behind a full channel when a deploy
removed its condition still reached i=2253 subscribers after the NodeDeleted
(a ghost Retain alarm for ScadaBridge) and folder items. Delivery now walks
the SDK path itself (OnReportEvent, OnReportEventAsync, inverse notifiers,
then the Parent as BaseInstanceState does) re-checking before EVERY hop that
the condition is the live instance; OnConditionReportEvent checks the same,
which also stops a non-live scripted condition being admitted through its
old equipment folder (#808). A guard test pins that only NodeState and
BaseInstanceState define the walk. New wire test removes the condition in
the same Lock hold as a flood; the flag-off variant fails without the checks.
2. Back-pressure. Deferral is per condition (one condition's events stay
ordered; others are not held up). Overflow policy: coalesce, newest wins --
past 1024 waiting per condition or 65,536 total, the oldest not-yet-started
event is discarded (a condition event carries full state). Warning on
entering deferral (<=1/min), Information on draining, meters
otopcua.opcua.condition_events.deferred / .discarded{reason}.
3. Verified by decompiling SDK 2.0.1: the notifier list is snapshotted under the
node's own lock, MonitoredNode2.Dispose completes its writer (pending writes
fail with ChannelClosedException, swallowed), and the consumer catches
per-event exceptions -- no fix needed; documented.
4. ConditionRefresh does not flush deferrals; documented as a residual.
#844 review: DescribeCredential canonicalises the key id (trim, lowercase;
non-hex ids fold into one identity) and the username, since ConfigDbApiKeyStore
matches with SQL Server's case-insensitive, trailing-space-blind `=`.
#838(a): each notifier's SDK MonitoredNode2 drains a bounded channel (4096,
FullMode=Wait) and the synchronous NodeState.ReportEvent blocks when it is
full. Condition events are reported under Lock, and the delivery task takes
Lock on a verdict-cache miss (the SDK's own GetNodeMetadata, flag off too, and
#826's IsNotifierEventVisibleTo). A burst of >4096 events under one Lock hold
therefore deadlocked the node manager -- FolderEventFloodWireTests stalled at
exactly 4097 events with enforcement on AND off (so it predates #826).
ReportConditionEvent now goes through ReportEventWithoutBlocking:
ReportEventAsync completes inline while channels have room (unchanged normal
path); on overflow the report continues asynchronously holding no thread or
lock, and later reports queue behind it so events keep report order. The
deferred work holds only frozen snapshots and drains once Lock is released;
client delivery stays bounded by each item's queue.
#838(b): documented in docs/security.md that Part 3 ReceiveEvents applies to
the event's EventType and SourceNode (the SDK check, kept first), not to the
notifier; our decision is layered on top and non-condition events on a folder
item fail closed under enforcement. The reflection item stays open.
#844: a success cleared the whole per-client count, so a client holding a valid
key could make four guesses at another key id, sign in with its own, and repeat
forever. Failures are now charged to the (client, credential identity) pair --
IOpcUaUserAuthenticator.DescribeCredential, key:<keyId> for API keys -- and to
the client as a whole. A success clears only its own identity's count; the
per-identity threshold locks that identity; a new per-client cap
(OpcUa:CredentialLockout:MaxFailedAttemptsPerClient, default 2 x
MaxFailedAttempts) that a success never resets bounds spraying across key ids
and locks every credential. Slots are bounded on both counts; a waiter whose
identity has room is not held behind one whose identity has none.
#845: (1) store timeouts, miss-budget refusals, store/authenticator exceptions,
an unset pepper and cancellation are reported Transient
(OpcUaUserAuthResult.Unavailable) and released uncounted, so a ConfigDb stall
can no longer lock every keyed client out; the client still sees the same
opaque denial. (2) a full 4096-entry table defers its next prune until the
earliest entry could age out instead of rescanning under the lock per failure.
(3) ApplicationUri deliberately NOT added to the key: on a None channel it is a
free string, so it would let an attacker reset the count per guess --
documented. (4) wire tests: distinct client certificates on a Sign endpoint are
locked out separately; the ApplicationConfigPath branch keeps the SDK lockout
off (falsified by removing the loaded-branch disable).
A legitimate consumer opening several keyed sessions at once from one key
(e.g. a ScadaBridge site node behind one NAT IP on a None endpoint) must
never see BadUserAccessDenied for parallelism. BeginAsync now hands out at
most MaxFailedAttempts - recordedFailures verification slots per key;
further activations queue FIFO and are woken as slots free. A waiter is
refused only when the key locks out (never reaching the authenticator) or,
uncounted, after OpcUa:CredentialLockout:SlotWaitSeconds (default 10,
BadTimeout). Cancelled waiters are dequeued; pruning accounts for waiters.
The security property is unchanged: no more than MaxFailedAttempts
unverified guesses in progress-or-failed per window.
1. Orphaned subscriptions (session closed without deleting subs) have Session == null, so the public
MonitoredNode2.InvalidatePermissionCacheForSession never reached their items: a cached allow survived a
deploy, the moved alarm's events were queued and delivered on TransferSubscriptions. Each notifier's
cache is now cleared whole through the SDK's private MonitoredNode2.InvalidatePermissionCaches
(reflection, guard-tested; fallback = per-session drop + Remove/Add of session-less items).
2. The verdict is decided on the condition LIVE under the event's NodeId, not the event's own instance:
the SDK key has no instance identity, so a replaced instance's late event cached a deny its successor
inherited until the next invalidation.
3. Invalidation is skipped while enforcement is off (forced across an on/off authorizer transition) and is
one O(cache) clear per node instead of a whole-cache scan per item.
4. TagReferencingEquipment carries alarm-bearing raw tags only (TagConfigIntent.Alarm); the snapshot adopts
an OrdinalIgnoreCase set instead of copying it again.
Tests (each fails with its fix reverted): FolderEventVerdictInvalidationTests (orphan + deploy + transfer;
replaced instance's late event; ACL-off skip; SDK private-method guard), DeploymentArtifactScopePathTests
(alarm-bearing projection).
Event items on an equipment / raw device folder were fed by the SDK's MonitoredNode2 fan-out with no ACL
decision, so after a deploy moved a scripted alarm (or dropped the reference projecting a native alarm into
an equipment) the OLD folder's subscribers kept receiving it - EventId included - until the rebuild landed,
indefinitely after a failed apply.
- OtOpcUaNodeManager re-implements INodeManager3 so ValidateEventRolePermissions (the SDK's per-event,
per-item hook; base not virtual) adds IsNotifierEventVisibleTo: live condition instance, notifier still a
legitimate notifier of it, and the #586/#808 Server-object rule (IsConditionVisibleTo over
ConditionVisibilityScopes).
- The SDK memoizes that verdict per (item, event type, SourceNode): InvalidateFolderEventVerdicts runs on the
authority/authorizer setters, RevalidateMonitoredItems (deploy + timer) and CompleteAddressSpaceApply.
- ConditionRefresh on direct items goes through RefreshDirectItems (base loop + the same decision).
- New generation field TagReferencingEquipment (RawPath -> EquipmentIds, from the artifact's
UnsTagReferences via AclScopePathResolver.ResolveTagRawPath): a native alarm's wired equipment folder only
counts (folder delivery AND Server-object scopes) while the current generation still references it.
- Secondary #808 edge: UNS variables wired UNS->Raw Organizes by AddReference are tracked and always placed
as reference variables (an Area named like its equipment's id no longer narrows them).
Tests: UnsFolderScopeWireTests (moved alarm on a folder item + ConditionRefresh + rebuild; area named like
equipment id), NativeAlarmFolderEventAclWireTests (dropped reference: folder + Server object + refresh +
restore), DeploymentArtifactScopePathTests (projection). Rig/event tests now supply tag references.
#820: SqlServer + QuestDB now serve Part 13 DurationGood / DurationBad from the
same Good / Bad region totals TimeWeightedAggregator already computes for
PercentGood / PercentBad — reported in milliseconds (OPC UA Duration, the SDK's
unit), Uncertain time in neither (Mantis 0006166), same BadNoData / status /
Partial rules. AggregateFamilies.Served grows 17 -> 19, so i=11201 and the
up-front refusal follow automatically; Gateway still refuses both (explicit
served set, unchanged). Client.Shared AggregateType / mapper / CLI gain both.
The #796 oracle answers DurationGood through the Good-only subclass as well.
QualityMix conformance asserts both directly (Q and QP, hand values, ms, and
= PercentGood x interval), replaces the "refused up front" test, and adds
Duration* to the forward/reverse/truncated oracle comparisons.
#821 (facts only, no decision): SdkAggregateParityTests pins an Uncertain-first
late-start interval (QP over [0,20), both directions) against ours (Part 13
Total 163.96, TimeAverage 10.93), the frozen 1.5.378.182 calculators (188.96,
9.448), SDK 2.0.1's stock calculators (188.96, 9.448) and a Good-first control
(all 163.96); LiveAggregateLateStartFactsTests pins the same through the booted
server's runtime AggregateManager (live AggregateFilter) incl. DurationGood
15000 / PercentGood 75 there vs 8000 / 40 in HistoryRead (#809). QualityMix
adds the reverse late-start variant (reverse TW pin + reverse oracle windows).
Co-Authored-By: Claude <noreply@anthropic.com>
OPC Foundation SDK 2.0.1's SessionManager lockout refused EVERY
activation (Anonymous included, before the token is read) from a client
with 5 failed identity validations in 60 s, for 5 minutes, keyed on cert
thumbprint else peer IP. Disable it (MaxFailedAuthenticationAttempts=0
on built and loaded configs) and enforce FailedCredentialLockout in the
identity-registry adapter instead: UserName activations only, keyed on
thumbprint+peer together, same 5/60s/300s defaults, configurable via
OpcUa:CredentialLockout.
Review of af5c9744:
1. UNS reference variables (s=Area/Line/Equip/Eff) of a moved or renamed
equipment stayed readable/writable under the OLD names' grants: they now
resolve as ReferenceVariable and are authorized at their split path only
while it equals their live equipment folder's placement (live chain ==
generation chain) + one name; otherwise denied (Read and Write).
2. TryPlaceScriptedCondition now also requires the owner folder's live chain
to match the generation (AuthorizeScriptedCondition gains ownerFolderChain),
so a moved equipment's alarm/children/commands follow its folder.
3. Identifiers containing NUL are denied before the decision cache, keeping
client ids disjoint from the NUL-prefixed resolved-scope keys (a client
could otherwise poison a real folder's cached verdict for its key shard).
4. An id no live node holds is Unknown: placed at [\0unknown] so only
Cluster / Namespace-uns grants decide it (a removed opaque id can no longer
split onto a same-named narrow grant; narrow grantees get no NodeDeleted for
removed UNS folders/vtags/conditions — documented); 4-segment
reference-shaped ids keep their split.
5. A wire test drives placements from DeploymentArtifact.ParseDataPlaneAuthority.
Baseline updates: #797 owner tests (unit + wire) and Sdk2RepeatedAlarmAuthority
now install folder scopes; Sdk2HistoryAuthority's UNS alias used the RAW path
as its UNS id (never minted in production) and now carries EqA/HistoryAlias.
Each new guard was falsified (reverting it fails its test).
UNS Area/Line/Equipment folders are minted under their opaque entity ids
(s=UA-/UL-/EQ-...), virtual tags under s=EQ-.../Name and scripted conditions
(+ #629 children) under s=<ScriptedAlarmId>[/...], while every UNS grant is
planted at a NAME path. DataPlaneAuthorizer split those ids, so with
Security:Acl:Enabled a narrow (Area/Line/Equipment) grant could not Browse,
Read, subscribe or HistoryRead them, and Server-object delivery never reached
it — so a narrow key never held the EventId Ack/Confirm/AddComment need.
- The generation carries UnsFolderScopes (folderId -> path + id chain), built
by DeploymentArtifact from the same AclScopePathResolver as the grants; ids
two entity kinds share are dropped; plumbed through IDataPlaneAuthoritySink.
- OtOpcUaNodeManager.ResolveUnsAclSubject reports live facts (folder id
ancestry / scripted owner binding); attached by the Authorizer setter.
- Evaluate places the subject against the CURRENT generation before the
decision cache, which now caches the walk keyed on the resolved scope.
Folders require live chain == generation chain (a moved equipment is denied
under old and new line until the rebuild). Owned nodes (vtags, conditions,
children) get owner path + a reserved segment, so Tag grants and their
Browse transit never expose them. Conditions share TryPlaceScriptedCondition
with the #797 command gate.
- Server-object visibility of a scripted condition is decided on the
condition alone, so a moved alarm cannot reach its old owner there.
Tests: UnsFolderScopeWireTests (opaque ids, end-to-end browse -> EventId ->
Acknowledge on an Equipment grant; sibling denied; Tag-only grant; moved alarm
and moved equipment stale windows). Rig tests now install folder scopes
explicitly (ServerEventRig.FolderScopes); the #797 recreate test deliberately
asserts the moved alarm is invisible to the Cluster observer in the window.
Review of 3d1b86b4: OpcUaPublishActor installs a new authority generation
before applying its address space, and an apply that throws keeps the old one.
A scripted alarm moved from equipment A to B therefore stayed commandable with
A's grant under B's generation (briefly before the rebuild, or indefinitely
after a failed apply).
The generation now carries ScriptedAlarmOwners (ScriptedAlarmId -> EquipmentId,
decoded by ParseDataPlaneAuthority from the artifact's ScriptedAlarms rows, the
same rows the composition materialises from). AuthorizeScriptedCondition denies
unless the node manager's live binding names the same owner as the generation:
a moved alarm is denied under the old owner's, the new owner's and a Cluster
grant until the address space re-binds it; an alarm the generation no longer
deploys is denied. Install/apply order unchanged.
Tests: window (a) generation moved / binding stale => both owners and Cluster
denied, then rebuild under the new owner => new owner allowed, old denied;
window (b) apply failed after install => denied across clock and further
generations, then a successful rebuild restores the new owner only; undeployed
alarm denied; artifact decode of the owner map.
Scripted condition NodeIds are opaque ScriptedAlarmIds, so splitting them as a
topology path could never match an Equipment grant: a narrow equipment grant was
denied while a Cluster grant passed.
- OtOpcUaNodeManager binds each LIVE scripted condition instance to the
EquipmentId it was materialised under (only when it hangs under that folder);
dropped on remove / drop-recreate / equipment-subtree removal / rebuild; a
same-id re-materialise under another equipment re-parents and re-binds.
- DataPlaneAuthoritySnapshot carries EquipmentScopePaths (EquipmentId ->
[uns, Area, Line, Equipment]) decoded from the artifact by the same
AclScopePathResolver call that plants Equipment grants.
- DataPlaneAuthorizer.AuthorizeScriptedCondition re-reads key, grant and
generation per call (uncached) and evaluates at the owner path; unbound,
replaced or unplaceable owners deny under every grant. No id-split or
realm-root fallback.
- Native conditions (RawPath) and the ACL-off role gate are unchanged.
NodeIds and AlarmCommand.AlarmId are unchanged.
Sdk2OpaqueScriptedScopeBaselineTests deliberately flipped: it pinned the denial
and now pins owner-grant allow / sibling deny / cluster allow. Follow-up #808
(folder ids + Server-object event visibility for narrow UNS grants).
- NodeManagerLockTimeBenchmark: wall-clock budget enforced only with OTOPCUA_BENCH=1; default run keeps the state-correctness asserts and logs timings.
- OpcUaClientDriverWire host-status: signal (semaphore) wait that only accepts a non-Running state observed after the server is disposed.
- AbCip PollLatencyComparison: retry once on a fixture connection reset; p95 criterion enforced only with AB_LAT_ENFORCE=1.
- ScriptRunGuardTests: orphan scripts held by a ctx.Released signal instead of a 250 ms wall-clock spin that could finish inside the 60 ms budget under load; stuck-orphan wall-clock rule disabled in the tests that pin the strike counting.
- DependencyMuxReplayTests: split the inside-grace positive control (1 h grace) from the release test (control asserted before unregister), removing the 200 ms grace race.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
Revises 963b0d66, which dropped a disabled VirtualTag from the runtime plan so a
bound client got BadNodeIdUnknown. Now the plan carries Enabled (part of value
equality): AddressSpaceComposer.Compose and DeploymentArtifact.BuildEquipmentVirtualTagPlans
keep the row with Enabled=false (byte-parity), the applier materialises the node as
normal, and VirtualTagHostActor spawns no VirtualTagActor for it but publishes
BadOutOfService (new OpcUaStatus constant) with a null value stamped at deploy, on
every apply. Enabled flips are node-irrelevant to the change classifier; enabled->disabled
stops the child, disabled->enabled resumes evaluation. Validator exemption and name
uniqueness unchanged. Scripted alarms keep their not-materialised convention.
Tests updated; new wire test DisabledVirtualTagWireTests. docs/VirtualTags.md updated.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
Behaviour-neutral hop: pin the SDK AggregateManager default to our
TreatUncertainAsBad=false (SDK .182 flipped it to true), parity guard now an
explicit deliberate-divergence assertion plus a booted-server check; adapt to
obsolete FindPredefinedNode(Type)/TraceConfiguration; Microsoft.Extensions.
Logging.Abstractions 10.0.7 -> 10.0.8 (SDK floor); stall wire test's late-flush
positive control is best-effort (.176 preserves publish queue ordering).
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
The 1500 ms pre-control and 500 ms trailing sleeps are gone. ConditionRefresh
completes server-side before SubscribeAlarmsAsync returns, so refresh events
queue ahead of the control Acknowledge; a trailing message-change barrier event
is projected and awaited (bounded 10 s poll) so any stray event must arrive
before it. The assertion is now the exact sequence [Acknowledge, Unspecified],
no weaker than before.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
Item 1 of #776 (the B2 over-the-wire ask): Client.CLI had no way to issue a
HistoryReadEvents. `historyread --events` now sends ReadEventDetails to an
event notifier and prints one line per event in select-clause order.
--fields picks the select clauses (default EventId, EventType, Time,
SourceName, Severity, Message, ConditionName (on ConditionType), SourceNode);
--of-type adds an OfType where-clause. --events is exclusive with --modified /
--aggregate, and --fields / --of-type require it.
Client.Shared gains IOpcUaClientService/ISessionAdapter.HistoryReadEventsAsync
(default-implemented as NotSupported for other implementations) backed by the
real session adapter through HistoryReadPaging, so continuation points are
followed up to --max and a Bad node status is surfaced, not printed as empty.
Tests: CLI tests over the fake service (default filter, --fields/--of-type
filter, option conflicts); an over-the-wire test drives the shared client's
event read against the in-process server — the default fields come back
non-null, OfType filters, an invalid where-clause is BadEventFilterInvalid.
The other #776 items are decisions and are left open.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
HistoryReadEvents projected only EventId / SourceName / Time / ReceiveTime /
Message / Severity: a select clause asking for EventType, ConditionName or
SourceNode (what most generic alarm viewers ask for) got nulls, and the
event filter's where-clause (an OfType) was ignored.
- HistoricalEvent gains optional EventTypeName, ConditionName and AlarmId.
SqlServer, QuestDB and Gateway event reads fill them from what their
alarm writers already store (AlarmTypeName / AlarmName / AlarmId; the
gateway event Type and its AlarmName / AlarmId properties).
- The node manager maps the type name to its Part 9 event type (unknown or
non-event => AlarmConditionType), projects ConditionName, and resolves
SourceNode to the materialised condition the alarm id names (the live
events' SourceNode), else null.
- The where-clause is evaluated per event with the SDK content filter
through an IFilterTarget (OfType via the type tree; other operators
against the projected fields), after the page's cursor is taken, so
paging is unchanged.
Tested in the node manager, over a real client session (the Client.CLI has
no `historyread --events` mode yet; filed as a follow-up), and by alarm
writer -> event read round trips on SqlServer and QuestDB.
Rebased from the unpushed remed/lane-H2 branch (originally authored 2026-10-22
in session_01Ub9hGmYLQvn9XETzw7CMsT) onto current master.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
Benchmark wall-clock budget 1 s -> 5 s (measured 5-60 ms; still catches O(N^2)). Host-status wait is already a TCS signal; its 30 s ceiling is raised to 120 s so a starved box cannot time out before the keep-alive reports the loss.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
The #733 miss budget (MissBurst / MissRefillPerSecond) was process-wide, because
the impersonation seam did not carry the client's address, so one noisy client
could drain it for everybody while the known-id set was unavailable.
- IOpcUaUserAuthenticator gains AuthenticateUserNameAsync(username, password,
IPEndPoint? remoteEndpoint, ct) (default: ignore it and delegate); the server
calls it. IApiKeyStore gains the matching FindAsync(..., IPAddress?, ...).
- The SDK (1.5.378) exposes no client address publicly. SecureChannelRemoteEndpoint
reads it from the TCP listener's private channel map by reflection (through the
protected TransportListeners, exposed by OtOpcUaSdkServer), keyed by the
session's secure channel id. Fail-soft: null => process-wide accounting only.
- BoundedApiKeyStore charges a miss to the client's own bucket (keyed by IP
address) and then to the process-wide one, which stays as the backstop. A
refusal by either takes from neither; a hit refunds both. New options
Security:ApiKeys:MissBurstPerEndpoint (10) / MissRefillPerSecondPerEndpoint (2),
0 disables; telemetry outcome endpoint_miss_budget. At most 4096 addresses are
tracked; idle buckets are pruned and an address beyond the cap is charged
process-wide only.
Tests: BoundedApiKeyStorePerEndpointTests (noisy client vs quiet one, process-wide
backstop, refund + refill, off switch, authenticator forwards the address) and
over the wire ApiKeyMissBudgetPerEndpointTests (activation hands the authenticator
the loopback endpoint; real authenticator + bounded store refuse a client's 3rd
and 4th unknown key without a store read). Each new behaviour test fails with its
fix mutated out. Host.Tests 224/0, OpcUaServer.Tests 1019/1 (the one failure is the
wall-clock NodeManagerLockTimeBenchmarkTests under suite load; passes alone).
Docs: security.md.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
AbLegacyDriver stamped LastSuccessfulRead (init, read, write), the read's sample
timestamps and host-state change times from raw DateTime.UtcNow; only the backoff
path read the injectable Clock. All of them now read Clock(), so
NativePcccBridgeStatusHealthTests drives a manual clock (init at T0, read at T1)
and asserts LastSuccessfulRead == T1 exactly instead of spin-waiting for the wall
clock to pass the init stamp (#767). Without the driver change the 6 tests fail
(init stamp is wall-clock, not T0).
Directory.Build.props sets TreatWarningsAsErrors for every project since #766, so
the 75 per-csproj copies (64 src + 11 tests) are removed and the props comment
says it is now the only place. tools/mem-probe keeps its explicit opt-out.
Release build: 0 warnings, 0 errors; a planted CS0168 still fails the build in a
src project and in a test project that used to carry its own copy.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
The native-ack path is fire-and-forget after the Part 9 Acknowledge returns, so
a Galaxy ack refused for lack of a credential (#749), or rejected by MXAccess,
left the client with Good and the condition showing Acknowledged while Galaxy
was never acked. Both options from the issue, layered:
1. Synchronous refusal for what the driver can decide without I/O. New optional
IAlarmAcknowledgePreflight (Core.Abstractions); GalaxyDriver refuses an
anonymous session when the driver has no AlarmAck fallback account.
DriverHostActor publishes a condition NodeId -> owning-driver snapshot into
NativeAlarmAckPreflightView (lock-free, volatile); the node manager's new
NativeAlarmAckPreflight seam, consulted after the authz and Primary gates,
returns BadUserAccessDenied with the reason - nothing routed, applied or
reported. A keyed session is not pre-checked (its identity lives in the
Secrets store, which must not be read under the SDK lock).
2. Revert for everything else. RouteAlarmAck carries the condition NodeId;
DriverInstanceActor replies AlarmAckFailed on a refusal, a backend failure,
a driver without an alarm source, or an ack dropped while connecting /
reconnecting. DriverHostActor re-projects the condition unacknowledged via
NativeAlarmProjector.TryRevertAcknowledge, but only while the local ack is
still pending - any driver transition projected since then wins. A disabled
or unspawned driver is not reverted (unchanged).
GatewayGalaxyAlarmAcknowledger now throws DriverOperationRefusedException on a
non-zero native hresult (wrong password, no ack permission) instead of only
warning, so that case reverts too; as a refusal it neither retries nor trips
the breaker.
Tests (each fails with its fix mutated out): projector revert/supersede,
DriverHostActor refused + failed ack -> unacked AlarmStateUpdate (successful
ack control), preflight view snapshot, node-manager preflight unit test,
over-the-wire ConditionMethodEventTests (BadUserAccessDenied, no route, no
event; positive control), Galaxy preflight + hresult refusal.
Docs: Galaxy.md, AlarmTracking.md, ScriptedAlarms.md, .claude/rules/alarms.md.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV