No read or write loop checked _plcDead between items: on a frozen-but-
established peer the first op blew its deadline and marked the handle dead,
and every remaining span / tag / write still went to the wire and could wait
its own deadline under _gate (a 20-span pass ~100 s), with Degraded and the
comms-loss watchdog's clock deferred until the pass ended.
- The span loop, the multi-var chunk loop, the per-tag loop and the write
loop stamp BadCommunicationError without I/O once _plcDead is set.
- A multi-var chunk that dies on a transport loss (socket / IO / timeout /
ConnectionError) marks the handle dead instead of falling back to one
doomed per-tag read per member. The framing class is deliberately excluded
there: snap7/S7.Net report a multi-var with one refused item as
ReadData(WrongNumberReceivedBytes) over a healthy stream.
- Live gate via an in-test freezable TCP proxy (counts request frames, not
seconds). Mutation shows S7.Net 0.20 already self-closes on a cancelled op,
so the gate pins the end-to-end property; the driver guard itself is proven
by the unit tests (an op that ignores its token keeps the socket open).
Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
A deterministic PLC refusal (object does not exist, address out of range,
type inconsistent...) degraded driver health, and an all-refused driver (a
wrong DB number) sat Degraded with LastSuccessfulRead frozen, so the 90 s
comms-loss watchdog reconnected it forever against a reachable PLC.
- IsRefusal / IsAccessDenied classify over the whole exception chain. Live
probe on the snap7 fixture: S7.Net's READ paths raise the item error as a
BARE Exception ("Received error from PLC: ..."), its write paths as
PlcException(WriteData). The old PlcException-only match missed the read
shape entirely, so a real read access-denied was BadCommunicationError +
Degraded instead of the Faulted PUT/GET alert; the Test Connect probe had
the same blind spot.
- A refusal (read or write) is BadDeviceFailure with a once-per-tag Warning,
no health write and no reopen; it counts as answered, so it advances
LastSuccessfulRead and restores Healthy after a comms fault. An undecodable
buffer (S7ValueRangeException) also counts as answered.
- A write batch the CPU answered without a failure advances
LastSuccessfulRead and retires a Degraded the write side itself published.
- Tests that used ReadData as their generic "device fault" now use SendData
so their Degraded leg is still exercised.
Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The init-time tag guards THREW: one mis-authored tag (DB1.DBZ0, DB1.DBW0 typed
Float64, T5 typed Int32, a writable Bool array) faulted the whole driver and the
actor retried the same init every 10 s forever, darkening every tag on the PLC.
Neither the editor nor the deploy gate checked any of it.
- S7AddressParser moves to S7.Contracts (same namespace) and a new
S7TagShapeRules there is the single authority on servable shapes.
- S7TagDefinitionFactory.FromTagConfig applies it, so the AdminUI editor, the
deploy gate (Inspect, with the specific reason) and the driver init refuse
the same tags. Init now skips a refused tag (ISkippedTagReporter) instead of
throwing; the throwing RejectUnsupportedTagConfigs is gone.
- New rules on top of the old guards: a narrow type at the wrong access width
(every read failed) and a Bool array not starting at bit 0 (U4: DB1.DBX0.3
silently read bit 0 of bytes 0..n).
- AdminUI test fixtures that used addresses the driver could never serve
(DB1.DBS0, a browse "SomeAddress", Int32/Float32 on DBW) now use real ones.
Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
New S7DataType members WString/Char/WChar/Dtl/Date/Tod/Time/S5Time mapped onto existing
DriverDataType (String / DateTime / Int32 ms); writes refuse out-of-range with BadOutOfRange.
Optional localTsap/remoteTsap/connectionType through options, factory JSON, probe and AdminUI form.
NegotiatedPduSize snapshotted at connect and exposed via GetDiagnostics (DriverHealth has no bag).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Array nodes were forced read-only for every driver. A new single authority,
Core.Abstractions DriverArrayWriteSupport, says which (driver, element type)
pairs encode a whole-array write: Modbus (Coils / numeric HoldingRegisters),
S7 (Byte/Int16/UInt16/Int32/UInt32/Float32), OpcUaClient (pass-through) and
Galaxy (Boolean/Int32/Int64/Float/Double/String/DateTime). Everything else
stays read-only, so the server never advertises a write the driver refuses.
- Composer derives RawTagPlan.ArrayWritable + UnsReferenceVariable
.BackingArrayWritable at compose time (both seams, byte-parity); the
applier's one writability rule is Writable && (!IsArray || ArrayWritable)
for materialise and surgical paths, raw and UNS alike.
- ArrayWritable is on the classifier's surgical raw-tag whitelist and
mirrored on the UNS record (UnsReferenceBackingParityTests updated).
- Node manager refuses a wrong-length / non-array value on an array node
(BadTypeMismatch) and any IndexRange write (BadWriteNotSupported) inline,
before dispatch; WriteOperate/ACL gates and the revert are unchanged.
- Per-driver parity tests pin the table against the real Modbus write path,
S7 EncodeArrayBlock and Galaxy MxValueEncoder (UInt32/UInt64 excluded:
array covariance reinterprets their bits).
- Over-the-wire proof in OpcUaServer.IntegrationTests (ArrayWriteWireTests).
- ValueRank > 1 documented as out of scope by decision (docs/Uns.md).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- Galaxy: deadline bounds the wait, not the subscribe RPC; BadTimeout for all tags and late handles unsubscribed; doc comment relocated
- S7: probe connect runs on the connect deadline so a timeout opens the backoff window
- S7: a successful write only retires a Faulted the write side owns
- S7: null array elements rejected (BadTypeMismatch); multi-PDU array writes documented non-atomic
- S7 integration: array write test gated on S7_SIM_ALLOW_WRITES=1
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
STAB-21 ConnectionBackoff in EnsureConnectedAsync; STAB-22 write-pass accumulator with a
write-side Faulted that a clean read does not erase; _health on the Volatile idiom;
S7-016 contiguous array write (Bool arrays stay refused).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Drop the "not yet implemented / BadNotSupported" stale note from all three
S7 CLI --type option descriptions (ReadCommand, WriteCommand, SubscribeCommand)
and replace with accurate help listing the full supported type set, byte-anchored
addressing for wide types, and Timer/Counter read-only status.
docs/v2/driver-specs.md §5: add Supported Data Types table, Byte-Anchored
Addressing table (DBB/MB/IB/QB + examples), Timer/Counter read section with
the Counter-BCD known-limitation, and Deferrals list.
docs/drivers/S7.md: expand Data types to a full table, add "Wide types &
Timer/Counter" section (byte-anchored addressing, Timer/Counter read-only,
Counter BCD known-limitation, deferrals), update Address forms table and
1-D array Deferrals note.