- The background probe reported the host Stopped whenever a read pass held
_gate past the probe deadline: contention is the connection being used,
not lost. A contended tick now gives no verdict (counted for tests); a
real probe failure still reports Stopped. A tick that races a teardown no
longer reopens a connection on an uninitialised driver.
- S7DriverProbe deserialised S7DriverOptions directly, whose Timeout is a
TimeSpan no config names, so "timeoutMs" was ignored and every handshake
waited the whole Test Connect budget. The handshake and test read are now
bounded by timeoutMs, capped by the caller's timeout.
Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
A span's block is the union of its members' ranges, so one member that runs
past the DB's real end (or over-declares a STRING) made the CPU refuse the
whole block, and every neighbour within it was Bad on every poll. The
planner's stated invariant (a grouped read cannot fault where per-tag reads
would succeed) was false; the multi-var path already fell back, spans did not.
- A refused multi-member span hands its members back; they are read one at a
time for that pass, bypassing the multi-var pass.
- _noGroup remembers the members refused on their own (or every member when
none was) and keeps them out of later plans, so the rest group again. It is
cleared by every initialize publish. Non-refusal span failures are
unchanged (every member stamped).
- The once-per-tag refusal Warning memo (R07:H4) is now also cleared by the
publish, and shutdown resets the write-side Degraded owner, as documented.
- Live gate: MW10 + MD254 (2 bytes past the 256-byte M area) merged into one
refused block; MW10 keeps reading 4097 on every pass.
Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
No read or write loop checked _plcDead between items: on a frozen-but-
established peer the first op blew its deadline and marked the handle dead,
and every remaining span / tag / write still went to the wire and could wait
its own deadline under _gate (a 20-span pass ~100 s), with Degraded and the
comms-loss watchdog's clock deferred until the pass ended.
- The span loop, the multi-var chunk loop, the per-tag loop and the write
loop stamp BadCommunicationError without I/O once _plcDead is set.
- A multi-var chunk that dies on a transport loss (socket / IO / timeout /
ConnectionError) marks the handle dead instead of falling back to one
doomed per-tag read per member. The framing class is deliberately excluded
there: snap7/S7.Net report a multi-var with one refused item as
ReadData(WrongNumberReceivedBytes) over a healthy stream.
- Live gate via an in-test freezable TCP proxy (counts request frames, not
seconds). Mutation shows S7.Net 0.20 already self-closes on a cancelled op,
so the gate pins the end-to-end property; the driver guard itself is proven
by the unit tests (an op that ignores its token keeps the socket open).
Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
A deterministic PLC refusal (object does not exist, address out of range,
type inconsistent...) degraded driver health, and an all-refused driver (a
wrong DB number) sat Degraded with LastSuccessfulRead frozen, so the 90 s
comms-loss watchdog reconnected it forever against a reachable PLC.
- IsRefusal / IsAccessDenied classify over the whole exception chain. Live
probe on the snap7 fixture: S7.Net's READ paths raise the item error as a
BARE Exception ("Received error from PLC: ..."), its write paths as
PlcException(WriteData). The old PlcException-only match missed the read
shape entirely, so a real read access-denied was BadCommunicationError +
Degraded instead of the Faulted PUT/GET alert; the Test Connect probe had
the same blind spot.
- A refusal (read or write) is BadDeviceFailure with a once-per-tag Warning,
no health write and no reopen; it counts as answered, so it advances
LastSuccessfulRead and restores Healthy after a comms fault. An undecodable
buffer (S7ValueRangeException) also counts as answered.
- A write batch the CPU answered without a failure advances
LastSuccessfulRead and retires a Degraded the write side itself published.
- Tests that used ReadData as their generic "device fault" now use SendData
so their Degraded leg is still exercised.
Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The init-time tag guards THREW: one mis-authored tag (DB1.DBZ0, DB1.DBW0 typed
Float64, T5 typed Int32, a writable Bool array) faulted the whole driver and the
actor retried the same init every 10 s forever, darkening every tag on the PLC.
Neither the editor nor the deploy gate checked any of it.
- S7AddressParser moves to S7.Contracts (same namespace) and a new
S7TagShapeRules there is the single authority on servable shapes.
- S7TagDefinitionFactory.FromTagConfig applies it, so the AdminUI editor, the
deploy gate (Inspect, with the specific reason) and the driver init refuse
the same tags. Init now skips a refused tag (ISkippedTagReporter) instead of
throwing; the throwing RejectUnsupportedTagConfigs is gone.
- New rules on top of the old guards: a narrow type at the wrong access width
(every read failed) and a Bool array not starting at bit 0 (U4: DB1.DBX0.3
silently read bit 0 of bytes 0..n).
- AdminUI test fixtures that used addresses the driver could never serve
(DB1.DBS0, a browse "SomeAddress", Int32/Float32 on DBW) now use real ones.
Refs #742
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
New S7DataType members WString/Char/WChar/Dtl/Date/Tod/Time/S5Time mapped onto existing
DriverDataType (String / DateTime / Int32 ms); writes refuse out-of-range with BadOutOfRange.
Optional localTsap/remoteTsap/connectionType through options, factory JSON, probe and AdminUI form.
NegotiatedPduSize snapshotted at connect and exposed via GetDiagnostics (DriverHealth has no bag).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Array nodes were forced read-only for every driver. A new single authority,
Core.Abstractions DriverArrayWriteSupport, says which (driver, element type)
pairs encode a whole-array write: Modbus (Coils / numeric HoldingRegisters),
S7 (Byte/Int16/UInt16/Int32/UInt32/Float32), OpcUaClient (pass-through) and
Galaxy (Boolean/Int32/Int64/Float/Double/String/DateTime). Everything else
stays read-only, so the server never advertises a write the driver refuses.
- Composer derives RawTagPlan.ArrayWritable + UnsReferenceVariable
.BackingArrayWritable at compose time (both seams, byte-parity); the
applier's one writability rule is Writable && (!IsArray || ArrayWritable)
for materialise and surgical paths, raw and UNS alike.
- ArrayWritable is on the classifier's surgical raw-tag whitelist and
mirrored on the UNS record (UnsReferenceBackingParityTests updated).
- Node manager refuses a wrong-length / non-array value on an array node
(BadTypeMismatch) and any IndexRange write (BadWriteNotSupported) inline,
before dispatch; WriteOperate/ACL gates and the revert are unchanged.
- Per-driver parity tests pin the table against the real Modbus write path,
S7 EncodeArrayBlock and Galaxy MxValueEncoder (UInt32/UInt64 excluded:
array covariance reinterprets their bits).
- Over-the-wire proof in OpcUaServer.IntegrationTests (ArrayWriteWireTests).
- ValueRank > 1 documented as out of scope by decision (docs/Uns.md).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
- Galaxy: deadline bounds the wait, not the subscribe RPC; BadTimeout for all tags and late handles unsubscribed; doc comment relocated
- S7: probe connect runs on the connect deadline so a timeout opens the backoff window
- S7: a successful write only retires a Faulted the write side owns
- S7: null array elements rejected (BadTypeMismatch); multi-PDU array writes documented non-atomic
- S7 integration: array write test gated on S7_SIM_ALLOW_WRITES=1
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
STAB-21 ConnectionBackoff in EnsureConnectedAsync; STAB-22 write-pass accumulator with a
write-side Faulted that a clean read does not erase; _health on the Volatile idiom;
S7-016 contiguous array write (Bool arrays stay refused).
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Drop the "not yet implemented / BadNotSupported" stale note from all three
S7 CLI --type option descriptions (ReadCommand, WriteCommand, SubscribeCommand)
and replace with accurate help listing the full supported type set, byte-anchored
addressing for wide types, and Timer/Counter read-only status.
docs/v2/driver-specs.md §5: add Supported Data Types table, Byte-Anchored
Addressing table (DBB/MB/IB/QB + examples), Timer/Counter read section with
the Counter-BCD known-limitation, and Deferrals list.
docs/drivers/S7.md: expand Data types to a full table, add "Wide types &
Timer/Counter" section (byte-anchored addressing, Timer/Counter read-only,
Counter BCD known-limitation, deferrals), update Address forms table and
1-D array Deferrals note.