Default Branch

bc282b6788 · Add Galaxy platform scope filter so multi-node deployments can restrict the OPC UA address space to only objects hosted by the local platform, reducing memory footprint and MXAccess subscription count from the full Galaxy (49 objects / 4206 attributes) down to the local subtree (3 objects / 386 attributes on the dev Galaxy). · Updated 2026-04-16 00:39:11 -04:00

Branches

d8ef35d5bd · Phase 3 PR 65 -- S7 ITagDiscovery + ISubscribable polling overlay + IHostConnectivityProbe. Three more capability interfaces on S7Driver, matching the Modbus driver's capability coverage. ITagDiscovery: DiscoverAsync streams every configured tag into IAddressSpaceBuilder under a single 'S7' folder; builder.Variable gets a DriverAttributeInfo carrying DriverDataType (MapDataType: Bool->Boolean, Byte/Int/UInt sizes->Int32 (until Core.Abstractions adds widths), Float32/Float64 direct, String + DateTime direct), SecurityClass (Operate if tag.Writable else ViewOnly -- matches the Modbus pattern so DriverNodeManager's ACL layer can gate writes per role without S7-specific logic), IsHistorized=false (S7 has no native historian surface), IsAlarm=false (S7 alarms land through TIA Portal's alarm-in-DB pattern which is per-site and out of scope for PR 65). ISubscribable polling overlay: same pattern Modbus established in PR 22. SubscribeAsync spawns a Task.Run loop that polls every tag, diffs against LastValues, raises OnDataChange on changes plus a force-raise on initial-data push per OPC UA Part 4 convention. Interval floored at 100ms -- S7 CPUs scan 2-10ms but process the comms mailbox at most once per scan, so sub-scan polling just queues wire-side with worse latency per S7netplus documented pattern. Poll errors tolerated: first-read fault doesn't kill the loop (caller can't receive initial values but subsequent polls try again); transient poll errors also swallowed so the loop survives a power-cycle + reconnect through the health surface. UnsubscribeAsync cancels the CTS + removes the subscription -- unknown handle is a no-op, not a throw, because the caller's race with server-side cleanup shouldn't crash either side. Shutdown tears down every subscription before disposing the Plc. IHostConnectivityProbe: HostName surfaced as host:port to match Modbus driver convention (Admin /hosts dashboard renders both families uniformly). GetHostStatuses returns one row (single-endpoint driver). ProbeLoopAsync serializes on the shared Gate + calls Plc.ReadStatusAsync (cheap Get-CPU-Status PDU that doubles as an 'is PLC up' check) every Probe.Interval with a Probe.Timeout cap, transitions HostState Unknown/Stopped -> Running on success and -> Stopped on any failure, raises OnHostStatusChanged only on actual transitions (no noise for steady-state probes). Probe loop starts at end of InitializeAsync when Probe.Enabled=true (default); Shutdown cancels the probe CTS. Initial state stays Unknown until first successful probe -- avoids broadcasting a premature Running before any PDU round-trip has happened. Unit tests (S7DiscoveryAndSubscribeTests, 4 facts): DiscoverAsync_projects_every_tag_into_the_address_space (3 tags + mixed writable/read-only -> Operate vs ViewOnly asserted), GetHostStatuses_returns_one_row_with_host_port_identity_pre_init, SubscribeAsync_returns_unique_handles_and_UnsubscribeAsync_accepts_them (diagnosticId uniqueness + idempotent double-unsubscribe), Subscribe_publishing_interval_is_floored_at_100ms (accepts 50ms request without throwing -- floor is applied internally). Uses a RecordingAddressSpaceBuilder stub that implements IVariableHandle.FullReference + MarkAsAlarmCondition (throws NotImplementedException since the S7 driver never calls it -- alarms out of scope). 57/57 S7 unit tests pass. dotnet build clean. All 5 capability interfaces (IDriver/ITagDiscovery/IReadable/IWritable/ISubscribable/IHostConnectivityProbe) now implemented -- the S7 driver surface is on par with the Modbus driver, minus the extended data types (Int64/UInt64/Float64/String/DateTime deferred per PR 64). · Updated 2026-04-19 00:16:10 -04:00    dohertj2

0
148
#64 Merged

394d126b2e · Phase 3 PR 64 -- S7 IReadable + IWritable via S7.Net string-based Plc.ReadAsync/WriteAsync. Adds IReadable + IWritable capability interfaces to S7Driver, routing reads/writes through S7netplus's string-address API (Plc.ReadAsync(string, ct) / Plc.WriteAsync(string, object, ct)). All operations serialize on the class's SemaphoreSlim Gate because S7netplus mandates one Plc connection per PLC with client-side serialization -- parallel reads against a single S7 CPU queue wire-side anyway and just eat connection-resource budget. Supported data types in this PR: Bool, Byte, Int16, UInt16, Int32, UInt32, Float32. S7.Net's string-based read returns UNSIGNED boxed values (DBX=bool, DBB=byte, DBW=ushort, DBD=uint); the driver reinterprets them into the requested S7DataType via the (DataType, Size, raw) switch: unchecked short-cast for Int16, unchecked int-cast for Int32, BitConverter.UInt32BitsToSingle for Float32. Writes inverse the conversion -- Int16 -> unchecked ushort cast, Int32 -> unchecked uint cast, Float32 -> BitConverter.SingleToUInt32Bits -- before handing to S7.Net's WriteAsync. This avoids a second PLC round-trip that a typed ReadAsync(DataType, db, offset, VarType, ...) overload would need. Int64, UInt64, Float64, String, DateTime throw NotSupportedException (-> BadNotSupported StatusCode); S7 STRING has non-trivial header semantics + LReal/DateTime need typed S7.Net API paths, both land in a follow-up PR when scope demands. InitializeAsync now parses every tag's Address string via S7AddressParser at init time. Bad addresses throw FormatException and flip health to Faulted -- callers can't register a broken driver. The parsed form goes into _parsedByName so Read/Write can consult Size/BitOffset without re-parsing per operation. StatusCode mapping in catch chain: unknown tag name -> BadNodeIdUnknown (0x80340000), unsupported data type -> BadNotSupported (0x803D0000), read-only tag write attempt -> BadNotWritable (0x803B0000), S7.Net PlcException (carries PUT/GET-disabled signal on S7-1200/1500) -> BadDeviceFailure (0x80550000) so operators see a TIA-Portal config problem rather than a transient-fault false flag per driver-specs.md \u00A75, any other runtime exception on read -> BadCommunicationError (0x80050000) to distinguish socket/timeout from tag-level faults. Write generic-exception path stays BadInternalError because write failures can legitimately be driver-side value-range problems. Unit tests (S7DriverReadWriteTests, 3 facts): Initialize_rejects_invalid_tag_address_and_fails_fast -- Tags with a malformed address must throw at InitializeAsync rather than producing a half-healthy driver; ReadAsync_without_initialize_throws_InvalidOperationException + WriteAsync_without_initialize_throws_InvalidOperationException -- pre-init calls hit RequirePlc and throw the uniform 'not initialized' message. Wire-level round-trip coverage (integration test against a live S7-1500 or a mock S7 server) is deferred -- S7.Net doesn't ship an in-process fake and a conformant mock is non-trivial. 53/53 Modbus.Driver.S7.Tests pass (50 parser + 3 read/write). dotnet build clean. · Updated 2026-04-19 00:10:41 -04:00    dohertj2

0
145
#63 Merged

d5034c40f7 · Phase 3 PR 63 -- S7AddressParser for DB/M/I/Q/T/C address strings. Adds S7AddressParser + S7ParsedAddress + S7Area + S7Size to the Driver.S7 project. Grammar follows driver-specs.md \u00A75 + Siemens TIA Portal / STEP 7 Classic convention: (1) Data blocks: DB{n}.DB{X|B|W|D}{offset}[.bit] where X=bit (requires .bit suffix 0-7), B=byte, W=word (16-bit), D=dword (32-bit). (2) Merkers: MB{n}, MW{n}, MD{n}, or M{n}.{bit} for bit access. (3) Inputs + Outputs: same {B|W|D} prefix or {n}.{bit} pattern as M. (4) Timers: T{n}. (5) Counters: C{n}. Output is an immutable S7ParsedAddress record struct with Area (DataBlock / Memory / Input / Output / Timer / Counter), DbNumber (only meaningful for DataBlock), Size (Bit / Byte / Word / DWord), ByteOffset (also timer/counter number when Area is Timer/Counter), BitOffset (0-7 for Size=Bit; 0 otherwise). Case-insensitive via ToUpperInvariant, whitespace trimmed on entry. Parse throws FormatException with the offending input echoed in the message; TryParse returns bool for config-validation callers that can't afford exceptions (e.g. Admin UI tag-editor live validation). Strict rejection policy -- 16 garbage cases covered in the theory test: empty/whitespace input, unknown area letter (Z0), DB without number/tail, DB bit size without .bit suffix, bit offset 8+, word/dword with .bit suffix, DB number 0 (must be >=1), non-numeric DB number, unknown size letter (Q), M without offset, M bit access without .bit, bit 8, negative offset, non-digit offset, non-numeric timer. Strict rejection surfaces config errors at driver-init time rather than as BadInternalError on every Read against the bad tag. No driver code wires through yet -- PR 64 is where IReadable/IWritable consume S7ParsedAddress and translate into S7netplus Plc.ReadAsync calls (the S7.Net address grammar is a strict subset of what we accept, and the parser's S7ParsedAddress is the bridge). Unit tests (S7AddressParserTests, 50 facts): parse-valid theories for DB/M/I/Q/T/C covering all size variants + edge bit offsets 0 and 7; case-insensitive + whitespace-trim theory; reject-invalid theory with 16 garbage cases; TryParse round-trip for valid and invalid inputs. 50/50 pass, dotnet build clean. · Updated 2026-04-19 00:06:24 -04:00    dohertj2

0
144
#62 Merged

0575280a3b · Phase 3 PR 62 -- Siemens S7 native driver project scaffold (S7comm via S7netplus). First non-Modbus in-process driver. Creates src/ZB.MOM.WW.OtOpcUa.Driver.S7 (.NET 10, x64 -- S7netplus is managed, no bitness constraint like MXAccess) + tests/ZB.MOM.WW.OtOpcUa.Driver.S7.Tests + slnx entries. Depends on S7netplus 0.20.0 which is the latest version on NuGet resolvable in this cache (0.21.0 per driver-specs.md is not yet published; 0.20.0 covers the same Plc+CpuType+ReadAsync surface). S7DriverOptions captures the connection settings documented in driver-specs.md \u00A75: Host, Port (default 102 ISO-on-TCP), CpuType (default S71500 per most-common deployment), Rack=0, Slot=0 (S7-1200/1500 onboard PN convention; S7-300/400 operators must override to slot 2 or 3), Timeout=5s, Tags list + Probe settings with default MW0 probe address. S7TagDefinition uses S7.Net-style address strings (DB1.DBW0, M0.0, I0.0, QD4) with an S7DataType enum (Bool, Byte, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float32, Float64, String, DateTime -- the full type matrix from the spec); StringLength defaults to 254 (S7 STRING max). S7Driver implements the IDriver-only subset per the PR plan: InitializeAsync opens a managed Plc with the configured CpuType + Host + Rack + Slot, pins WriteTimeout / ReadTimeout on the underlying TcpClient, awaits Plc.OpenAsync with a linked CTS bounded by Options.Timeout so the ISO handshake itself respects the configured bound; health transitions Unknown -> Initializing -> Healthy on success or Unknown -> Initializing -> Faulted on handshake failure, with a best-effort Plc.Close() on the faulted path so retries don't leak the TcpClient. ShutdownAsync closes the Plc and flips health back to Unknown. DisposeAsync routes through ShutdownAsync + disposes the SemaphoreSlim. Internal Gate + Plc accessors are exposed to the test project (InternalsVisibleTo) so PRs 63-65 can stack read/write/subscribe on the same serialization semaphore per the S7netplus documented 'one Plc per PLC, SemaphoreSlim-serialized' pattern. ITagDiscovery, IReadable, IWritable, ISubscribable, IHostConnectivityProbe are all deliberately omitted from this PR -- they depend on the S7AddressParser (PR 63) and land sequenced in PRs 64-65. Unit tests (S7DriverScaffoldTests, 5 facts): default options target S7-1500 / port 102 / slot 0, default probe interval 5s, tag defaults to writable with StringLength 254, driver reports DriverType=S7 + Unknown health pre-init, Initialize against RFC-5737 reserved IP 192.0.2.1 with 250ms timeout transitions to Faulted and throws (tests the connect-failure path doesn't leave the driver in an ambiguous state). 5/5 pass. dotnet build ZB.MOM.WW.OtOpcUa.slnx: 0 errors. No regression in Modbus / Galaxy suites. PR 63 ships S7AddressParser next, PR 64 wires IReadable/IWritable over S7netplus, PR 65 adds discovery + polling-overlay subscribe + probe. · Updated 2026-04-19 00:03:09 -04:00    dohertj2

0
142
#61 Merged

56d8af8bdb · Phase 2 PR 61 -- Close V1_ARCHIVE_STATUS.md; Phase 2 Streams D + E done. Purely a documentation-closure PR. The v1 archive deletion itself happened across earlier PRs: PR 2 on phase-2-stream-d archive-marked the four v1 projects (IsTestProject=false so dotnet test slnx bypassed them); Phase 3 PR 18 deleted the archived project source trees. What remained on disk was stale bin/obj residue from pre-deletion builds -- git never tracked those, so removing them from the working tree is cosmetic only (no source-file diff in this PR). What this PR actually changes: V1_ARCHIVE_STATUS.md is rewritten from 'Deletion plan (Phase 2 PR 3)' pre-work prose to a CLOSED retrospective that (a) lists all five v1 directories as deleted with check-marks (src/OtOpcUa.Host, src/Historian.Aveva, tests/Historian.Aveva.Tests, tests/Tests.v1Archive, tests/IntegrationTests), (b) names the parity-bar tests that now fill the role the 494 v1 tests originally held (Driver.Galaxy.E2E cross-FX subprocess parity + stability-findings regression, per-component *.Tests projects, Driver.Modbus.IntegrationTests, LiveStack/ smoke tests), and (c) gives the closure timeline connecting PR 2 -> Phase 3 PR 18 -> this PR 61. Also added the Modbus TCP driver family as parity coverage that didn't exist in v1 (DL205 + S7-1500 + Mitsubishi MELSEC via pymodbus sim). Stream D (retire legacy Host) has been effectively done since Phase 3 PR 18; Stream E (parity validation) is done since PR 2 landed the Driver.Galaxy.E2E project with HostSubprocessParityTests + HierarchyParityTests + StabilityFindingsRegressionTests. This PR exists to definitively close the two pending Phase 2 tasks on the task list and give future-me (or anyone picking up Phase 2 retrospectives) a single 'what actually happened' doc instead of a 'what we plan to do' prose that didn't match reality. dotnet build ZB.MOM.WW.OtOpcUa.slnx: 0 errors, 200 warnings (all xunit1051 cancellation-token analyzer advisories, unchanged from v2 tip). No test regressions -- no source code changed. · Updated 2026-04-18 23:20:54 -04:00    dohertj2

0
140
#60 Merged

a44fc7a610 · Phase 3 PR 60 -- Mitsubishi MELSEC quirk integration tests against mitsubishi pymodbus profile. Seven facts in MitsubishiQuirkTests covering the quirks documented in docs/v2/mitsubishi.md that are testable end-to-end via pymodbus: (1) Mitsubishi_D0_fingerprint_reads_0x1234 -- MELSEC operators reserve D0 as a fingerprint word so Modbus clients can verify they're hitting the right Device Assignment block; test reads HR[0]=0x1234 via DRegisterToHolding('D0') helper. (2) Mitsubishi_Float32_CDAB_decodes_1_5f_from_D100 -- reads HR[100..101] with WordSwap AND BigEndian; asserts WordSwap==1.5f AND BigEndian!=1.5f, proving (a) MELSEC uses CDAB default same as DL260, (b) opposite of S7 ABCD, (c) driver flag is not a no-op. (3) Mitsubishi_D10_is_binary_not_BCD -- reads HR[10]=0x04D2 as Int16 and asserts value 1234 (binary decode), contrasting with DL205's BCD-by-default convention. (4) Mitsubishi_D10_as_BCD_throws_because_nibble_is_non_decimal -- reads same HR[10] as Bcd16 and asserts StatusCode != 0 because nibble 0xD fails BCD validation; proves the BCD decoder fails loud when the tag config is wrong rather than silently returning garbage. (5) Mitsubishi_QLiQR_X210_hex_maps_to_DI_528_reads_ON -- reads FC02 at the MelsecAddress.XInputToDiscrete('X210', Q_L_iQR)-resolved address (=528 decimal) and asserts ON; proves the hex-parsing path end-to-end. (6) Mitsubishi_family_trap_X20_differs_on_Q_vs_FX -- unit-level proof in the integration file so the headline family trap is visible to anyone filtering by Device=Mitsubishi. (7) Mitsubishi_M512_maps_to_coil_512_reads_ON -- reads FC01 at MRelayToCoil('M512')=512 (decimal) and asserts ON; proves the decimal M-relay path. Test fixture pattern: single MitsubishiQuirkTests class with a shared ShouldRun + NewDriverAsync helper rather than per-quirk classes (contrast with DL205's per-quirk splits). MELSEC per-model differentiation is handled by MelsecFamily enum on the helper rather than per-PR -- so one quirk file + one family enum covers Q/L/iQ-R/FX/iQ-F, and a new PLC family just adds an enum case instead of a new test class. 8/8 Mitsubishi integration tests pass (1 smoke + 7 quirk). 176/176 Modbus.Tests unit suite still green. S7 + DL205 integration tests can be run against their respective profiles by swapping MODBUS_SIM_PROFILE and restarting the pymodbus sim -- each family gates on its profile env var so no cross-family test pollution. · Updated 2026-04-18 23:07:00 -04:00    dohertj2

0
134
#59 Merged

d4c1873998 · Phase 3 PR 59 -- MelsecAddress helper for MELSEC X/Y hex-vs-octal family trap + D/M bank bases. Adds MelsecAddress static class with XInputToDiscrete, YOutputToCoil, MRelayToCoil, DRegisterToHolding helpers and a MelsecFamily enum {Q_L_iQR, F_iQF} that drives whether X/Y addresses are parsed as hex (Q-series convention) or octal (FX-series convention). This is the #1 MELSEC driver bug source per docs/v2/mitsubishi.md: the string 'X20' on a MELSEC-Q means DI 32 (hex 0x20) while the same string on an FX3U means DI 16 (octal 0o20). The helper forces the caller to name the family explicitly; no 'sensible default' because wrong defaults just move the bug. Key design decisions: (1) Family is an enum argument, not a helper-level static-selector, because real deployments have BOTH Q-series and FX-series PLCs on the same gateway -- one driver instance per device means family must be per-tag, not per-driver. (2) Bank base is a ushort argument defaulting to 0. Real QJ71MT91/LJ71MT91 assignment blocks commonly place X at DI 8192+, Y at coil 8192+, etc. to leave the low-address range for D-registers; the helper takes the site's configured base as runtime config rather than a compile-time constant. Matches the 'driver opt-in per tag' pattern DirectLogicAddress established for DL260. (3) M-relay and D-register are DECIMAL on every MELSEC family -- docs explicitly; the MELSEC confusion is only about X/Y, not about data registers or internal relays. Helpers reject non-numeric M/D addresses and honor bank bases the same way. (4) Parser walks digits manually for both hex and octal (instead of int.Parse with NumberStyles) so non-hex / non-octal characters give a clear ArgumentException with the offending char + family name. Prevents a subtle class of bugs where int.Parse('X20', Hex) silently returns 32 even for F_iQF callers. Unit tests (MelsecAddressTests, 34 facts): XInputToDiscrete_QLiQR_parses_hex theory (X0, X9, XA, XF, X10, X20, X1FF + lowercase); XInputToDiscrete_FiQF_parses_octal theory (X0, X7, X10, X20, X777); YOutputToCoil equivalents; Same_address_string_decodes_differently_between_families (the headline trap, X20 => 32 on Q vs 16 on FX); reject-non-octal / reject-non-hex / reject-empty / overflow facts; honors-bank-base for X and M and D. 176/176 Modbus.Tests pass (143 prior + 34 new Melsec). No driver core changes -- this is purely a new helper class in the Driver.Modbus project. PR 60 wires it into integration tests against the mitsubishi pymodbus profile. · Updated 2026-04-18 23:04:52 -04:00    dohertj2

0
133
#58 Merged

f52b7d8979 · Phase 3 PR 58 -- Mitsubishi MELSEC pymodbus profile + smoke integration test. Adds tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/Pymodbus/mitsubishi.json modelling a representative MELSEC Modbus Device Assignment block: D0..D1023 -> HR[0..1023], M-relay marker at coil 512 (cell 32) and X-input marker at DI 528 (cell 33). Covers the canonical MELSEC quirks from docs/v2/mitsubishi.md: D0 fingerprint at HR[0]=0x1234 so clients can verify the assignment parameter block is in effect, scratch HR 200..209 mirroring dl205/s7_1500/standard scratch range for uniform smoke tests, Float32 1.5f at HR[100..101] in CDAB word order (HR[100]=0, HR[101]=0x3FC0) -- same as DL260, OPPOSITE of S7 ABCD, confirms MELSEC-family driver profile default must be ByteOrder.WordSwap. Int32 0x12345678 CDAB at HR[300..301]. D10 = binary 1234 (0x04D2) proves MELSEC is BINARY-by-default (opposite of DL205 BCD-by-default quirk) -- reading D10 with Bcd16 data type would throw InvalidDataException on nibble 0xD. M-relay marker cell moved to address 32 (coil 512) to avoid shared-block collision with D0 uint16 marker at cell 0; pymodbus shared-blocks=true semantics allow only one type per cell index, so Modbus-coil-0 can't coexist with Modbus-HR-0 on the same sim. Same pattern we applied to dl205 profile (X-input bank at cell 1, not cell 0, to coexist with V0 marker). Adds Mitsubishi/ test directory with MitsubishiProfile.cs (SmokeHoldingRegister=200, SmokeHoldingValue=7890, BuildOptions with probe-disabled + 2s timeout) and MitsubishiSmokeTests.cs (Mitsubishi_roundtrip_write_then_read_of_holding_register single fact that writes 7890 at HR[200] then reads back, gated on MODBUS_SIM_PROFILE=mitsubishi). csproj copies Mitsubishi/** as PreserveNewest. Per-model differences (FX5U firmware gate, QJ71MT91 FC22/23 absence, FX/iQ-F octal vs Q/L/iQ-R hex X-addressing) are handled in the MelsecAddress helper (PR 59) + per-model test classes (PR 60). Verified: smoke 1/1 passes against live mitsubishi sim. Prior S7 tests 4/4 still green when swapped back. Modbus.Tests unit suite 143/143. · Updated 2026-04-18 23:02:29 -04:00    dohertj2

0
132
#57 Merged

b54724a812 · Phase 3 PR 57 -- S7 byte-order + fingerprint integration tests against s7_1500 pymodbus profile. Three facts in new S7_ByteOrderTests class: (1) S7_Float32_ABCD_decodes_1_5f_from_HR100 reads HR[100..101] with ModbusByteOrder.BigEndian AND with WordSwap on the same wire bytes; asserts BigEndian==1.5f AND WordSwap!=1.5f -- proving both that Siemens S7 stores Float32 in ABCD word order (opposite of DL260 CDAB) and that the ByteOrder flag is not a no-op on the same wire buffer. (2) S7_Int32_ABCD_decodes_0x12345678_from_HR300 reads HR[300]=0x1234 + HR[301]=0x5678 with BigEndian and asserts the reassembled Int32 = 0x12345678; documents the contrast with DL260 CDAB Int32 encoding. (3) S7_DB1_fingerprint_marker_at_HR0_reads_0xABCD reads HR[0]=0xABCD -- real MB_SERVER deployments reserve DB1.DBW0 as a fingerprint so clients can verify they're pointing at the right DB, protecting against typos in the MB_SERVER.MB_HOLD_REG.DB_number parameter. No driver code changes -- the ByteOrder.BigEndian path has existed since PR 24; this PR exists to lock in the S7-specific semantics at the integration level so future refactors of NormalizeWordOrder can't silently break S7. All 3 tests gate on MODBUS_SIM_PROFILE=s7_1500 so they skip cleanly against dl205 or standard profiles. Verified end-to-end: 4/4 S7 integration tests pass (1 smoke from PR 56 + 3 new). No regression in driver unit tests. Per the per-quirk-PR plan: the S7 quirks NOT testable via pymodbus sim (MB_SERVER STATUS 0x8383 optimized-DB behavior, port-per-connection semantics, CP 343-1 Lean license rejection, STOP-mode non-determinism) remain in docs/v2/s7.md as design guidance for driver users rather than automated tests -- they're TIA-Portal-side or CP-hardware-side behaviors that pymodbus cannot reproduce without custom Python actions. · Updated 2026-04-18 22:58:44 -04:00    dohertj2

0
131
#56 Merged

10c724b5b6 · Phase 3 PR 56 -- Siemens S7-1500 pymodbus profile + smoke integration test. Adds tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/Pymodbus/s7_1500.json modelling the SIMATIC S7-1500 + MB_SERVER default deployment documented in docs/v2/s7.md: DB1.DBW0 = 0xABCD fingerprint marker (operators reserve this so clients can verify they're talking to the right DB), scratch HR range 200..209 for write-roundtrip tests mirroring dl205.json + standard.json, Float32 1.5f at HR[100..101] in ABCD word order (high word first -- OPPOSITE of DL260 CDAB), Int32 0x12345678 at HR[300..301] in ABCD. Also seeds a coil at bit-addr 400 (= cell 25 bit 0) and a discrete input at bit-addr 500 (= cell 31 bit 0) so future S7-specific tests for FC01/FC02 have stable markers. shared blocks=true to match the proven dl205.json pattern (pymodbus's bits/uint16 cells coexist cleanly when addresses don't collide). Write list references cells (0, 25, 100-101, 200-209, 300-301), not bit addresses -- pymodbus's write-range entries are cell-indexed, not bit-indexed. Adds tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/S7/ directory with S7_1500Profile.cs (mirrors DL205Profile pattern: SmokeHoldingRegister=200, SmokeHoldingValue=4321, BuildOptions tags + probe-disabled + 2s timeout) and S7_1500SmokeTests.cs (single fact S7_1500_roundtrip_write_then_read_of_holding_register that writes SmokeHoldingValue then reads it back, asserting both write status 0 and read status 0 + value equality). Gates on MODBUS_SIM_PROFILE=s7_1500 so the test skips cleanly against other profiles. csproj updated to copy S7/** to test output as PreserveNewest (pattern matching DL205/**). Pymodbus/serve.ps1 ValidateSet extended from {standard,dl205} to {standard,dl205,s7_1500,mitsubishi} -- mitsubishi.json lands in PR 58 but the validator slot is claimed now so the serve.ps1 diff is one line in this PR and zero lines in future PRs. Verified end-to-end: smoke test 1/1 passes against the running pymodbus s7_1500 profile (localhost:5020 FC06 write of 4321 at HR[200] + FC03 read back). 143/143 Modbus.Tests pass, no regression in driver code because this PR is purely test-asset. Per-quirk S7 integration tests (ABCD word order default, FC23 IllegalFunction, MB_SERVER STATUS 0x8383 behaviour, port-per-connection semantics) land in PR 57+. · Updated 2026-04-18 22:57:03 -04:00    dohertj2

0
130
#55 Merged

c506ea298a · Phase 3 PR 55 -- Mitsubishi MELSEC Modbus TCP quirks research document. 451-line doc at docs/v2/mitsubishi.md mirroring the docs/v2/dl205.md template for the MELSEC family (Q-series + QJ71MT91, L-series + LJ71MT91, iQ-R + RJ71EN71, iQ-R built-in Ethernet, iQ-F FX5U built-in, FX3U + FX3U-ENET / FX3U-ENET-P502, FX3GE built-in). Like Siemens S7, MELSEC Modbus is a patchwork of per-site-configured add-on modules rather than a fixed firmware stack, but the MELSEC-specific traps are different enough to warrant their own document. Key findings worth flagging for the PR 58+ implementation track: (1) MODULE NAMING TRAP -- QJ71MB91 is SERIAL RTU, not TCP. The Q-series TCP module is QJ71MT91. Driver docs + config UI should surface this clearly because the confusion costs operators hours when they try to connect to an RS-232 module via Ethernet. (2) NO CANONICAL MAPPING -- every MELSEC Modbus site has a unique 'Modbus Device Assignment Parameter' block of up to 16 assignments (each binding a MELSEC device range like D0..D1023 to a Modbus-address range); the driver must treat the mapping as runtime config, not device-family profile. (3) X/Y BASE DEPENDS ON FAMILY -- Q/L/iQ-R use HEX notation for X/Y (X20 = decimal 32), FX/iQ-F use OCTAL (X20 = decimal 16, same as DL260); iQ-F has a GX Works3 project toggle that can flip this. Single biggest off-by-N source in MELSEC driver code -- driver address helper must take a family selector. (4) Word order CDAB across Q/L/iQ-R/iQ-F by default (CPU-level, not module-level) -- no user-configurable swap on the server side. FX5U's SWAP instruction is for CLIENT mode only. Driver Mitsubishi profile default must be ByteOrder.WordSwap, matching DL260 but OPPOSITE of Siemens S7. (5) D-registers are BINARY by default (opposite of DL205's BCD-by-default). FNC 18 BCD / FNC 19 BIN instructions confirm binary-by-default in the ladder. Caller must explicitly opt-in to Bcd16/Bcd32 tags when the ladder stores BCD, same pattern as DL205 but the default is inverted. (6) FX5U FIRMWARE GATE -- needs firmware >= 1.060 for native Modbus TCP server; older firmware is client-only. Surface a clear capability error on connect. (7) FX3U PORT 502 SPLIT -- the standard FX3U-ENET cannot bind port 502 (lower port range restricted on the firmware); only FX3U-ENET-P502 can. FX3U-ENET-ADP has no Modbus at all and is a common operator mis-purchase -- driver should surface 'module does not support Modbus' as a distinct error, not 'connection refused'. (8) QJ71MT91 does NOT support FC22 (Mask Write) or FC23 (Read-Write Multiple). iQ-R and iQ-F do. Driver bulk-read optimization must gate on module capability. (9) MAX CONNECTIONS -- 16 simultaneous on Q/L/iQ-R, 8 on FX5U and FX3U-ENET. (10) STOP-mode writes -- configurable on Q/L/iQ-R/iQ-F (default = accept writes even in STOP), always rejected with exception 04 on FX3U-ENET. Per-model test differentiation section names the tests Mitsubishi_QJ71MT91_*, Mitsubishi_FX5U_*, Mitsubishi_FX3U_ENET_*, with a shared Mitsubishi_Common_* fixture for CDAB-word-order + binary-not-BCD + standard-exception-codes tests. 17 cited references including primary Mitsubishi manuals (SH-080446 for QJ71MT91, JY997D56101 for FX5, SH-081259 for iQ-R Ethernet, JY997D18101 for FX3U-ENET) plus Ignition / Kepware / Fernhill / HMS third-party driver release notes. Three unconfirmed rumours flagged explicitly: iQ-R RJ71EN71 early firmware rumoured ABCD word order (no primary source), QJ71MT91 firmware < 2010-05 FC15 odd-byte-count truncation (forum report only), FX3U-ENET firmware < 1.14 out-of-order TxId echoes under load (unreproducible on bench). Pure documentation PR -- no code, no tests. Per-quirk implementation lands in PRs 58+. Research conducted 2026-04-18. · Updated 2026-04-18 22:51:28 -04:00    dohertj2

0
126
#54 Merged

9e2b5b330f · Phase 3 PR 54 -- Siemens S7 Modbus TCP quirks research document. 485-line doc at docs/v2/s7.md mirroring the docs/v2/dl205.md template for the Siemens SIMATIC S7 family (S7-1200 / S7-1500 / S7-300 / S7-400 / ET 200SP / CP 343-1 / CP 443-1 / CP 343-1 Lean / MODBUSPN). Siemens S7 is fundamentally different from DL260: there is no fixed Modbus memory map baked into firmware -- every deployment runs MB_SERVER (S7-1200/1500/ET 200SP), MODBUSCP (S7-300/400 + CP), or MODBUSPN (S7-300/400 PN) library blocks wired up to user DBs via the MB_HOLD_REG / ADDR parameters. The driver's job is therefore to handle per-site CONFIG rather than per-family QUIRKS, and the doc makes that explicit. Key findings worth flagging for the PR 56+ implementation track: (1) S7 has no fixed memory map -- must accept per-site DriverConfig, cannot assume vendor-standard layout. (2) MB_SERVER requires NON-optimized DBs in TIA Portal; optimized DBs cause the library to return STATUS 0x8383 on every access -- the single most common S7 Modbus deployment bug in the field. (3) Word order is ABCD by default (big-endian bytes + big-endian words) across all Siemens S7 Modbus paths, which is the OPPOSITE of DL260 CDAB -- the Modbus driver's S7 profile default must be ByteOrder.BigEndian, not WordSwap. (4) MB_SERVER listens on ONE port per FB instance; multi-client support requires running MB_SERVER on 502 / 503 / 504 / ... simultaneously -- most clients assume port 502 multiplexes, which is wrong on S7. (5) CP 343-1 Lean is SERVER-ONLY and requires the separate 2XV9450-1MB00 MODBUS TCP CP library license; client mode calls return immediate error on Lean. (6) MB_SERVER does NOT filter Unit ID, accepts any value. Means the driver can't use Unit ID to detect 'direct vs gateway' topology. (7) FC23 Read-Write Multiple, FC22 Mask Write, FC20/21 File Records, FC43 Device Identification all return exception 01 Illegal Function on every S7 variant -- the driver MUST NOT attempt bulk-read optimisation via FC23 when talking to S7. (8) STOP-mode read/write behaviour is non-deterministic across firmware bands: reads may return cached data (library internal buffer), writes may succeed-silently or return exception 04 depending on CPU firmware version -- flagged as 'driver treats both as unavailable, do not distinguish'. Unconfirmed rumours flagged separately: 'V2.0+ reverses float byte order' claim (cited but not reproduced), STOP-mode caching location (folklore, no primary source). Per-model test differentiation section names the tests as S7_<model>_<behavior> matching the DL205 template convention (e.g. S7_1200_MB_SERVER_requires_non_optimized_DB, S7_343_1_Lean_rejects_client_mode, S7_FC23_returns_IllegalFunction). 31 cited references across the Siemens Industry Online Support entry-ID system (68011496 for MB_SERVER FAQ, etc.), TIA Portal library manuals, and three third-party driver vendor release notes (Kepware, Ignition, FactoryTalk). This is a pure documentation PR -- no code, no tests, no csproj changes. Per-quirk implementation lands in PRs 56+. Research conducted 2026-04-18 against latest publicly-available Siemens documentation; STOP-mode behaviour and MB_SERVER versioning specifically cross-checked against Siemens forum answers from 2024-2025. · Updated 2026-04-18 22:50:51 -04:00    dohertj2

0
126
#53 Merged

793c787315 · Phase 3 PR 53 -- Transport reconnect-on-drop + SO_KEEPALIVE for DL205 no-keepalive quirk. AutomationDirect H2-ECOM100 does NOT send TCP keepalives per docs/v2/dl205.md behavioral-oddities section -- any NAT/firewall device between the gateway and the PLC can silently close an idle socket after 2-5 minutes of inactivity. The PLC itself never notices and the first SendAsync after the drop would previously surface as IOException / EndOfStreamException / SocketException to the caller even though the PLC is perfectly healthy. PR 53 makes ModbusTcpTransport survive mid-session socket drops: SendAsync wraps the previous body as SendOnceAsync; on the first attempt, if the failure is a socket-layer error (IOException, SocketException, EndOfStreamException, ObjectDisposedException) AND autoReconnect is enabled (default true), the transport tears down the dead socket, calls ConnectAsync to re-establish, and resends the PDU exactly once. Deliberately single-retry -- further failures propagate so the driver health surface reflects the real state, no masking a dead PLC. Protocol-layer failures (e.g. ModbusException with exception code 02) are specifically NOT caught by the reconnect path -- they would just come back with the same exception code after the reconnect, so retrying is wasted wire time. Socket-level vs protocol-level is a discriminator inside IsSocketLevelFailure. Also enables SO_KEEPALIVE on the TcpClient with aggressive timing: TcpKeepAliveTime=30s, TcpKeepAliveInterval=10s, TcpKeepAliveRetryCount=3. Total time-to-detect-dead-socket = 30 + 10*3 = 60s, vs the Windows default 2-hour idle + 9 retries = 2h40min. Best-effort: older OSes that don't expose the fine-grained keepalive knobs silently skip them (catch {}). New ModbusDriverOptions.AutoReconnect bool (default true) threads through to the default transport factory in ModbusDriver -- callers wanting the old 'fail loud on drop' behavior can set AutoReconnect=false, or use a custom transportFactory that ignores the option. Unit tests: ModbusTcpReconnectTests boots a FlakeyModbusServer in-process (real TcpListener on loopback) that serves one valid FC03 response then forcibly shuts down the socket. Transport_recovers_from_mid_session_drop_and_retries_successfully issues two consecutive SendAsync calls and asserts both return valid PDUs -- the second must trigger the reconnect path transparently. Transport_without_AutoReconnect_propagates_drop_to_caller asserts the legacy behavior when the opt-out is taken. Validates real socket semantics rather than mocked exceptions. 142/142 Modbus.Tests pass (113 prior + 2 mapper + 2 reconnect + 25 accumulated across PRs 45-52); 11/11 DL205 integration tests still pass with MODBUS_SIM_PROFILE=dl205 -- no regression from the transport change. · Updated 2026-04-18 22:32:13 -04:00    dohertj2

0
121
#52 Merged

cde018aec1 · Phase 3 PR 52 -- Modbus exception-code -> OPC UA StatusCode translation. Before this PR every server-side Modbus exception AND every transport-layer failure collapsed to BadInternalError (0x80020000) in the driver's Read/Write results, making field diagnosis 'is this a tag misconfig or a driver bug?' impossible from the OPC UA client side. PR 52 adds a MapModbusExceptionToStatus helper that translates per spec: 01 Illegal Function -> BadNotSupported (0x803D0000); 02 Illegal Data Address -> BadOutOfRange (0x803C0000); 03 Illegal Data Value -> BadOutOfRange; 04 Server Failure -> BadDeviceFailure (0x80550000); 05/06 Acknowledge/Busy -> BadDeviceFailure; 0A/0B Gateway -> BadCommunicationError (0x80050000); unknown -> BadInternalError fallback. Non-Modbus failures (socket drop, timeout, malformed frame) in ReadAsync are now distinguished from tag-level faults: they map to BadCommunicationError so operators check network/PLC reachability rather than tag definitions. Why per-DL205: docs/v2/dl205.md documents DL205/DL260 returning only codes 01-04 with specific triggers -- exception 04 specifically means 'CPU in PROGRAM mode during a protected write', which is operator-recoverable by switching the CPU to RUN; surfacing it as BadDeviceFailure (not BadInternalError) makes the fix obvious. Changes in ModbusDriver: Read catch-chain now ModbusException first (-> mapper), generic Exception second (-> BadCommunicationError); Write catch-chain same pattern but generic Exception stays BadInternalError because write failures can legitimately come from EncodeRegister (out-of-range value) which is a driver-layer fault. Unit tests: MapModbusExceptionToStatus theory exercising every code in the table including the 0xFF fallback; Read_surface_exception_02_as_BadOutOfRange with an ExceptionRaisingTransport that forces code 02; Write_surface_exception_04_as_BadDeviceFailure for CPU-mode faults; Read_non_modbus_failure_maps_to_BadCommunicationError with a NonModbusFailureTransport that raises EndOfStreamException. 115/115 Modbus.Tests pass. Integration test: DL205ExceptionCodeTests.DL205_FC03_at_unmapped_register_returns_BadOutOfRange reads HR[16383] which is beyond the seeded uint16 cells on the dl205.json profile; pymodbus returns exception 02 and the driver surfaces BadOutOfRange. 11/11 DL205 integration tests pass with MODBUS_SIM_PROFILE=dl205. · Updated 2026-04-18 22:28:37 -04:00    dohertj2

0
120
#51 Merged

9892a0253d · Phase 3 PR 51 -- DL260 X-input FC02 discrete-input mapping end-to-end test. Integration test DL205XInputTests reads FC02 at the DirectLogicAddress.XInputToDiscrete-resolved address and asserts two behaviors against the dl205.json pymodbus profile: (1) X20 octal (=decimal 16 = Modbus DI 16) reads ON, proving the helper correctly octal-parses the trailing number and adds it to the 0 base; (2) X21 octal reads OFF (not exception) -- per docs/v2/dl205.md §I/O-mapping, 'reading a non-populated X input returns zero, not an exception' on DL260, because the CPU sizes the discrete-input table to the configured I/O not the installed hardware. Pymodbus models this by returning the default 0 value for any DI bit in the configured 'di size' range that wasn't explicitly seeded, matching real DL260 behaviour. Test uses X20 rather than X0 to sidestep a shared-blocks conflict: pymodbus places FC01/FC02 bit-address 0..15 into cell 0, but cell 0 is already uint16-typed (V0 marker = 0xCAFE) per the register-zero quirk test, and shared-blocks semantics allow only one type per cell. X20 octal = DI 16 lands in cell 1 which is free, so both the V0 quirk AND the X-input quirk can coexist in one profile. dl205.json: bits cell 1 seeded value=9 (bits 0 and 3 set -> X20, X23 octal = ON), write-range extended to include cell 1 (though X-inputs are read-only; the write-range entry is required by pymodbus for ANY cell referenced in a bits section even if only reads are expected -- pymodbus validates write-access uniformly). 10/10 DL205 integration tests pass with MODBUS_SIM_PROFILE=dl205. No driver code changes -- the XInputToDiscrete helper + FC02 read path already landed in PRs 50 and 21 respectively. This PR closes the integration-test gap that docs/v2/dl205.md called out under test name DL205_Xinput_unpopulated_reads_as_zero. · Updated 2026-04-18 22:25:13 -04:00    dohertj2

0
119
#50 Merged

b5464f11ee · Phase 3 PR 50 -- DL260 bit-memory address helpers (Y/C/X/SP) + live coil integration tests. Adds four new static helpers to DirectLogicAddress covering every discrete-memory bank on the DL260: YOutputToCoil (Y0=coil 2048), CRelayToCoil (C0=coil 3072), XInputToDiscrete (X0=DI 0), SpecialToDiscrete (SP0=DI 1024). Each helper takes the DirectLOGIC ladder-logic address (e.g. 'Y0', 'Y17', 'C1777') and adds the octal-decoded offset to the bank's Modbus base per the DL260 user manual's I/O-configuration chapter table. Uses the same 'octal-walk + reject 8/9' pattern as UserVMemoryToPdu so misaligned addresses fail loudly with a clear ArgumentException rather than silently hitting the wrong coil. Fixes a pymodbus-config bug surfaced during integration-test validation: dl205.json had bits entries at cell indices 2048 / 3072 / 4000, but pymodbus's ModbusSimulatorContext.validate divides bit addresses by 16 before indexing into the shared cell array -- so Modbus coil 2048 reads cell 128, not cell 2048. The sim was returning Illegal Data Address (exception 02) for every bit read in the Y/C/scratch range. Moved bits entries to cells 128 (Y bank marker = 0b101 for Y0=ON, Y1=OFF, Y2=ON), 192 (C bank marker = 0b101 for C0/C1/C2), 250 (scratch cell covering coils 4000..4015). write list updated to the correct cell addresses. Unit tests: YOutputToCoil theory sweep (Y0->2048, Y1->2049, Y7->2055, Y10->2056 octal-to-decimal, Y17->2063, Y777->2559 top of DL260 Y range), CRelayToCoil theory (C0->3072 through C1777->4095), XInputToDiscrete theory, SpecialToDiscrete theory (with case-insensitive 'SP' prefix). Bit_address_rejects_non_octal_digits (Y8/C9/X18), Bit_address_rejects_empty, accepts_lowercase_prefix, accepts_bare_octal_without_prefix. 48/48 Modbus.Tests pass. Integration tests: DL205CoilMappingTests with three facts -- DL260_Y0_maps_to_coil_2048 (FC01 at Y0 returns ON), DL260_C0_maps_to_coil_3072 (FC01 at C0 returns ON), DL260_scratch_Crelay_supports_write_then_read (FC05 write + FC01 read round-trip at coil 4000 proves the DL-mapped coil bank is fully read/write capable end-to-end). 9/9 DL205 integration tests pass against the pymodbus dl205 profile with MODBUS_SIM_PROFILE=dl205. Caller opts into the helpers per tag the same way as PR 47's V-memory helper -- pass DirectLogicAddress.YOutputToCoil("Y0") as the ModbusTagDefinition Address; no driver-wide DL-family flag. PR 51 adds the X-input read-side integration test (there's nothing to write since X-inputs are FC02 discrete inputs, read-only); PR 52 exception-code translation; PR 53 transport reconnect-on-drop since DL260 doesn't send TCP keepalives. · Updated 2026-04-18 22:22:42 -04:00    dohertj2

0
118
#49 Merged

a3f2f95344 · Phase 3 PR 49 -- Per-device FC03/FC16 register caps with auto-chunking. Adds MaxRegistersPerRead (default 125, spec max) + MaxRegistersPerWrite (default 123, spec max) to ModbusDriverOptions. Reads that exceed the cap automatically split into consecutive FC03 requests: the driver dispatches chunks of [cap] regs at incrementing addresses, copies each response into an assembled byte[] buffer, and hands the full payload to DecodeRegister. From the caller's view a 240-char string read against a cap-100 device is still one Read() call returning one string -- the chunking is invisible, the wire shows N requests of cap-sized quantity plus one tail chunk. Writes are NOT auto-chunked. Splitting an FC16 across two transactions would lose atomicity -- mid-split crash leaves half the value written, which is strictly worse than rejecting upfront. Instead, writes exceeding MaxRegistersPerWrite throw InvalidOperationException with a message naming the tag + cap + the caller's escape hatch (shorten StringLength or split into multiple tags). The driver catches the exception internally and surfaces it to IWritable as BadInternalError so the caller pattern stays symmetric with other failure modes. Per-family cap cheat-sheet (documented in xml-doc on the option): Modbus-TCP spec = 125 read / 123 write, AutomationDirect DL205/DL260 = 128 read / 100 write (128 exceeds spec byte-count capacity so in practice 125 is the working ceiling), Mitsubishi Q/FX3U = 64 / 64, Omron CJ/CS = 125 / 123. Not all PLCs reject over-cap requests cleanly -- some drop the connection silently -- so having the cap enforced client-side prevents the hard-to-diagnose 'driver just stopped' failure mode. Unit tests: Read_within_cap_issues_single_FC03_request (control: no unnecessary chunking), Read_above_cap_splits_into_two_FC03_requests (120 regs / cap 100 -> 100+20, asserts exact per-chunk (Address,Quantity) and end-to-end payload continuity starting with register[100] high byte = 'A'), Read_cap_honors_Mitsubishi_lower_cap_of_64 (100 regs / cap 64 -> 64+36), Write_exceeding_cap_throws_instead_of_splitting (110 regs / cap 100 -> status != 0 AND Fc16Requests.Count == 0 to prove nothing was sent), Write_within_cap_proceeds_normally (control: cap honored on short writes too). Tests use a new RecordingTransport that captures the (Address, Quantity) tuple of every FC03/FC16 request so the chunk layout is directly assertable -- the existing FakeTransport does not expose request history. 103/103 Modbus.Tests pass; 6/6 DL205 integration tests still pass against the live pymodbus dl205 profile with MODBUS_SIM_PROFILE=dl205. · Updated 2026-04-18 21:58:49 -04:00    dohertj2

0
112
#48 Merged

463c5a4320 · Phase 3 PR 48 -- DL205 CDAB word order for Float32 end-to-end test. The driver has supported ModbusByteOrder.WordSwap (CDAB) since PR 24 for all multi-register types -- the underlying word-swap code path was already there. PR 48 closes the loop with an integration test that validates it end-to-end against the dl205 pymodbus profile: HR[1056..1057] stores IEEE-754 1.5f with the low word at the lower address (0x0000 at HR[1056], 0x3FC0 at HR[1057]). Reading with WordSwap returns 1.5f; reading with BigEndian returns a tiny denormal (~5.74e-41) -- a silent "value is 0" bug that typically surfaces in the field only when an operator notices a setpoint readout stuck at 0 while the PLC display shows the real value. Test asserts both: WordSwap==1.5f AND BigEndian!=1.5f, proving the flag is not a no-op. No driver code changes -- the word-swap normalization at NormalizeWordOrder() has handled Float32/Int32/UInt32 correctly since PR 24 and the unit test suite already covers it (Int32_WordSwap_decodes_CDAB_layout + Float32 equivalent). This PR exists primarily to lock in the integration-level validation so future refactors of the codec don't silently break DL205/DL260 floats. 6/6 DL205 integration tests pass with MODBUS_SIM_PROFILE=dl205. · Updated 2026-04-18 21:51:15 -04:00    dohertj2

0
111
#47 Merged

2b5222f5db · Phase 3 PR 47 -- DL205 V-memory octal-address helper. Adds DirectLogicAddress static class with two entry points: UserVMemoryToPdu(string) parses a DirectLOGIC V-address (V-prefixed or bare, whitespace tolerated) as OCTAL and returns the 0-based Modbus PDU address. V2000 octal = decimal 1024 = PDU 0x0400, which is the canonical start of the user V-memory bank on DL205/DL260. SystemVMemoryBasePdu + SystemVMemoryToPdu(ushort offset) handle the system bank (V40400 and up) which does NOT follow the simple octal-to-decimal formula -- the CPU relocates the system bank to PDU 0x2100 in H2-ECOM100 absolute mode. A naive caller converting 40400 octal would land at PDU 0x4100 (decimal 16640) and miss the system registers entirely; the helper routes the correct 0x2100 base. Why this matters: DirectLOGIC operators think in OCTAL (the ladder-logic editor, the Productivity/Do-more UI, every AutomationDirect manual addresses V-memory octally) while the Modbus wire is DECIMAL. Integrators routinely copy V-addresses from the PLC documentation into client configs and read garbage because they treated V2000 as decimal 2000 (HR[2000] = 0 in the dl205 sim, zero in most PLCs). The helper makes the translation explicit per the D2-USER-M appendix + H2-ECOM-M \u00A76.5 references cited in docs/v2/dl205.md. Unit tests: UserVMemoryToPdu_converts_octal_V_prefix (V0, V1, V7, V10, V2000, V7777, V10000, V17777 -- the exact sweep documented in dl205.md), UserVMemoryToPdu_accepts_bare_or_prefixed_or_padded (case + whitespace tolerance), UserVMemoryToPdu_rejects_non_octal_digits (V8/V19/V2009 must throw ArgumentException with 'octal' in the message -- .NET has no base-8 int.Parse so we hand-walk digits to catch 8/9 instead of silently accepting them), UserVMemoryToPdu_rejects_empty_input, UserVMemoryToPdu_overflow_rejected (200000 octal = 0x10000 overflows ushort), SystemVMemoryBasePdu_is_0x2100_for_V40400, SystemVMemoryToPdu_offsets_within_bank, SystemVMemoryToPdu_rejects_overflow. 23/23 Modbus.Tests pass. Integration tests against dl205.json pymodbus profile: DL205_V2000_user_memory_resolves_to_PDU_0x0400_marker (reads HR[0x0400]=0x2000), DL205_V40400_system_memory_resolves_to_PDU_0x2100_marker (reads HR[0x2100]=0x4040). 5/5 DL205 integration tests pass. Caller opts into the helper per tag by calling DirectLogicAddress.UserVMemoryToPdu("V2000") as the ModbusTagDefinition Address -- no driver-wide "DL205 mode" flag needed, because users mix DL and non-DL tags in a single driver instance all the time. · Updated 2026-04-18 21:49:58 -04:00    dohertj2

0
110
#46 Merged

8248b126ce · Phase 3 PR 46 -- DL205 BCD decoder (binary-coded-decimal numeric encoding). Adds ModbusDataType.Bcd16 and Bcd32 to the driver. Bcd16 is 1 register wide, Bcd32 is 2 registers wide; Bcd32 respects ModbusByteOrder (BigEndian/WordSwap) the same way Int32 does so the CDAB-style families (including DL205/DL260 themselves) can be configured. DecodeRegister uses the new internal DecodeBcd helper: walks each nibble from MSB to LSB, multiplies the running result by 10, adds the nibble as a decimal digit. Explicitly rejects nibbles > 9 with InvalidDataException -- hardware sometimes produces garbage during write-in-progress transitions and silently returning wrong numeric values would quietly corrupt the caller's data. EncodeRegister's new EncodeBcd inverts the operation (mod/div by 10 nibble-by-nibble) with an up-front overflow check against 10^nibbles-1. Why this matters for DL205/DL260: AutomationDirect DirectLOGIC uses BCD as the default numeric encoding for timers, counters, and operator-display numerics (not binary). A plain Int16 read of register 0x1234 returns 4660; the BCD path returns 1234. The two differ enough that silently defaulting to Int16 would give wildly wrong HMI values -- the caller must opt in to Bcd16/Bcd32 per tag. Unit tests: DecodeBcd (theory: 0,1,9,10,1234,9999), DecodeBcd_rejects_nibbles_above_nine, EncodeBcd (theory), Bcd16_decodes_DL205_register_1234_as_decimal_1234 (control: same bytes as Int16 decode to 4660), Bcd16_encode_round_trips_with_decode, Bcd16_encode_rejects_out_of_range_values, Bcd32_decodes_8_digits_big_endian, Bcd32_word_swap_handles_CDAB_layout, Bcd32_encode_round_trips_with_decode, Bcd_RegisterCount_matches_underlying_width. 66/66 Modbus.Tests pass. Integration test: DL205BcdQuirkTests.DL205_BCD16_decodes_HR1072_as_decimal_1234 against dl205.json pymodbus profile (HR[1072]=0x1234). Asserts Bcd16 decode=1234 AND Int16 decode=0x1234 on the same wire bytes to prove the paths are distinct. 3/3 DL205 integration tests pass with MODBUS_SIM_PROFILE=dl205. · Updated 2026-04-18 21:46:25 -04:00    dohertj2

0
109
#45 Merged