docs(index): OtOpcUa #663 in-place ApplyDelta re-subscribes data + alarms
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
This commit is contained in:
@@ -154,3 +154,7 @@ AddRoute of the dev Mac (`oee-tagdump-mac`, `10.181.206.245.1.1`) on the two tes
|
||||
so a failed alarm subscribe after an outage is retried. **ScadaBridge-visible:** native conditions keep updating across
|
||||
unrelated deploys and recover after an upstream outage without a driver respawn. No wire-contract change. Pinned by an
|
||||
end-to-end `NativeAlarmFeedSurvivesDeployTests`; not live-gated on the rig.
|
||||
- **2026-10-09 #663 (closed; OtOpcUa `1355049f`).** #662 review follow-up: an in-place `ApplyDelta` on a Connected driver
|
||||
called `ReinitializeAsync` but kept the actor's data + alarm handles, which the reinit had invalidated, so the driver
|
||||
would go silent. Now releases both at the driver, reinitialises, and re-subscribes both. **Latent only** — unreachable
|
||||
from a deploy since #516 (a DriverConfig change respawns). **ScadaBridge impact: none.**
|
||||
|
||||