docs(index): OtOpcUa #662 native-alarm feed survives non-respawning deploys

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
This commit is contained in:
Joseph Doherty
2026-10-09 07:36:04 -04:00
parent 63cc772e8d
commit dd1eea2106
@@ -146,3 +146,11 @@ AddRoute of the dev Mac (`oee-tagdump-mac`, `10.181.206.245.1.1`) on the two tes
AbLegacy Test Connect normalises the probe address per family (PLC-5 octal). (3) **#661** — flaky MTConnect test fixed.
(4) **#592** — Z-35162 real-hardware: #566 (a Logix drops idle TCP ≈16 s, driver reconnects), native STRING write and
array-element write (`_SEQ_EP[31]`) proven, restored. No wire-contract change.
- **2026-10-09 #662 (closed; OtOpcUa `83d129d1`).** Native-alarm feed loss: a data re-subscribe in `DriverInstanceActor`
(every deploy's bulk desired-set push to a KEPT driver) also unhooked `OnAlarmEvent` and dropped the alarm handle, so
after any deploy that did not respawn a driver its native alarms froze until a reconnect/respawn — **all native-alarm
drivers** (OpcUaClient, Galaxy, FOCAS, MTConnect, AbCip), not just OpcUaClient. Fixed by splitting a data-only detach;
the #488 health-poll reconcile now also re-attaches/re-subscribes alarms (backing off to ≤ 4 min on persistent failure),
so a failed alarm subscribe after an outage is retried. **ScadaBridge-visible:** native conditions keep updating across
unrelated deploys and recover after an upstream outage without a driver respawn. No wire-contract change. Pinned by an
end-to-end `NativeAlarmFeedSurvivesDeployTests`; not live-gated on the rig.