Ran #491's live gate against a real ZB.MOM.WW.HistorianGateway talking to a real AVEVA Historian, and it found a production-fatal defect on the first value it ever saw. ContinuousHistorizationRecorder.OnValueChangedAsync touched `Self` after awaiting IHistorizationOutbox.AppendAsync(...).ConfigureAwait(false). ConfigureAwait(false) discards Akka's ActorTaskScheduler synchronization context, so `Self` — which reads ActorBase.Context — threw NotSupportedException. The throw escaped into supervision, which RESTARTED the actor; because production seeds an EMPTY ref set (the deployed set arrives later via UpdateHistorizedRefs), the restart silently discarded every historized ref. Net effect: one value captured, then nothing, with no further error to show for it. Fixed by capturing `IActorRef self = Self` before the await — the idiom the GetStatus handler already applied to Sender. Thirteen unit tests missed it because InMemoryOutbox.AppendAsync returned ValueTask.CompletedTask: a completed ValueTask never yields, so the continuation ran inline with the context still installed. The production FasterLog outbox fsyncs per entry and does yield. The first regression test was itself vacuous — `await Task.Yield()` posts back to the CAPTURED context, so the append still completed on the actor thread and reverting the fix left the test green. The fake must complete on a POOL thread (Task.Delay(1).ConfigureAwait(false)), as a real fsync does; with that, reverting the fix reddens exactly one test. The rig could not run this gate at all: docker-dev carried ServerHistorian__* but no ContinuousHistorization__* keys, so the recorder could never spawn. Both centrals now carry them (default OFF — the recorder needs ContinuousHistorization:Enabled AND ServerHistorian:Enabled), with the outbox on the per-node named volume so it survives a container recreate. ServerHistorian__UseTls was hard-coded true and is now parameterized; a plaintext h2c gateway was unreachable without it. Gate results: outbox append, drain, WriteLiveValues accepted by a real historian, and restart convergence (capture resumes after a restart with no new deployment) all pass. The read-back hop is NOT proven — the LAN historian accepts writes but serves no reads under a "License violation: Database tag count exceeds license tag count", and the licensed corporate one needs the VPN. EnsureTags provisioning is likewise unexercised there (RemoteGrpc-only, and that CAP is not listening). #491 stays open for the read-back hop alone. Also recorded, not fixed: the recorder has NO Primary gate, unlike the alarm store-and-forward sink, so both nodes of a redundant pair send duplicate live values. Gating it would introduce a failover window with no capture — that is a design decision, not a cleanup. Evidence: docs/plans/2026-08-01-continuous-historization-live-gate.md Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
OtOpcUa
OPC UA server (.NET 10 AnyCPU) that exposes a fleet of industrial drivers as a single OPC UA address space. Drivers ship in-process for AVEVA System Platform Galaxy (via the sibling mxaccessgw repo), Modbus TCP, Siemens S7, Allen-Bradley CIP (ControlLogix / CompactLogix), Allen-Bradley Legacy (SLC 500 / MicroLogix), Beckhoff TwinCAT (ADS), FANUC FOCAS, OPC UA Client (gateway), and MQTT (broker subscribe; Sparkplug B in progress).
A cross-platform client stack (.NET 10) — shared library, CLI, and Avalonia desktop app — connects to any OPC UA server.
Architecture
OPC UA Clients (CLI, Desktop UI, 3rd-party)
|
v
+-------------------------------------+
| OtOpcUa.Server (.NET 10 AnyCPU) |
| address space + capability fan-out|
+-------------------------------------+
| | | | | | | |
Galaxy Modbus S7 AbCip AbLeg TwinCAT FOCAS OpcUaClient MQTT
|
v
mxaccessgw (sibling repo, gRPC)
|
v
MXAccess COM (x86 worker, on AVEVA box)
Galaxy is the only driver with an external runtime: it speaks gRPC to a separately installed mxaccessgw server (sibling repo at c:\Users\dohertj2\Desktop\mxaccessgw\) which owns the MXAccess COM apartment and the x86/STA bitness constraint server-side. Everything in this repo is platform-agnostic .NET 10.
Prerequisites
- .NET 10 SDK (server, drivers, clients all target .NET 10)
- SQL Server reachable for the central config DB
- For Galaxy specifically: a running
mxaccessgwdeployment — see docs/v2/Galaxy.ParityRig.md - For historian read-back / alarm history / continuous historization: a running
ZB.MOM.WW.HistorianGatewaydeployment (the sole historian backend; consumed as theZB.MOM.WW.HistorianGateway.ClientgRPC package). It must runRuntimeDb:Enabled=true+RuntimeDb:EventReadsEnabled=true, and the API key must carryhistorian:read+historian:write+historian:tags:writescopes.
Quick Start
dotnet restore ZB.MOM.WW.OtOpcUa.slnx
dotnet build ZB.MOM.WW.OtOpcUa.slnx
dotnet test ZB.MOM.WW.OtOpcUa.slnx
# Run the server in dev (foreground)
dotnet run --project src/Server/ZB.MOM.WW.OtOpcUa.Host
The server starts on opc.tcp://localhost:4840 with the None security profile. Configure Security.Profiles in src/Server/ZB.MOM.WW.OtOpcUa.Host/appsettings.json to enable Basic256Sha256-Sign or Basic256Sha256-SignAndEncrypt. See docs/security.md.
Install as Windows Services
Production deployment is driven by scripts/install/Install-Services.ps1, which registers the OtOpcUa server service under a chosen service account. Historian support requires a separately deployed ZB.MOM.WW.HistorianGateway and Galaxy support a separately installed mxaccessgw — neither this repo nor the install script provisions them.
.\scripts\install\Install-Services.ps1 `
-InstallRoot 'C:\Program Files\OtOpcUa' `
-ServiceAccount 'DOMAIN\svc-otopcua'
The historian backend is the external ZB.MOM.WW.HistorianGateway (not installed by this script). See the script header and docs/ServiceHosting.md for full options.
Client CLI
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- connect -u opc.tcp://localhost:4840
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- browse -u opc.tcp://localhost:4840 -r -d 3
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- read -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode"
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- write -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -v 42
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- subscribe -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -i 500
See docs/Client.CLI.md and docs/Client.UI.md.
Documentation
Architecture deep-dives
| Topic | Doc |
|---|---|
| OPC UA server composition, namespace fan-out, Polly invoker | docs/OpcUaServer.md |
| Address space layout | docs/AddressSpace.md |
| Read / Write dispatch (driver vs virtual vs scripted-alarm) | docs/ReadWriteOperations.md |
| Incremental sync (driver-backend rediscovery + config publishes) | docs/IncrementalSync.md |
| Service hosting (Server + Admin; external HistorianGateway backend) | docs/ServiceHosting.md |
| Security (transport, LDAP, certificates) | docs/security.md |
| Redundancy | docs/Redundancy.md |
| Status dashboard | docs/StatusDashboard.md |
Drivers
| Topic | Doc |
|---|---|
| Driver specs (per-driver capability surface, config, addressing) | docs/v2/driver-specs.md |
| Galaxy driver | docs/drivers/Galaxy.md |
| Modbus / S7 / AbCip / AbLegacy / TwinCAT / FOCAS / OpcUaClient / MQTT | docs/drivers/ |
| Galaxy parity rig (mxaccessgw setup) | docs/v2/Galaxy.ParityRig.md |
| Galaxy performance + tracing | docs/v2/Galaxy.Performance.md |
Clients
| Topic | Doc |
|---|---|
| Client CLI | docs/Client.CLI.md |
| Client UI (Avalonia desktop) | docs/Client.UI.md |
v1 archive
The original v1 in-process MXAccess docs (Galaxy.Host topology, Configuration env vars, AlarmTracking, DataTypeMapping, HistoricalDataAccess, Subscriptions, etc.) are preserved under docs/v1/ — historical reference only. PR 7.2 retired the v1 architecture on 2026-04-30; current state is documented in the sections above.
License
Internal use only.