Joseph Doherty 5533de6281 feat(arrays): Modbus String[]/BitInRegister[] array writes reachable; table follows the resolver
The Modbus lane (#741 U3) gave the driver String[] and BitInRegister[] holding-register array encoders, and
moved address resolution to ModbusTagAddressResolution (keys first, a bit region coerced to Bool, strict key
reads), but DriverArrayWriteSupport still listed both array shapes read-only (follow-up F1), so a client
write was BadNotWritable before it reached the driver.

Modbus row now mirrors the driver end to end:
- Keys shape only (region + address both present). A string-only addressString tag is resolved by the
  driver with its own family through a parser Core.Abstractions cannot reference, so it stays read-only
  (pinned: the conservative direction).
- Strict reads as the resolver: address an integer 0-65535; a present region / dataType / byteOrder /
  stringByteOrder string must name a member.
- Coils: any dataType (coerced to Bool), <= 1968 coils (FC15).
- HoldingRegisters (FC16, never Bool): numeric, String ((stringLength+1)/2 registers, stringLength >= 1),
  BitInRegister (1 register, bitIndex 0-15, span ending <= 65535), all within maxRegistersPerWrite.
  FC23 is opt-in and never changes the answer.
- Elements convert (ScadaBridge int[] -> Int16 stays writable); only a String / DateTime node over a
  numeric or bit element is left out, since such an element never converts.

Tests: the parity test's PendingF1 exemption and its guard are gone; the parity matrix is now region x
element type x node type against the real WriteAsync with a spec-conformant device (FC15 > 1968 refused),
plus shape edges at every cap boundary (numeric, String, BitInRegister, coil), strict key reads, FC23
on/off, string-only, the ScadaBridge int[] shape and U3 wire bytes. Core.Abstractions row tests and a
composer test (String[] and BitInRegister[] writable; over-cap, no-stringLength and string-only read-only).
Docs: table XML doc, Uns.md, modbus-addressing.md, drivers/Modbus.md, data-plane rules.

Refs #741

Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 17:10:00 -04:00

317 lines
15 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Modbus tag-addressing reference
Foundational doc for the Modbus addressing grammar shipped across #136–#144.
Covers the address-string parser (`ModbusAddressParser`) that the wire driver
and the Admin UI both consume, the per-tag suffix modifiers, and the family-
native branch.
## Grammar
```
<region><offset>[.<bit>][:<type>[<len>]][:<order>][:<count>]
```
Each field is optional from left to right; the parser fills defaults.
### Region + offset
Three accepted forms — pick whichever matches your tag spreadsheet's
convention. All three resolve to the same `(Region, ushort PduOffset)`
on the wire.
| Form | Example | Means |
|---|---|---|
| Modicon 5-digit | `40001` | Holding register 1 (PDU 0) |
| Modicon 6-digit | `400001` | Holding register 1 (PDU 0); supports up to `465536` (PDU 65535) |
| Mnemonic | `HR1`, `IR1`, `C100`, `DI1` | Same regions; `1`-based register number |
Modicon leading-digit → region:
| Digit | Region | OPC UA wire FC |
|---|---|---|
| `0` | Coils | FC01 / FC05 / FC15 |
| `1` | DiscreteInputs | FC02 (read-only) |
| `3` | InputRegisters | FC04 (read-only) |
| `4` | HoldingRegisters | FC03 / FC06 / FC16 |
### Bit suffix `.N`
`40001.5` = bit 5 (LSB-first) of HR[0]. Implies `DataType=BitInRegister`;
mixing with an explicit type or array-count is rejected.
### Type code `:T`
Codes verified 2026-04-25 against [Wonderware DASMBTCP user
guide](https://cdn.logic-control.com/media/DASMBTCP.pdf) and the
[Ignition Modbus addressing
manual](https://www.docs.inductiveautomation.com/docs/8.1/ignition-modules/opc-ua/opc-ua-drivers/modbus/modbus-addressing).
The `I` / `UI` / `I_64` / `UI_64` / `BCD_32` shapes match Wonderware's
suffix convention and Ignition's underscore-N prefix variants where
those vendors agree.
| Code | Type | Registers | Vendor reference |
|---|---|---|---|
| `BOOL` | Boolean | 1 (region must be Coils / DiscreteInputs) | universal |
| `S` | Int16 | 1 | Wonderware DASMBTCP `S` = 16-bit signed |
| `US` | UInt16 | 1 | Ignition `HRUS` = Unsigned Short |
| `I` | Int32 | 2 | Wonderware DASMBTCP `I` = 32-bit signed; Ignition `HRI` |
| `UI` | UInt32 | 2 | Ignition `HRUI` |
| `I_64` | Int64 | 4 | Ignition `HRI_64` |
| `UI_64` | UInt64 | 4 | Ignition `HRUI_64` |
| `F` | Float32 | 2 | Wonderware `F`; Ignition `HRF` |
| `D` | Float64 | 4 | Ignition `HRD` |
| `BCD` | 16-bit BCD | 1 | Ignition `HRBCD` |
| `BCD_32` | 32-bit BCD | 2 | Ignition `HRBCD_32` |
| `STR<len>` | ASCII string, `len` chars (2 chars / register) | `ceil(len/2)` | analogous to Ignition `HRS<addr>:<len>` |
Default when omitted:
- Coils / DiscreteInputs → `BOOL`
- HoldingRegisters / InputRegisters → `S` (Int16) — matches Ignition's bare-`HR` default
**Codes removed in #146** (silent wrong-data risk, never compatible with the
two reference vendors): `:DI`, `:L`, `:UDI`, `:UL`, `:LI`, `:ULI`, `:LBCD`.
Pre-#146 configs that use these get a clear "Unknown type code" diagnostic at
parse time; rewrite to the post-#146 codes per the table above.
### Byte order `:O`
| Mnemonic | Meaning | Wire |
|---|---|---|
| `ABCD` | Big-endian (Modbus spec default) | `[A,B,C,D]` |
| `CDAB` | Word swap (Siemens, several AB) | `[C,D,A,B]` |
| `BADC` | Byte swap (legacy little-endian-internal devices) | `[B,A,D,C]` |
| `DCBA` | Full reverse (some EtherNet/IP gateways) | `[D,C,B,A]` |
For 8-byte values (Int64 / Float64) the same labels apply pairwise.
### Array count `:N`
`40001:F:5` = `Float32[5]` (consumes HR[0..9]). Array + bit suffix is
rejected. Strings are not arrays.
An array written through the grammar string alone (a **string-only** tag —
`addressString` with no `region`/`address` keys) is served and written by the
driver, but its OPC UA node stays **read-only**: whether a write fits is
decided at compose time, where the driver's family is not known. Pin the keys
(the editor's "Resolve with driver family") to make the array writable — see
"Array writes" below.
### Composition
The 3-field shorthand `40001:F:5` is parsed as `(type=F, count=5)` because
`5` isn't a valid byte-order mnemonic. Use the explicit 4-field form
`40001:F:CDAB:5` when you need a non-default order.
## Family-native syntax (#144)
When the driver instance has `Family != Generic`, the parser tries the
family's native syntax FIRST, then falls back to Modicon / mnemonic.
### DL205 (AutomationDirect DirectLOGIC)
| Form | Example | Mapping |
|---|---|---|
| `Vnnnn` (octal) | `V2000` | HoldingRegisters[1024] (octal 2000 = decimal 1024) |
| `Ynn` (octal) | `Y17` | Coils[2048 + 15] (Y-output base + offset) |
| `Cnn` (octal) | `C100` | Coils[3072 + 64] (C-relay base + offset) |
| `Xnn` (octal) | `X17` | DiscreteInputs[15] |
| `SPnn` (octal) | `SP10` | DiscreteInputs[1024 + 8] |
**Cross-family ambiguity**: `C100` means Coils[99] under `Generic`
(mnemonic) but Coils[3136] under `DL205`. Per-driver Family choice
disambiguates.
### MELSEC (Mitsubishi)
| Form | Example | Mapping (sub-family Q_L_iQR / F_iQF) |
|---|---|---|
| `Dnnn` (decimal) | `D100` | HoldingRegisters[100] |
| `Mnnn` (decimal) | `M50` | Coils[50] |
| `Xnn` | `X20` | DiscreteInputs[32 hex / 16 octal] |
| `Ynn` | `Y20` | Coils[32 hex / 16 octal] |
X / Y digit interpretation depends on `MelsecSubFamily`:
- `Q_L_iQR` → hex (default)
- `F_iQF` → octal
Bank-base offsets default to 0 in the grammar string. Sites with non-zero
"Modbus Device Assignment" bases use the structured tag form.
## Driver-instance options
Beyond per-tag addressing, `ModbusDriverOptions` exposes (#139–#143):
### Connection (#139)
- `KeepAlive { Enabled, Time, Interval, RetryCount }` — TCP-level probes.
Defaults match the historical PR 53 wire output (Enabled=true, Time=30s,
Interval=10s, RetryCount=3).
- `IdleDisconnectTimeout` — proactively close + reconnect after this much
socket idle time. Default null = disabled.
- `Reconnect { InitialDelay, MaxDelay, BackoffMultiplier }` — geometric
backoff for the post-drop reconnect loop. Default
`(0, 30s, 2.0)` = immediate first retry, geometric thereafter.
### Protocol (#140)
- `MaxCoilsPerRead` (default 2000) — separate cap for FC01/FC02 coil reads.
- `UseFC15ForSingleCoilWrites` — force FC15 (write multiple coils
qty=1) for single-coil writes. Safety/audit PLCs may require this.
- `UseFC16ForSingleRegisterWrites` — same for FC16 vs FC06.
- `UseFC23ForMultiRegisterWrites` (default `false`) — opt-in: a 2–121-register
holding write is sent as one FC23 (write + read-back). A unit answering
exception 01 moves to FC16 until the next re-init. Without the key the
wire stays FC16 (#741).
- `DisableFC23` — hard kill switch: never send FC23, even when opted in.
### Subscribe (#141)
- Per-tag `Deadband` — suppress sub-threshold publishes on numeric tags.
- `WriteOnChangeOnly` (driver-level) — short-circuit identical-value
writes. Cache invalidates on read-divergence.
### Multi-unit (#142)
- Per-tag `UnitId` — overrides the driver-level UnitId in the MBAP
header. Required for one-Ethernet-gateway / N-RTU-slave deployments.
- `IPerCallHostResolver.ResolveHost` returns `host:port/unitN` per tag so
per-PLC circuit breakers fire per slave.
- Per-tag `CoalesceProhibited` — escape hatch for #143's planner (read
this tag in isolation regardless of `MaxReadGap`).
### Block-read coalescing (#143)
- `MaxReadGap` — gap budget the planner is willing to bridge between
adjacent tags of one (unit, region). With `MaxReadGap=10`, three tags at
HR 100/102/110 collapse into one FC03 of quantity 11. An explicit `0` =
coalescing off (its historical meaning); the default `8` applies only when
the key is absent (#741). Coils / DiscreteInputs (gap in bits), `String`
scalars and same-word `BitInRegister` tags coalesce too.
- `DisableReadCoalescing` — turn coalescing off regardless of the gap.
### Coalescing auto-recovery (#148 / #150 / #151 / #152)
- A coalesced read that fails with a Modbus exception (write-only or
protected register mid-block) records the failed range as
auto-prohibited. The planner stops re-coalescing across the range; the
per-tag fallback path keeps healthy members working in the same scan.
- **Bisection (#150)**: every re-probe pass narrows multi-register
prohibitions by trying the two halves separately. Over log2(span)
ticks the prohibition pins at the actual offending register(s);
intermediate halves that succeed get cleared.
- **Periodic re-probe (#151)**: opt in via
`AutoProhibitReprobeInterval` (TimeSpan?). Default null = disabled
(prohibitions persist for the driver lifetime; clear on
`ReinitializeAsync`).
- **Per-tag escape hatch**: `CoalesceProhibited` (bool, default false)
on `ModbusTagDefinition`. The planner reads such tags in isolation
regardless of `MaxReadGap`. Use for known-bad addresses you want to
exclude from the auto-discovery loop.
- **Diagnostics (#152)**: `ModbusDriver.GetAutoProhibitedRanges()`
returns a snapshot of every active prohibition as
`ModbusAutoProhibition` records (UnitId / Region / StartAddress /
EndAddress / LastProbedUtc / BisectionPending). Surface in the
driver-diagnostics RPC channel when that wiring lands; for now
consumable by in-process callers (Server health endpoints, log
aggregation).
## JSON DTO shape
The factory accepts both the structured form (legacy) and the new
`AddressString` form per-tag. Mix freely — newer pasted rows use the
grammar string; legacy rows keep the structured fields.
```json
{
"host": "10.1.2.3",
"port": 502,
"unitId": 1,
"family": "DL205",
"keepAlive": { "enabled": true, "timeMs": 30000, "intervalMs": 10000, "retryCount": 3 },
"idleDisconnectMs": 120000,
"reconnect": { "initialDelayMs": 0, "maxDelayMs": 30000, "backoffMultiplier": 2.0 },
"maxCoilsPerRead": 2000,
"writeOnChangeOnly": false,
"maxReadGap": 8,
"tags": [
{ "name": "Temp", "addressString": "V2000:F:CDAB" },
{ "name": "Setpoint", "addressString": "40001:I" },
{ "name": "Outputs", "addressString": "Y0:5" },
{ "name": "AlarmCount", "region": "HoldingRegisters", "address": 200, "dataType": "Int16", "deadband": 5.0 }
]
}
```
## Vendor compatibility caveat
The exact spelling of type codes (e.g. `I` vs `INT`, `BCD` vs `L_BCD`) and
the byte-order mnemonics were synthesised from training-era vendor docs
(Wonderware DASMBTCP, Kepware KEPServerEX, Ignition, Matrikon, OAS).
Before locking the grammar for a production deployment, verify against
the current Kepware "Modbus Ethernet Driver Help" PDF and Ignition's
"Modbus Addressing" user-manual page — if a critical tool's mnemonics
have shifted, add aliases in `ModbusAddressParser.TryParseType` rather
than asking users to rewrite spreadsheets.
## Address strings, families and region/type rules (#741)
- **One authority: `ModbusTagAddressResolution` (Driver.Modbus.Contracts).** The
driver's tag reader, the deploy gate (`Inspect`), the AdminUI editor model
(load / save / `Validate` / the hint text) and the CSV import/export all ask
it which part of a blob is the address; none restates the rule. Its
agreement is pinned by one table-driven test that runs every persisted shape
through every consumer (`ModbusAddressAuthorityAgreementTests`).
- **Whenever a tag carries both `region` and `address`, those keys are its
address** — a classic tag, an editor-pinned tag, and a pre-#741 row that
carried an `addressString` beside its keys (the old driver never read the
string) all load from the keys, exactly as before, and a family change never
remaps them. Only a **string-only** blob (an `addressString` with NO
`region`/`address` — CSV / API authoring) is resolved through
`ModbusAddressParser` with the **driver's** `Family` / `MelsecSubFamily`; a
family that cannot parse it refuses the tag (BadNodeIdUnknown). It is never
served as HR[0].
- `"addressResolved": true` is editor display / CSV state only: it never makes
keys authoritative, and a marker on a blob WITHOUT keys is ignored (the blob
is string-only) and dropped on the next editor save.
- The AdminUI never writes default keys it did not resolve: the editor model
stamps `region`/`address`/type only when the loaded blob had the keys, or when
a field is set (hand edit, CSV address cell, Resolve). A string-only,
non-string-`addressString` or address-less blob keeps its keys unwritten, and
its CSV export leaves the address cells blank.
- The editor's "Resolve with driver family" persists the resolved
`region`/`address`/type fields plus `"addressResolved": true` (the pinned
state). Editing a resolved field by hand in the editor drops the string and
the marker. A typed CSV address cell keeps them only while the string still
describes the cells under some family (so an unchanged export → import of a
pinned row is lossless); a contradicting cell drops them, and the import
review grid reports that column as an override.
- Coils / DiscreteInputs carry only Bool. A bit-region tag persisted with a
register `dataType` (the pre-#741 editor saved `Int16`) is coerced to Bool,
never refused. A register region with `Bool` is refused (use
`BitInRegister`).
- Exception 01/02/03 are device refusals: per-tag Bad, one Warning per tag,
no driver Degraded; reads and writes share one comms-fault health slot.
## Array writes (#610, #741)
Whether an array node is client-writable is decided by
`DriverArrayWriteSupport` (Core.Abstractions) at compose time, and it says yes
only for what `ModbusDriver.WriteAsync` encodes end to end
(`ModbusArrayWriteSupportParityTests` pins the two against each other):
- **Keys only.** The tag must carry `region` + `address` (read as strictly as
the driver reads them). A string-only tag stays read-only — the composer
cannot resolve the grammar under the driver's family.
- **Coils:** one FC15 of at most 1968 coils (the spec ceiling; the driver does
not chunk). Any `dataType` — a bit region is coerced to Bool.
- **HoldingRegisters:** one FC16 whose register count fits
`maxRegistersPerWrite` (default 123; the smallest value on the driver or the
tag's device wins). Registers per element: 1 / 2 / 4 for the numeric types,
`(stringLength+1)/2` for `String` (each element nul-padded to that width), 1
for `BitInRegister` (the span is read with one FC03, the addressed bit of each
register is set or cleared, and the span is written back with one FC16 —
the other 15 bits are preserved; `bitIndex` 0–15, the span must end at or
before register 65535). FC23 (`useFC23ForMultiRegisterWrites`) is opt-in,
capped at 121 registers and falls back to FC16 above that, so it never
changes which arrays are writable.
- **Never writable:** DiscreteInputs / InputRegisters, Bool in a register
region, a `String` with no `stringLength`, a `bitIndex` above 15, a missing
or zero `arrayLength`, and a `String` / `DateTime` node over a numeric or bit
element (such an element never converts). Elements otherwise convert, so a
ScadaBridge `int[]` to an `Int16` node is writable.