v2-ci / unit-tests (push) Failing after 16m11s
docs(drivers): un-stale the MQTT README rows + track every known gap as an issue
The cross-driver README still described MQTT as pre-P2 — "Sparkplug B is P2
(`mode: SparkplugB` is a placeholder)" and "Sparkplug B has no fixture yet (P2)".
Both were false as of the P2 merge (c3a2b0f7): SparkplugB is a fully implemented
mode and the live suite is 15 tests (7 plain + 8 Sparkplug) against a
project-owned C# edge-node simulator. Mqtt.md and the scadaproj index were both
already correct; only this file missed the P2 sweep.

Filed the nine Known-gaps rows as tracking issues and linked them, so the table
stops being the only record of them:

  #507  IRediscoverable is inert in v3 (platform gap — also Galaxy/TwinCAT/AbCip)
  #508  write-through (IWritable) — NCMD/DCMD + plain publish
  #509  a metric name containing '/' cannot be browse-committed
  #510  _canRebirth captured at browse-open — reaped session still draws button
  #511  Sparkplug primary-host STATE publishing (ActAsPrimaryHost)
  #512  .Browser references .Driver — extract the client-options builder
  #513  editor writes a meaningless payloadFormat into a Sparkplug blob
  #514  Request-rebirth unarmable on a plant that birthed before the window
  #515  DataSet / Template / PropertySet metric support

#507 is the one worth reading: it is a v3 platform gap, not an MQTT bug —
DriverHostActor.HandleDiscoveredNodes hard-returns, so every IRediscoverable
driver fires into a void and the edge gaining a point needs a redeploy to show up.

No code change; docs + issue links only.
2026-07-27 13:52:08 -04:00

398 lines
28 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# MQTT Driver
In-process MQTT **broker-subscribe** driver. It holds one MQTTnet 5 client against one broker,
subscribes to the topics its authored tags name, and forwards each PUBLISH straight to
`ISubscribable.OnDataChange`. Ingest is **push, not poll**, and **one-way** — there is no `IWritable`.
**Two ingest shapes, selected by the driver's `Mode`:** `Plain` binds a tag to a concrete MQTT topic;
`SparkplugB` binds it to a `group / edge node / device? / metric` tuple and decodes Eclipse-Tahu
protobuf under one `spBv1.0/{GroupId}/#` subscription. Both run over the same single client.
See [Mqtt-Test-Fixture.md](Mqtt-Test-Fixture.md) for the harness and
[`../plans/2026-07-15-mqtt-sparkplug-driver-design.md`](../plans/2026-07-15-mqtt-sparkplug-driver-design.md)
for the design.
> **Status.** P1 (plain MQTT) and P2 (Sparkplug B ingest) are both shipped and live-gated against the
> Mosquitto + Sparkplug-simulator fixture. Write-through (`IWritable` — NCMD/DCMD/plain publish) is
> **deferred** ([#508](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/508)); every MQTT node
> materializes read-only. See [Known gaps](#known-gaps) — every entry there carries a tracking issue
> (#507#515).
## Project Layout
| Project | Holds |
|---|---|
| `Driver.Mqtt.Contracts` | Config records, enums, `MqttTagDefinition` + the pure `MqttTagDefinitionFactory`, and the one shared `MqttJson.Options`. **Deliberately transport-free** — no MQTTnet reference |
| `Driver.Mqtt` | Runtime: `MqttDriver`, `MqttConnection` (connect + reconnect supervisor), `MqttSubscriptionManager`, `LastValueCache`, factory registration, `MqttDriverProbe` |
| `Driver.Mqtt.Browser` | `MqttDriverBrowser` + `MqttBrowseSession` — the AdminUI address picker's `#`-observation session |
> `.Browser` references `.Driver` (not just `.Contracts`) — a **documented, deliberate exception**
> so browse can reuse `MqttConnection.BuildClientOptions` (TLS / CA-pin / credentials / protocol
> mapping). Its cost is pulling `Core` into the AdminUI graph. The csproj carries a boxed warning;
> do not copy the pattern into a new driver's browser. The clean fix — extract the pure
> options builder down into `.Contracts` — is tracked as
> [#512](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/512).
## Capability Surface
```csharp
public sealed class MqttDriver
: IDriver, ITagDiscovery, ISubscribable, IReadable, IHostConnectivityProbe, IRediscoverable, IAsyncDisposable, IDisposable
```
| Capability | Entry point | Notes |
|---|---|---|
| `IDriver` | `InitializeAsync` / `ReinitializeAsync` / `ShutdownAsync` / `GetHealth` | Order **register → attach → connect** is contractual. `ReinitializeAsync` applies a tag-only delta in place, and rebuilds the session when the broker identity changed |
| `ITagDiscovery` | `DiscoverAsync` | Replays **only the authored `rawTags`** into an `Mqtt` folder. `SupportsOnlineDiscovery => false`. `RediscoverPolicy` is `Once` in Plain and **`UntilStable` in Sparkplug** (half of what a Sparkplug tag needs — its datatype — is only knowable from a birth) |
| `ISubscribable` | `SubscribeAsync` / `OnDataChange` | One SUBSCRIBE per distinct authored topic. **`publishingInterval` is ignored** — MQTT is push-based; this driver neither polls nor throttles |
| `IReadable` | `ReadAsync` | Serves the last received/retained value from `LastValueCache`; never throws. A never-seen tag reads `BadWaitingForInitialData` |
| `IHostConnectivityProbe` | `GetHostStatuses` | 1-second poll of `MqttConnection.State`; `HostName` is `"{host}:{port}"` |
| `IRediscoverable` | `OnRediscoveryNeeded` | Nothing raises it in Plain mode. **Sparkplug raises it** when a birth for an *authored* scope carries a metric-name set different from the last one seen for that scope — both conditions are anti-storm, see [Rediscovery](#rediscovery-sparkplug) |
**Not implemented:** `IWritable`, `IPerCallHostResolver`, `IAlarmSource`, `IHistoryProvider`.
Materialized nodes are `SecurityClassification.ViewOnly`, `IsAlarm: false`, `IsHistorized: false`
*"MQTT ingest is one-way … ViewOnly rather than an Operate node whose writes would silently vanish."*
Driver-type string: **`Mqtt`** (`DriverTypeNames.Mqtt`).
## Configuration
Bound through `MqttJson.Options`**case-insensitive**, enums by **name**, unknown members skipped.
**The whole connection is authored on the DRIVER** (`DriverConfig`), via `MqttDriverForm` in the `/raw`
driver-config modal. Unlike Modbus / S7 / OPC UA Client, MQTT does **not** use the v3
endpoint→`DeviceConfig` split: an MQTT driver instance holds exactly one broker session, so
`MqttDeviceForm` is informational (the same shape as `GalaxyDeviceForm`) and devices under an MQTT
driver are pure organisational grouping in the RawPath.
> **Why not the device.** `DriverDeviceConfigMerger` merges a device's keys up to the top level *only
> when the driver has exactly one device*. A device-authored broker connection therefore disappears
> from the merged blob the moment a second device is added — a silent outage with nothing to see at
> deploy time. Driver-level authoring is correct for 0, 1 or N devices. A pre-form deployment that put
> the connection on a sole device still works (merge-up wins over the driver's keys) and
> `MqttDeviceForm` flags those keys so the mismatch is visible; move them to the driver.
`DriverDeviceConfigMerger` still merges driver + device and injects `rawTags`.
```jsonc
// DriverConfig — authored by MqttDriverForm. PascalCase keys, enums as names.
{
"Host": "10.100.0.35",
"Port": 8883,
"UseTls": true,
"AllowUntrustedServerCertificate": false,
"CaCertificatePath": null, // pins the chain; null = OS trust store
"Username": "otopcua",
"Password": "", // never commit
"ProtocolVersion": "V500",
"CleanSession": true,
"KeepAliveSeconds": 30,
"ConnectTimeoutSeconds": 15,
"ReconnectMinBackoffSeconds": 1,
"ReconnectMaxBackoffSeconds": 30,
"MaxPayloadBytes": 1048576,
"Mode": "Plain",
"Plain": { "TopicPrefix": "", "DefaultQos": 1 }
}
// DeviceConfig — empty; MQTT has no per-device endpoint.
{}
```
### `Sparkplug` sub-object (`Mode: "SparkplugB"`)
```jsonc
{
"Mode": "SparkplugB",
"Sparkplug": {
"GroupId": "OtOpcUaSim", // REQUIRED — the driver's whole subscription scope
"HostId": "", // Host Application identity; receive-only (see below)
"ActAsPrimaryHost": false, // NOT IMPLEMENTED — logs a warning when true
"RequestRebirthOnGap": true, // a seq gap asks the edge node to re-announce (NCMD)
"BirthObservationWindowSeconds": 15 // how long discovery collects births before calling it stable
}
}
```
| Key | Default | Notes |
|---|---|---|
| `GroupId` | `""` | **Required.** The driver subscribes exactly `spBv1.0/{GroupId}/#`. Blank ⇒ it connects, reports `Healthy`, and ingests **nothing**. It is a literal topic segment, so `/`, `+`, `#` are refused by the form |
| `HostId` | `""` | Sparkplug Host Application identity. **Receive-only** — the driver observes `STATE` and never publishes one |
| `ActAsPrimaryHost` | `false` | **Not implemented.** Setting it logs a startup **warning** rather than being silently inert — being a primary host is a three-part contract (retained `ONLINE`, a matching `OFFLINE` registered as the MQTT Will *at connect time*, an explicit `OFFLINE` on clean shutdown), and shipping the `ONLINE` half without the Will is strictly worse than shipping neither: a crashed node would leave a retained `ONLINE` asserting forever that a dead host is alive |
| `RequestRebirthOnGap` | `true` | On a detected sequence-number gap, publish a rebirth-request NCMD instead of running on stale metric state |
| `BirthObservationWindowSeconds` | `15` | Discovery's birth-collection window. Must be ≥ 1 |
`MqttDriverForm` authors all five in Sparkplug mode. The sub-object is **merged, never replaced** (a
key a newer driver adds inside it survives an older AdminUI), and in `Plain` mode it is not touched at
all — so flipping a driver to Plain to look at it and back does not lose the group id. The form never
writes `RawTags`; the deploy artifact owns it.
> **This was a live-gate finding.** Through the P2 implementation `MqttDriverForm` still carried its P1
> placeholder — switching Mode to `SparkplugB` rendered a "not available yet" notice and **no group-id
> field**, so once Sparkplug ingest shipped there was no way to author a Sparkplug driver from the
> AdminUI at all. Pinned by `MqttDriverFormModelTests`' Sparkplug cases.
Every key has a default, so nothing is strictly required by the binder. Notable ones:
`port` **8883**, `useTls` **true**, `protocolVersion` **V500**, `cleanSession` **true**,
`keepAliveSeconds` **30**, `connectTimeoutSeconds` **15**,
`reconnectMinBackoffSeconds` **1** / `reconnectMaxBackoffSeconds` **30**,
`maxPayloadBytes` **1 MiB**, `allowUntrustedServerCertificate` **false**.
> ⚠️ **Leave `clientId` unset on a redundant pair.** Both nodes of a pair run the driver. MQTT
> requires client ids to be unique per broker, so a *fixed* `clientId` makes the two nodes evict each
> other forever — the broker logs `Client <id> already connected, closing old connection` and both
> nodes reconnect every few seconds while still reporting `Healthy`. Unset (the default) lets MQTTnet
> generate a unique id per connection, which is correct. This was observed live during the P1 gate.
> (The probe and browser already self-uniquify with `-probe-` / `-browse-` suffixes.) `MqttDriverForm`
> defaults the field blank and raises this warning inline the moment a value is typed.
The form validates every knob against the driver's own `[Range]` bounds (port 165535, keep-alive /
connect-timeout / backoffs ≥ 1 s, max-backoff ≥ min-backoff, `maxPayloadBytes` ≥ 1, QoS 02) and
additionally **clamps** on serialize, so an operator who ignores the inline error still cannot persist
a `connectTimeoutSeconds: 0` driver-brick.
## Tag Configuration
A tag binds in **one of two shapes**, and which one is decided by *which keys are present*, not by a
`mode` key on the tag. `MqttTagDefinitionFactory` reads the Sparkplug tuple when any Sparkplug
descriptor key is set, and the topic otherwise; the AdminUI's "Tag shape" selector infers the same way
on reopen. The key names are single-sourced in `MqttTagConfigKeys` so the browse-commit mapper and the
factory cannot drift.
### Plain shape
| Key | Type | Default | Notes |
|---|---|---|---|
| `topic` | string | — | **Required.** Absent/blank rejects the tag ⇒ `BadNodeIdUnknown` |
| `payloadFormat` | `Json` \| `Raw` \| `Scalar` | `Json` | **Strict** — a typo'd value rejects the tag |
| `jsonPath` | string | `"$"` | Absent *or empty* ⇒ document root. `Json` only |
| `dataType` | `DriverDataType` | `String` | **Strict.** `Float64`, not `Double` — see below |
| `qos` | int 02 | driver's `defaultQos` | **Strict** — a malformed value rejects rather than silently weakening delivery |
| `retainSeed` | bool | `true` | Seed this tag from the broker's retained message on subscribe |
There is **no `mode` key** — the AdminUI's "Tag shape" selector is UI-only, inferred from the blob and
never serialized.
**`dataType` uses `DriverDataType`, which has `Float64` and has no `Double`.** Authoring `"Double"` is
a strict-enum rejection, not a fallback.
Payload handling: `Json` selects via JSONPath then coerces (miss ⇒ `BadDecodingError`, coerce fail ⇒
`BadTypeMismatch`); `Raw` returns the payload's UTF-8 text verbatim and **ignores `dataType`**;
`Scalar` decodes then coerces. The JSONPath subset is `$`, `$.a.b`, `$['a']`, `$.a[0]` — **no
filters, slices, wildcards or recursive descent**.
### Wildcards
The **runtime accepts** a `+`/`#` topic (it is ambiguous, not unparseable) and the deploy-time
`Inspect` pass **warns**. The **AdminUI editor rejects** it outright — the one place the editor is
deliberately stricter than the driver, because one Tag holds one value and a wildcard would feed it
from many source topics. Wildcard tags are indexed **by filter**, not by concrete topic, so they
survive a reconnect; a message fans out to *every* matching tag, and unauthored topics are dropped.
### Sparkplug shape
| Key | Type | Default | Notes |
|---|---|---|---|
| `groupId` | string | — | **Required.** Must match the driver's `Sparkplug.GroupId` to ever receive a message |
| `edgeNodeId` | string | — | **Required.** |
| `deviceId` | string | *absent* | **Omit** for a metric published by the edge node itself (NBIRTH/NDATA). Absent is meaningfully different from `""` |
| `metricName` | string | — | **Required.** The tag's stable binding key across rebirths. **May contain `/`**`Node Control/Rebirth` and `Properties/Serial Number` are canonical Sparkplug names, and the whole name is one value, never split |
| `dataType` | `DriverDataType` | *from the birth* | **Optional override.** Absent ⇒ take whatever type the birth certificate declared. The AdminUI's "(from birth certificate)" option removes the key entirely |
| `isHistorized` / `historianTagname` | — | — | Server-side historization, unchanged from Plain |
`payloadFormat`, `jsonPath`, `qos` and `retainSeed` are **Plain-only** and meaningless here: a
Sparkplug body is protobuf, and the subscription is one driver-wide `spBv1.0/{GroupId}/#`, not a
per-tag filter.
`groupId` / `edgeNodeId` / `deviceId` are literal MQTT topic segments, so the AdminUI editor refuses
`/`, `+` and `#` in them — a decoded incoming id can never contain one, so such a tag could never
bind. `metricName` is deliberately **exempt**: it is not a topic segment.
```jsonc
// A device metric.
{"groupId":"OtOpcUaSim","edgeNodeId":"EdgeA","deviceId":"Filler1","metricName":"FillCount"}
// A node-level metric — note deviceId is ABSENT, not blank.
{"groupId":"OtOpcUaSim","edgeNodeId":"EdgeA","metricName":"Temperature"}
```
## Sparkplug B Ingest
One subscription (`spBv1.0/{GroupId}/#`) feeds a per-edge-node state machine
(`SparkplugIngestor` + `SparkplugCodec` / `AliasTable` / `BirthCache` / `SequenceTracker`):
- **Births are the only self-describing message.** NBIRTH/DBIRTH name every metric and assign its
alias; NDATA/DDATA carry an **alias and no name at all**. So the alias table is rebuilt *per birth*
and tags bind **by name**, never by alias — aliases are per-birth and may be reused for a different
metric after a rebirth.
- **NBIRTH is node-scoped, DBIRTH is device-scoped**, and routing a DBIRTH through the node path
wipes `bdSeq`. They are handled separately on purpose.
- **Sequence tracking**: `seq` is a wrapping 0255 counter. A detected gap raises a rebirth request
when `RequestRebirthOnGap` is on, rather than silently continuing on stale metric state.
- **Death → STALE.** An NDEATH whose `bdSeq` matches the live session (the bdSeq tie is what stops a
stale death from killing a fresh session) marks every metric under that edge node `Bad` /
`BadNoCommunication`. A DDEATH does the same for one device. The next birth restores them.
- **Unsupported datatypes are skipped with a warning, never guessed**: `DataSet`, `Template`,
`PropertySet`, `PropertySetList`, `Unknown`. `Int8``Int16` and `UInt8``UInt16` widen; `*Array`
variants map to the element type with the array bit set.
- **Ingest state is reset at every session/authoring seam** — a reconnect or a `ReinitializeAsync`
must not carry a previous session's alias table into a new one.
### Rediscovery (Sparkplug)
`OnRediscoveryNeeded` fires only when a birth is **for an authored scope** *and* its metric-name set
**differs** from the last one seen for that scope (order-insensitive, ordinal). Both conditions are
anti-storm, not optimisations: rediscovery triggers an address-space rebuild, and an edge node
re-births freely — on its own schedule, on every reconnect, and once per rebirth NCMD.
> ⚠️ **Nothing consumes the signal today.** No runtime component subscribes to
> `IRediscoverable.OnRediscoveryNeeded`, and `DriverHostActor.HandleDiscoveredNodes` hard-returns —
> discovered-node injection is dormant in v3. The served address space comes from the deploy artifact,
> so **a DBIRTH introducing a new metric does not change the OPC UA tree**; you must redeploy. The
> driver's decision is observable only as an Information log line
> (`… requesting rediscovery.`). This is a v3 platform gap, not an MQTT one.
## Connection + Failure Semantics
`MqttConnectionState`: `Disconnected → Connected → Reconnecting → Faulted → Disposed`.
A broker that is merely down stays **`Reconnecting` indefinitely** — unreachable is never a fault.
Backoff is exponential between the two `reconnectBackoff` bounds.
**MQTTnet 5 does not throw on a rejected CONNACK** — it returns the code and leaves the client
disconnected. Left unhandled, a wrong password produced a `Healthy` driver that never received a
value. `MqttConnection` therefore raises `MqttConnectRejectedException`:
- **Unrecoverable ⇒ `Faulted`, supervisor stops** (retrying cannot help): `MalformedPacket`,
`ProtocolError`, `UnsupportedProtocolVersion`, `ClientIdentifierNotValid`, `BadUserNameOrPassword`,
`NotAuthorized`, `Banned`, `BadAuthenticationMethod`, `TopicNameInvalid`, `PacketTooLarge`,
`PayloadFormatInvalid`, `RetainNotSupported`, `QoSNotSupported`, `ServerMoved`.
- **Everything else is transient** and keeps retrying — including `UnspecifiedError` and any future
code. (`ServerMoved` is permanent, `UseAnotherServer` is temporary — per the MQTT 5 spec.)
A reconnect that completes without re-subscribing would be a healthy-looking connection that receives
nothing forever, so `OnReconnectedAsync` **throws** when zero filters are granted, tearing the session
down rather than swallowing it. A SUBACK failure degrades just the affected RawPaths to
`BadCommunicationError`.
## Browse
`MqttDriverBrowser` opens a **read-only observation session**: it subscribes at QoS 0 to `#` (or
`{topicPrefix}/#`) under a `-browse-`-suffixed client id and builds a `/`-segment tree from whatever
publishes. **Nothing is ever published.** It is *inherently incomplete* — a topic that stays silent
during the window is invisible — so manual entry remains the escape hatch.
Bounds: 50 000 nodes (then `⚠ Observation truncated`), 1024-char topics / 256-char segments (then
`⚠ Some topics were too long`), 512-byte payload inspection. Sessions are reaped after 2 minutes idle.
**Sparkplug B browse serves a different tree from the same passive window**: observed NBIRTH/DBIRTH
certificates are decoded into `Group → EdgeNode → [Device] → Metric` (a birth is the only Sparkplug
message that names its metrics). Same node cap, same bounds, same "publishes nothing" guarantee.
The bespoke browser wins over the universal `DiscoveryDriverBrowser`, which would decline MQTT anyway
(`SupportsOnlineDiscovery` is `false`).
### Browse-commit writes the address the factory reads
A committed leaf's address is a **descriptor**, not a single reference string, so
`RawBrowseCommitMapper` reads it from the `AttributeInfo.AddressFields` the session states — Plain
emits `topic`; Sparkplug emits `groupId` / `edgeNodeId` / `deviceId?` / `metricName`, the names
`MqttTagConfigKeys` single-sources for both the mapper and `MqttTagDefinitionFactory`.
**It is never parsed out of the browse node id.** A Sparkplug node id is
`{group}/{node}[/{device}]::{metric}` and a metric name legitimately contains `/`
(`Node Control/Rebirth`), so splitting the id cannot recover the tuple. Which keys the session emits
is also how the mapper learns the shape — the driver *type* reaching it is just `Mqtt`, and the mode
lives on the driver config. A leaf whose attribute lookup returned nothing carries no address and is
refused **at commit, in words**, rather than committed as a tag that deploys clean and then reports
`BadNodeIdUnknown` forever.
### Request rebirth (Sparkplug only)
Births are never retained, so a healthy but quiet plant shows an **empty** picker tree until one
lands. The `Request rebirth` affordance in the browse modal is the way to fill it on demand: it
publishes a Sparkplug rebirth-request NCMD (`Node Control/Rebirth`) to the selected scope — the **one
and only** browse action that publishes anything.
- **Scope** is the last node clicked in the tree. A device or metric resolves **up to its owning edge
node** (Sparkplug has no device-scoped rebirth); a group fans out to every observed edge node
beneath it and is refused **whole** past 32, publishing nothing.
- **Two clicks, never one** — `Request rebirth…` arms a confirm panel naming the resolved scope and
its consequence; changing the selection disarms it.
- **Gated on `DriverOperator`**, enforced server-side in `BrowserSessionService.RequestRebirthAsync`
(fail-closed) before the session is touched; the UI gate is defence in depth. A refusal — policy,
over-wide group, unresolvable scope — is **shown**, not swallowed.
- Offered only for a Sparkplug session (`IRebirthCapableBrowseSession.RebirthAvailable`); a Plain
MQTT window publishes nothing, ever.
### Refresh
An observation window **accumulates**, but the tree renders **once**, when it is created — and
`OpenAsync` returns as soon as the SUBSCRIBE is granted, without waiting for the birth-observation
window. So the first render is normally empty on Plain (a topic that has not published yet is
invisible) and *almost always* empty on Sparkplug (births are never retained). **Refresh** re-reads
the root against the same session: nothing reconnects, nothing already observed is lost, and the tag
selection is kept. Only the armed rebirth scope is cleared, because the node it named may no longer be
in the rebuilt tree.
> **Also fixed by this gate, and not MQTT-specific:** every node label in the shared
> `DriverBrowseTree` was an `<a href="#">`. `blazor.web.js`'s enhanced-navigation click interceptor
> resolves a bare `#` against `<base href="/">`, so clicking a node **label** navigated the whole
> AdminUI to `/` and destroyed the hosting modal (`@onclick:preventDefault` suppresses the browser's
> default action, not Blazor's interceptor). The labels are now `<button type="button">`. This
> affected **every** driver's picker since 2026-05-28; it surfaced here because choosing a rebirth
> scope is the first flow that requires clicking a label rather than the ▶ toggle.
> ⚠️ **Known gap — a completely empty tree cannot arm a rebirth.** The rebirth scope is taken from the
> last node clicked *in the tree*, so on a plant that has not birthed since the window opened there is
> nothing to click and `Request rebirth…` stays disabled — the exact case the affordance exists for.
> `MqttBrowseSession.ResolveRebirthTargets` already accepts a bare `{group}/{edgeNode}` for a node the
> window has never seen (it calls that "the prime rebirth target"); what is missing is a UI path to
> enter one, or to default the scope to the driver's own configured `GroupId`. Until then: use
> **Refresh** after any birth, or author the tags by **Manual entry**, which is always available.
## Test Connect
`MqttDriverProbe` performs **one CONNECT** (no SUBSCRIBE, no publish) under a `-probe-` client id and
disconnects. Success message: `"MQTT CONNECT OK"`. A rejected CONNACK is described by the same
`DescribeConnackRejection` the running driver uses, so the button and the driver report a rejection in
identical words. See [TestConnectProbes.md](TestConnectProbes.md).
## Testing
- **Unit** — `tests/Drivers/…Driver.Mqtt.Tests` (**581 tests**): tag-config mapping (both shapes),
JSONPath subset, strict-enum rejection, subscription indexing (incl. the wildcard-by-filter case),
reconnect/rebuild branches, CONNACK classification, and the Sparkplug half — golden-payload decode,
topic parse/format, datatype map, alias/birth-cache rebuild, sequence + bdSeq-death ties, the
rediscovery change gate, and the browse session's "publishes nothing" assertion.
- **Live (env-gated)** — `tests/Drivers/…Driver.Mqtt.IntegrationTests` (**15 tests**) against the
Mosquitto broker + the C# Sparkplug edge-node simulator; skips cleanly when `MQTT_FIXTURE_ENDPOINT`
is unset. See [Mqtt-Test-Fixture.md](Mqtt-Test-Fixture.md) and `infra/README.md` §3.
- **AdminUI** — `MqttDriverFormModelTests` / `MqttTagConfigModelTests` cover both editors'
round-trip, mode inference and validation. AdminUI has no bUnit, so the razor shells themselves are
only ever proven by a live `/run` gate.
## Operational Notes
- **Read-only.** No writes reach the broker; every node is ViewOnly. Sparkplug NCMD is used for
**rebirth requests only** — never to command a device.
- **No alarms, no driver-side history.** Historization is a server-side concern (`isHistorized`).
- **Both pair nodes subscribe independently** — MQTT fan-out is per-connection, and the Primary gate
applies downstream, not to ingest. This is also why `clientId` must stay unset (above).
- **Unauthored traffic is ignored.** A busy broker is normal; the driver never auto-provisions a tag.
## Known gaps
Every row is tracked. None is a silent failure — each either refuses in words or logs.
| Gap | Issue | Effect | Notes |
|---|:---:|---|---|
| **Write-through (`IWritable`)** | [#508](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/508) | Every MQTT node is read-only | Deferred to P3 — NCMD/DCMD + plain publish, optimistic-Good + self-correct on echo |
| **Rediscovery is inert** | [#507](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/507) | A DBIRTH introducing a metric does not change the OPC UA tree; redeploy to pick it up | v3 **platform** gap, not MQTT-specific — nothing subscribes to `OnRediscoveryNeeded` and `DriverHostActor.HandleDiscoveredNodes` hard-returns. Also affects Galaxy / TwinCAT / AbCip. Driver-side decision is log-observable |
| **Rebirth needs a non-empty tree** | [#514](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/514) | `Request rebirth…` cannot be armed on a plant that has not birthed since the window opened | See [Refresh](#refresh). Session side already supports a bare `{group}/{edgeNode}` scope |
| **`_canRebirth` is captured at browse-open** | [#510](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/510) | A session reaped for idleness (2 min) still draws the button, and using it errors | The error is shown, not swallowed; reopen the browser |
| **Primary-host STATE publishing** | [#511](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/511) | `ActAsPrimaryHost` does nothing | Logs a startup warning rather than being silently inert — see the `Sparkplug` sub-object table |
| **A metric whose name contains `/` cannot be browse-committed** | [#509](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/509) | The commit is refused **whole**, in words (`Row N: Name must not contain '/'`) | The derived **tag Name** is a RawPath segment and may not contain `/`, while `metricName` legitimately may. This blocks the spec-mandatory `Node Control/Rebirth`. **Workaround: Manual entry** — author the tag with a `/`-free name and type the slashed `metricName` into the Sparkplug editor, which accepts it. Nothing is silently mis-bound |
| **`DataSet` / `Template` / `PropertySet` metrics** | [#515](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/515) | Skipped with a warning | v1-unsupported; never coerced into a guessed type |
| **The tag editor writes `payloadFormat` into a Sparkplug blob** | [#513](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/513) | Cosmetic only | `payloadFormat` is Plain-only; the factory routes on the Sparkplug keys and ignores it. Noise in the blob, not a mis-binding |
| **`.Browser` references `.Driver`, not just `.Contracts`** | [#512](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/512) | A documented layering exception | Taken to reuse `MqttConnection.BuildClientOptions` rather than duplicate TLS/CA-pin logic — see the note at the top of this doc |