`ActAsPrimaryHost` was accepted by config and by the AdminUI form and did nothing but
log a warning. It now delivers the whole three-part contract or none of it: a retained
`ONLINE` on `spBv1.0/STATE/{hostId}`, a matching retained `OFFLINE` armed as the MQTT
Last Will, and an explicit `OFFLINE` on a clean stand-down.
**The claim is a dedicated connection, not a message.** A Will can only be registered in
the CONNECT packet — it cannot be added to a live session, changed, or withdrawn. So a
claim that is acquired and released at runtime cannot ride the long-lived ingest session.
`SparkplugPrimaryHost` opens its own connection (client id `{clientId}-spbhost`, forced
clean-session) when the node gains Primary and closes it when the node loses Primary; the
connection's lifetime *is* the claim, so every leg follows from its lifecycle. Ingest is
untouched by a role change — no dropped subscriptions, no lost birth cache, no data gap at
the Secondary->Primary transition.
**Primary-gated** (owner decision, recorded on the issue). Both pair nodes subscribe
independently, so an ungated claim means both claim the same host id — and the sharp
failure is not the two fighting over the retained STATE, it is that the SECONDARY's death
fires its Will and publishes OFFLINE while the Primary is healthy, stopping every edge node
in the group. Registering the Will only on whichever node is Primary at connect time fails
the other way: a node that later gains Primary would publish ONLINE with no Will behind it.
New seam: `IDriverPrimaryRoleSource` (`Core.Abstractions`) carrying the *data-plane* verdict
(`PrimaryGatePolicy.ShouldServiceAsPrimary`), not the alarm-drain verdict — an unknown role
with a driver peer present must deny. Registered unconditionally by `AddOtOpcUaRuntime`,
deliberately NOT alongside `IRedundancyRoleView`, which `AddAlarmHistorian` registers only
when that section is enabled: piggybacking would leave a pair with no alarm historian
falling back to "claim unconditionally". Polled on a 1s timer rather than evented — a
process singleton raising events at per-instance drivers outlives every driver it holds.
Accepted trade: a brief edge-visible OFFLINE window during failover. That is a genuine
state transition, not a glitch to hide.
Live-gated 5/5 against the Mosquitto fixture, including the Will leg — `AbandonForTests`
drops the socket with no DISCONNECT, because a clean disconnect makes the broker discard
the Will by protocol rule, so a test driven through `StopAsync` would observe the
stand-down OFFLINE and pass against an implementation that never armed a Will. Falsified:
removing the Will turns that leg and only that leg red.
Also corrects two stale claims found en route: the AdminUI form still said MQTT tags are
read-only (#508 shipped), and the driver doc still said nothing consumes `IRediscoverable`.
Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
OtOpcUa
OPC UA server (.NET 10 AnyCPU) that exposes a fleet of industrial drivers as a single OPC UA address space. Drivers ship in-process for AVEVA System Platform Galaxy (via the sibling mxaccessgw repo), Modbus TCP, Siemens S7, Allen-Bradley CIP (ControlLogix / CompactLogix), Allen-Bradley Legacy (SLC 500 / MicroLogix), Beckhoff TwinCAT (ADS), FANUC FOCAS, OPC UA Client (gateway), and MQTT (broker subscribe; Sparkplug B in progress).
A cross-platform client stack (.NET 10) — shared library, CLI, and Avalonia desktop app — connects to any OPC UA server.
Architecture
OPC UA Clients (CLI, Desktop UI, 3rd-party)
|
v
+-------------------------------------+
| OtOpcUa.Server (.NET 10 AnyCPU) |
| address space + capability fan-out|
+-------------------------------------+
| | | | | | | |
Galaxy Modbus S7 AbCip AbLeg TwinCAT FOCAS OpcUaClient MQTT
|
v
mxaccessgw (sibling repo, gRPC)
|
v
MXAccess COM (x86 worker, on AVEVA box)
Galaxy is the only driver with an external runtime: it speaks gRPC to a separately installed mxaccessgw server (sibling repo at c:\Users\dohertj2\Desktop\mxaccessgw\) which owns the MXAccess COM apartment and the x86/STA bitness constraint server-side. Everything in this repo is platform-agnostic .NET 10.
Prerequisites
- .NET 10 SDK (server, drivers, clients all target .NET 10)
- SQL Server reachable for the central config DB
- For Galaxy specifically: a running
mxaccessgwdeployment — see docs/v2/Galaxy.ParityRig.md - For historian read-back / alarm history / continuous historization: a running
ZB.MOM.WW.HistorianGatewaydeployment (the sole historian backend; consumed as theZB.MOM.WW.HistorianGateway.ClientgRPC package). It must runRuntimeDb:Enabled=true+RuntimeDb:EventReadsEnabled=true, and the API key must carryhistorian:read+historian:write+historian:tags:writescopes.
Quick Start
dotnet restore ZB.MOM.WW.OtOpcUa.slnx
dotnet build ZB.MOM.WW.OtOpcUa.slnx
dotnet test ZB.MOM.WW.OtOpcUa.slnx
# Run the server in dev (foreground)
dotnet run --project src/Server/ZB.MOM.WW.OtOpcUa.Host
The server starts on opc.tcp://localhost:4840 with the None security profile. Configure Security.Profiles in src/Server/ZB.MOM.WW.OtOpcUa.Host/appsettings.json to enable Basic256Sha256-Sign or Basic256Sha256-SignAndEncrypt. See docs/security.md.
Install as Windows Services
Production deployment is driven by scripts/install/Install-Services.ps1, which registers the OtOpcUa server service under a chosen service account. Historian support requires a separately deployed ZB.MOM.WW.HistorianGateway and Galaxy support a separately installed mxaccessgw — neither this repo nor the install script provisions them.
.\scripts\install\Install-Services.ps1 `
-InstallRoot 'C:\Program Files\OtOpcUa' `
-ServiceAccount 'DOMAIN\svc-otopcua'
The historian backend is the external ZB.MOM.WW.HistorianGateway (not installed by this script). See the script header and docs/ServiceHosting.md for full options.
Client CLI
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- connect -u opc.tcp://localhost:4840
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- browse -u opc.tcp://localhost:4840 -r -d 3
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- read -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode"
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- write -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -v 42
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- subscribe -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -i 500
See docs/Client.CLI.md and docs/Client.UI.md.
Documentation
Architecture deep-dives
| Topic | Doc |
|---|---|
| OPC UA server composition, namespace fan-out, Polly invoker | docs/OpcUaServer.md |
| Address space layout | docs/AddressSpace.md |
| Read / Write dispatch (driver vs virtual vs scripted-alarm) | docs/ReadWriteOperations.md |
| Incremental sync (driver-backend rediscovery + config publishes) | docs/IncrementalSync.md |
| Service hosting (Server + Admin; external HistorianGateway backend) | docs/ServiceHosting.md |
| Security (transport, LDAP, certificates) | docs/security.md |
| Redundancy | docs/Redundancy.md |
| Status dashboard | docs/StatusDashboard.md |
Drivers
| Topic | Doc |
|---|---|
| Driver specs (per-driver capability surface, config, addressing) | docs/v2/driver-specs.md |
| Galaxy driver | docs/drivers/Galaxy.md |
| Modbus / S7 / AbCip / AbLegacy / TwinCAT / FOCAS / OpcUaClient / MQTT | docs/drivers/ |
| Galaxy parity rig (mxaccessgw setup) | docs/v2/Galaxy.ParityRig.md |
| Galaxy performance + tracing | docs/v2/Galaxy.Performance.md |
Clients
| Topic | Doc |
|---|---|
| Client CLI | docs/Client.CLI.md |
| Client UI (Avalonia desktop) | docs/Client.UI.md |
v1 archive
The original v1 in-process MXAccess docs (Galaxy.Host topology, Configuration env vars, AlarmTracking, DataTypeMapping, HistoricalDataAccess, Subscriptions, etc.) are preserved under docs/v1/ — historical reference only. PR 7.2 retired the v1 architecture on 2026-04-30; current state is documented in the sections above.
License