A browse-committed AB CIP / TwinCAT / FOCAS tag bound with its model's DEFAULT
data type, not the one the device reported. A browsed REAL committed as
`{"tagPath":"Pump_1_Speed","dataType":"DInt"}` — and those three drivers decode
the wire bytes by that field, not by the raw row's OPC UA DataType — so the tag
read four bytes of a float through an integer decoder and published a plausible
wrong number with no error raised anywhere. FOCAS was missed when #536 was filed.
The type is CARRIED, not derived. Reverse-mapping the leaf's driver-agnostic
DriverDataType looks like the smaller fix and is wrong: SInt/Int/DInt/USInt/UInt
all collapse into Int32 on the way out of the driver, so that version would bind
a 16-bit INT as a 32-bit DINT while appearing to fix the REAL. Drivers now state
their own type name on DriverAttributeInfo.NativeDataType, which reaches the
picker as AttributeInfo.AddressFields["dataType"] and the commit mapper from
there. A leaf that states nothing keeps the model default — the pre-#536
behaviour, kept deliberately as the fallback rather than a guess.
Numeric strings are refused before parsing: Enum.TryParse accepts "9" for any
enum and Enum.IsDefined then confirms it, so an unguarded parse would bind a tag
to a type nobody named. A test caught this in the first version of the guard.
--- and the other half, which the fixture was hiding ---
Test Connect on a device with NO authored tags — every AB CIP device at the
moment an operator first presses the button — reported "CIP handshake failed"
against a healthy controller. That was written down as a fixture limitation
("ab_server doesn't implement @raw_cpu_type"). Both halves of that were wrong:
* @raw_cpu_type is not a libplctag special tag at all (only @raw, @tags and
@udt/ are), so it goes out as an ordinary symbolic name that no controller
defines, and the controller's "tag does not exist" IS the successful answer.
* ab_server answered an unresolvable tag path with CIP 0x03 where a Logix
controller answers 0x04 — ErrorBadParam vs ErrorNotFound, which the probe
classifies oppositely. Fixed in vendored patch 0002.
* With the fixture then telling the truth, the real defect surfaced:
AbCipDriverProbe.IsReachableException matched the native C status spellings
("STATUS_NOT_FOUND"), but libplctag.NET throws with the MANAGED enum name
("ErrorNotFound"). Those substrings can never match, so the reachable
classification could not fire on the exception path — which is the path every
no-authored-tags probe takes. This was failing on real hardware too, not just
against the sim. It now recovers the Status and defers to IsReachableStatus,
so there is one classification rather than two that can drift.
Rejected: switching the fallback to @tags. libplctag builds a tag-listing tag
with NO network I/O, so it reports OK against any TCP listener — measured green
against a Mosquitto broker.
Verification: full solution suite green. Falsification runs confirm exactly the
intended tests go red — 9 for the type carry, 3 (the reachable statuses only) for
the probe classification. Live on docker-dev: browse-committed TestString/
Motor_Run/TestSINT now store String/Bool/SInt, alongside last session's
Pump_1_Speed still holding the wrong DInt. TestSINT is the falsifier — its row
DataType is Int32, identical to TestDINT's, so no reverse map could have produced
"SInt".
Known consequence: pre-existing browse-committed tags keep their wrong dataType;
the fix applies to new commits only.
Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
OtOpcUa
OPC UA server (.NET 10 AnyCPU) that exposes a fleet of industrial drivers as a single OPC UA address space. Drivers ship in-process for AVEVA System Platform Galaxy (via the sibling mxaccessgw repo), Modbus TCP, Siemens S7, Allen-Bradley CIP (ControlLogix / CompactLogix), Allen-Bradley Legacy (SLC 500 / MicroLogix), Beckhoff TwinCAT (ADS), FANUC FOCAS, OPC UA Client (gateway), and MQTT (broker subscribe; Sparkplug B in progress).
A cross-platform client stack (.NET 10) — shared library, CLI, and Avalonia desktop app — connects to any OPC UA server.
Architecture
OPC UA Clients (CLI, Desktop UI, 3rd-party)
|
v
+-------------------------------------+
| OtOpcUa.Server (.NET 10 AnyCPU) |
| address space + capability fan-out|
+-------------------------------------+
| | | | | | | |
Galaxy Modbus S7 AbCip AbLeg TwinCAT FOCAS OpcUaClient MQTT
|
v
mxaccessgw (sibling repo, gRPC)
|
v
MXAccess COM (x86 worker, on AVEVA box)
Galaxy is the only driver with an external runtime: it speaks gRPC to a separately installed mxaccessgw server (sibling repo at c:\Users\dohertj2\Desktop\mxaccessgw\) which owns the MXAccess COM apartment and the x86/STA bitness constraint server-side. Everything in this repo is platform-agnostic .NET 10.
Prerequisites
- .NET 10 SDK (server, drivers, clients all target .NET 10)
- SQL Server reachable for the central config DB
- For Galaxy specifically: a running
mxaccessgwdeployment — see docs/v2/Galaxy.ParityRig.md - For historian read-back / alarm history / continuous historization: a running
ZB.MOM.WW.HistorianGatewaydeployment (the sole historian backend; consumed as theZB.MOM.WW.HistorianGateway.ClientgRPC package). It must runRuntimeDb:Enabled=true+RuntimeDb:EventReadsEnabled=true, and the API key must carryhistorian:read+historian:write+historian:tags:writescopes.
Quick Start
dotnet restore ZB.MOM.WW.OtOpcUa.slnx
dotnet build ZB.MOM.WW.OtOpcUa.slnx
dotnet test ZB.MOM.WW.OtOpcUa.slnx
# Run the server in dev (foreground)
dotnet run --project src/Server/ZB.MOM.WW.OtOpcUa.Host
The server starts on opc.tcp://localhost:4840 with the None security profile. Configure Security.Profiles in src/Server/ZB.MOM.WW.OtOpcUa.Host/appsettings.json to enable Basic256Sha256-Sign or Basic256Sha256-SignAndEncrypt. See docs/security.md.
Install as Windows Services
Production deployment is driven by scripts/install/Install-Services.ps1, which registers the OtOpcUa server service under a chosen service account. Historian support requires a separately deployed ZB.MOM.WW.HistorianGateway and Galaxy support a separately installed mxaccessgw — neither this repo nor the install script provisions them.
.\scripts\install\Install-Services.ps1 `
-InstallRoot 'C:\Program Files\OtOpcUa' `
-ServiceAccount 'DOMAIN\svc-otopcua'
The historian backend is the external ZB.MOM.WW.HistorianGateway (not installed by this script). See the script header and docs/ServiceHosting.md for full options.
Client CLI
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- connect -u opc.tcp://localhost:4840
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- browse -u opc.tcp://localhost:4840 -r -d 3
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- read -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode"
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- write -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -v 42
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- subscribe -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -i 500
See docs/Client.CLI.md and docs/Client.UI.md.
Documentation
Architecture deep-dives
| Topic | Doc |
|---|---|
| OPC UA server composition, namespace fan-out, Polly invoker | docs/OpcUaServer.md |
| Address space layout | docs/AddressSpace.md |
| Read / Write dispatch (driver vs virtual vs scripted-alarm) | docs/ReadWriteOperations.md |
| Incremental sync (driver-backend rediscovery + config publishes) | docs/IncrementalSync.md |
| Service hosting (Server + Admin; external HistorianGateway backend) | docs/ServiceHosting.md |
| Security (transport, LDAP, certificates) | docs/security.md |
| Redundancy | docs/Redundancy.md |
| Status dashboard | docs/StatusDashboard.md |
Drivers
| Topic | Doc |
|---|---|
| Driver specs (per-driver capability surface, config, addressing) | docs/v2/driver-specs.md |
| Galaxy driver | docs/drivers/Galaxy.md |
| Modbus / S7 / AbCip / AbLegacy / TwinCAT / FOCAS / OpcUaClient / MQTT | docs/drivers/ |
| Galaxy parity rig (mxaccessgw setup) | docs/v2/Galaxy.ParityRig.md |
| Galaxy performance + tracing | docs/v2/Galaxy.Performance.md |
Clients
| Topic | Doc |
|---|---|
| Client CLI | docs/Client.CLI.md |
| Client UI (Avalonia desktop) | docs/Client.UI.md |
v1 archive
The original v1 in-process MXAccess docs (Galaxy.Host topology, Configuration env vars, AlarmTracking, DataTypeMapping, HistoricalDataAccess, Subscriptions, etc.) are preserved under docs/v1/ — historical reference only. PR 7.2 retired the v1 architecture on 2026-04-30; current state is documented in the sections above.
License
Internal use only.