Joseph Doherty 620ecc41dd fix(modbus): refusals are per-tag Bad, batch health, generation-stamped lifecycle, write status mapping
H4: exception 01/02/03 (and undecodable data) are device refusals - per-tag
Bad with a once-per-tag Warning, no Degraded, and they advance
LastSuccessfulRead (the device answered), so an all-refused driver no longer
trips the 90 s watchdog. 04/05/06 still degrade (answered); 0A/0B degrade
without advancing. Health is one worst-wins write per batch instead of
last-writer-wins per tag. A comms failure on one unit fails the rest of
that unit's batch fast; an unreachable endpoint fails the whole batch fast.
H7: write transport failures map to BadCommunicationError, value overflow and
array length mismatch to BadOutOfRange, conversion failures to
BadTypeMismatch; writes report write-side health (a good write or a refusal
clears a write-side Degraded; a good read does not).
Lifecycle: every health write and the transport/table publish carry a
generation; a superseded init releases its transport and publishes nothing,
a read straddling a re-init cannot degrade the new transport, and the
shutdown's final write cannot clobber a newer init. The tag table is
build-and-swapped (re-init no longer merges into the old table). Teardown
joins the probe/re-probe loops (bounded); a probe answer advances
LastSuccessfulRead and an exception PDU from the device counts as Running.
Transports latch dispose atomically and never reconnect after it.

Refs #741
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
2026-10-22 15:15:20 -04:00

276 lines
15 KiB
C#

using System.Net.Sockets;
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
/// <summary>
/// Owns the raw TCP socket lifecycle shared by every Modbus-over-TCP transport (MBAP and
/// RTU-over-TCP alike): the IPv4-preference connect, OS-level keep-alive, throttled
/// reconnect (one attempt per geometric-backoff window), idle-disconnect tracking, and teardown. It exposes the current
/// <see cref="NetworkStream"/> so the composing transport can drive its own framing on top —
/// the lifecycle knows nothing about MBAP / RTU wire layout.
/// </summary>
/// <remarks>
/// <para>
/// Extracted verbatim from <see cref="ModbusTcpTransport"/> so the connect / reconnect /
/// keep-alive / idle behaviour is written once and composed by both transports. The
/// constructor is connection-free — all socket I/O happens in <see cref="ConnectAsync"/> /
/// <see cref="EnsureConnectedAsync"/> (one throttled attempt per call — never a sleep loop).
/// </para>
/// <para>
/// Why keep-alive matters for DL205/DL260: the AutomationDirect H2-ECOM100 does NOT send
/// TCP keepalives per <c>docs/v2/dl205.md</c> §behavioral-oddities, so any NAT/firewall
/// between the gateway and PLC can silently close an idle socket after 2-5 minutes.
/// Enabling OS-level <c>SO_KEEPALIVE</c> lets the driver's own side detect a stuck socket
/// in reasonable time even when the application is mostly idle.
/// </para>
/// </remarks>
public sealed class ModbusSocketLifecycle : IAsyncDisposable
{
private readonly string _host;
private readonly int _port;
private readonly TimeSpan _timeout;
private readonly bool _autoReconnect;
private readonly ModbusKeepAliveOptions _keepAlive;
private readonly TimeSpan? _idleDisconnect;
private readonly ModbusReconnectOptions _reconnect;
private TcpClient? _client;
private NetworkStream? _stream;
private DateTime _lastSuccessUtc = DateTime.UtcNow;
/// <summary>Monotonic millisecond clock for the reconnect throttle (test seam).</summary>
internal Func<long> NowMs { get; set; } = () => Environment.TickCount64;
/// <summary>Initializes a new instance of the <see cref="ModbusSocketLifecycle"/> class.</summary>
/// <param name="host">The host address or hostname of the Modbus server.</param>
/// <param name="port">The TCP port of the Modbus server.</param>
/// <param name="timeout">The timeout for socket operations.</param>
/// <param name="autoReconnect">Whether to automatically reconnect on socket failures.</param>
/// <param name="keepAlive">Optional keep-alive configuration for the socket.</param>
/// <param name="idleDisconnect">Optional duration after which an idle socket is disconnected.</param>
/// <param name="reconnect">Optional reconnect backoff configuration.</param>
public ModbusSocketLifecycle(
string host, int port, TimeSpan timeout, bool autoReconnect = true,
ModbusKeepAliveOptions? keepAlive = null,
TimeSpan? idleDisconnect = null,
ModbusReconnectOptions? reconnect = null)
{
_host = host;
_port = port;
_timeout = timeout;
_autoReconnect = autoReconnect;
_keepAlive = keepAlive ?? new ModbusKeepAliveOptions();
_idleDisconnect = idleDisconnect;
_reconnect = reconnect ?? new ModbusReconnectOptions();
}
/// <summary>Gets the current live <see cref="NetworkStream"/>, or <see langword="null"/> when not connected.</summary>
public NetworkStream? Stream => _stream;
/// <summary>Gets a value indicating whether auto-reconnect on socket failures is enabled.</summary>
public bool AutoReconnect => _autoReconnect;
/// <summary>Establishes a connection to the Modbus server, preferring IPv4.</summary>
/// <param name="ct">A cancellation token to observe for cancellation.</param>
/// <returns>A task representing the asynchronous connection operation.</returns>
public async Task ConnectAsync(CancellationToken ct)
{
// A previous socket (failed, torn down or idle-reaped) is released FIRST: overwriting _client
// used to strand the old TcpClient for the finalizer — up to nine per backoff loop.
ThrowIfDisposed();
await TearDownAsync().ConfigureAwait(false);
// DNS resolution runs under the same per-op deadline as the TCP connect: an unresolvable or
// slow resolver must not hold the transport gate for the OS resolver's own (much longer) timeout.
using var cts = CancellationTokenSource.CreateLinkedTokenSource(ct);
cts.CancelAfter(_timeout);
TcpClient? client = null;
try
{
// Resolve the host explicitly + prefer IPv4. .NET's TcpClient default-constructor is
// dual-stack (IPv6 first, fallback to IPv4) — but most Modbus TCP devices (PLCs and
// simulators like pymodbus) bind 0.0.0.0 only, so the IPv6 attempt times out and we
// burn the entire ConnectAsync budget before even trying IPv4. Resolving first +
// dialing the IPv4 address directly sidesteps that.
var addresses = await System.Net.Dns.GetHostAddressesAsync(_host, cts.Token).ConfigureAwait(false);
var ipv4 = System.Linq.Enumerable.FirstOrDefault(addresses,
a => a.AddressFamily == System.Net.Sockets.AddressFamily.InterNetwork);
var target = ipv4 ?? (addresses.Length > 0 ? addresses[0] : System.Net.IPAddress.Loopback);
client = new TcpClient(target.AddressFamily);
EnableKeepAlive(client, _keepAlive);
await client.ConnectAsync(target, _port, cts.Token).ConfigureAwait(false);
ThrowIfDisposed(); // disposed while dialling — the finally releases the fresh client
_stream = client.GetStream();
_client = client;
client = null; // ownership transferred
_lastSuccessUtc = DateTime.UtcNow;
}
catch (OperationCanceledException) when (!ct.IsCancellationRequested)
{
// The per-op deadline, not the caller: normalise to a socket-level failure so every
// classifier treats a connect timeout as a comms fault.
throw new ModbusTransportUnavailableException(
$"Modbus connect to {_host}:{_port} timed out after {_timeout.TotalMilliseconds:0}ms");
}
finally
{
// A failed attempt disposes its own client — never leave it for the finalizer.
client?.Dispose();
}
}
// Reconnect throttle state. Guarded by the composing transport's single-flight gate (every caller of
// EnsureConnectedAsync holds it), so no extra lock is needed.
private long _connectNotBeforeMs;
private TimeSpan _failureDelay = TimeSpan.Zero;
/// <summary>
/// Ensures a live socket for the next transaction with AT MOST ONE connect attempt, throttled by the
/// configured geometric backoff: after a failed attempt, calls inside the backoff window fail fast
/// with <see cref="ModbusTransportUnavailableException"/> and never dial. The window starts at
/// <see cref="ModbusReconnectOptions.InitialDelay"/> (floored at 1 s) and grows by
/// <c>BackoffMultiplier</c> per consecutive failure up to <c>MaxDelay</c>; a successful connect
/// resets it. Never sleeps — the composing transport calls it inside its gate, and a sleep there
/// used to queue every read, write and probe behind one dead socket for up to ~81 s.
/// </summary>
/// <param name="ct">A cancellation token to observe for cancellation.</param>
/// <returns>A task that completes when a socket is live.</returns>
/// <exception cref="ModbusTransportUnavailableException">Auto-reconnect is off, or the call is inside the backoff window.</exception>
public async Task EnsureConnectedAsync(CancellationToken ct)
{
if (_stream is not null) return;
if (!_autoReconnect)
throw new ModbusTransportUnavailableException(
$"Modbus transport to {_host}:{_port} is not connected and auto-reconnect is disabled");
var now = NowMs();
if (now < _connectNotBeforeMs)
throw new ModbusTransportUnavailableException(
$"Modbus reconnect to {_host}:{_port} throttled for another {_connectNotBeforeMs - now}ms after a failed connect");
try
{
await ConnectAsync(ct).ConfigureAwait(false);
_failureDelay = TimeSpan.Zero;
_connectNotBeforeMs = 0;
}
catch (Exception) when (!ct.IsCancellationRequested)
{
_failureDelay = NextDelay(_failureDelay);
_connectNotBeforeMs = NowMs() + (long)_failureDelay.TotalMilliseconds;
throw;
}
}
/// <summary>Minimum reconnect window after a failed connect — a dead device is dialled at most once per second.</summary>
private static readonly TimeSpan MinReconnectWindow = TimeSpan.FromSeconds(1);
private TimeSpan NextDelay(TimeSpan previous)
{
if (previous <= TimeSpan.Zero)
{
var first = _reconnect.InitialDelay > MinReconnectWindow ? _reconnect.InitialDelay : MinReconnectWindow;
return first < _reconnect.MaxDelay ? first : _reconnect.MaxDelay > TimeSpan.Zero ? _reconnect.MaxDelay : first;
}
// Geometric growth, capped. Math.Min on ticks so a pathological multiplier cannot overflow.
var multiplier = _reconnect.BackoffMultiplier >= 1.0 ? _reconnect.BackoffMultiplier : 1.0;
var nextTicks = previous.Ticks * multiplier;
var cap = _reconnect.MaxDelay > TimeSpan.Zero ? _reconnect.MaxDelay.Ticks : long.MaxValue;
return TimeSpan.FromTicks(nextTicks >= cap ? cap : (long)nextTicks);
}
/// <summary>
/// Reports whether the socket has been idle longer than the configured idle-disconnect
/// threshold and should be proactively torn down + reconnected before the next transaction.
/// Always <see langword="false"/> when no idle-disconnect timeout is configured.
/// </summary>
/// <returns><see langword="true"/> when the idle threshold has been exceeded.</returns>
public bool ShouldReconnectForIdle() =>
_idleDisconnect.HasValue && DateTime.UtcNow - _lastSuccessUtc > _idleDisconnect.Value;
/// <summary>Records that a transaction just succeeded, resetting the idle-disconnect clock.</summary>
public void MarkSuccess() => _lastSuccessUtc = DateTime.UtcNow;
/// <summary>Tears down the current socket + stream, leaving the lifecycle ready to reconnect.</summary>
/// <returns>A task representing the asynchronous teardown operation.</returns>
public async Task TearDownAsync()
{
try { if (_stream is not null) await _stream.DisposeAsync().ConfigureAwait(false); }
catch { /* best-effort */ }
_stream = null;
try { _client?.Dispose(); } catch { }
_client = null;
}
/// <summary>
/// Enable SO_KEEPALIVE with aggressive probe timing. DL205/DL260 doesn't send keepalives
/// itself; having the OS probe the socket every ~30s lets the driver notice a dead PLC
/// or broken NAT path long before the default 2-hour Windows idle timeout fires.
/// Non-fatal if the underlying OS rejects the option (some older Linux / container
/// sandboxes don't expose the fine-grained timing levers — the driver still works,
/// application-level probe still detects problems).
/// </summary>
private static void EnableKeepAlive(TcpClient client, ModbusKeepAliveOptions opts)
{
if (!opts.Enabled) return;
try
{
client.Client.SetSocketOption(SocketOptionLevel.Socket, SocketOptionName.KeepAlive, true);
// A TimeSpan < 1s previously truncated to 0 via the int cast,
// which Windows / Linux interpret as "use the default" — silently defeating the
// configured keep-alive timing. Round up to at least 1 second so a sub-second
// configuration still produces a real keep-alive cadence. Negative values are
// also clamped to 1 to avoid surfacing as OS errors.
client.Client.SetSocketOption(SocketOptionLevel.Tcp, SocketOptionName.TcpKeepAliveTime,
ClampToWholeSeconds(opts.Time));
client.Client.SetSocketOption(SocketOptionLevel.Tcp, SocketOptionName.TcpKeepAliveInterval,
ClampToWholeSeconds(opts.Interval));
client.Client.SetSocketOption(SocketOptionLevel.Tcp, SocketOptionName.TcpKeepAliveRetryCount, opts.RetryCount);
}
catch { /* best-effort; older OSes may not expose the granular knobs */ }
}
/// <summary>
/// Cast a <see cref="TimeSpan"/> to a whole number of seconds with a
/// minimum of 1 — protects callers from the int-cast truncation that turned 500 ms
/// keep-alive timing into "use the default" on most OSes.
/// </summary>
/// <param name="ts">The timespan to clamp to whole seconds.</param>
/// <returns>The clamped duration expressed as a whole number of seconds, never less than 1.</returns>
internal static int ClampToWholeSeconds(TimeSpan ts)
{
var seconds = (int)Math.Ceiling(ts.TotalSeconds);
return seconds < 1 ? 1 : seconds;
}
/// <summary>
/// Distinguish socket-layer failures (eligible for reconnect-and-retry) from
/// protocol-layer failures (must propagate — retrying the same PDU won't help if the
/// PLC just returned exception 02 Illegal Data Address).
/// </summary>
/// <param name="ex">The exception to classify.</param>
/// <returns><see langword="true"/> when the exception is a socket-level failure.</returns>
internal static bool IsSocketLevelFailure(Exception ex) =>
ex is EndOfStreamException
|| ex is IOException
|| ex is SocketException
|| ex is ObjectDisposedException;
/// <summary>Asynchronously disposes the underlying socket + stream resources.</summary>
/// <returns>A task that represents the asynchronous operation.</returns>
public async ValueTask DisposeAsync()
{
// Latch first: a SendAsync still in flight (the driver tearing down under it) must not reconnect
// a fresh socket after this point — ConnectAsync checks the latch both before and after dialling.
Volatile.Write(ref _disposed, 1);
await TearDownAsync().ConfigureAwait(false);
}
private int _disposed;
private void ThrowIfDisposed()
{
if (Volatile.Read(ref _disposed) != 0) throw new ObjectDisposedException(nameof(ModbusSocketLifecycle));
}
}