N2: pre-#741 rows carry region/address beside an addressString with no marker (the old driver never read the string, the old model preserved it as an unknown key). The r1 rule resolved those from the string - a silent remap or BadNodeIdUnknown on upgrade. The driver now loads from region+address whenever both are present (classic, editor-pinned, pre-lane); only a blob with NO keys is string-only and resolved through the parser. This is safe because the model no longer stamps keys onto a string-only tag. The model distinguishes string-only / legacy-string-beside-keys / pinned, and the editor hint says so. Test matrix over every persisted shape (keys only, pre-lane keys+string, pre-lane stamped HR/0+string, string only, marker+keys, marker no keys) under every family; the pre-lane row also through a model save and a CSV export->import. n5: a typed CSV address cell is an authored address - it drops addressString and the marker (new CsvTypedColumn.ClearsKeys) instead of being discarded. n6: Validate skips the region/dataType/byteOrder enum checks on a string-only tag (the driver ignores them). n7: docs/v2/modbus-addressing.md restates the key-presence rule. Refs #741 Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
11 KiB
Modbus tag-addressing reference
Foundational doc for the Modbus addressing grammar shipped across #136–#144.
Covers the address-string parser (ModbusAddressParser) that the wire driver
and the Admin UI both consume, the per-tag suffix modifiers, and the family-
native branch.
Grammar
<region><offset>[.<bit>][:<type>[<len>]][:<order>][:<count>]
Each field is optional from left to right; the parser fills defaults.
Region + offset
Three accepted forms — pick whichever matches your tag spreadsheet's
convention. All three resolve to the same (Region, ushort PduOffset)
on the wire.
| Form | Example | Means |
|---|---|---|
| Modicon 5-digit | 40001 |
Holding register 1 (PDU 0) |
| Modicon 6-digit | 400001 |
Holding register 1 (PDU 0); supports up to 465536 (PDU 65535) |
| Mnemonic | HR1, IR1, C100, DI1 |
Same regions; 1-based register number |
Modicon leading-digit → region:
| Digit | Region | OPC UA wire FC |
|---|---|---|
0 |
Coils | FC01 / FC05 / FC15 |
1 |
DiscreteInputs | FC02 (read-only) |
3 |
InputRegisters | FC04 (read-only) |
4 |
HoldingRegisters | FC03 / FC06 / FC16 |
Bit suffix .N
40001.5 = bit 5 (LSB-first) of HR[0]. Implies DataType=BitInRegister;
mixing with an explicit type or array-count is rejected.
Type code :T
Codes verified 2026-04-25 against Wonderware DASMBTCP user
guide and the
Ignition Modbus addressing
manual.
The I / UI / I_64 / UI_64 / BCD_32 shapes match Wonderware's
suffix convention and Ignition's underscore-N prefix variants where
those vendors agree.
| Code | Type | Registers | Vendor reference |
|---|---|---|---|
BOOL |
Boolean | 1 (region must be Coils / DiscreteInputs) | universal |
S |
Int16 | 1 | Wonderware DASMBTCP S = 16-bit signed |
US |
UInt16 | 1 | Ignition HRUS = Unsigned Short |
I |
Int32 | 2 | Wonderware DASMBTCP I = 32-bit signed; Ignition HRI |
UI |
UInt32 | 2 | Ignition HRUI |
I_64 |
Int64 | 4 | Ignition HRI_64 |
UI_64 |
UInt64 | 4 | Ignition HRUI_64 |
F |
Float32 | 2 | Wonderware F; Ignition HRF |
D |
Float64 | 4 | Ignition HRD |
BCD |
16-bit BCD | 1 | Ignition HRBCD |
BCD_32 |
32-bit BCD | 2 | Ignition HRBCD_32 |
STR<len> |
ASCII string, len chars (2 chars / register) |
ceil(len/2) |
analogous to Ignition HRS<addr>:<len> |
Default when omitted:
- Coils / DiscreteInputs →
BOOL - HoldingRegisters / InputRegisters →
S(Int16) — matches Ignition's bare-HRdefault
Codes removed in #146 (silent wrong-data risk, never compatible with the
two reference vendors): :DI, :L, :UDI, :UL, :LI, :ULI, :LBCD.
Pre-#146 configs that use these get a clear "Unknown type code" diagnostic at
parse time; rewrite to the post-#146 codes per the table above.
Byte order :O
| Mnemonic | Meaning | Wire |
|---|---|---|
ABCD |
Big-endian (Modbus spec default) | [A,B,C,D] |
CDAB |
Word swap (Siemens, several AB) | [C,D,A,B] |
BADC |
Byte swap (legacy little-endian-internal devices) | [B,A,D,C] |
DCBA |
Full reverse (some EtherNet/IP gateways) | [D,C,B,A] |
For 8-byte values (Int64 / Float64) the same labels apply pairwise.
Array count :N
40001:F:5 = Float32[5] (consumes HR[0..9]). Array + bit suffix is
rejected. Strings are not arrays.
Composition
The 3-field shorthand 40001:F:5 is parsed as (type=F, count=5) because
5 isn't a valid byte-order mnemonic. Use the explicit 4-field form
40001:F:CDAB:5 when you need a non-default order.
Family-native syntax (#144)
When the driver instance has Family != Generic, the parser tries the
family's native syntax FIRST, then falls back to Modicon / mnemonic.
DL205 (AutomationDirect DirectLOGIC)
| Form | Example | Mapping |
|---|---|---|
Vnnnn (octal) |
V2000 |
HoldingRegisters[1024] (octal 2000 = decimal 1024) |
Ynn (octal) |
Y17 |
Coils[2048 + 15] (Y-output base + offset) |
Cnn (octal) |
C100 |
Coils[3072 + 64] (C-relay base + offset) |
Xnn (octal) |
X17 |
DiscreteInputs[15] |
SPnn (octal) |
SP10 |
DiscreteInputs[1024 + 8] |
Cross-family ambiguity: C100 means Coils[99] under Generic
(mnemonic) but Coils[3136] under DL205. Per-driver Family choice
disambiguates.
MELSEC (Mitsubishi)
| Form | Example | Mapping (sub-family Q_L_iQR / F_iQF) |
|---|---|---|
Dnnn (decimal) |
D100 |
HoldingRegisters[100] |
Mnnn (decimal) |
M50 |
Coils[50] |
Xnn |
X20 |
DiscreteInputs[32 hex / 16 octal] |
Ynn |
Y20 |
Coils[32 hex / 16 octal] |
X / Y digit interpretation depends on MelsecSubFamily:
Q_L_iQR→ hex (default)F_iQF→ octal
Bank-base offsets default to 0 in the grammar string. Sites with non-zero "Modbus Device Assignment" bases use the structured tag form.
Driver-instance options
Beyond per-tag addressing, ModbusDriverOptions exposes (#139–#143):
Connection (#139)
KeepAlive { Enabled, Time, Interval, RetryCount }— TCP-level probes. Defaults match the historical PR 53 wire output (Enabled=true, Time=30s, Interval=10s, RetryCount=3).IdleDisconnectTimeout— proactively close + reconnect after this much socket idle time. Default null = disabled.Reconnect { InitialDelay, MaxDelay, BackoffMultiplier }— geometric backoff for the post-drop reconnect loop. Default(0, 30s, 2.0)= immediate first retry, geometric thereafter.
Protocol (#140)
MaxCoilsPerRead(default 2000) — separate cap for FC01/FC02 coil reads.UseFC15ForSingleCoilWrites— force FC15 (write multiple coils qty=1) for single-coil writes. Safety/audit PLCs may require this.UseFC16ForSingleRegisterWrites— same for FC16 vs FC06.UseFC23ForMultiRegisterWrites(defaultfalse) — opt-in: a 2–121-register holding write is sent as one FC23 (write + read-back). A unit answering exception 01 moves to FC16 until the next re-init. Without the key the wire stays FC16 (#741).DisableFC23— hard kill switch: never send FC23, even when opted in.
Subscribe (#141)
- Per-tag
Deadband— suppress sub-threshold publishes on numeric tags. WriteOnChangeOnly(driver-level) — short-circuit identical-value writes. Cache invalidates on read-divergence.
Multi-unit (#142)
- Per-tag
UnitId— overrides the driver-level UnitId in the MBAP header. Required for one-Ethernet-gateway / N-RTU-slave deployments. IPerCallHostResolver.ResolveHostreturnshost:port/unitNper tag so per-PLC circuit breakers fire per slave.- Per-tag
CoalesceProhibited— escape hatch for #143's planner (read this tag in isolation regardless ofMaxReadGap).
Block-read coalescing (#143)
MaxReadGap— gap budget the planner is willing to bridge between adjacent tags of one (unit, region). WithMaxReadGap=10, three tags at HR 100/102/110 collapse into one FC03 of quantity 11. An explicit0= coalescing off (its historical meaning); the default8applies only when the key is absent (#741). Coils / DiscreteInputs (gap in bits),Stringscalars and same-wordBitInRegistertags coalesce too.DisableReadCoalescing— turn coalescing off regardless of the gap.
Coalescing auto-recovery (#148 / #150 / #151 / #152)
- A coalesced read that fails with a Modbus exception (write-only or protected register mid-block) records the failed range as auto-prohibited. The planner stops re-coalescing across the range; the per-tag fallback path keeps healthy members working in the same scan.
- Bisection (#150): every re-probe pass narrows multi-register prohibitions by trying the two halves separately. Over log2(span) ticks the prohibition pins at the actual offending register(s); intermediate halves that succeed get cleared.
- Periodic re-probe (#151): opt in via
AutoProhibitReprobeInterval(TimeSpan?). Default null = disabled (prohibitions persist for the driver lifetime; clear onReinitializeAsync). - Per-tag escape hatch:
CoalesceProhibited(bool, default false) onModbusTagDefinition. The planner reads such tags in isolation regardless ofMaxReadGap. Use for known-bad addresses you want to exclude from the auto-discovery loop. - Diagnostics (#152):
ModbusDriver.GetAutoProhibitedRanges()returns a snapshot of every active prohibition asModbusAutoProhibitionrecords (UnitId / Region / StartAddress / EndAddress / LastProbedUtc / BisectionPending). Surface in the driver-diagnostics RPC channel when that wiring lands; for now consumable by in-process callers (Server health endpoints, log aggregation).
JSON DTO shape
The factory accepts both the structured form (legacy) and the new
AddressString form per-tag. Mix freely — newer pasted rows use the
grammar string; legacy rows keep the structured fields.
{
"host": "10.1.2.3",
"port": 502,
"unitId": 1,
"family": "DL205",
"keepAlive": { "enabled": true, "timeMs": 30000, "intervalMs": 10000, "retryCount": 3 },
"idleDisconnectMs": 120000,
"reconnect": { "initialDelayMs": 0, "maxDelayMs": 30000, "backoffMultiplier": 2.0 },
"maxCoilsPerRead": 2000,
"writeOnChangeOnly": false,
"maxReadGap": 8,
"tags": [
{ "name": "Temp", "addressString": "V2000:F:CDAB" },
{ "name": "Setpoint", "addressString": "40001:I" },
{ "name": "Outputs", "addressString": "Y0:5" },
{ "name": "AlarmCount", "region": "HoldingRegisters", "address": 200, "dataType": "Int16", "deadband": 5.0 }
]
}
Vendor compatibility caveat
The exact spelling of type codes (e.g. I vs INT, BCD vs L_BCD) and
the byte-order mnemonics were synthesised from training-era vendor docs
(Wonderware DASMBTCP, Kepware KEPServerEX, Ignition, Matrikon, OAS).
Before locking the grammar for a production deployment, verify against
the current Kepware "Modbus Ethernet Driver Help" PDF and Ignition's
"Modbus Addressing" user-manual page — if a critical tool's mnemonics
have shifted, add aliases in ModbusAddressParser.TryParseType rather
than asking users to rewrite spreadsheets.
Address strings, families and region/type rules (#741)
- Whenever a tag carries both
regionandaddress, those keys are its address — a classic tag, an editor-pinned tag, and a pre-#741 row that carried anaddressStringbeside its keys (the old driver never read the string) all load from the keys, exactly as before, and a family change never remaps them. Only a string-only blob (anaddressStringwith NOregion/address— CSV / API authoring) is resolved throughModbusAddressParserwith the driver'sFamily/MelsecSubFamily; the AdminUI never stamps default keys onto it, so it cannot collapse onto HR[0], and a family that cannot parse it refuses the tag (BadNodeIdUnknown). - The editor's "Resolve with driver family" persists the resolved
region/address/type fields plus"addressResolved": true(the pinned state). Editing a resolved field by hand — in the editor or a typed CSV address cell — drops the string and the marker. - Coils / DiscreteInputs carry only Bool. A bit-region tag persisted with a
register
dataType(the pre-#741 editor savedInt16) is coerced to Bool, never refused. A register region withBoolis refused (useBitInRegister). - Exception 01/02/03 are device refusals: per-tag Bad, one Warning per tag, no driver Degraded; reads and writes share one comms-fault health slot.