# TwinCAT Test Connect on a real ADS target: Z35474, 2026-11-11
|
||
|
||
Gitea #755 item: "Driver probe (Test Connect) happy path on a real ADS target".
|
||
|
||
**Result: the item cannot be ticked. On real hardware the probe returns a false RED.** The ADS
|
||
target is healthy and reachable through the router, but `TwinCATDriverProbe` never gets to its
|
||
ADS handshake: its TCP preflight dials the wrong endpoint.
|
||
|
||
## Target and scope
|
||
|
||
| | |
|
||
|---|---|
|
||
| Press | Z35474 (Elma cleaner), production |
|
||
| IP | 10.201.23.227 (reached over the VPN) |
|
||
| AmsNetId / port | `5.118.56.93.1.1` : 851 (TC3 PLC runtime 1) |
|
||
| Route used | the existing press-side route `otopcua-mac-20261111` → `10.181.201.5.1.1` (no AddRoute sent) |
|
||
| Scope | read-only: ReadState, ReadDeviceInfo, symbol upload (Flat), two scalar reads. No writes, no WriteControl, no notifications, no route-table change. One session at a time, a few seconds per run. |
|
||
|
||
## Harness
|
||
|
||
This is a scratch console app outside the repo. It has a `ProjectReference` to
|
||
`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.TwinCAT` and hosts `Beckhoff.TwinCAT.Ads.TcpRouter` 7.0.172 in
|
||
process. The router's local NetId is `10.181.201.5.1.1`, with one route `Z35474 → 10.201.23.227 /
|
||
5.118.56.93.1.1`. The package's sample `StaticRoutes.xml` is excluded, so the router loads no other
|
||
routes. The Beckhoff ADS client is 7.0.172, the same version the driver uses.
|
||
|
||
The harness drives the probe the way AdminUI does:
|
||
|
||
- `RawTreeService.LoadMergedProbeConfigAsync` builds the config through
|
||
`DriverDeviceConfigMerger.Merge("{}", [DeviceRow("Z35474", {"hostAddress":"ads://5.118.56.93.1.1:851"})], [])`.
|
||
- `AdminOperationsActor.ProbeAsync` calls `new TwinCATDriverProbe().ProbeAsync(merged, 10 s, cts(10 s))`.
|
||
The 10 s budget is `TestConnectBudget`'s TwinCAT default.
|
||
|
||
The merged config the probe received:
|
||
|
||
```json
|
||
{"hostAddress":"ads://5.118.56.93.1.1:851","Devices":[{"hostAddress":"ads://5.118.56.93.1.1:851","DeviceName":"Z35474"}],"RawTags":[]}
|
||
```
|
||
|
||
## Observed (two runs, identical)
|
||
|
||
```
|
||
[probe] Ok=False Message="Probe timed out after 10s." Latency=- wall=10003ms
|
||
[phase2] ReadState Succeeded=True Err=Succeeded AdsState=Run DeviceState=0 189ms (2nd run 109ms)
|
||
[phase2] DeviceInfo Succeeded=True Name="Plc30 App" Version=3.1.1940
|
||
[browse] roots=3384 (Flat symbol upload)
|
||
[read] .actualOperationMode : INT = 2
|
||
[read] .CFG_NUM_CDA_MAX : INT = 5
|
||
```
|
||
|
||
`[phase2]` is not the probe. It reproduces the probe's own Phase 2 (`AdsClient.Connect(netId, 851)` +
|
||
`ReadStateAsync`, `Timeout` = 10 s) in the same process through the same router. It shows that the
|
||
handshake the probe would have done succeeds: Run state in about 0.1–0.2 s.
|
||
|
||
Device: **"Plc30 App", ADS version 3.1.1940, AdsState Run, DeviceState 0.** The browse found 3,384 Flat
|
||
roots, which matches the 2026-10-08 count.
|
||
|
||
## Defect: the Phase 1 TCP preflight targets `(NetId[0..4]):(AMS port)`
|
||
|
||
`TwinCATDriverProbe.ExtractTarget` builds the preflight target as the first four octets of the AmsNetId
|
||
plus the AMS port. It then runs `Socket.ConnectAsync(host, port)` before it tries ADS. That target is
|
||
wrong in two separate ways:
|
||
|
||
1. **The AmsNetId is not the IP.** For Z35474 the preflight dialled **`5.118.56.93:851`**. That is a
|
||
public internet address unrelated to the press; on this Mac it routes out of the LAN gateway, not the
|
||
VPN. It black-holes, so the probe spends its whole 10 s budget and returns "Probe timed out after
|
||
10s." The press is at 10.201.23.227. The driver config has no IP field, so the probe cannot know it.
|
||
Only the AMS router knows it.
|
||
2. **851 is an AMS port, not a TCP port.** ADS/TCP is 48898. On a press where the NetId happens to equal
|
||
the IP (for example Z33856 `10.201.45.236.1.1`), the preflight would dial `10.201.45.236:801/851`.
|
||
That should be refused and return "Connect failed: ConnectionRefused", also a RED. I inferred this
|
||
from the code and did not run it against that press.
|
||
|
||
Consequence: Test Connect cannot go green against a real TwinCAT runtime. It stops at Phase 1 before
|
||
the ADS handshake, which works. The unit tests (`TwinCATDriverProbeTests`) pin the current behaviour:
|
||
they open a loopback `TcpListener` on the "AMS port" and use `ads://127.0.0.1.1.1:{port}`, so the
|
||
mismatch never shows up there. The probe also sends a TCP SYN to whatever internet host the NetId's
|
||
first four octets name.
|
||
|
||
The fix is not made here: tracked source was left unedited, as the task asked. The fix direction is
|
||
to drop the remote preflight, or point it at the local AMS router (`127.0.0.1:48898`), which is the
|
||
only TCP endpoint the ADS client actually uses. Phase 2's `ReadStateAsync`, bounded by the timeout,
|
||
then becomes the real reachability check. The unit tests would need to change with it.
|
||
|
||
## #755 status
|
||
|
||
- "Test Connect happy path on a real ADS target": **not tickable.** The ADS path works (router, route,
|
||
ReadState = Run, device info, browse, reads), but the probe as AdminUI runs it returns a false RED.
|
||
Re-run this gate after the preflight fix.
|
||
- The harness lives in session scratch, not in the repo:
|
||
`scratchpad/twincat/probeharness/` (`Program.cs`, modes `probe` | `read`).
|