@@ -0,0 +1,170 @@
# Galaxy H6 (#614): OPC UA ack of a real Galaxy native alarm to AVEVA history, 2026-11-11
Gitea #614 item H6: "an OPC UA Acknowledge of a REAL Galaxy native alarm reaches AVEVA event history".
**Result: FAIL — the item cannot be ticked.** The OPC UA path worked end to end inside OtOpcUa: the
Part 9 `Acknowledge` returned Good, the client saw the condition go `Active, Acknowledged`, and the driver
sent the ack to mxaccessgw as the owner-provided Galaxy account with no error. **The acknowledgement
never reached Galaxy.** After the ack, Galaxy's own `.Acked` was still `False`, `.AckMsg` was still
empty, the gateway feed still showed the alarm as unacknowledged, and AVEVA event history has no ACK
row. So OtOpcUa now shows the condition acknowledged while Galaxy and the Historian do not (a
silent-divergence defect, below).
Exactly **one** acknowledge was sent (approved write, 2026-11-11T17:37:55Z). It was not retried. No
remote command ran on any wonder box. Galaxy access was through the gateway's gRPC API and read-only
SQL only.
## Target
| | |
|---|---|
| Alarm | `Galaxy!CVDAisle_1.TableAlarms_008.RuntimeAlert` (object `TableAlarms_008`, contained as `Right_004.TableAlarms`), priority 400, "Run Time Exceeded" |
| Gateway | `wonder-app-vd03.zmr.zimmer.com:5120` (h2c) |
| Galaxy security | OS/domain accounts (`ZB.dbo.user_profile`). Every 2026 ack in the Historian before this gate is a `NAM\…` operator from an InTouch node; none came through the gateway. |
| Historian | `wonder-sql-vd03` → `Runtime.dbo.v_AlarmEventHistory2`. Queries need an `EventStamp` range. There is no `A2ALMDB` or `WWALMDB`. |
## Setup (docker-dev, temporary, all removed afterwards)
| Item | Value |
|---|---|
| Node | SITE-B `site-b-1` (OPC UA `opc.tcp://localhost:4844`). Its partner `site-b-2` was stopped for the run so site-b-1 was the sole (Primary) node. |
| Driver | `h6gal`, DriverType `GalaxyMxGateway`, seeded straight into the ConfigDb. `Gateway.Endpoint` = the VD03 gateway, `UseTls=false`, `ApiKeySecretRef=env:GALAXY_MXGW_API_KEY`, `MxAccess.ClientName=OtOpcUa-H6-gate`, `Repository.WatchDeployEvents=false`. `AlarmAck.FallbackUser`/`FallbackDomain` = the owner-provided account (domain `NAM`); `FallbackPasswordSecretRef=env:OTOPCUA_GALAXY_ACKPW` |
| Device / tag | device `vd03` (`{}`), tag `RuntimeAlert`, Boolean, Read, `TagConfig` = `{"attributeRef":"Galaxy!CVDAisle_1.TableAlarms_008.RuntimeAlert","alarm":{"alarmType":"AlarmCondition","severity":400,"historizeToAveva":false}}`. `historizeToAveva:false` keeps OtOpcUa's own alarm historian from writing anything to AVEVA. |
| Secrets | the gateway key and the ack password were injected into the site-b-1 container as runtime env only, through a scratch compose override that held `${VAR}` references, never values. Nothing secret went into the repo, the compose files, the ConfigDb or this file. |
| OPC UA client | `otopcua-cli` (`src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI`), UserName `apikey` + a temporary data-plane key (`h6-gate`, principal `h6gate`, 4 h expiry) with a SITE-B `Cluster` grant: Browse, Read, Subscribe, HistoryRead, AlarmRead and AlarmAcknowledge (399). LDAP was not used. |
| Deploy | `POST /api/deployments`. The first attempt used DriverType `Galaxy`, which is wrong: the registered name is `GalaxyMxGateway`. It was corrected and deployed again. Deployments to SITE-B end `TimedOut` while `site-b-2` is stopped (the same as the Heidenhain gate); `site-b-1` applied each one. |
Driver start (site-b-1): `GalaxyMxSession connected — clientName=OtOpcUa-H6-gate`, `DriverInstance h6gal: connected`,
`native-alarm subscription established for 1 alarm ref(s)`.
## Step 1: OPC UA, condition and Acknowledge (PASS within OtOpcUa)
`alarms --refresh` before the ack:
```
[2026-07-29T01:02:46.8300000Z] ALARM h6gal/vd03/RuntimeAlert
Condition: RuntimeAlert
State: Active, Unacknowledged
Severity: 500
Retain: True
ConditionNodeId: ns=2;s=h6gal/vd03/RuntimeAlert
EventId: 8DB71E793FBD7040993404E30808FADC
```
The single ack, at 17:37:55Z:
```
otopcua-cli ack -u opc.tcp://localhost:4844 -n "ns=2;s=h6gal/vd03/RuntimeAlert" -e 8DB71E793FBD7040993404E30808FADC -c "OtOpcUa #614 H6 gate" -U apikey -P <temp key>
Acknowledge successful: ns=2;s=h6gal/vd03/RuntimeAlert
```
The live subscriber running during the ack saw:
```
[2026-11-11T17:37:55.8648690Z] ALARM h6gal/vd03/RuntimeAlert
State: Active, Acknowledged
Severity: 500
Retain: True
EventId: 0F15D34C9D0B6D43B7A4B08F3A72D047
```
Driver log (account name redacted):
```
[17:37:55 INF] Galaxy driver h6gal: acknowledging Galaxy!CVDAisle_1.TableAlarms_008.RuntimeAlert as Galaxy user NAM\<ack account> (Fallback) for OPC UA principal h6gate (key fa1d95d325ab9ab5)
[17:37:55 INF] DriverInstance h6gal: acknowledged native condition h6gal/vd03/RuntimeAlert by h6gate
```
No warning, refusal or revert followed. So the gateway answered `PROTOCOL_STATUS_CODE_OK` with
`hresult` 0 (or absent): a non-OK status or a non-zero hresult throws and is logged. The comment the
driver sent was `OtOpcUa #614 H6 gate [OPC UA: h6gate, key fa1d95d325ab9ab5]`.
## Step 2: Galaxy and the gateway alarm feed (FAIL)
`QueryActiveAlarms` (prefix = the alarm reference) about 30 s after the ack, unchanged from before:
```
"currentState": "ALARM_CONDITION_STATE_ACTIVE", "severity": 400,
"lastTransitionTimestamp": "2026-07-29T01:02:46.830Z", "operatorComment": "Run Time Exceeded"
```
Read-only gateway session (`OpenSession` → `Register` → `ReadBulk` → `CloseSession`), at 17:39:24Z and again at 17:40:18Z:
| Attribute | Value | Quality |
|---|---|---|
| `TableAlarms_008.RuntimeAlert.Acked` | **False** | 192 |
| `TableAlarms_008.RuntimeAlert.AckMsg` | **""** (empty) | 192 |
| `TableAlarms_008.RuntimeAlert.InAlarm` | True (since 2026-07-28T20:02:46.830Z) | 192 |
On the windev rig, mxaccessgw's gateway-level verification (`AlarmProbeFindings.md`) showed a
successful ack turning `.Acked` True and leaving the comment in `.AckMsg`. Neither happened here.
## Step 3: AVEVA event history (FAIL)
`v_AlarmEventHistory2`, `EventStamp` 2026-11-11 12:00 to 23:59 local, queried at 17:38, 17:39 and 17:46 UTC.
The Historian is live: it stored other events at 17:00 UTC. Nothing for this alarm:
```
2026-11-11 12:00:30.922 | 17:00:30.922 | UNACK_ALM | DevWinPlatform.CPULoadHiAlarm | NULL | NULL
2026-11-11 12:00:50.918 | 17:00:50.918 | UNACK_RTN | DevWinPlatform.CPULoadHiAlarm | NULL | NULL
```
There is no `ACK_ALM` or `ACK_RTN` row for `TableAlarms_008.RuntimeAlert` and no row with `OperatorNode=MxGateway`.
## Defect: OtOpcUa reports Acknowledged on an ack Galaxy never applied (reported, not fixed)
mxaccessgw returns `OK`/`hresult 0` both for "write applied" and for "write sent, no `OnWriteComplete`
within the wait (unconfirmed, with a diagnostic)" (mxaccessgw `docs/Grpc.md`, `AcknowledgeAlarm`
outcome table). Its own docs say that "a client that must be certain should watch for the resulting
transition on `StreamAlarms`".
`GatewayGalaxyAlarmAcknowledger.EvaluateReply`
(`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.Galaxy/Runtime/GatewayGalaxyAlarmAcknowledger.cs`) treats OK +
hresult 0 as success. It never reads or logs `AcknowledgeAlarmReply.diagnostic_message`, and nothing
in the driver or host waits for the upstream Acknowledge transition. So the #760 revert never fires,
and the OPC UA condition stays Acknowledged while Galaxy holds `.Acked=False`. A ScadaBridge or
operator client would believe the alarm was handled.
Why the gateway-side write did not take effect cannot be determined from here: the gateway's logs are
on wonder-app-vd03, and remote commands are barred. Candidates:
- an unconfirmed `AckMsg` write that was later dropped or rejected;
- the account lacking acknowledge permission on the object's security group;
- a VD03 gateway build that predates the `AckMsg` path.
Not attempted again (one-ack rule). Suggested follow-ups (not filed, no Gitea per brief):
- **OtOpcUa:** log `diagnostic_message` on every ack reply. Treat an unconfirmed ack as pending until
the feed shows the Acknowledge transition, and revert on timeout.
- **mxaccessgw:** expose applied vs unconfirmed as a field rather than only in a diagnostic.
- **Owner:** check the VD03 gateway log around 2026-11-11T17:37:55Z for the ack's diagnostic.
## Other observations (not filed)
- **The gateway snapshot timestamp is 5 h off.** It reports `lastTransitionTimestamp
2026-07-29T01:02:46.830Z`. MXAccess's own `InAlarm` timestamp and the Historian's `EventStampUTC`
both say 2026-07-28T20:02:46.830Z. Cross-repo, mxaccessgw.
- **The gateway snapshot and the Historian disagree on state.** The gateway says ACTIVE since July,
and `.InAlarm` agrees. The Historian logged five later "set off scan" `UNACK_RTN` rows (latest
2026-10-22) with no new `UNACK_ALM`.
- **Severity differs between the three views.** The OPC UA condition shows Severity 500. The authored
`alarm.severity` was 400, and so is the Galaxy priority.
- **site-b-2 never acknowledged the cleanup deploys.** After cleanup, the standby `site-b-2` (restarted
and restored from its LocalDb at the same revision `e221b179…`) did not ack the re-dispatched
deployment, so the reseal deploy also ended `TimedOut` (site-b-1 Applied).
- **The rig needed a nudge after the OrbStack restart.** `otopcua-dev-sql-1` and
`otopcua-dev-traefik-1` stayed Exited. I started them and restarted central-1 and central-2 (#868
ordering) before seeding.
## Cleanup
- Deleted from the ConfigDb:
- `Tag h6gal-rtalert`, `Device h6gal-vd03` and `DriverInstance h6gal`;
- `NodeAcl h6gate-acl` and `ApiKey h6-gate` (`fa1d95d325ab9ab5`);
- the two gate `Deployment` rows that carried the driver config, and their `NodeDeploymentState` rows,
so the account name is not left in an artifact blob.
- Cleanup deployed (`h6-gate-cleanup`, `h6-gate-cleanup-reseal`). site-b-1 logged `GalaxyDriver h6gal shutting down … disposed`.
- site-b-1 recreated from the plain compose file: the ack password is absent and the gateway key is back
to the committed default. site-b-2 restarted.
- The scratch key file was deleted. The shell env was unset.
- The site-b-1 LocalDb cache may still hold a gate-era artifact until its next replacement.
@@ -0,0 +1,195 @@
# Heidenhain LSV2 live commissioning — 2026-11-11 (#829, #853)
.NET commissioning evidence for the read-only Heidenhain LSV2 driver (`Driver.Heidenhain`) against four
**production** Hermle iTNC 530 mills, through a deployed OtOpcUa server and OPC UA clients. Owner-approved scope:
read-only LSV2 only (INSPECT login with an empty password, plus the driver's default optional DNC login attempt and
its allowlisted reads), no writes to the controls, no DATA login, no controller configuration change, one
concurrent session per control, poll intervals at or above the driver defaults. Outages were simulated only by
stopping a local TCP proxy.
## Setup
| Item | Value |
|---|---|
| Server | docker-dev rig, image `otopcua-host:dev` built 2026-11-11 15:45 UTC from master (newest Heidenhain commit at build time: `ddc1f29e`, #839) |
| Node | SITE-B, `site-b-1` (OPC UA `opc.tcp://localhost:4844`). Its pair partner `site-b-2` was **stopped** for the run so each control had exactly one session (a warm standby acquires too) |
| Driver | `hh829`, DriverType `Heidenhain`, seeded straight into the ConfigDb, deployed with `POST /api/deployments` |
| Devices | `Hermle59`, `Hermle49`, `Hermle70`, `Hermle29`, each `host.docker.internal:190xx` → a socat proxy on the Mac → `<control>:19000` |
| Proxies | `socat -x TCP-LISTEN:<port>,bind=127.0.0.1,fork,max-children=1 TCP:<control>:19000`; `max-children=1` caps upstream sessions at one, `-x` hex-dumps every byte in both directions (the wire census below is parsed from those dumps) |
| Tags | 46 per control (184 total): the 35 fixed leaves — Controller, Status, Program, Overrides, Axes, Tool, Alarms and 11 Capabilities (timers left off) — plus 11 `ALARM:` conditions (`ALARM:*`, `ALARM:OTHER`, `ALARM:CLASS=1..9`, severity 700). Tag `DataType`s follow `HeidenhainTagRules`; AccessLevel `Read`. Deploy reported 184 authored, 0 skipped |
| Config, phase A (steps 1–3) | `TimeoutMs` 5000; Status/Custom/Slow/Alarm **15000 ms**; MaxAlarms 64; Telemetry on; DNC login on (driver default); DATA off; timers off; reconnect 1000–30000 ms |
| Config, phase B (step 4) | the driver defaults: Status 1000, Custom 1000, Slow 10000, Alarm 2000 ms (about 3 minutes) |
| Clients | `otopcua-cli` (`src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI`) and python-opcua 0.98.13 (bulk typed reads and raw Write service calls) |
## Controls
Identity read through OPC UA; it matches the Java/Ignition evidence (`ignitionoee/docs/recipes/evidence/heidenhain-final-0.20.3-2026-11-03`).
| Control | Endpoint | Model / NC / PLC | Options |
|---|---|---|---|
| Hermle59 | 10.201.29.226:19000 | iTNC530 / 340490 04 SP10 / iC30v7.1_1 | `%0000111100000111` |
| Hermle49 | 10.201.29.225:19000 | iTNC530 / 340490 03 SP10 / iC30V6.1_2SP3 | `%0000111100000111` |
| Hermle70 | 10.201.22.225:19000 | iTNC530 / 606420 03 SP4 / iC22_V20.1_2SP2 | `%0000111100000111` |
| Hermle29 | 10.201.22.215:19000 | iTNC530 / 606420 03 SP4 / iC22_V20.1_2SP2 | `%0000111100000111` |
## Step 1 — browse and read through OPC UA
The raw tree browses as `ns=2;s=hh829/<Control>/<Folder>/<Leaf>`, and every condition carries its Part 9 children.
Every leaf advertises **AccessLevel = 1 and UserAccessLevel = 1** (CurrentRead only). Array leaves have ValueRank 1.
| Leaf group | Hermle59 | Hermle49 | Hermle70 | Hermle29 |
|---|---|---|---|---|
| Controller/* (4) | Good | Good | Good | Good |
| Status/ExecutionState, ProgramState | Good (1, 7) | Good (4, 7) | Good (4, 0) | Good (4, 0) |
| Program/Main, Current, Line | Good (Line 0) | Good (Line 0) | Good, running (Line 42255 and counting) | Good, running (Line 40474 and counting) |
| Overrides/* (R_RI 25) | BadUserAccessDenied | BadUserAccessDenied | BadUserAccessDenied | BadUserAccessDenied |
| Axes/Names | `X Y Z C a A` | `X Y Z C a A` | `X Y Z C a A` | `X Y Z C a A` |
| Axes/Positions | Good, 6 values | Good, 6 values | Good, 6 values, moving | Good, 6 values, moving |
| Tool/* (R_RI 51) | Good (tool 0) | **BadNotSupported** (all 5) | Good (T49, L 138.1506, R −0.0101) | Good (T17, L 138.303, R −0.0101) |
| Alarms/* | Good, Count 0 | Good, Count 0 | Good, Count 0, then 1 (below) | Good, Count 1 |
| Capabilities | DncLogin `AccessDenied`, Overrides `AccessDenied`, DataLogin/PlcLayout `Disabled`, the rest `Supported` | same, and Tool `Unsupported` | as Hermle59 | as Hermle59 |
Per control: 32 Good + 3 BadUserAccessDenied (Hermle49: 27 Good + 3 BadUserAccessDenied + 5 BadNotSupported).
This matches the LiveIntegration results and the Java evidence: R_RI 25 refused 23 (access denied) on all four,
R_RI 51 refused 24 (unsupported) on Hermle49, and the DNC login refused 23 on all four. INSPECT alone serves every
other selector.
### Defect found — Tool Number/Index/AxisCode are published as Double
`Tool/Number` (node DataType Int64) and `Tool/Index` / `Tool/AxisCode` (Int32) arrive at the client as a
**Double** variant (49.0, 0.0, 2.0) on every control that serves R_RI 51. Other integer leaves are correct
(`Program/Line` Int64, `Status/*` and `Alarms/Count` Int32). Cause: `HeidenhainSession.Leaf`, `case Lsv2Tool t`,
returns a switch expression whose arms are `long`, `int`, `int`, `double?`, `double?`. C# gives the expression the
type `double?`, so the integers are converted before boxing. The `Lsv2Program` arm next to it avoids this with an
`(object)` cast. `HeidenhainSessionTests.Tool_without_geometry_is_not_supported_not_zero` does not catch it:
Shouldly's `ShouldBe(7L)` treats a boxed `7.0` as equal. `otopcua-cli read` also hides it, because it prints `49`.
A strict client, or one that checks the variant type against the node's DataType, gets a type mismatch. Not fixed
here, per the run's read-only brief.
## Step 2 — OPC UA write attempts are refused; no write frame leaves the driver
| Attempt | Principal | Result |
|---|---|---|
| `otopcua-cli write` Controller/Model, Status/ExecutionState, Tool/Number × 4 controls | Anonymous and a temporary API key with all permissions on SITE-B | **BadNotWritable** (0x803B0000), all 24 |
| `otopcua-cli write` Overrides/Feed (all), Tool/Number (Hermle49) | both | the CLI's pre-write read fails (BadUserAccessDenied / BadNotSupported) and nothing is sent |
| Raw Write service (python): Overrides/Feed, Tool/Number, Axes/Positions, AlarmConditions/AnyAlarm/ActiveState × 4 controls | both | **BadNotWritable**, all 32 |
| Part 9 Acknowledge, Hermle29 AnyAlarm | API key | Good — applied **server-side only** (AckedState → Acknowledged) |
| Part 9 Acknowledge, Hermle29 Class7 | Anonymous | BadUserAccessDenied (AlarmAck gate) |
Unlike the Java run, where the anonymous access check rejected every write first, a principal that **holds write
permission** was refused here by the node's access level (BadNotWritable).
**Wire census.** The proxies' byte dumps, parsed frame by frame for the whole run (all sessions, both phases),
contain only `A_LG INSPECT`, `A_LG DNC` (each once per session, empty password), `R_VR`, `R_RI` 22/23/24/25/26/27/28/51.
There were **no** non-allowlisted commands and no `R_MB`, `R_DP` or `C_*` frames. In the write and acknowledge
window (17:00:45–17:02:20 UTC), each control received only its regular poll reads (`R_VR`, `R_RI` 22–28/51).
Client→control bytes for the whole run: Hermle59 12 876, Hermle49 12 746, Hermle70 13 396, Hermle29 15 526.
## Step 3 — outage and recovery (Hermle59 proxy)
An OPC UA read loop sampled once a second: every value leaf of all four controls (35 each), plus each control's
AnyAlarm condition Quality.
| Event (UTC) | Hermle59 | Others |
|---|---|---|
| Before the stop | 32 Good + 3 BadUserAccessDenied | unchanged |
| 17:06:02.6 proxy stopped | — | — |
| 17:06:05 (next poll, +2.4 s) | **all 24 remote leaves BadNoCommunication**; the 11 Capabilities leaves read `CommunicationLost`; AnyAlarm Quality BadNoCommunication; log: `LSV2 communication lost; reconnecting with backoff`, `alarm list unavailable (CommunicationLost); its 11 alarm condition(s) keep their state` | unchanged, Good |
| 17:06:06–12 | reconnects back off (connection refused at 1, 2, 4… s) | unchanged |
| 17:06:15.8 proxy restarted | — | — |
| 17:06:20 reconnect (backoff) → 17:06:22 | **all Good again** (~6 s after the proxy came back); `alarm list readable again` | unchanged |
Across 327 of 328 samples, Hermle49, Hermle70 and Hermle29 kept their exact status mix. The one exception was the
17:10:31 phase-B redeploy, which respawned the whole driver. The driver's health read `Degraded` with the connect
error while Hermle59 was down. Detection is bounded by the next poll of that control (Status interval + TimeoutMs).
A second, unplanned leg (below) also showed that a control unreachable at driver start retries and recovers: from
17:04:04 to 17:05:34 Hermle59's leaves were BadNoCommunication with `CommunicationLost` capabilities, and they were
all Good about 1 s after the reconnect at 17:05:35.
## Step 4 — load at default intervals
The proxy byte dumps give these per-control figures (RTT = request → reply). The channel is one transaction at a
time.
| Phase | Control | Requests/s | Bytes/s out / in | RTT median / p95 / max (ms) | Channel busy |
|---|---|---|---|---|---|
| A (all 15 s), 180 s | Hermle59 | 0.53 | 5.2 / 16.4 | 50 / 133 / 175 | — (one ~0.5 s batch per 15 s) |
| | Hermle49 | 0.47 | 4.5 / 14.5 | 48 / 134 / 159 | |
| | Hermle70 | 0.53 | 5.2 / 18.5 | 47 / 135 / 170 | |
| | Hermle29 | 0.67 | 6.5 / 27.5 | 50 / 137 / 160 | (batch ≈ 0.67–0.83 s) |
| B (defaults 1/1/10/2 s), 180 s | Hermle59 | 4.78 | 47.6 / 148.5 | 50 / 133 / 396 | 30.3 % |
| | Hermle49 | 4.68 | 46.6 / 145.6 | 48 / 135 / 474 | 28.6 % |
| | Hermle70 | 4.78 | 47.6 / 176.3 | 47 / 132 / 244 | 28.1 % |
| | Hermle29 | 5.38 | 53.6 / 216.3 | 48 / 128 / 244 | 32.1 % |
Request mix at the defaults over 180 s, per control: R_RI 22/23/24/26 179 each (the 1 s status group keeps up),
R_VR 18 and R_RI 51 18 (10 s slow group), and **R_RI 27 108**, which is 90 alarm walks (2 s) plus 18 slow-group
walks. R_RI 28 also ran 108 times on Hermle29, the control with an active alarm. R_RI 25, and R_RI 51 on Hermle49,
were sent **once per session** and then suppressed as documented. No control slowed down or refused anything new
under either cadence.
Observation, not a defect: when a control carries `ALARM:` tags **and** the `Alarms/*` arrays, the alarm walk runs
twice — once per `AlarmMs` for the conditions and again in the Slow group for the arrays. The two are separate reads,
not shared. At the defaults that is about 0.1 extra R_RI 27 per second per control.
## #853 — alarm class/group → Part 9 condition class
Every alarm seen during the run (about 16 minutes of walks on all four controls). None were provoked.
| Control | Wire record (`S_RI 27`) | Class | Group | Number (int32 / hex) | Text | Driver's condition class |
|---|---|---|---|---|---|---|
| Hermle29 | `0007 0003 8100017b …` | 7 Info | 3 Plc | −2130706053 / `0x8100017B` | `702126 Filter wait for spindle cooling (U02) E161` | `BaseConditionClass` (i=11163) |
| Hermle70 (raised 17:01:47, cleared before 17:13) | `0007 0003 8100015e …` | 7 Info | 3 Plc | −2130706082 / `0x8100015E` | `701550 Cabin unlocked! B301` | `BaseConditionClass` (i=11163) |
| Hermle59, Hermle49 | — (R_RI 27 → T_ER 57, empty list throughout) | | | | | |
- Both conditions behaved as designed. `AnyAlarm` and `Class7` went Active, severity 700, Quality Good, with the
message `<number> <text> (class 7, group 3)`. The `OtherAlarms` and other class conditions stayed Inactive.
Hermle70's alarm raised live, mid-run.
- **Consistent with the mapping table.** Group 3 (`Plc`) maps to Base. Both texts are machine-builder (Hermle) PLC
messages: a 70xxxx message number and a device tag (`E161`, `B301`). That fits the RemoTools `DNC_ERROR_GROUP`
numbering, where 3 = PLC. Class 7 = Info fits non-fatal status notices, and the one record captured earlier
(−1 "Run test of cutout channels", class 7 / group 4) is consistent too. The live data now corroborates
**class 7, group 3 and group 4**.
- **Still unobserved on hardware:** classes 1–6, 8 and 9 (including 5 EmergencyStop → Safety) and groups 1, 2, 5
and 6 (the Process/System/Python rows). Confirming them would need an active alarm of those kinds, which this run
did not provoke.
- Note for authors: on these controls the alarm **number** field is not the displayed message number. It reads as
`0x81xxxxxx`, which is negative as int32, and the HMI number is the leading digits of the text. A `NUMBER=` selector
therefore has to use the negative raw value. This is documented ("filter on the raw codes"), but worth knowing.
## Incidental findings (outside the Heidenhain driver)
1. **Operator error during the run, now recovered.** When the first outage leg stopped the Hermle59 proxy,
`kill $(lsof -ti tcp:19059)` also matched and killed OrbStack's networking helper, which held the forwarded
connection. The OrbStack VM stopped; every container restarted when `orbctl start` was run (17:03–17:04 UTC), and
`otopcua-dev-sql-1` / `otopcua-dev-traefik-1` were started by hand. The outage leg was then re-run cleanly by
killing only the socat processes. **After this restart the OrbStack containers can no longer reach the LAN host
10.100.0.35** (the driver fixtures and opc-plc). The Mac itself, internet access and the 10.201.x VPN still work.
Before 17:03 there were no such errors. This most likely needs OrbStack restarted from the app, or its macOS
Local Network permission re-granted.
2. **ConfigPublishCoordinator does not survive a ConfigDb that is unreachable at singleton start.**
`ConfigPublishCoordinator.PreStart` queries the DB synchronously. With SQL still starting, it threw
`ActorInitializationException` (SqlException: name not resolved), the singleton was terminated
(`Singleton actor [akka://otopcua/user/config-publish/config-publish] was terminated`) and it never restarted.
Every deploy then waited forever (`ClusterSingletonProxy failed to find … [config-publish]` every 30 s). Restarting
central-1 moved the singleton to central-2, which recovered it. This is a real resilience defect for any host that
boots before its ConfigDb.
3. The first deployment (`7a47a745`) ended `TimedOut` (5/6 acks) because `site-b-2` was stopped. The later deploys
set `ClusterNode.MaintenanceMode = 1` on `site-b-2` and sealed. The flag was reset to 0 afterwards.
## Cleanup
The `hh829` driver, its 4 devices, 36 tag groups and 184 tags were deleted, along with the temporary API key and
SITE-B NodeAcl. Deployment `6c7f859f` sealed at 17:14:13, and the driver was stopped and disposed on `site-b-1` at the
same moment. All four proxy sessions closed, and then the proxies were stopped. `site-b-2` was restarted (standby,
no Heidenhain driver), and `site-b-2` MaintenanceMode was restored to 0. Nothing on the controls was changed.
## Status against the gates
- **#829:** browse/read, write refusal (including a write-capable principal), outage and recovery with the other
controls unaffected, bounded traffic at default intervals, and retained evidence are **done** on four iTNC 530
controls. **Open:** the Tool Number/Index/AxisCode Double-variant defect above, which should be fixed and
re-verified with a strict variant-type assertion. Still unproven as before: other control families
(TNC 320/430/640), successful `R_MB`, units, timers 30–34, and DATA (not exercised under this scope).
- **#853:** partially confirmed — class 7, groups 3 and 4 match the RemoTools numbering and map as documented
(Base). Classes other than 7 (notably 5 → Safety) and groups 1/2/5/6 are not yet observed on hardware.
@@ -0,0 +1,91 @@
# TwinCAT Test Connect on a real ADS target: Z35474, 2026-11-11
Gitea #755 item: "Driver probe (Test Connect) happy path on a real ADS target".
**Result: the item cannot be ticked. On real hardware the probe returns a false RED.** The ADS
target is healthy and reachable through the router, but `TwinCATDriverProbe` never gets to its
ADS handshake: its TCP preflight dials the wrong endpoint.
## Target and scope
| | |
|---|---|
| Press | Z35474 (Elma cleaner), production |
| IP | 10.201.23.227 (reached over the VPN) |
| AmsNetId / port | `5.118.56.93.1.1` : 851 (TC3 PLC runtime 1) |
| Route used | the existing press-side route `otopcua-mac-20261111` → `10.181.201.5.1.1` (no AddRoute sent) |
| Scope | read-only: ReadState, ReadDeviceInfo, symbol upload (Flat), two scalar reads. No writes, no WriteControl, no notifications, no route-table change. One session at a time, a few seconds per run. |
## Harness
This is a scratch console app outside the repo. It has a `ProjectReference` to
`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.TwinCAT` and hosts `Beckhoff.TwinCAT.Ads.TcpRouter` 7.0.172 in
process. The router's local NetId is `10.181.201.5.1.1`, with one route `Z35474 → 10.201.23.227 /
5.118.56.93.1.1`. The package's sample `StaticRoutes.xml` is excluded, so the router loads no other
routes. The Beckhoff ADS client is 7.0.172, the same version the driver uses.
The harness drives the probe the way AdminUI does:
- `RawTreeService.LoadMergedProbeConfigAsync` builds the config through
`DriverDeviceConfigMerger.Merge("{}", [DeviceRow("Z35474", {"hostAddress":"ads://5.118.56.93.1.1:851"})], [])`.
- `AdminOperationsActor.ProbeAsync` calls `new TwinCATDriverProbe().ProbeAsync(merged, 10 s, cts(10 s))`.
The 10 s budget is `TestConnectBudget`'s TwinCAT default.
The merged config the probe received:
```json
{"hostAddress":"ads://5.118.56.93.1.1:851","Devices":[{"hostAddress":"ads://5.118.56.93.1.1:851","DeviceName":"Z35474"}],"RawTags":[]}
```
## Observed (two runs, identical)
```
[probe] Ok=False Message="Probe timed out after 10s." Latency=- wall=10003ms
[phase2] ReadState Succeeded=True Err=Succeeded AdsState=Run DeviceState=0 189ms (2nd run 109ms)
[phase2] DeviceInfo Succeeded=True Name="Plc30 App" Version=3.1.1940
[browse] roots=3384 (Flat symbol upload)
[read] .actualOperationMode : INT = 2
[read] .CFG_NUM_CDA_MAX : INT = 5
```
`[phase2]` is not the probe. It reproduces the probe's own Phase 2 (`AdsClient.Connect(netId, 851)` +
`ReadStateAsync`, `Timeout` = 10 s) in the same process through the same router. It shows that the
handshake the probe would have done succeeds: Run state in about 0.1–0.2 s.
Device: **"Plc30 App", ADS version 3.1.1940, AdsState Run, DeviceState 0.** The browse found 3,384 Flat
roots, which matches the 2026-10-08 count.
## Defect: the Phase 1 TCP preflight targets `(NetId[0..4]):(AMS port)`
`TwinCATDriverProbe.ExtractTarget` builds the preflight target as the first four octets of the AmsNetId
plus the AMS port. It then runs `Socket.ConnectAsync(host, port)` before it tries ADS. That target is
wrong in two separate ways:
1. **The AmsNetId is not the IP.** For Z35474 the preflight dialled **`5.118.56.93:851`**. That is a
public internet address unrelated to the press; on this Mac it routes out of the LAN gateway, not the
VPN. It black-holes, so the probe spends its whole 10 s budget and returns "Probe timed out after
10s." The press is at 10.201.23.227. The driver config has no IP field, so the probe cannot know it.
Only the AMS router knows it.
2. **851 is an AMS port, not a TCP port.** ADS/TCP is 48898. On a press where the NetId happens to equal
the IP (for example Z33856 `10.201.45.236.1.1`), the preflight would dial `10.201.45.236:801/851`.
That should be refused and return "Connect failed: ConnectionRefused", also a RED. I inferred this
from the code and did not run it against that press.
Consequence: Test Connect cannot go green against a real TwinCAT runtime. It stops at Phase 1 before
the ADS handshake, which works. The unit tests (`TwinCATDriverProbeTests`) pin the current behaviour:
they open a loopback `TcpListener` on the "AMS port" and use `ads://127.0.0.1.1.1:{port}`, so the
mismatch never shows up there. The probe also sends a TCP SYN to whatever internet host the NetId's
first four octets name.
The fix is not made here: tracked source was left unedited, as the task asked. The fix direction is
to drop the remote preflight, or point it at the local AMS router (`127.0.0.1:48898`), which is the
only TCP endpoint the ADS client actually uses. Phase 2's `ReadStateAsync`, bounded by the timeout,
then becomes the real reachability check. The unit tests would need to change with it.
## #755 status
- "Test Connect happy path on a real ADS target": **not tickable.** The ADS path works (router, route,
ReadState = Run, device info, browse, reads), but the probe as AdminUI runs it returns a false RED.
Re-run this gate after the preflight fix.
- The harness lives in session scratch, not in the repo:
`scratchpad/twincat/probeharness/` (`Program.cs`, modes `probe` | `read`).