Array tags were advertised writable but every write threw InvalidCastException
in ConvertForWrite (reported BadTypeMismatch); STRING writes went through the
Beckhoff marshaller with no length check against STRING(n) and the host's
ANSI code page, which the read side deliberately avoids.
- Array write: TwinCATArrayCodec.ToWriteElements converts exactly ArrayLength
elements to the declared type (CLR lists convert - ScadaBridge writes int[]
to Int16 nodes; a length mismatch or out-of-range element is BadOutOfRange, a
scalar value BadTypeMismatch) before any wire traffic; the ADS client plans
the layout from the resolved PLC array (TwinCATTypeGuard.CheckArray, as the
read does), encodes with TwinCATArrayCodec.Encode - the exact inverse of
Decode - and writes the raw bytes (new ITwinCATClient.WriteArrayAsync).
- STRING / WSTRING write: encoded at the PLC's declared width by
TwinCATStringCodec.EncodeString/EncodeWString (Windows-1252 or UTF-8 per
target, NUL-padded, strict: an over-long value or unrepresentable character
is OverflowException -> BadOutOfRange) and written as raw bytes.
- TwinCAT CLI read/write gain --array-length (+ --separator) for the hardware
gate.
Refs #739
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The bit write read and wrote the parent word as a 32-bit UDInt with no parent
check: a bit beyond a 16-bit parent was written into neighbouring bytes, and a
signed parent with its sign bit set read back >= 2^31, so the checked
conversion turned any bit write into BadOutOfRange.
The write now goes through ITwinCATClient.WriteBitAsync: the ADS client
resolves the parent symbol, checks the bit against it (TwinCATBitAccess.
CheckParent, as the notification path already did), reads exactly
parent.ByteSize raw bytes, flips one bit (TwinCATBitAccess.ApplyBitWrite) and
writes the bytes back by index group/offset or variable handle. A bit beyond
the parent is BadOutOfRange, a non-integer parent BadTypeMismatch, a short
parent read BadCommunicationError (never written back), all without a health
write. The per-parent RMW lock stays in the driver.
Refs #739
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
CompleteRead logged a Warning for every non-Good status on every poll and
latched Degraded for all of them. Now a bad tag warns once per bad episode
(re-armed when it reads Good, and on re-initialise), a comms-class status
(BadCommunicationError / BadTimeout) degrades with LastSuccessfulRead
preserved, and any other status - the device answered and refused this tag -
advances LastSuccessfulRead with no state change. Read-path exception
handlers now go through MarkCommsFault, so they never downgrade Faulted.
Refs #739
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
In native-notification mode LastSuccessfulRead never moved past the init
stamp, so one Degraded write on a connection older than 90 s latched the
comms-loss watchdog into a full reconnect (every notification on every device
deleted and re-registered). Conversely an unreachable AMS router was swallowed
by the probe and never left Healthy.
- a native push and a successful probe now stamp LastSuccessfulRead (throttled
to one health record per 250 ms) and restore Healthy unless a device is still
probe-unreachable;
- 3 consecutive failed probe ticks write Degraded with the stamp preserved;
- a NotSupportedException write is BadNotSupported with no health write (#611);
- a reconnect replay the PLC refuses republishes the refusal's status without
degrading (it used to report BadCommunicationError + Degraded on every
reconnect for a correctly-isolated type-mismatch tag).
Refs #739
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Native subscribe was all-or-nothing: any registration failure other than a
type refusal disposed every registration and rethrew, so one typo'd symbol or
one unreachable PLC in a multi-device driver served zero data, churned
register/delete every reconcile tick, and left health Healthy.
Now each registration fails on its own: a refusal (the device answered: symbol
not found, PLC not ready, type mismatch) publishes its status with no health
write; any other per-tag failure publishes BadCommunicationError and degrades;
a connect failure marks the device unreachable for the rest of the call and
stores its tags as dead intents. Every failed tag is kept as a dead intent that
the probe-tick retry and the reconnect replay re-register. The ADS client now
classifies a failed symbol resolve / AddDeviceNotification by status instead of
throwing InvalidOperationException for all of them. Cancellation still tears
the partial subscription down.
Refs #739
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The native subscribe path silently skipped a reference it could not resolve
(unknown RawPath, or a tag routed to an unconfigured device), leaving the node
on whatever status the server seeded. It now publishes one BadNodeIdUnknown
snapshot, matching the poll path.
Refs #739
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
GalaxyTelemetryTests (ActivityListener) and GatewayGalaxyDataWriterFailClosedTests
(MeterListener, filtered only by meter and instrument name) observe every Galaxy span or
measurement in the process. They now run in a collection with parallelization disabled
(F-FU6), because a parallel driver test, or its background probe seed, polluted their counts.
The stream-cancel assertion in GalaxyDriverShutdownTests goes back to a bounded wait: the
instantaneous IsCompleted check introduced in round 1 was racy.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review fix round 2 for lane F:
- N1: the init platform seed no longer runs inline under the init token. Galaxy's Tier-A
Initialize budget is 5 s, and a cold gateway DiscoverHierarchy can spend all of it, so the
OperationCanceledException rethrow failed init, opened the Initialize breaker and cost a full
rebuild per retry. InitializeAsync now only resolves the platform source (no network) and
queues a background seed tied to a per-runtime CTS that the teardown cancels. A result that
lands after its runtime was torn down is discarded.
- N2: the seed worker serves the runtime that is live when each pass STARTS, so a request made
under a new runtime while a stale pass is in flight always gets a pass of its own.
- N3: SubscribeAsync and the subscribe-once read capture the runtime generation before
SubscribeBulk and register only if it is unchanged, atomically with the teardown's registry
Clear (_registryGate). On a mismatch they release the handles and fail the call. Re-subscribe
Rebind uses the same gate, and the production rebuild clears the registry unconditionally.
- PerPlatformProbeWatcher re-checks its stop after the SubscribeBulk await, atomically with
the record and publish. A pass that straddles StopAsync releases the handles it acquired
instead of writing the probe entry back into a cleared registry.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The writer concurrency fake parks on its release signal (the 300 ms delay could release the
gate early on a starved pool), the supervisor test's cross-thread hold flag is Volatile, and
the EffectiveTimeout doc now states the 1 s floor the code and tests implement.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review fix round 1 for lane F:
- The ScanState probe watcher is seeded at InitializeAsync from a platform-only
DiscoverHierarchy query (IGalaxyPlatformSource / GatewayGalaxyPlatformSource over the owned
repository client) and re-seeded on every deploy-watcher rediscovery. The runtime never
calls DiscoverAsync on a live driver, so per-platform host status was unreachable in
production. A failed fetch logs a Warning and never fails init; re-seeds coalesce so a
deploy during an in-flight pass still gets a pass that starts after it.
- EnsureEventPumpStarted refuses while the runtime is stopping, BEFORE reusing the live pump
(that pump belongs to the dying subscriber), and the production rebuild disposes any stale
pump before wiring the new subscriber.
- TeardownRuntimeAsync closes the MX session under the caller's token linked with a 5 s
SessionCloseDeadline, so a blackholed gateway cannot hold DriverInstanceActor.PostStop for 30 s.
- A runtime generation counter, bumped by every teardown, is re-checked before each Rebind
in ResubscribeAllAsync, so a replay-gap re-snapshot that straddles a teardown cannot
resurrect handles into the cleared registry.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The SDK's DisposeAsync closes with no token, i.e. under the 30 s DefaultCallTimeout, so a
blackholed gateway parked the driver's teardown for the whole of it. CloseAsync(ct) runs the
close under the caller's token, drops the channel on a cancelled/failed close (the gateway
reaps the session on its idle lease) and leaves the session re-openable. A close followed by
the final dispose closes the gateway session once.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 2026-10-21 G-5, G-6, G-8 ("wire them all").
- G-5: GatewayGalaxyHierarchySource now pages the DiscoverHierarchy RPC
itself (DiscoverHierarchyRawAsync) at Repository.DiscoverPageSize. The
mxaccessgw client's typed DiscoverHierarchyAsync overloads hard-code a
5000-row page and DiscoverHierarchyOptions carries no page size, so the
authored knob reached nothing; the raw request takes page_size on the
wire, so it is honoured here (non-positive → 5000). The loop keeps the
client's repeated-page-token guard.
- G-6: GalaxyDriverProbe reads ProbeTimeoutSeconds from the config and
runs under min(caller budget, configured cap) — the knob can shorten a
probe, never extend it past the host's budget. The TCP preflight now
shares that deadline instead of hanging on the caller's token alone.
- G-8: GatewayGalaxyDataWriter runs a batch as one lane per distinct tag,
concurrently and bounded at 8 (MaxConcurrentWriteLanes); same-tag
writes keep their authored order inside one lane and results land at
their request's index. Acks stay serial by design.
- GalaxyDriverForm: help text now says what the two knobs actually do.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 2026-10-21 G-4, G-7, G-11, G-10.
- G-4: PerPlatformProbeWatcher publishes its probe handles into the
driver's SubscriptionRegistry under the reserved ProbeSubscriptionId
(-1), so the EventPump's fan-out finally reaches the watcher — every
ScanState event used to be dropped as "stale after unsubscribe" and
per-platform host status never updated. ResubscribeAllAsync delegates
the reserved entry to the watcher's new ResubscribeAsync, so the probe
survives a reconnect; StopAsync removes the entry. Probe traffic is
routed by the reserved handle and never reaches the public OnDataChange.
The watcher is also built on the seam path (subscriber only), which is
what makes the wiring testable without a gateway.
- G-7: GalaxyDiscoverer.DiscoverAsync returns the hierarchy it fetched and
the driver selects its $WinPlatform/$AppEngine probe targets from that
same sweep instead of asking the gateway for the whole galaxy twice.
- G-11: OnPumpDataChange stamps LastSuccessfulRead from inbound stream
data, throttled (1 s default), so the comms-loss watchdog has honest
liveness evidence under a Degraded supervisor.
- G-10: an EventPump dispatch-loop exit that is not a cancellation now
reports a stream fault so the supervisor recreates the pump, instead of
leaving a deaf pump reporting Healthy.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
GalaxyDriver.ShutdownAsync was a no-op: the MX session, both owned gRPC
channels, the EventPump, the alarm feed, the DeployWatcher, the probe
watcher and the reconnect supervisor were released only by DisposeAsync,
which the host never calls — one leaked gateway session per respawn,
removal and /raw browse, and a watchdog Shutdown→Initialize that neither
tore down nor rebuilt anything (review 2026-10-21 G-1, G-2, G-9, G-3).
- ShutdownAsync and DisposeAsync share one ordered TeardownRuntimeAsync
(supervisor first, then deploy/probe watchers, pump, alarm feed,
session, channels); owned seams are nulled so the next InitializeAsync
rebuilds; injected seams survive a shutdown and drop only on the final
dispose. Lifecycle calls are serialised behind a gate.
- A failed production connect releases its partial runtime (no orphaned
client per watchdog retry) and lands Faulted before and after.
- StartDeployWatcherAsync stops the previous watcher before starting a
replacement, and now starts on a production instance's FIRST
InitializeAsync (the old guard returned whenever discovery had not run
here, which on a runtime instance is always).
- ReconnectSupervisor releases each cycle's CancellationTokenSource when
its loop exits and gains an awaitable StopAsync; PerPlatformProbeWatcher
gains an awaitable StopAsync.
- EventPump treats any exception under cancellation as a clean stop, so a
teardown never wakes the supervisor.
- Internal seams for tests: an IGalaxyDeployWatchSource ctor parameter and
a session-open override forwarded to the owned GalaxyMxSession.
Refs #735
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review R08:1.1: an uncapped HistoryRead-Raw (NumValuesPerNode = 0) read a
tag's whole window into memory on every backend (SQL TOP(int.MaxValue),
QuestDB LIMIT, Gateway max_values = int.MaxValue + a second snapshot copy).
New ServerHistorian:MaxRawValuesPerRead (default 10 000; <= 0 unbounded with
a Validate() warning; 1 raised to 2). Each backend data source takes it,
reports it as IHistorianDataSource.MaxRawValuesPerRead (the Gateway: min
with a strict gateway's learned ceiling), so the node manager's existing
RawPageLimit paging serves N = 0 and N > cap as pages of at most the cap
with a continuation point. Independently, a backend raw read asking for 0
or more than the cap reads cap + 1 rows and is REFUSED
(HistoryReadLimitExceededException => BadTooManyOperations) when the window
holds more - never answered truncated, since the server's paging reads a
short answer as the last page. Bound through the Host registry, the
SqlServer/QuestDb providers and GatewayHistorian.CreateDataSource.
Tests: options (default/binding/warnings), provider binding, Gateway unit +
through a real SDK node manager (uncapped -> 999/998/998/605 + CPs), and a
conformance case for the SQL backends.
Refs #736
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
The #687/F4 crowding re-read doubled its room up to 8 re-reads with no cap, so a pathological single-ms
cluster on a streaming gateway was streamed several times over for one page. The room is now capped at
ServerHistorian:MaxTieClusterOverfetch (plumbed into GatewayHistorianDataSource as maxPreWindowRows,
default 65536); past it, or once a read has already seen more, the read is BadTooManyOperations with
PreWindowRows set.
Item 1: IHistorianDataSource.MaxRawValuesPerRead (Gateway: learned ceiling - 16 = L; 0 elsewhere, guard-tested).
RawPageLimit plans every raw page on top of #692's lookahead: with L > 0 the read (page P + boundary ties k
+ lookahead) is <= L, P = min(N, L - k - 1) (uncapped: L - k - 1); no room => straight to the tie-cluster
over-fetch (never an uncapped or underflowing request). One re-plan + re-read when the read taught a new
limit or was refused for crowding pre-window rows (HistoryReadLimitExceededException.PreWindowRows): the
page shrinks by them. Over-fetch bound min(MaxTieClusterOverfetch, L - 1); slice size never 0.
Review fixes: F1 a window starting at/before the epoch counts AVEVA's synthetic row as pre-window (a
ceiling-truncated read was reported complete); F2 the page path disables ReverseRawReader's own re-run
(cold end-only ceiling 20/N=3000 cost 3,023 reads, now <= 40); F3 crowded look-back re-read around, not
refused; F4 the #687 crowding re-read room at least doubles (up to 8 re-reads), so a cluster of hundreds
just before a resume point no longer fails on a default gateway; a crowding refusal that leaves no room
is BadTooManyOperations, never a tick-by-tick cursor.
Item 2: ServerHistorian:EventReadHorizon (default 00:00:00 = exact, unchanged). When set, every fresh
HistoryReadEvents window's earlier bound is raised to now - horizon (both directions, all backends).
Lossy by design; documented.
Item 3 (native TimeAverage/Total re-check) stays blocked on historiangw#27.
A time inside a gap of a bursty tag costs a 64-row jump read landing in the next
burst plus a bisection back across the gap (~6 reads), so the 64 + 4/time cap
refused a 1 h/day 1 Hz tag asked at noon on 30/100/300 consecutive days
(186/606/1,806 reads) that AVEVA's own AtTime served. The cap is a runaway guard
(HistoryReadDeadline bounds wall clock): now 64 + 16 per distinct time.
Regression tests for x30/x100/x300 (each <= 7 reads a time, values checked).
Docs: DateTime-hinted nodes are stepped but keep the gateway's Double (the
Gateway never historizes DateTime nodes; the SQL backends return DateTime).
H1: the walk-back reset its width after a full segment and discarded a full
whole-remainder read, so a dense tag that stopped reporting weeks ago gave up
after 65 reads (BadTooManyOperations). It now gallops (x4, whole-remainder read
after two empties) and then BISECTS once any stored row is known below — a full
segment's (incl. a full whole-remainder read's) last row, or an earlier window
read's last row: (mid, hi] empty => hi = mid; full => known = its last row;
complete with rows => done; one density-aimed segment after a full read until an
aimed segment comes back empty; below 2 ms the whole stretch from the known row
(never a 100 ns step). Stopped 1 h..365 d with 5 y history: 6-18 reads at
1/min, 21-25 at 1 Hz, 25-31 at 10 Hz.
M1: a jump read asks for 64 rows (1,000 times over 10 y: ~66k rows, was ~1M).
L1: per-request read cap 64 + 4 x distinct times with a clear message; a strict
ceiling below 4 rows is refused naming the ceiling.
L2: DateTime hints are stepped. L3: under an integer hint a NaN/inf or
out-of-Int64-range value is unusable, never saturated Good.
L5: conformance Int64 AtTime asserts the type. L4: docs name the backend
differences. Nit: the window read end is clamped to now + 1 day.
Reviewer harnesses (Scratch693Fuzz/Cost, not committed): 0 differential diffs
over 2,400 cases.
Review follow-up: on the Gateway every value is a Double (AVEVA stores a Boolean
as a 0/1 Int2), so the raw-evaluated AtTime interpolated a Boolean node to 0.5.
- IHistorianDataSource gains a default-interface overload
ReadAtTimeAsync(fullReference, timestamps, TypeCode? valueType, ct) that
forwards to the existing one (SqlServer/QuestDB/Null/fakes unchanged).
- OtOpcUaNodeManager.HistoryReadAtTime passes the node's scalar DataType
(AtTimeValueType: built-in type -> TypeCode; arrays/other types => null);
Raw and UNS NodeIds alike.
- GatewayAtTimeReader converts each raw row to the hinted kind BEFORE the shared
AtTimeEvaluator runs (Boolean = value != 0 => stepped; integers => Int64 =>
interpolated, rounded half away from zero, returned as the node's integer
type; floats Double), so the evaluator's own type branch decides.
- AtTimeEvaluator boxed every interpolated Int64 as a Double (`cond ? (long)x :
v` widens to double); its "keeping its type" test passed because Shouldly
ShouldBe compares numbers across types. Fixed (affects SqlServer/QuestDB too)
and pinned with ShouldBeOfType.
Gateway HistoryRead-AtTime passed AVEVA's own interpolation through: live it
answered the previous value as Good at a stored NULL's own time, null + Bad at
a Good sample right after a NULL, a drifted 99.99999999944 for a stored 100,
and no Interpolated bit. It is now served from raw gateway reads and evaluated
with Sql.Common's AtTimeEvaluator, as the SQL backends do (Part 11 §6.5.4).
GatewayAtTimeReader: one <=1,024-row forward window read [first-1ms, last+1ms]
for the batch, a walk-back (density-seeded, x4 growth, whole-remainder shortcut,
bisects dense history) for the first time's prev, and an 18-row probe for the
last time's next; truncated window reads continue or jump with a density-sized
margin. All bounds whole ms; a row counts only strictly inside its request
(AVEVA's boundary row never a sample); Bad rows value-less (#690); never past
now + 1 day; strict-gateway ceiling learned (#691.3) without re-probing.
10 dense times = 1 read (exact) / 3 (interpolated); 10 hourly = 12.
Kill switch ServerHistorian:GatewayAtTimeFromRaw (default true; false = the
old AVEVA passthrough). Known limit: the wire carries no data type, so numeric
tags interpolate as Double (Boolean/integer nodes are not stepped/rounded as on
the SQL backends).
1. The at-or-after bound read on a forward-only backend (Gateway) ends at
now + ReverseRawReader.LookAhead instead of DateTime.MaxValue (the gateway
only checks start <= end, so a year-9999 end reached AVEVA); a bound beyond
the horizon is not found without a read. SqlServer/QuestDB keep MaxValue:
they bind it safely and may hold samples further ahead. The Gateway fake now
refuses far-future ends, so the missing-end-bound test is no longer vacuous.
3. No data and no bound found (whole read empty) => GoodNoData, no values —
the pre-bounds answer (6.5.3.2: success only if one or both bounds exist).
A one-value page whose start bound is missing first checks there is data or
a found end bound.
4. ServerHistorian:HonorReturnBounds (default true); false ignores ReturnBounds
as before #691, including the modified-read Bad_InvalidArgument.
The start bound is the stored prior sample at its own time (walked back), never
the synthetic boundary row stamped at the query start; a stored NULL is a Bad
bound; reverse end bound walks back too.
The node manager composes the start/end bounds from each backend's existing raw
reads (one authority, HistoryBounds): at-or-before = a capped reverse read
(native, or ReverseRawReader's walk-back on a forward-only backend — never
AVEVA's synthetic boundary row), at-or-after = a capped forward read. Bounds
count toward NumValuesPerNode, the start bound leads the first page, the end
bound ends the last (carried in the continuation point). Missing bound =
Bad_BoundNotFound (null, at the bound time; one-sided reads ±1 s from the
previous value, Table 1 footnotes a/b). A modified read with ReturnBounds is
Bad_InvalidArgument (Part 11 6.5.3.3).
The .NET SDK's ReadRawModifiedDetails defaults ReturnBounds to TRUE; the
existing tests built details without setting it and now set it false.
Oracle: every row of Part 11 Table 1 over three backend shapes, plus paging
concatenation, ties, Bad bounds, microsecond truncation; conformance pins the
lookup primitives on SqlServer + QuestDB.
GatewayHistorianDataSource.ReadEventsAsync sized its result list to
maxEvents, which is int.MaxValue for NumValuesPerNode = 0: every
uncapped Gateway events read (forward on master, and the new walked
reverse one) threw 'Array dimensions exceeded' and counted as a backend
failure. Capacity is bounded at 1024. The events walk delegate moved to
ReverseEventsReader so it is tested over the real Gateway source
(forward uncapped, reverse uncapped, reverse capped).
A reverse or end-only capped events read on a backend without
SupportsReverseEvents (Gateway, Null) was refused
BadHistoryOperationUnsupported (explicit reverse) or answered with the
OLDEST N ascending (end-only, #675). It is now served newest-first by
the same ReverseWalk as raw reads: page-sized ms-aligned segments,
never answered from a read the source flagged truncated, ties sorted by
EventId (the gateway orders by event time only - the fake shuffles
them per call), one extra event walked to signal 'more', uncapped = one
forward read reversed, and the width + proven-empty stretch carried in
the events cursor. The oversized-cluster over-fetch keeps exactly the
events at T in the same order. A tie cluster over the budget is
BadTooManyOperations. Docs note the gateway's EventReadMaxRows must be
unlimited (it truncates silently).
With StartTime at or before the epoch, RequestStartFor has no margin left, so
AVEVA's synthetic no-data/boundary row is stamped exactly at StartTime and was
kept: raw reads returned a fabricated Bad sample at 1970-01-01 and the per-sample
aggregates put it in bucket 0 (Start/End fabricated, Min/Max status Uncertain).
IsWindowSample and the aggregate loop now drop any row with t <= ProbeFloor
(RawAggregateReader.IsAfterFloor), matching the #686 walk-back's assumption.
- M1/M2: when the 1 ms pre-window margin (boundary row + stored samples, e.g. a
>16-sample tie cluster at start-1ms / lastTs-1ms) uses up the cap + 16 budget,
re-read ONCE asking for cap + m + 16 (m = pre-window rows seen); fail
BadTooManyOperations only if the re-read is still short because of them. The
raw budget is no longer clamped at the gateway default ceiling (AVEVA always
emits the boundary row, so page sizes 999,985-1,000,000 always came back
short); the #688 clamp stays on the per-sample aggregate path only.
- Merge trap: NumValuesPerNode 0 => int.MaxValue, never through the clamp.
- L3: the forward end is exclusive ([start, end), the IHistorianDataSource
contract); a point read (start == end, the tie-cluster over-fetch) inclusive.
- RequestStartFor never goes before the Unix epoch (#686's walk-back floor).
- L4 (docs): an Uncertain native row for an all-NULL interval is unverified live.
The default MaxTimeWeightedRawRows (1,000,000) + 18 exceeded the gateway's
default MaxValuesCeiling (1,000,000), so with AllowStreamingBeyondCeiling=false
every Gateway per-sample aggregate read was refused. The allowance is now clamped
at 1,000,000 while the cap is at or under it (RawAggregateReader.
ClampToGatewayCeiling); a cap above it keeps its allowance. Raw reads are not
clamped (rebased onto #686).
An AVEVA Full raw read leads with a row stamped at the query start (the value in
effect, Quality=133, or a no-data NULL row); it was returned as a stored sample.
Raw reads now use the #681 classification (RawAggregateReader.RequestStartFor /
IsWindowSample — one authority, by timestamp, since a stored NULL looks the same
on the wire): request from 1 ms early with NumValuesPerNode + 16 rows, keep rows
at or after StartTime, drain the whole stream. A full page still holds exactly
the cap, so #669 paging/resume/tie-cluster reads are unchanged; a margin that
swallows the allowance fails the node rather than ending paging early.
ReturnBounds is not plumbed on any backend (documented).
AVEVA answers one extra row for the interval before the window; it was mapped as
a result stamped before StartTime (N+1 values). Rows whose interval lies outside
the requested span (either direction) are now dropped after the drained stream.
An Uncertain (opc 64-191) interval kept no value (opc >= 192 was the only data
test); it now carries its value as UncertainDataSubNormal | Calculated.
Docs: AVEVA's TWA excludes NULL-gap time while the SQL backends bridge it;
end-to-end per-interval values also need historiangw#27.
1. Uncapped reverse raw read on a forward-only backend = ONE forward read of the
window, filtered and reversed in memory (was a segment-by-segment walk).
2. Segment width is aimed at ~half the row budget from the density just observed
(overflow: from the truncated read's own sample span) and carried page to page
in HistoryContinuationState.SegmentWidthTicks.
3. The walk starts no later than now + 1 day and never reads before the epoch.
4. Request bounds are rounded outward to the millisecond, so a row AVEVA
fabricates at a rounded-up query start cannot land inside the segment.
5. Budget M = max(1, MaxTieClusterOverfetch); reads ask M + 2 rows, completeness is
'short OR last row past the segment', and a read crowded by rows before the
segment is re-read once (<= 2M + 4). A cluster of exactly M, neighbouring
clusters each within M, and M <= 1 are all served; only one timestamp over M
is refused. ServerHistorianOptions text updated.
6. The raw and events tie-path oversized-cluster refusal is BadTooManyOperations
(was BadHistoryOperationUnsupported), consistent with the walk.
7. GatewayHistorianDataSource.ReadRawAsync: a caller cancellation is not a backend
failure; NumValuesPerNode = 0 is sent as int.MaxValue (the client package and
the gateway reject max_values <= 0, so every uncapped Gateway raw read failed);
a MaxValuesCeiling refusal is a HistoryReadLimitExceededException.
8. Tests: upper-edge filter, epoch floor, look-ahead, ms alignment, exact/adjacent
clusters, minimal budget, carried density, and the walk over the real Gateway
source + FakeHistorianGatewayClient (OpcUaServer internals visible to it).
#669 turned an end-only capped HistoryRead-Raw into a reverse read (start > end)
for every backend; the gateway rejects start > end (InvalidArgument), so on the
default Gateway backend every end-only capped and every explicit reverse raw read
failed the node and was counted as a backend health failure.
- IHistorianDataSource.SupportsReverseRaw (default false; SqlServer/QuestDB/Null
true, Gateway false; guard test pins that every production backend declares it).
- OtOpcUaNodeManager sends a reverse window only to a backend that declares it;
otherwise ReverseRawReader walks (lo, hi] back in bounded forward segment reads
(1 min, x4 while sparse; each <= MaxTieClusterOverfetch + 1 rows; a full read is
re-read narrower, never answered truncated; filtered on sample timestamps, which
also drops AVEVA's fabricated query-start rows; stops at the Unix epoch). A
one-timestamp tie cluster over the bound => BadTooManyOperations.
- ServeRawPagedAsync maps HistoryReadLimitExceededException to BadTooManyOperations.
- GatewayHistorianDataSource.ReadRawAsync refuses start > end unsent, without
recording a health failure.
The window-bounded pick joins (4a3b1256) let the optimizer choose, under
understated statistics, a nested-loops RANGE seek over the window with the pick
time as a residual, once per bucket (O(buckets x window rows)); the cached plan
was then reused for wide reads: gate 9 1d@1min 20 s, here 47 s / 3.6M reads.
Each pick join now carries WITH (FORCESEEK (PK_Sample (TagId, SourceTimeUtc))):
an exact-key seek on both columns per bucket under any statistics, and no
hash/merge join over the tag's history can exist (forcing one is error 8622), so
the window bound is dropped from the join. Output identical (EXCEPT both ways,
fwd/rev, incl. a mixed Double/Int64/Boolean/String/DateTime/outage tag).
Measured (6M-row tag + 86k mixed-kinds tag; ms / logical reads), understated
stats: 1d@1min 47,223/3.6M -> 253/25.6k; mixed 1d@1min 20,164/1.66M -> 137/24k;
accurate stats: 1d@1min 121 -> 160 ms, 1d@1h 79 -> 117 ms. Rejected: OUTER
APPLY TOP(1) FORCESEEK (identical), OPTION (RECOMPILE) (still 20 s under the bad
stats, and a compile per read).
StartEndJoinBackTests rewritten: understated statistics + compile-small/reuse-wide
(18,645 reads; the merged query read 1,645,845 / 23 s and failed it), accurate
statistics with 300k history rows either side (22,616), forced HASH/MERGE
refused (8622 — also failed against the merged query).
Docs: perf table + explanation; SDK-parity N2 (*ActualTime Calculated bit) and
N3 (Good String => BadAggregateInvalidInputs, SDK skips it).
- SqlServer StartEnd join-back: every pick join also carries the window predicate
(forward >= @start AND < @end, reverse > @start AND <= @end). Keyed on the pick
time alone a hash/merge/adaptive join read the tag's whole history (review:
43,657 vs 361 logical reads), and parameter sniffing reused that plan for every
tag. Forced OPTION (HASH JOIN), 1d@1h on 6M rows: 152,524 -> 6,756 reads.
- Usable picks (x/y) re-check the exact u predicate in the join, so a concurrent
HistoryUpdate Replace that turned the picked sample Bad/Empty reads as absent
(BadNoData), never a Bad row's value under Delta.
- StartEndJoinBackTests (integration): 300k history rows either side of a 1 h
window, forced HASH and MERGE joins, results identical to the unhinted plan and
Start/End correct, session logical reads < 1,000 (183 bounded; 8,055 with the
bound removed — the test fails then).
- TagIndexTests: the refused-ADD-INDEX test asserts the Warning naming the ALTER.
- Historian.md: re-measured table incl. long-history windows (output identical by
EXCEPT both ways in all 7 cases) and the forced-join read counts.