Live on Z33856 a UInt tag over .ARRFAULTCODE (ARRAY [0..12] OF UINT) made the
Beckhoff read throw - BadCommunicationError and a Degraded driver - while the
native path reported BadTypeMismatch. CheckRead now refuses a scalar declared
over an array (by category, so an alias of an array type is caught), pointing
at the array-tag / element-path alternatives.
A native notification for MAIN.Flags.3 / .ADSSTATE_RUN.0 was registered on the
literal WORD.N path, which ADS has no symbol for: live on the TC 2.11 Elma
cleaner Z33856 it failed with DeviceSymbolNotFound, and that registration
error tore down the whole subscribe call. The read path already reads the
parent word; the notification now does the same - it registers the parent as
raw bytes at its resolved width and reads the bit (TwinCATBitAccess), refusing
a bit outside the parent or a non-integer parent with BadTypeMismatch.
An array tag subscribed natively used to register only its declared scalar
(publishing element 0 at Good) and was then refused wholesale with
BadTypeMismatch. The driver now hands the authored ArrayLength to the client,
which registers the whole array as raw bytes and decodes every notification.
- TwinCATTypeGuard.CheckArray plans the layout from the RESOLVED array type:
element checked like a scalar notification (width / float kind / string
kind); STRING(n)/WSTRING(n) elements stride n+1 / 2(n+1); multi-dim arrays
flattened in PLC memory order; an authored ArrayLength shorter than the PLC
array reads the leading sub-range, a longer one is refused; struct / pointer
/ nested-array elements, non-array symbols and VAR_IN_OUT refs are refused.
- CheckNotificationSize caps a native array at 128 KiB (largest registration
proven on a live TC 2.11 target); above it the tag is refused BadOutOfRange.
- TwinCATArrayCodec decodes the bytes into the element-typed CLR array.
- The poll read uses the same plan + codec instead of the Beckhoff typed array
read, which failed live for most real arrays (exact CLR element type, rank-N
for multi-dim, member arrays sliced by the under-reported TC2 symbol size).
- TwinCATNotificationRefusedException carries the refusal's status; the type
mismatch derives from it and the driver isolates either per tag.
Found by the read-only live gate against the TwinCAT 2.11 Elma cleaners
Z33856 / Z33733:
- The Beckhoff library reports a TC2 dotted MEMBER symbol's ByteSize as if the
PLC's byte count were a bit count (STRING(80) -> 11, INT -> 1, UDINT -> 1)
while DataType.ByteSize is right (81/2/4, raw SYM_INFOBYNAMEEX says 81). The
previous commit's typeof(byte[]) read sliced by the symbol size, so
.OPC_MACHINEDATA.PROCESSSTATUS read "ready for o" at Good; the notification
width check would also have refused every numeric member. The shape now takes
the resolved type's size, and string reads go by index group/offset (or a
fresh handle for 0xF005) at that width.
- P_INITINPUT_ACTION.SLOTID is "STRING(20) (VAR_IN_OUT)" - a 4-byte reference -
but resolves to a plain STRING(20); a String tag read 21 bytes at the pointer
as text at Good. The symbol's own VAR_IN_OUT marker now classifies it
NonScalar -> BadTypeMismatch.
libplctag decodes whatever bytes the controller returns as the authored type and never
checks the CIP type code. Live read-only check on a production press: WW_ActualVacuum is a
REAL (L5X + the controller's symbol table agree) but the legacy Kepware export in the
ignitionoee repo types it Short; read as INT it returned Good -17346 while the real value
was 5.37. A scalar atomic read (not an array, not a bit-in-DINT) whose buffer size is not
the authored type's width now reads BadTypeMismatch with a warning naming both. Widths
observed live: SINT/BOOL 1, INT 2, DINT/REAL 4, LINT 8. IAbCipTagRuntime.GetSize() is a
default-interface member (-1 = unknown, never checked). Same-width mismatches (DINT vs
REAL) stay undetectable without the type code libplctag strips.
The mock had served the shapes the driver once agreed with it on, so it
validated the very defects just fixed: it ANSWERED the non-existent 0x00D3
cnc_getfigure, wrote base/exponent 0/0 into position blocks, put the macro
decimal at offset 4, and served spindle 'max rpm' as a raw constant.
Ported from the sister ignitionoee mock (local divergence recorded in
VENDORED.md; the LE timer and alarm cap are kept):
- 0x00D3 refused with EW_FUNC, as the real control does.
- 0x0026 blocks carry base 10 / position_figures exponent; signed arg2,
arg2 = 0 or past the axis count refused EW_ATTRIB.
- cnc_rdmacro is the 8-byte ODBM shape, 9-digit mantissa, unset = vacant.
- servo/spindle meter records carry the envelope; spindle meters are
1/16384-of-full-scale counts (motor speed = speed / max_rpm).
Integration tests: spindle test reads Load/MotorSpeedPct percentages; the
position-scale test now proves the block's own scale wins; new
Vacant_positions_and_macros_read_bad_over_the_wire. 12/12 pass against the
mock run locally (python -m focas_mock.cli serve, OTOPCUA_FOCAS_SIM_ENDPOINT).
Live read-only check against a production CompactLogix press: Program:UN01_Press._ModeNames
(STR0016[32], 4 elements requested) returned an 80-byte buffer with libplctag.NET 1.5.2's
ElementSize unset. The driver fell back to the static 88-byte STRING stride, read element
1 past the buffer, and the whole read failed (ErrorOutOfBounds -> BadCommunicationError).
When the buffer divides evenly by the element count, that quotient is now the stride;
the read returns [undefined, Production, Maintenance, Manual] as the controller holds.
Live read-only check against a production CompactLogix press: with one nonexistent tag
first in the read list, libplctag's create threw LibPlcTagException("ErrorNotFound"); the
driver counted it as a failed Forward-Open, opened the device's 05/STAB-8 connect-backoff
window, and every other cold tag on the device - all real (WW_InCycle, WW_ActualPress,
WW_WorkOrderNum) - read BadCommunicationError. In steady polling the bad tag re-opens
the window each attempt, so siblings ordered after it may never connect.
- A create that fails with a "controller answered" status (NotFound/NoMatch/BadDevice,
the probe's existing reachable classification) records backoff SUCCESS, not failure.
Genuine connection failures still open the window (falsification control test).
- Read exceptions map through the libplctag Status they carry: unknown tag ->
BadNodeIdUnknown, decode past the buffer -> BadOutOfRange, timeout -> BadTimeout,
instead of a blanket BadCommunicationError. One status-name parser
(AbCipStatusMapper.TryGetStatus) now serves both the read path and the probe.
WireFocasClient.GetProgramInfoAsync defaulted every field the CNC did not report:
ONumber ?? 0 when the cnc_exeprgname2 payload was too short to carry it, and
Name '' / BlockCount 0 / Mode 0 when the sub-read was refused. 0 is a genuine
O-number (a 31i reports 0 for a path-executed program -- live Z-34184), a
genuine block count, and Mode 0 is MDI, a real operating mode.
FocasProgramInfo fields are now nullable; MapProgramInfo leaves unreported
fields null and the fixed tree publishes them BadNoData while the bundle's
other fields stay Good.
Ported from the sister ignitionoee FOCAS driver (101a3b1, 2026-08-12).
Live read-only check: a production CompactLogix lists the module tag ABB_OmniCore:I in
@tags and libplctag reads ABB_OmniCore:I.ConnectionFaulted without complaint, but the
driver refused the path as malformed (identifier rule had no colon) and reported the
tag BadCommunicationError. Colon-separated identifier/slot parts are now legal in the
controller-scope base segment only (never past it, never under Program: scope).
Servo (0x0056) and spindle (0x0040) meter records are 8 bytes:
[i32 value][u16 base][u16 exponent], the same self-describing envelope as the
position blocks.
Servo: offset 4 was read as a decimal count. It is the BASE (a steady 10), so
every load was divided by 10^10 and published ~0 -- the sister ignitionoee panel
read servo 0% on every axis of a Makino cutting at 20,000 rpm. Loads are now
value / base^exponent, a direct percentage.
Spindle: the raw meter is a 1/16384 fraction of full scale. Settled on the real
Z-34184 by regressing the type-1 meter against cnc_rddynamic2 spindle speed over
596..20,000 rpm (rpm = 1.220749 x meter; 16384 x 1.220749 = 20000.75). So:
- Spindle/{name}/Load publishes % of rated load (Float64; was the raw Int32
count -- a reading of 9155 meant 55.9%).
- Spindle/{name}/MaxRpm is RENAMED Spindle/{name}/MotorSpeedPct (Float64, % of
maximum speed) and is polled with Load. The old node was actively wrong: the
type-1 meter is the live motor speed, and it was read once at bootstrap and
served forever as if it were a max-RPM constant. Client-visible: FIXED: tags
on .../MaxRpm must be re-pointed.
- The spindle read no longer stops at the first zero after slot 1 (which dropped
an idle second spindle and kept non-zero residue); every slot is returned.
A record whose envelope is undescribable (base not 2/10, exponent > 18 -- e.g.
residue past the configured axis/spindle count) publishes BadNoData, never a Good 0.
Ported from the sister ignitionoee FOCAS driver v0.17.2/v0.17.3 (Focas.Wire-019);
live captures live-spmeter-{load,maxrpm}-0x0040.bin added as fixtures.
Live read-only check against production CompactLogix 5069-L320ERS2 presses:
- The controller @tags listing names each program (Program:UN01_Press, a system symbol)
but none of its tags; those are listed only by Program:<name>.@tags. The enumerator read
@tags alone, so every program-scoped tag was unbrowseable — including the PackML state
(Program:UN01_Press.Out_eState) and all 51 alarm bits the Ignition project reads. The
enumerator now reads each program's listing and decodes it with that program as scope;
an unreadable program listing is skipped, not fatal.
- The Symbol Object decoder ignored the dimension bits + dim words, so every discovered
array (DINT[32], REAL[32], STRING[50], UDT[23] on the two controllers checked) browsed as
a scalar. IsArray/ElementCount are now populated (multi-dim flattened). A 1-D single
element entry stays scalar: ab_server reports every scalar that way, a real controller
sets no dimension bits on scalars.
Pinned by entries captured off the controllers (CipSymbolObjectRealControllerCaptureTests,
AbCipProgramScopeEnumerationTests).
Port of the ignitionoee TwinCAT string + type-reconciliation fixes onto the
Beckhoff-library client:
- STRING/WSTRING subscriptions never worked: AddDeviceNotificationExAsync was
called with typeof(string) and no length, and the Beckhoff any-type
marshaller throws ArgumentNullException for a string without one, so one
string tag tore down its whole subscribe call. A string now registers the
PLC's own byte width as raw bytes (0.19.2: STRING(n) of any n).
- Strings are read as raw bytes and decoded by TwinCATStringCodec. The
Beckhoff marshaller already cut a read at the first NUL (0.19.3 / TwinCAT-007
were not defects on the read path); the codec keeps that rule for both STRING
and WSTRING and extends it to the new notification path. A STRING now decodes
as Windows-1252 (TwinCAT-010) - or UTF-8 when the target reports UTF-8
strings - instead of the host culture's ANSI code page the Beckhoff
marshaller falls back to (1250 on a Polish host, 1251 Cyrillic, ...).
- TwinCATTypeGuard (TwinCAT-002/-008): a read refuses a numeric tag over a PLC
string (and vice versa / STRING vs WSTRING / string over a container) with
BadTypeMismatch instead of handing back a string object at Good; a
notification - raw bytes decoded as the DECLARED type - additionally refuses
width and float/integer mismatches (DINT over REAL reinterpreted the bits).
- A refused notification is isolated: that tag publishes BadTypeMismatch with
one WARN, keeps a dead intent for the probe-tick retry, and the rest of the
subscription registers.
Live read-only check against production CompactLogix 5069-L320ERS2 rev 34.11 presses
(Z-35162 / 10.209.70.160): every @udt/<id> template the controller returned decoded to
null, so controller-discovered UDTs never fanned out. The decoder assumed a 12-byte
header led by the member count and [info][array][offset] blocks with ';'-terminated
names; libplctag actually returns a 14-byte header (u16 id, u32 def words, u32 instance
size, u16 member count, u16 handle), [info][type][offset] blocks, and NUL-terminated
names after a 'Name;<tail>' type name. All three test builders restated the old
assumption, so the unit suite agreed with itself (the #468 trap again); they now share a
TemplateBufferBuilder pinned by real captures (CipTemplateObjectWireCaptureTests).
Discovery follow-ons that the working decoder exposed:
- STRING (and user string types, LEN DINT + DATA SINT[n]) browse as one String variable,
top-level and nested, not as a LEN/DATA folder.
- Controller-generated members (ZZZZZZZZZZ* BOOL hosts, __* AOI backing) are not browsed.
- A UDT array is not fanned out into element-free Tag.Member paths.
Every 0x0026 position block is self-describing: [i32 raw][u16 base][u16 exponent],
value = raw / base^exponent. The live 31i-B capture (ref-dynamic2-axis1.bin)
reports base 10 / exponent 4 on every block, so axis 1 is 280.1574 mm, not
2801574. The driver ignored the envelope and instead sent 'cnc_getfigure'
(0x00D3) -- a command that does not exist in the FOCAS wire protocol, served only
by the in-tree mock; the real control refuses it with rc=1, so on hardware every
position fell back to PositionDecimalPlaces (default 0) and published raw counts.
- ParsePositionBlock decodes the envelope into FocasPosition; the driver applies
raw / base^exponent at publish. PositionDecimalPlaces is now only the fallback
for a scale-less (4-byte) block.
- A block describing no position (0xFFFF vacant marker, base not 2/10, exponent
> 18 -- raw / 10^400 would read as a Good 0.0) publishes BadNoData on that node
alone; siblings are untouched.
- ReadPositionFiguresAsync / IFocasClient.GetPositionFiguresAsync and the
per-axis figure cache are deleted.
Ported from the sister ignitionoee FOCAS driver v0.17.0 (+ Focas.Wire-014);
live axis-scoped captures live-dynamic2-axis{1,2}-0x0026.bin (Z-34184 X 0.0374,
Y 370.177) added as fixtures.
A TC2 PLC reports top-level integer globals as INT16/UINT16 (354 symbols on
the Elma cleaner Z33856) and the Beckhoff type system keeps that spelling as
a built-in primitive, so MapSymbolTypeName returned null and discovery dropped
them silently. INT16/UINT16/INT32/UINT32/UINT8/FLOAT/DOUBLE now map like their
IEC twins; padded member names ("REAL ") are trimmed; a parenthesised
non-string form ("INT (VAR_IN_OUT)", a reference) stays unsupported.
ReadNameRecord read only the first 2 bytes of each 4-byte 0x0089/0x008A record,
so the real 31i-B's paired axes 'AA6'/'AA7' (live capture ref-axisname-0x0089.bin)
both decoded as 'AA' -- the 'Makino with two AA axes' that #548 then had to
disambiguate as AA_1/AA_2. The name is now the record's ASCII up to its FIRST
NUL (not trailing-NUL trimming), so buffer residue such as Z-34184's spindle
record 53 31 00 4e ('S1' + an 'N' left from an earlier 'CNC') is discarded.
Client-visible: on such a machine Axes/AA_1 and Axes/AA_2 become Axes/AA6 and
Axes/AA7 (the old names were a decode artefact). #548's disambiguation stays as
the guard for genuinely duplicate names.
Ported from the sister ignitionoee FOCAS driver (Focas.Wire-001, Focas.Wire-022
/ v0.18.1).
A TC2 global is named with ONE leading dot (.OPC_HEARTBEAT) and the PLC
requires it (SYM_HNDBYNAME answers 0x710 without it). TryParse rejected the
dot, so the driver fell back to the raw string and lost bit-index parsing:
.X.WORD.3 went to ADS verbatim instead of reading .X.WORD and extracting bit 3.
The dot now stays on the root segment and round-trips through ToAdsSymbolName;
.., ., .[1] and .9x stay invalid.
The ODBM wire payload is [i32 mantissa][i16 length, a constant 10][i16 dec_val].
ReadMacroAsync read the decimal at offset 4, so every macro decoded without
failing but wrongly: the captured #500 = 1.0 (05 f5 e1 00 00 0a 00 08) published
0.01. FANUC normalises macros to a 9-significant-digit mantissa, so the error
was never small.
- dec_val is read at [6..7]; a payload < 8 bytes is refused, not guessed at.
- A vacant variable (dec_val 0xFFFF) publishes BadNoData, never a Good 0.
- Integer-typed tags get the exact whole value (integer arithmetic); a
fractional macro on an integer tag is BadTypeMismatch, a whole value that
does not fit the type BadOutOfRange. Float tags get mantissa / 10^dec.
Ported from the sister ignitionoee FOCAS driver v0.15.0 (Focas.Wire-013,
Focas-017/018); live vectors from Makino Z-34184 (31i-B, G431).
Adds a WireFixtures helper that loads the raw 31i-B captures in Fixtures/v3.
BoundedApiKeyStore bounded ConfigDbApiKeyStore with a
CancellationTokenSource(TimeSpan, TimeProvider) linked into the inner call. That
bounds the call only if the callee chooses to observe the token, and
Microsoft.Data.SqlClient does not while a connect/login is in flight on a
black-holed socket. The 2026-08-20 live gate paused the SQL container and watched
a keyed activation hang 42.9 s past its 2000 ms bound — the "did not answer
within 2000 ms" Warning fired only at unpause — and because this runs inside the
SDK's synchronous SessionManager-lock-holding impersonation callback, an
unrelated already-open subscription stalled 57 s behind it. That is precisely the
hazard the bound exists to prevent, and the TTL cache cannot help a miss.
BoundAsync now races the inner call against Task.Delay on the injected clock with
Task.WhenAny. Inner wins: stop the timer, await it, faults and genuine caller
cancellation propagate unchanged. Delay wins: cancel the linked token anyway (a
cooperative inner store should still stop), hand the abandoned task to
ObserveAbandoned, meter outcome=timeout, log the now-honest Warning, and throw
OperationCanceledException — the same exception the authenticator's catch-all
already maps to the standard opaque denial. Fail-closed is unchanged: nothing
here can admit.
ObserveAbandoned disposes the CTS and TOUCHES finished.Exception (the observation
itself), so a late SqlClient fault can never become an UnobservedTaskException.
Debug, not Warning — the timeout is already reported at Warning, and an outage
must not produce two lines per activation for one event.
An abandoned answer is NEVER cached: it was taken before the deadline and would
be served after it, so a key revoked or expired in the meantime could be admitted
from a lookup nobody was still waiting for. StoreTimeoutMs <= 0 still
short-circuits to the unbounded call byte-for-byte (the documented rollback).
RED BEFORE GREEN. Every pre-existing deadline test drives GatedApiKeyStore, whose
waits take the token, so a cooperative CancelAfter unblocks them and all 15
passed against the defective build — the suite could not see the gate's failure
at all. The new UncooperativeApiKeyStore ignores ct entirely and completes only
when the test releases it. Against the unmodified store the three new tests fail
3/18 with "should throw OperationCanceledException but threw TimeoutException"
under a test-side WaitAsync(2 s), so the red is a failure and not a hang — and
that exception swap IS the finding restated as an assertion.
Host.Tests 137/137.
options.Roles is unconditionally overwritten by AddOtOpcUaCluster's PostConfigure to equal
EffectiveRoles.Gossiped (T2's own structural-identity fix), so comparing options.Roles against
Gossiped could never observe a divergence — an overlay setting Cluster:Roles was silently
ignored, not fail-start. The validator now injects IConfiguration and re-reads the raw
Cluster:Roles section LIVE (reflecting any overlay applied after EffectiveRoles was first
resolved), normalized through EffectiveRoles.Resolve for reuse of its own validation.
AddOtOpcUaCluster now TryAddSingleton(configuration) so a bare ServiceCollection test harness
(not just WebApplicationBuilder) can supply IConfiguration to the validator.
Both guard tests rewritten to go through the real AddOtOpcUaCluster + PostConfigure pipeline
over a live ConfigurationManager, simulating an overlay as a second provider added AFTER
EffectiveRoles was resolved off the same object — exactly Program.cs's own sequencing. Confirmed
red beforehand: the "changes" test failed to throw against the pre-fix validator.
The default decider restarts a faulting child immediately and without limit, and
the hook makes every restart do ShutdownAsync+InitializeAsync+SubscribeAsync, so a
driver faulting on every value became a reconnect storm. Per-driver last-reprovision
stamp + DefaultReprovisionBackoff (10s, matched to DefaultReconnectInterval);
a held request is re-delivered by a single per-driver timer carrying the original
incarnation ref, so the F2 identity check still applies.
Seen RED with the backoff disabled: InitializeCount == 3 (second applied
immediately) where the test requires 2-then-3.
Also: the _children.Keys union-arm test (seeder gained taglessDrivers) and the
_desiredByDriver xmldoc note that it lingers on last-known-good after a failed apply.
A ReprovisionRequested in flight from an old incarnation could reach the NEW child
after HandleRestartDriver swapped it in. In Connecting that child DOES handle
InitializeRequested, so it started a second concurrent InitializeAsync, racing the
#527 dispose-before-overwrite.
Seen RED: InitializeCount == 2 on a child held in Connecting by a gated init
(an already-connected child swallows InitializeRequested and passes vacuously).
MeshGrpcMapConventionTests - source-scan of Program.cs (solution-root walk,
following FlushLoggingConventionTests.cs's idiom): zero direct
MapGrpcService</MapZbLocalDbSync( occurrences, exactly one
MapOtOpcUaMeshGrpcServices( call.
Complements the endpoint-metadata census (T1-T3): the census catches a map
added to MeshGrpcEndpoints without the AllowAnonymous convention, but cannot
see a map that bypasses the helper and goes straight into Program.cs - that
shape never reaches MapOtOpcUaMeshGrpcServices at all. Verified red against
the pre-T1 Program.cs (five inline map sites, zero mapper calls) and green
against the current extracted form.